ASPENMANUFACTURING373 ATASCOCITA RD. • HUMBLE, TX • 77396TEL (281) 441-6500 • FAX (281) 441-6510><strong>FMW</strong> Series Multi-Position Hydronic Air HandlerDimensions and <strong>Spec</strong>ificationsSTANDARD EQUIPMENTFully insulated cabinetGalvanized steel cabinet with painted front panelsDirect drive flex mounted multi speed blowerCheck style flowrater used for a/c and heat pumpsPrimary and secondary 3/4'' MPT drain connectionsCircuit breaker disconnectUpflow or horizontal and right as shipped(Field convertible to downflow or horizontal left)Filter rack and disposable filterHorizontal drain pan with primary and secondary3/4'' MPT connection40 VA TransformerTop or left hand electric connectionFan time delayFactory installed circulator pump with check valveOPTIONSTXV availableTerminal blockStainless steel powder coated drain panA participating Corporation in theARI Air Conditioning CertificationProgram.SS-<strong>FMW</strong>-7/7/03


PERFORMANCE DATAMODELNOMINALCOOLINGHEATING CAPACITY E.W.T. DEG. F (1)Heating CoilRows/PatternMINIMUM CIRCUITAMPACITYMAX FUSE ORHACR BKR(tons) 120º140º 180º<strong>FMW</strong>30 18 1.5 24800 35200 56400 2 / 1 x .886<strong>FMW</strong>35 18 1.5 29100 41100 65500 3 / 1 x .886<strong>FMW</strong>32 24 2 26200 37200 59600 2 / 1 x .886<strong>FMW</strong>37 24 2 30900 43700 69700 3 / 1 x .886<strong>FMW</strong>33 30 2.5 26500 37600 60400 2 / 1 x .886<strong>FMW</strong>39 30 2.5 31300 44300 70800 3 / 1 x .886<strong>FMW</strong>41 30 2.5 34000 48000 76400 4 / 1 x .886<strong>FMW</strong>34 36 3 27500 39000 62600 2 / 1 x .886<strong>FMW</strong>40 36 3 32600 46100 73700 3 / 1 x .886<strong>FMW</strong>43 36 3 35500 50100 79700 4 / 1 x .886<strong>FMW</strong>34 37 3 27800 39500 63500 2 / 1 x .886<strong>FMW</strong>40 37 3 33100 46800 74800 3 / 1 x .886<strong>FMW</strong>43 37 3 36100 50900 82000 4 / 1 x .886<strong>FMW</strong>44 42 3.5 30900 43800 70000 2 / 1 x .886<strong>FMW</strong>52 42 3.5 36200 51100 81300 3 / 1 x .886<strong>FMW</strong>56 42 3.5 38800 54700 86800 4 / 1 x .886<strong>FMW</strong>47 48 4 32900 46600 74700 2 / 1 x .886<strong>FMW</strong>56 48 4 38700 54600 87000 3 / 1 x .886<strong>FMW</strong>60 48 4 41600 58600 93100 4 / 1 x .886<strong>FMW</strong>50 60 5 34400 48800 78300 2 / 1 x .886<strong>FMW</strong>60 60 5 40600 57400 91400 3 / 1 x .886<strong>FMW</strong>65 60 5 43700 61700 98000 4 / 1 x .886<strong>FMW</strong>50 61 5 34400 48800 78300 2 / 1 x .886<strong>FMW</strong>60 61 5 40600 57400 91400 3 / 1 x .886<strong>FMW</strong>65 61 5 43700 61700 98000 4 / 1 x .886120V120V4.1 154.14.14.17.47.47.41515151515157.4157.4157.47.415157.4157.41512.61512.61512.61512.6 1512.6 1512.6 1512.61512.61512.61512.6 1512.6 1512.6 15BLOWER DATAMODELMOTORMOTORCFM VS. EXTERNAL STATIC PRESSURE (2,3)SPEEDMOTOR HPVOLTAGE0.10 0.15 0.20 0.30 0.40 0.50<strong>FMW</strong>XX - 18 LOW 0.20 120 890 875 860 845 810 (4)<strong>FMW</strong>XX - 24HIGH 0.20 120 1020 1005 990 975 939 (4)<strong>FMW</strong>XX - 30 LOW 0.33 120 1116 10941069 1010 960 (4)<strong>FMW</strong>XX - 36 HIGH 0.33 120 1233 1203 1178 1121 1054 (4)<strong>FMW</strong>XX - 37 HIGH 0.33 120 1283 1253 1228 1171 1104 (4)<strong>FMW</strong>XX - 42 LOW 0.75 120 1507 1500 1493 1470 1452 1431<strong>FMW</strong>XX - 48 MEDIUM 0.75 120 1823 1815 1806 1782 1753 1717<strong>FMW</strong>XX - 60 HIGH 0.75 120 2180 2160 2141 2081 2051 1989<strong>FMW</strong>XX - 61 HIGH 0.75 120 2180 2160 2141 2081 2051 19891) 70º EAT2)Dry coil with filter in place3)For 208v operation multiply by .904)Not rated.A participating Corporationin the ARI Air ConditioningCertification Program.Aspen reserves the right to make changes without notice or obligation.Page 2


INSTALLATION CLEARANCESTOPFRONTSIDESREAROPERATION0''0''0''0''SERVICE0''30''0''0''Model A B C D E G H J K<strong>FMW</strong>XX 18-37 20 20 43.25 18 x 12 4.75 14.62 12.62 10 8<strong>FMW</strong>XX 42-61 27.5 21.5 52.25 19.5 x 19.5 4.5 14.5 12.5 13.5 10.5Model L M N O P Q R S<strong>FMW</strong>XX 18-37 2.75 2.37 1.5 1.75 14.37 16.37 18.25 18.5<strong>FMW</strong>XX 42-61 2.75 2.37 1.5 1.75 16.37 18.37 19.75 20Model X Y<strong>FMW</strong>XX 18-37 2.5 17.5<strong>FMW</strong>XX 42-61 3.0 18.5BDAXYEERSCGH J LKMNOQPA participating Corporationin the ARI Air ConditioningCertification Program.Aspen reserves the right to make changes without notice or obligation.Page 3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!