To protect the gears from overload, the oscillating mechanism willdisengage if sufficient force is applied to either side of the oscillatoroutlet. The green START KNOB will pop up to indicate themechanism is disengaged. See the instructions above to engagethe drive mechanism.Oscillation speed: The chart shows how many times per minutethe oscillator makes one complete cycle as a function of flow. Thehigher the flow, the faster it oscillates.APPROXIMATECYCLES/MIN8132128GPM175250375500L/MIN650100015002000BLITZFIRE OSCILLATION SPEEDDISTANCE IN METERS61m53m45m38m30m22m15mDISTANCE IN FEET200’175’150’125’100’75’50’WIDTH OF COVERAGE150’ / 45m125’ / 38m100’ / 30m75’ / 23m50’ / 15m500 GPM / 1892 Lpm400 GPM / 1514 Lpm300 GPM / 1135 Lpm200 GPM / 757 Lpm100 GPM / 378 Lpm20 DEGREES30 DEGREES40 DEGREES0’FLOW @ 100 PSI / 7 BARCOVERAGE AREA OF BLITZFIRE OSCILLATING UNIT7.0 STORAGEThe monitor may be stored pre-connected to its hose on the optional storage bracket, TFT part number XX-B. The storage bracketmay be mounted on a horizontal surface, or a vertical surface with the nozzle end pointing up or sideways. Mounting instructionsare included with the bracket.©Copyright <strong>Task</strong> <strong>Force</strong> <strong>Tips</strong>, Inc. 2002-200513<strong>LIX</strong>-<strong>630</strong> September 22, 2005 Rev05