ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

JO<strong>IN</strong>T VAR AND W<br />

REGULATOR<br />

<strong>IMPLEMENTED</strong> <strong>IN</strong> <strong>TPP</strong><br />

<strong>”NIKOLA</strong> <strong>TESLA</strong> <strong>A”</strong><br />

<strong>–</strong><br />

<strong>OBRENOVAC</strong><br />

J: Dragosavac, Ž. Janda, T. Gajić, J. Pavlović,<br />

DA D. Arnautović, S. Dbičić Dobričić,* and Lj. Mihailović** il ić**<br />

* Electrical Engineering Institute “Nikola Tesla”<br />

** “Thermal Power Plants Nikola Tesla” Ltd


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

ŠTA JE GRARS?<br />

• GRRS<br />

• Regulacija reaktivne snage (ostvarivanje zadate<br />

ukupne reaktivne snage elektrane)<br />

• Regulacija napona na sabirnicama<br />

• Ravnomerna raspodela ukupne reaktivne snage po<br />

agregatima uključenim u grupnu regulaciju<br />

• Praćenje ć i poštovanje ograničenja<br />

• Inkrementalni uticaj na reference pobude za svaki<br />

generator ponaosob


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

ŠTA JE GRARS?<br />

• GRAS<br />

• Regulacija aktivne snage (ostvarivanje zadate ukupne<br />

aktivne snage elektrane)<br />

• Ravnomerna raspodela ukupne aktivne snage po<br />

agregatima uključenim u grupnu regulaciju<br />

• Praćenje i poštovanje ograničenja<br />

• Inkrementalni uticaj na reference frekvencija<br />

turbinskih regulatora za svaki generator ponaosob


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

KRITERIJUMI<br />

• Svaki generator je opterećen srazmerno svojim<br />

mogućnostima i trenutnoj spremnosti ili po drugom<br />

kriterijumu (stepen iskorišćenja, druga ograničenja)<br />

• Granice Q su određene pogonskim kartama i<br />

trenutnom t vrednošću P<br />

• Granice P su određene maksimalnom dozvoljenom<br />

aktivnom snagom i tehničkim minimumom kotla<br />

• Granice se mogu menjati


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

POGONSKA KARTA AGREGATA<br />

Pogonska karta agregata A1i A2 prilagodjena potrebama GRASP<br />

220<br />

Sn=247MVA<br />

Un=15750V<br />

200<br />

cosϕn=0,85<br />

P(MW)<br />

180<br />

160<br />

140<br />

200 150 100 50 0 -50<br />

Q(MVAr)


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

KAKO RADI GRARS?<br />

• GRRS može raditi u 3 režima:<br />

regulacija po Q<br />

regulacija po U sa zadatim statizmom<br />

kombinovana regulacija<br />

• GRAS uvek reguliše aktivnu snagu<br />

• Poseban deo regulatora vrši ravnomernu raspodelu<br />

snaga po generatorima koji su uključeni u regulaciju


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

KAKO RADI GRARS?


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REGULACIJA NAPONA SABIRNICA<br />

U<br />

Karakteristika elektrane<br />

B<br />

Približna<br />

karakteristika<br />

mreže<br />

A<br />

Q A<br />

Q<br />

U A<br />

Q<br />

new<br />

=<br />

U −<br />

U<br />

+<br />

eo<br />

X<br />

A<br />

m<br />

+<br />

X<br />

X<br />

e<br />

m<br />

Q new<br />

⋅<br />

Q<br />

A


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

IMPLEMENTACIJA<br />

• TENT A<br />

4 agregata na sabirnicama 220 kV (A1-A4)<br />

2 agregata g na sabirnicama 400 kV (A5 i A6)<br />

• GRRS čine dva nezavisna regulatora reaktivne snage<br />

• Uređaj je realizovan kao centralna jedinica sa<br />

lokalnim upravljanjem preko operatorskog panela i<br />

terminalni računar


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

IMPLEMENTACIJA


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REZULTATI - simulacija promene zahtevane<br />

reaktivne snage<br />

100<br />

80<br />

60<br />

40<br />

Q (MVA Ar)<br />

20<br />

0<br />

-20<br />

Q1<br />

Q2<br />

Q5<br />

Q5<br />

-40<br />

-60<br />

-80<br />

Q3<br />

Q4<br />

-100<br />

800 825 850 875 900 925 950 975 1000 1025<br />

t (s)<br />

Promena zahtevane Q za grupu generatora na sabirnicama 220kV<br />

u stepovima od -50MVAr do 300MVAr


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REZULTATI - simulacija kratkotrajnog forsiranja<br />

225<br />

200<br />

175<br />

150<br />

Q1<br />

125<br />

Q (MV VAr)<br />

100<br />

75<br />

50<br />

Q2<br />

Q3<br />

Q4<br />

25<br />

0<br />

-25<br />

Q5<br />

Q6<br />

-50<br />

700 705 710 715 720 725 730 735 740 745 750<br />

t (s)<br />

Ostali agregati nisu reagovali na kratkotrajni poremećaj


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REZULTATI <strong>–</strong> simulacija dužeg forsiranja<br />

225<br />

200<br />

175<br />

150<br />

Q1<br />

125<br />

Q (M MVAr)<br />

100<br />

75<br />

50<br />

Q2<br />

Q3<br />

Q4<br />

25<br />

0<br />

-25<br />

Q5<br />

Q6<br />

-50<br />

800 825 850 875 900 925 950 975 1000<br />

t (s)<br />

Ostali agregati jesu osetili duži poremećaj


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REZULTATI testiranja regulatora na elektrani<br />

80<br />

70<br />

1<br />

4<br />

6<br />

7<br />

60<br />

50<br />

Q [%]<br />

40<br />

30<br />

20<br />

10<br />

2<br />

3<br />

5<br />

Q1<br />

Q2<br />

Q4<br />

0<br />

0 5 10 15 20 25<br />

tim e [m in]<br />

1 - promena željene Q sa 300 MVAr na 250 MVAr i sva tri agregata su uključena u GRRS<br />

2 - A2 i A4 su isključeni iz GRRS i zahtevano Q je promenjeno na 220 MVAr<br />

3 <strong>–</strong> A2 i A4 su vraćeni u grupnu regulaciju<br />

4 <strong>–</strong> A1 i A4 su isključeni č i iz GRRS i zahtevano Q je promenjeno na 250 MVAr<br />

5 <strong>–</strong> A1 i A4 su vraćeni u grupnu regulaciju<br />

6 - A1 i A2 su isključeni iz GRRS i zahtevano Q je promenjeno na 280 MVAr<br />

7 - A1 i A2 su vraćeni u grupnu regulaciju


ELEKTROTEHNIČKI <strong>IN</strong>STITUT NIKOLA <strong>TESLA</strong><br />

REZULTATI <strong>–</strong> snimak promene e reference e e napona<br />

sabirnica 220 kV za 1 kV<br />

227<br />

226<br />

U220 [kV]<br />

225<br />

224<br />

223<br />

0 5 10 15 20 25 30 35<br />