NYISO Normal Operat<strong>in</strong>g State Criteria<br />

• Pre-Cont<strong>in</strong>gency (Actual) Flow Criteria:<br />

• Actual load<strong>in</strong>g of equipment def<strong>in</strong>ed as part of the NYS Transmission<br />

System should not exceed the associated Normal rat<strong>in</strong>gs of the<br />

equipment<br />

• Post-Cont<strong>in</strong>gency Flow Criteria:<br />

• Preventitive mode:<br />

• the loss of any s<strong>in</strong>gle generator, s<strong>in</strong>gle circuit, or adjacent circuits on the same<br />

structure, together with other facilities, which will trip at the same time due to pre-set<br />

automatic devices, will not cause any portion of the NYS Transmission System to<br />

exceed its LTE rat<strong>in</strong>g.<br />

• Corrective mode:<br />

• Underground cable : may exceed its LTE rat<strong>in</strong>g, but not its STE rat<strong>in</strong>g, provided 10-<br />

m<strong>in</strong>ute reserve or PAR control is available to return its post-cont<strong>in</strong>gency load<strong>in</strong>g to<br />

its LTE rat<strong>in</strong>g with<strong>in</strong> 15 m<strong>in</strong>utes, without caus<strong>in</strong>g another facility exceed its LTE<br />

rat<strong>in</strong>g<br />

• Overhead Transmission: with prior approval of the NYISO, the post-cont<strong>in</strong>gency<br />

load<strong>in</strong>g of any portion of the NYS Transmission System may exceed its LTE rat<strong>in</strong>g,<br />

provided sufficient control is available to return the load<strong>in</strong>g on the facility to its LTE<br />

rat<strong>in</strong>g with<strong>in</strong> 15 m<strong>in</strong>utes, without caus<strong>in</strong>g another facility to exceed its LTE rat<strong>in</strong>g<br />