5<br />
1<br />
<strong>Cylon</strong> M-<strong>Bus</strong> <strong>Gateway</strong><br />
Dimensions<br />
Free space recommended to install the device into<br />
a cabinet (wall or DIN rail mounting), with space<br />
enough for external connections:<br />
Ethernet Port<br />
+Power<br />
Ethernet Port<br />
+Power<br />
58mm<br />
RS232<br />
port<br />
Console<br />
port<br />
100mm<br />
RS232<br />
port<br />
Console<br />
port<br />
107mm<br />
105mm<br />
115mm<br />
130mm<br />
Connections<br />
<strong>Cylon</strong>M-<strong>Bus</strong> <strong>Gateway</strong><br />
(DB9 M)<br />
Cable<br />
(DB9 F)<br />
Rx<br />
Tx<br />
GND<br />
C1<br />
2<br />
3<br />
5<br />
M-<strong>Bus</strong> Connection<br />
RS232 (straight)<br />
Maximum length 15m<br />
C1<br />
2<br />
3<br />
7<br />
M-<strong>Bus</strong> to RS232level convertor<br />
(DB9 F)<br />
Cable<br />
(DB9 M)<br />
Tx<br />
Rx<br />
GND<br />
(See device<br />
manufacturer's<br />
documentation for<br />
pin-out details)<br />
<strong>Cylon</strong>M-<strong>Bus</strong> <strong>Gateway</strong><br />
(RJ45 F)<br />
C2<br />
<strong>Cylon</strong> Connection<br />
<strong>Cylon</strong> UC32.net<br />
(RJ45 F)<br />
Cable<br />
(RJ45 M)<br />
Ethernet<br />
Maximum length 100m<br />
Cable UTP/FTP Cat5 Crossed<br />
Hub<br />
Cable<br />
(RJ45 M)<br />
1 UCC<br />
device<br />
X UCC devices<br />
<strong>Cylon</strong>M-<strong>Bus</strong> <strong>Gateway</strong><br />
(DB9 F)<br />
C3<br />
PC (CGCT) Connection<br />
PC<br />
(DB9 M)<br />
Cable<br />
(DB9 M)<br />
Tx<br />
Rx<br />
GND<br />
2<br />
3<br />
5<br />
RS232 (straight)<br />
Maximum length 15m<br />
Connections to M-<strong>Bus</strong> - RS232 level convertor<br />
Recommended Cable Lengths<br />
<strong>Bus</strong> Type<br />
Maximum Conductor<br />
Cable Crosssection<br />
Length<br />
Building Installation<br />
Number of<br />
Terminal<br />
Devices<br />
350 m 0.5 sq mm* 250<br />
Baud<br />
Rate<br />
9600<br />
M+ M-<br />
M+ M+<br />
M- M-<br />
M-<strong>Bus</strong><br />
On Slave Max Short<br />
2<br />
3<br />
5<br />
M-<strong>Bus</strong><br />
-<strong>Bus</strong><br />
Cable<br />
(DB9 F)<br />
Rx<br />
Tx<br />
GND<br />
-<strong>Bus</strong><br />
Small Wide Area<br />
Installation<br />
Standard<br />
1 km 0.5 sq mm* 60<br />
2 km 0.8 sq mm 60<br />
Large Wide Area 3 km 1.5 sq mm 60<br />
Installation<br />
Provider Network 5 km 1.5 sqmm 16<br />
Installation<br />
Maximum Length 10 km 1.5 mm 1<br />
(for linear topology)<br />
*For Example JY(ST)Y 2x2x0.8 mm<br />
2400<br />
2400<br />
2400<br />
300<br />
300<br />
RS232<br />
PW60<br />
Po we r<br />
RS485 RS232C<br />
V+ V-<br />
S- S+ DSR RX TX<br />
24 V ac<br />
9 6<br />
Maximum length 15 m<br />
M-<strong>Bus</strong> - to - RS232<br />
level convertor<br />
<strong>Cylon</strong> M-<strong>Bus</strong><br />
<strong>Gateway</strong><br />
certified<br />
Due to <strong>Cylon</strong>'s policy of continuous improvements<br />
these specifications may be upgraded without notice.<br />
Building Management System<br />
© <strong>Cylon</strong> <strong>Controls</strong> Limited www.cylon.com UCDS0059 rev 5