■ Technical specifications (continued)<br />

6ES7 455-<br />

0VS00-0AE0<br />

Input ranges (rated values),<br />

currents<br />

- 0 to 20 mA Yes Yes<br />

- 0 to 23.5 mA Yes Yes<br />

- -3.5 to +23.5 mA Yes Yes<br />

- 4 to 20 mA Yes Yes<br />

Input ranges (rated values),<br />

thermocouples<br />

- Type B Yes Yes<br />

- Type J Yes Yes<br />

- Type K Yes Yes<br />

- Type R Yes Yes<br />

- Type S Yes Yes<br />

Input ranges (rated values),<br />

resistance thermometer<br />

- Pt 100 Yes Yes<br />

Characteristic curve linearization<br />

- parameterizable Yes Yes<br />

- for thermocouples Type B, J, K,<br />

R, S<br />

- for resistance thermometer Pt 100<br />

(standard)<br />

Temperature compensation<br />

- external temperature<br />

compensation with Pt100<br />

- internal temperature<br />

compensation possible<br />

Yes; parameterizable<br />

Yes; parameterizable<br />

Analog outputs<br />

• Number of analog outputs 16<br />

• Length of cable shielded, max 200 m;<br />

50m at 80 mV<br />

and thermocouples<br />

• Voltage output,<br />

Yes<br />

short-circuit protection<br />

• Voltage output,<br />

25 mA<br />

short-circuit current, max<br />

• Current output,<br />

18 V<br />

open-circuit voltage, max.<br />

Output ranges, voltage<br />

- 0 to 10 V Yes<br />

- -10 to +10 V Yes<br />

Output ranges, current<br />

- 0 to 20 mA Yes<br />

- -20 to +20 mA Yes<br />

- 4 to 20 mA Yes<br />

Actuator connection<br />

- for voltage output<br />

Yes<br />

2-wire connection<br />

- for current output<br />

Yes<br />

2-wire connection<br />

Burden resistance<br />

(in the nominal output range)<br />

- at voltage outputs, min. 1 kΩ<br />

- at voltage outputs,<br />

1 µF<br />

capacitive load, max.<br />

- at current outputs, max. 500 Ω<br />

- at current outputs, inductive 1 mH<br />

load, max.<br />

Analog value formation<br />

6ES7 455-<br />

1VS00-0AE0<br />

Type B, J, K,<br />

R, S<br />

Pt 100<br />

(standard)<br />

Yes; parameterizable<br />

Yes; parameterizable<br />

• Measuring principle integrating integrating<br />

Integration and conversion<br />

time/triggering per channel<br />

- with over-range (bits incl. sign),<br />

max<br />

SIMATIC S7-400<br />

Function modules<br />

FM 455 closed-loop control modules<br />

6ES7 455-<br />

0VS00-0AE0<br />

14 Bit;<br />

12 or 14 bits,<br />

parameterizable<br />

- Conversion time (per channel) 16.67 ms;<br />

at 12 bits:<br />

16 2/3 ms at<br />

60 Hz, 20 ms<br />

at 50 Hz;<br />

at 14 bits:<br />

100 ms at 50<br />

and 60 Hz<br />

6ES7 455-<br />

1VS00-0AE0<br />

14 Bit;<br />

12 or 14 bits,<br />

parameterizable<br />

16.67 ms;<br />

at 12 bits:<br />

16 2/3 ms at<br />

60 Hz, 20 ms<br />

at 50 Hz;<br />

at 14 bits:<br />

100 ms at 50<br />

and 60 Hz<br />

Settling time<br />

- for resistive load 0.1 ms 0.1 ms<br />

- for capacitive load 3.3 ms 3.3 ms<br />

- for inductive load 0.5 ms 0.5 ms<br />

Sensor<br />

Sensing element connection<br />

- for voltage measurement Yes Yes<br />

- for current measurement, Yes<br />

Yes<br />

as 4-wire measuring transducer<br />

Connectable encoders<br />

- 2-wire BEROS Yes Yes<br />

- permissible closed-circuit 1.5 mA 1.5 mA<br />

current (2-wire BEROS), max.<br />

Error/accuracies<br />

• Linearity error<br />

+/- 0.05 %<br />

(relative to the output range)<br />

• Linearity error<br />

+/- 0.05 % +/- 0.05 %<br />

(relative to the input range)<br />

• Temperature error<br />

+/- 0.02 %/K<br />

(relative to the output range)<br />

• Temperature error<br />

+/- 0.005 %/K +/- 0.005 %/K<br />

(relative to the input range)<br />

Operational limit in the<br />

entire temperature range<br />

- Relative to the output range, +/- 0.5 %<br />

voltage<br />

- Relative to the output range, +/- 0.6 %<br />

current<br />

- relative to the input range, +/-0.6 to +/-1% +/-0.6 to +/-1%<br />

voltage<br />

- relative to the input range, +/-0.6 to +/-1% +/-0.6 to +/-1%<br />

current<br />

- relative to the input range, +/-0.6 to +/-1% +/-0.6 to +/-1%<br />

resistance thermometer<br />

Basic error limit<br />

(operational limit at 25 °C)<br />

- relative to the output range, +/- 0.2 %<br />

voltage<br />

- relative to the output range, +/- 0.3 %<br />

current<br />

- relative to the input range,<br />

voltage<br />

+/-0.4 to<br />

+/-0.6%<br />

+/-0.4 to<br />

+/-0.6%<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance thermometer<br />

Interference voltage suppression<br />

for f = n x (fl +/- 1 %)<br />

- Series-mode interference<br />

(peak value of<br />

interference < rated val, min.<br />

- Common-mode interference<br />

(USS < 2.5 V), min.<br />

+/-0.4 to<br />

+/-0.6%<br />

+/-0.4 to<br />

+/-0.6%<br />

+/-0.4 to<br />

+/-0.6%<br />

+/-0.4 to<br />

+/-0.6%<br />

40 dB 40 dB<br />

70 dB 70 dB<br />

5<br />

Siemens ST 70 · 2005<br />

5/55