Split System Heat Pump
Fedder HEAT PUMP - Betz Heating and Plumbing
Fedder HEAT PUMP - Betz Heating and Plumbing
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Product Specifications<br />
GUIDE SPECIFICATIONS<br />
<strong>Split</strong> <strong>System</strong> <strong>Heat</strong> <strong>Pump</strong><br />
HVAC Guide Specifications<br />
Size Range: 1 1 ⁄2 to 5 Nominal Tons<br />
18,000 to 60,000 Btuh<br />
<strong>System</strong> Description<br />
Outdoor mounted, air-cooled, split system heat pump<br />
unit suitable for ground or rooftop installation. Unit<br />
consists of a hermetic compressor, an air-cooled coil,<br />
propeller type condenser fan and a control box. Unit<br />
discharges supply air upward as shown on contract<br />
drawings. Unit used in a refrigeration circuit to match up<br />
to an air handler or coil unit.<br />
Quality Assurance<br />
• Unit rated in accordance with the latest edition of<br />
ARI Standard 210/240<br />
• Unit construction complies with latest edition of<br />
ANSI / ASHRAE and with NEC<br />
• Unit constructed in accordance with UL standards<br />
and carries the UL and CUL labels of approval<br />
• Unit cabinet capable of withstanding test of a 1,000-hrs<br />
of salt spray<br />
• Air-cooled condenser coils leak tested and pressure tested<br />
• Unit constructed in ISO9000 approved facility<br />
Delivery, Storage and Handling<br />
• Unit shipped as single package only and must be stored<br />
and handled per unit manufacturer’s recommendations<br />
PRODUCTS<br />
Equipment<br />
• Factory assembled, single piece, air-cooled air<br />
conditioner unit. Contained within the unit enclosure<br />
is all factory wiring, piping, controls, compressor,<br />
refrigerant charge R-22 or 410A and special features<br />
required prior to field start up.<br />
Unit Cabinet<br />
• Unit cabinet, including louvered coil guard, constructed<br />
of galvanized steel and coated with a powder-coat paint<br />
Fans<br />
• Direct drive propeller type condenser fan discharging<br />
air upward<br />
• Condenser fan motors totally enclosed, with class B<br />
insulation and permanently lubricated bearings.<br />
Corrosion resistant shafts.<br />
• Fan blades statically and dynamically balanced<br />
• Condenser fan openings equipped with coated<br />
steel wire safety guards<br />
Compressor<br />
• Hermetically sealed compressor<br />
• Compressor mounted on rubber vibration isolators<br />
Condenser Coil<br />
• Air cooled condenser coil<br />
• Coil constructed of aluminum fins mechanically<br />
bonded to copper tubes which are cleaned, dehydrated<br />
and sealed<br />
Refrigeration Components<br />
• Refrigeration components include liquid line shutoff<br />
valve with sweat connections, vapor line shutoff valve<br />
with sweat connections, system charge of R-22 or 410A<br />
refrigerant, compressor oil, high pressure switch and<br />
reversing valve<br />
6<br />
Specifications subject to change without notice.