Product Specifications<br />

GUIDE SPECIFICATIONS<br />

<strong>Split</strong> <strong>System</strong> <strong>Heat</strong> <strong>Pump</strong><br />

HVAC Guide Specifications<br />

Size Range: 1 1 ⁄2 to 5 Nominal Tons<br />

18,000 to 60,000 Btuh<br />

<strong>System</strong> Description<br />

Outdoor mounted, air-cooled, split system heat pump<br />

unit suitable for ground or rooftop installation. Unit<br />

consists of a hermetic compressor, an air-cooled coil,<br />

propeller type condenser fan and a control box. Unit<br />

discharges supply air upward as shown on contract<br />

drawings. Unit used in a refrigeration circuit to match up<br />

to an air handler or coil unit.<br />

Quality Assurance<br />

• Unit rated in accordance with the latest edition of<br />

ARI Standard 210/240<br />

• Unit construction complies with latest edition of<br />

ANSI / ASHRAE and with NEC<br />

• Unit constructed in accordance with UL standards<br />

and carries the UL and CUL labels of approval<br />

• Unit cabinet capable of withstanding test of a 1,000-hrs<br />

of salt spray<br />

• Air-cooled condenser coils leak tested and pressure tested<br />

• Unit constructed in ISO9000 approved facility<br />

Delivery, Storage and Handling<br />

• Unit shipped as single package only and must be stored<br />

and handled per unit manufacturer’s recommendations<br />

PRODUCTS<br />

Equipment<br />

• Factory assembled, single piece, air-cooled air<br />

conditioner unit. Contained within the unit enclosure<br />

is all factory wiring, piping, controls, compressor,<br />

refrigerant charge R-22 or 410A and special features<br />

required prior to field start up.<br />

Unit Cabinet<br />

• Unit cabinet, including louvered coil guard, constructed<br />

of galvanized steel and coated with a powder-coat paint<br />

Fans<br />

• Direct drive propeller type condenser fan discharging<br />

air upward<br />

• Condenser fan motors totally enclosed, with class B<br />

insulation and permanently lubricated bearings.<br />

Corrosion resistant shafts.<br />

• Fan blades statically and dynamically balanced<br />

• Condenser fan openings equipped with coated<br />

steel wire safety guards<br />

Compressor<br />

• Hermetically sealed compressor<br />

• Compressor mounted on rubber vibration isolators<br />

Condenser Coil<br />

• Air cooled condenser coil<br />

• Coil constructed of aluminum fins mechanically<br />

bonded to copper tubes which are cleaned, dehydrated<br />

and sealed<br />

Refrigeration Components<br />

• Refrigeration components include liquid line shutoff<br />

valve with sweat connections, vapor line shutoff valve<br />

with sweat connections, system charge of R-22 or 410A<br />

refrigerant, compressor oil, high pressure switch and<br />

reversing valve<br />

6<br />