24.09.2015 Views

Sprinkler control unit - BN-320/5

Sprinkler control unit - BN-320/5 - SISPA Sicurezza

Sprinkler control unit - BN-320/5 - SISPA Sicurezza

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Sprinkler</strong> <strong>control</strong> <strong>unit</strong> - <strong>BN</strong>-<strong>320</strong>/5<br />

Interactive fire detection systems<br />

Product datasheet<br />

Features<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Interactive<br />

1 monitored input<br />

Handles both normal open and normal closed flow<br />

switch<br />

Connected directly to the detection loop<br />

Loop powered<br />

Built in short circuit isolator<br />

Automatic addressing<br />

Proven technology<br />

With SelfVerify function for reduced<br />

maintenance/testing and increased reliability<br />

Application / Description<br />

The sprinkler <strong>control</strong> <strong>unit</strong> <strong>BN</strong>-<strong>320</strong>/5 is designed for use<br />

with the interactive fire detection system, and has a<br />

SelfVerify function. This function secures the highest<br />

degree of reliability and reduces the need for manual<br />

testing, because all <strong>unit</strong>s with this function are<br />

automatically checked once a day.<br />

The <strong>unit</strong> is used for monitoring and <strong>control</strong> of sprinkler<br />

systems. If a local blackout of the sprinkler contact is<br />

desired, a BW-200 shut-off-switch is used together with<br />

<strong>BN</strong>-<strong>320</strong>/5. Both <strong>unit</strong>s are directly connected to the detector<br />

loop.<br />

Principle<br />

The <strong>unit</strong> has 1 monitored input monitoring the flow switch<br />

(input A). It can be configured to handle normal open and<br />

normal closed flow switch; this is achieved with Input B:<br />

Input B open: Normal open flow switch<br />

Input B shorted: Normal closed flow switch<br />

An open circuit (loss of 2k on the inputs) gives fault<br />

warning.<br />

Stable signal on input for time 1 gives prealarm.<br />

Stable signal on input for time 2 gives fire alarm.<br />

Times 1 and 2 are configurable by means of the<br />

configuration tool (0-127 seconds).<br />

The <strong>unit</strong> has a built in short circuit isolator. In the event of<br />

a short circuit, the short circuit location will be isolated.<br />

SelfVerify: the ability to initiate alarm signal is regularly<br />

checked.<br />

Technical specifications<br />

Weight<br />

Material<br />

Colour<br />

Input<br />

Max. capacitance on<br />

input<br />

Voltage, AlCom<br />

(detection loop)<br />

Current consumption:<br />

Stand by<br />

Environm.<br />

requirement<br />

Degree of protection:<br />

Membr. inlets<br />

PG-inlets (PG-13,5)<br />

175 g<br />

Thermo plastic<br />

Light grey<br />

Max. cable resistance 30 Ω<br />

If the cable data is unknown, use max.<br />

100 m cable.<br />

40 nF<br />

10 - 27 VDC<br />

0,3mA<br />

EN 54-5/EN 54-7<br />

IP54<br />

IP67<br />

Working temperature - 20 - + 70°C<br />

Humidity (non<br />

condensing)<br />

Maintenance<br />

Service<br />

Approvals<br />

Max. 95% RH<br />

None<br />

Replace if faulty<br />

See Autronica’s website<br />

116-P-<strong>BN</strong><strong>320</strong>-5/CGB, Rev. F, 2009-12-07<br />

Protecting life, environment and property…


BRAN NALAR M<br />

T ilpasnin gsenhet<br />

FIRE ALARM<br />

Interface un it<br />

Nr.<br />

No.<br />

BRANNALARM<br />

Tilp asningsenhet<br />

FIRE ALARM<br />

Interface <strong>unit</strong><br />

N r.<br />

No.<br />

KNUS G LAS SE T<br />

TRYK K HER<br />

PRESS HERE<br />

BRE AK GLA SS<br />

<strong>Sprinkler</strong> <strong>control</strong> <strong>unit</strong> - <strong>BN</strong>-<strong>320</strong>/5<br />

Part number<br />

116-<strong>BN</strong>-<strong>320</strong>/5<br />

Description<br />

<strong>Sprinkler</strong> <strong>control</strong> <strong>unit</strong><br />

Dimensions (mm)<br />

Overview<br />

BW-200<br />

<strong>BN</strong>- <strong>320</strong><br />

Loop<br />

Driver<br />

Module<br />

<strong>BN</strong>-<strong>320</strong>/5<br />

<strong>BN</strong>- <strong>320</strong><br />

Input A<br />

<strong>Sprinkler</strong><br />

Flow<br />

Switch<br />

* Disable<br />

<strong>unit</strong><br />

* BW-200 can be used as a local sprinkler disable <strong>unit</strong>.<br />

Connections<br />

<strong>Sprinkler</strong><br />

Control Unit<br />

R<br />

Or NC.<br />

R<br />

Short: (7-8)<br />

Open: (7-8)<br />

AUTRONICA FIRE AND SECURITY AS<br />

Head office, NO-7483 Trondheim, Norway Tel: +47 73 58 25 00, fax: +47 73 58 25 01, e-mail: info@autronicafire.no<br />

Oil and Gas division, Stavanger, Norway Tel: +47 51 84 09 00, fax: +47 51 84 09 99<br />

Maritime division, Spikkestad, Norway Tel: +47 31 29 55 00, fax: +47 31 29 55 01<br />

Visit Autronica Fire and Security AS’ website: www.autronicafire.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!