SUPER COMPACT - SCP
SUPER COMPACT - SCP - Zucchini
SUPER COMPACT - SCP - Zucchini
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Operating instructions on how<br />
to design riser mains<br />
N L1 L2 L3<br />
[7]<br />
[1]<br />
Use an RH end feed unit (without monobloc).<br />
In order to position the tap-off boxes correctly, the neutral conductor of the<br />
riser main must be on the left side of the element.<br />
[3]<br />
[2]<br />
Use one or more suspension brackets for the vertical elements, according to<br />
the weight of the whole riser mains.<br />
For risers that are shorter than 4 metres, fix to the base with type B brackets (see<br />
p.42)<br />
when longer, use a type A suspension bracket (see p. 42) every 300 kg of<br />
risers (including the boxes).<br />
[5]<br />
[3]<br />
Use a standard suspension bracket to hang the busbar every 2 metres of riser<br />
mains.<br />
[4] Use elements with tap-off outlets (see page 13).<br />
[4]<br />
[6]<br />
[5] Use S120 fire barrier kit for each compartment floor (see page 15).<br />
[6]<br />
The tap-off boxes can be installed in the tap-off outlets and near the connection<br />
between the elements.<br />
In both cases, the boxes extend downward.<br />
N<br />
[7] At the end of the riser mains, position the IP55 end cover.<br />
N<br />
[2]<br />
N<br />
N<br />
[1]<br />
(For further information, please refer to the technical guide)<br />
46 <strong>SUPER</strong> <strong>COMPACT</strong>