YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

36 kV insulation class<br />

Technical information (250-3000 kVA)<br />

TECHNICAL DATA from 250 to 3000 kVA<br />

kVA Item Prim V Sec V Uk% Po (W) Pk(W) Io% Sound Sound Weight<br />

pressure level power level<br />

kV V 120° 75° dB dB kg<br />

250 EE5NAIBA 25 400 6 1320 3600 3180 1.5 55 68 1380<br />

315 EF5NAIBA 25 400 6 1450 4800 4250 1.4 56 69 1500<br />

400 EG5NAIBA 25 400 6 1600 5800 5100 1.3 57 70 1700<br />

500 EH5NAIBA 25 400 6 1800 7200 6350 1.2 58 71 1900<br />

630 EI5NAIBA 25 400 6 2100 7600 6750 1 59 73 2250<br />

800 EJ5NAIBA 25 400 6 2580 9400 8370 0.9 60 74 2700<br />

1000 EK5NAIBA 25 400 7 2800 10500 9280 0.8 61 75 3100<br />

1250 EL5NAIBA 25 400 8 3000 14000 12350 0.7 62 76 3400<br />

1600 EM5NAIBA 25 400 8 3600 16500 14600 0.6 64 77 4050<br />

2000 EN5NAIBA 25 400 8 4600 18000 16200 0.5 65 79 4900<br />

2500 EO5NAIBA 25 400 8 5780 22000 19800 0.5 67 80 6000<br />

3000 EP5NAIBA 25 400 8 6620 25500 22500 0.4 68 82 7000<br />

Standards CEI 14-4 and 14-8 - IEC 60076-11 - CENELEC HD 538.1<br />

Power (kVA) 250 to 3000<br />

Frequency (Hz) 50<br />

Primary Voltages (kV) 25 - 33 insulation class 36 kV BIL 145/170 kV<br />

Secondary Voltages (V) 400 - 420 insulation class 1.1 kV<br />

Adjustment, MV side ± 2 x 2.5%<br />

Vectorial group<br />

Dyn11 (replace the final letter of the item code with “B” for Dyn5 or “C” for Dyn1)<br />

Insulating system insulation class F / F<br />

Temperature rise<br />

100 / 100 K<br />

Class E2 - C2 - F1 Certified CESI No. 98/11 908<br />

Tolerances<br />

According to CEI / IEC<br />

Notes<br />

The values shown are referred to the ratio 25/0.4 kV.<br />

These values may slightly change when there are different combinations.<br />

dB = Value measured at a distance of one metre, according to standard CEI EN 60076-10<br />

Dimensions and weight of integral boxes: page 131<br />

BIL 170 available on request in the order phase<br />