29.04.2016 Views

Enclosure Catalogue

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Accessories<br />

Power distribution<br />

Busbars and blocks<br />

Linergy FM<br />

Insulated busbars - spring connection<br />

PD390660d-40<br />

DB123592<br />

PD390661-40<br />

Characteristics<br />

Linergy FM: for cable links<br />

Rating 63 A 80 A 160 A 200 A<br />

Length in 9 mm modules 24 96 48 48 72<br />

in 18 mm modules 12 48 24 24 36<br />

Upstream connection capacity Tunnel terminals for cables<br />

up to 25 mm²<br />

Tunnel terminals for cables up<br />

to 25 mm²<br />

Direct on connecting pads by 50 mm² cables or by 20 x 3 flexible<br />

bar with a prefabricated connection from a busbar<br />

Downstream Max. Phase 2 - - -<br />

connection 4 mm² Neutral 4 - - -<br />

capacity<br />

Max. Phase 2 - - -<br />

6 mm² Neutral 4 - - -<br />

Max. Phase - 18 6 12 18<br />

10 mm² Neutral - 18 6 18 27<br />

Accessories Pre-stripped copper 10 of 4 mm² + 6 of<br />

12 blue + 12 black 20 of 4 mm² + 6 of 6 mm² (L=100 mm)<br />

included connections 6 mm² (L=100 mm)<br />

Protective cover - - For pads (IPxxB)<br />

Screws and nuts - - For pads<br />

References<br />

2P - - - 04012 -<br />

3P - - - 04013 -<br />

4P 04008 04000 04018 04014 04026<br />

Accessories<br />

Type<br />

Manufactured cable links for upstream liaison<br />

References / type of liaison - - 4 x 160 A cable links<br />

04030 - Between<br />

Linergy FM and<br />

switchgear<br />

4 x 200 A cable links<br />

04021 - Between Linergy FM and<br />

Powerclip busbar<br />

04029 - Between Linergy FM and<br />

back busbar<br />

04024 - Between Linergy FM and<br />

busbar in duck<br />

259