Turbine Type<br />

MUDDY RUN PUMPED STORAGE PROJECT (FERC NO. <strong>2355</strong>)<br />

EXHIBIT A-PROJECT DESCRIPTION<br />

Turbine<br />

Characteristics<br />

TABLE 3-1: TURBINE UNIT CHARACTERISTICS<br />

A-8<br />

Generating Pumping<br />

Reversible Francis<br />

(No’s. 1 through 8)<br />

Nameplate Turbine Capacity (MW) 100<br />

Rated Hydraulic Capacity (cfs) 4,000 3,500<br />

Design Head (ft)<br />

Runner Diameter (ft)<br />

412 427<br />

Inlet 17.45 11.9<br />

Outlet 11.9 17.45<br />

Runner Speed (rpm) 180<br />

Number of Buckets 7<br />

Bucket (blade) Tip Speed (ft/sec) 164.5<br />

No. of Wicket Gates 20<br />

Wicket Gate Spacing (in) 16.6<br />

Pad Height (in) - clear distance between<br />

top and bottom of wicket gate<br />

36