24.07.2018 Views

Siepan 8PU Panels

Cotmac is one of the select few Licensed Partners for the Siemens SIEPAN 8PU totally type tested (TTA) low voltage switchboards. Siepan 8PU design for low voltage switchboards has become an industry benchmark with proven performance for the past many decades. It is Compact, safe and reliable.

Cotmac is one of the select few Licensed Partners for the Siemens SIEPAN 8PU totally type tested (TTA) low voltage switchboards. Siepan 8PU design for low voltage switchboards has become an industry benchmark with proven performance for the past many decades. It is Compact, safe and reliable.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

• A Low Voltage switchboard is a device that<br />

directs electricity from one or more sources of<br />

supply to several smaller regions of usage.<br />

•The aim of Low Voltage Switchboards is to<br />

produce a superior quality product suitable for its<br />

intended use with regards to functionality,<br />

structural integrity and conformance to<br />

established industry and practices.<br />

•Siemens <strong>8PU</strong> has been designed to operate in<br />

challenging conditions of high ambient & dust.


• Maximum reliability in protection of your<br />

plant and equipment.<br />

• Maximum safety for operating personnel.<br />

• Suited for the most arduous site conditions.<br />

• Compact and space saving.


• Various segments like cement, steel, refinery,<br />

oil & gas, pharma, F&B, data centres, hospitals<br />

& hotels, metro-rail projects having deployed<br />

more than 100,000 LV switchboards for<br />

maximum reliability and performance, are the<br />

main patrons of this type of solution.


Conformance to Internal Arc Containment as<br />

per IEC-61641<br />

Conformance to Seismic<br />

withstand upto Zone 5 as<br />

per IS 1893


Safety to plant and personnel<br />

o Design verified in conformance to IEC 61439 for variants of 50KA, 65KA, 80KA / 1s<br />

o Design verification in conformance to IEC 61641 for safety against Internal Arc faults up-to 80KA / 0.3s<br />

o Design certified for maximum seismic intensity – Zone V<br />

Flexibility<br />

o Design verified up-to 5000A without de-rating of ACBs<br />

o Design verified both with aluminum and copper bus-bar<br />

Reliability<br />

o Single Tier Double panel verticals – Ease of cable termination, maintenance and no de-rating of the ACB<br />

o Type Tested simulating actual field connections:<br />

e.g. 5000A Al Panel Temperature rise Tested with 5000 sq. mm incoming connection<br />

o Local R&D & service support for SIEPAN <strong>8PU</strong> from the house of Siemens


IP 2X Finger touch proof<br />

Form 4B as per the cable dimension<br />

CPCC meeting the requirement for building and Infra customers<br />

Most suited for Al field cables<br />

Vertical bus bars tested to carry currents upto 1500 Amps<br />

11 no control bus bar carry current upto – 100 / 200 Amps<br />

Easy to maintain VBB connections<br />

Double panels (DP) configuration to optimize the space<br />

<strong>Panels</strong> desinged and tested for IP 54<br />

<strong>Panels</strong> suitable for SIESMIC Zone-5<br />

Most compact panels – Double front in 560 mm<br />

Conformance to Internal Arc Containment (IAC)<br />

Designed for Multiples earth bus to accommodate automation components