Termination of Armoured Cable

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

As 17 th Edition IEE Regulations (BS 7671:2008)

Termination of Armoured Cable

Only incoming armoured cable termination

shown, for clarity. The outgoing cable, if

armoured, would be terminated as for the

incomer with, in effect, copper protective

conductors bridging, and connecting, the

enclosure.

Figure A : Termination of Amoured Cables

Termination glands for rubber-insulated and plastic-insulated cables must comply with BS 6121.

Where the armouring forms part or all of the CPC it is inadvisable to rely on detachable plates of

equipment as a permanent and reliable path for earth fault current. Detachable plates are often

covered with ‘non-conductive’ finishes and are usually secured by a few very small screws, which are

unlikely to sustain earth fault current adequately. In such circumstances, it should be considered

essential to make the protective conductor connection via a gland tag, nut, bolt and washers with a

crimped protective conductor connecting the tag to the earthing terminal in the equipment,

repeating the procedure for the outgoing cable (see Figure A).

“Hopefully it’s useful as a knowledge and guideline”

Prepaired by : Hafriq

Aug-2018