<strong>Motor</strong> <strong>Protection</strong> against short<br />
circuits and overload upto 400 A<br />
<strong>Motor</strong> <strong>Protection</strong><br />
<strong>Circuit</strong> <strong>Breakers</strong>
World class Controlgear products now in India<br />
Rockwell <strong>Automation</strong> a leader in Complete <strong>Automation</strong> worldwide<br />
brings Sprecher + Schuh a legendary Swiss brand to India.<br />
Sprecher + Schuh Low Voltage Controlgear products are also<br />
manufactured & sold in India, conforming to the strict Swiss quality<br />
and technology standards. The manufacturing in India fulfils the<br />
stringent ISO 9002 quality standards under the supervision of<br />
Rockwell <strong>Automation</strong> experts.<br />
All Sprecher + Schuh products have CE, UL, CSA conformance<br />
that correspond in every respect and meet the applicable<br />
regulations. Sprecher + Schuh’s world class products are available<br />
and supported through our nationwide network of channels. With<br />
the Rockwell <strong>Automation</strong> back-up you have the assurance of the<br />
strictest international quality, logistics, distribution and our flexible,<br />
efficient response to the market requirement any where, any time.<br />
Buy Reliability. Buy Sprecher+Schuh
Bringing about a revolution in circuit breaker technology<br />
I [kA]<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
0<br />
0 1 2 3 4 5 6 7 8 9 10<br />
t [ms]<br />
Cut-off current<br />
by KTA 3-100<br />
Solid short-circuit current<br />
I K = 50kA eff at 400V 50Hz.<br />
The difference between type “2” and type “1”<br />
✔ For type “2”, IEC 947 requires that the starter must<br />
remain functionally serviceable after a short-circuit<br />
switch-off.<br />
✔ For type “1”, the contactor and overload relay may<br />
be damaged after a short-circuit switch-off.<br />
Replacement of the motor starter is usually<br />
necessary.<br />
Type “2” is therefore the better solution:<br />
✔ Advantages of type “2”:<br />
• no reserve starter is required<br />
• rapid restoration of operation after a short-circuit<br />
switch-off.<br />
✔ For modern facilities and controllers, type “2” is the<br />
clear solution.<br />
Unique advantages of the KTA 3<br />
✔ <strong>Circuit</strong> breakers type KTA 3-100 and above<br />
automatically give type “2” co-ordination in high<br />
power industrial systems.<br />
Modern and simple starter engineering<br />
✔ <strong>Circuit</strong> breakers from KTA 3-100 upward make<br />
configuring starters significantly easier:<br />
✔ Type “2” short-circuit co-ordinated motors can be<br />
implemented<br />
• without oversizing of the power contactors<br />
• with a minimal volume = space saving in the<br />
switching cabinet.<br />
✔ The devices and equipment supplied are<br />
protected from damage.<br />
Lightning fast switch-off of short-circuit<br />
currents<br />
✔ High current limitation plus extremely short<br />
switch-off times mean that short-circuit coordinated<br />
motor starters need no additional motor<br />
protector.<br />
Cost-effective and versatile to use<br />
✔ Genuine integrated motor protection, with<br />
temperature compensation and differential<br />
release.<br />
✔ Rapid return to operational status with no<br />
replacement parts and no device exchange after<br />
release by a short circuit.<br />
✔ Safe operation.<br />
Type “2” co-ordination without oversized contactors<br />
Minimises contactor size for type “2” co-ordination<br />
IEC 947-4-1 type “2” short-circuit co-ordination at 400V 50Hz, 50kA<br />
Conventional switching device technology (standard circuit breaker + contactor, without thermo-relay)<br />
[A]<br />
180<br />
160<br />
140<br />
120<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
[kW]<br />
0 10 20 30 40 50 60 70 80<br />
KTA 3-25 KTA 3-100 KTA 3-160S<br />
Nom. motor current Sprecher + Schuh Conventional circuit-breaker technology<br />
Starter combinations with a KTA3-100 allow the smallest circuit-breaker<br />
to be used, avoiding expensive and bulky over-sizing
<strong>Circuit</strong> <strong>Breakers</strong> KTA 3 Range<br />
400 / 415 V Rated voltage<br />
Thermal Magnetic Switching<br />
release release of three-<br />
Setting Response phase<br />
range current/ motors at I cu I cs 3 - pole 4 - pole<br />
Setting AC-2, AC-3<br />
[A] range [A] [kW] [kA] [kA] Type designation Type designation<br />
0.1...0.16 1.8 0.02 100 100 KTA 3-25-0.16A<br />
0.16...0.25 2.8 0.04 100 100 KTA 3-25-0.25A<br />
0.25...0.4 4.4 0.06 / 0.09 100 100 KTA 3-25-0.4A<br />
0.4...0.63 6.9 0.09 / 0.12 100 100 KTA 3-25-0.63A<br />
0.63...1.0 11 0.18 / 0.37 100 100 KTA 3-25-1A<br />
1.0...1.6 18 0.37 / 0.55 100 100 KTA 3-25-1.6A<br />
1.6...2.5 28 0.55 / 0.75 100 100 KTA 3-25-2.5A<br />
2.5...4.0 44 1.1 / 1.5 100 100 KTA 3-25-4A<br />
4.0...6.3 69 2.2 / 2.5 100 100 KTA 3-25-6.3A<br />
6.3...10 110 3 / 5.5 20 16 KTA 3-25-10A<br />
10...16 176 5.5 / 7.5 10 6 KTA 3-25-16A<br />
16...20 220 7.5 / 10 8 6 KTA 3-25-20A<br />
20...25 275 11 / 12.5 8 6 KTA 3-25-25A<br />
25...40 560 15 / 22 65 50 KTA 3-100-40A<br />
40...63 882 25 / 31.5 65 50 KTA 3-100-63A<br />
63..90 1260 37 / 45 50 25 KTA 3-100-90A<br />
40...50 300...600 25 65 33 KTA 3-160S-50A KTA 3-160S4-50A<br />
50...63 380...760 31.5 65 33 KTA 3-160S-63A KTA 3-160S4-63A<br />
63...80 480...960 37 / 45 65 33 KTA 3-160S-80A KTA 3-160S4-80A<br />
80...100 600...1200 50 / 55 65 33 KTA 3-160S-100A KTA 3-160S4-100A<br />
100...125 750...1500 63 65 33 KTA 3-160S-125A KTA 3-160S4-125A<br />
125...160 950...1900 75 / 90 65 33 KTA 3-160S-160A KTA 3-160S4-160A<br />
125...160 950...1900 75 / 90 65 33 KTA 3-250S-160A KTA 3-250S4-160A<br />
160...200 1200...2400 110 65 33 KTA 3-250S-200A KTA 3-250S4-200A<br />
200...250 1500...3000 132 / 150 65 33 KTA 3-250S-250A KTA 3-250S4-250A<br />
200...250 1500...3000 132 / 150 65 33 KTA 3-400S-250A KTA 3-400S4-250A<br />
250...320 1900...3800 160 / 185 65 33 KTA 3-400S-320A KTA 3-400S4-320A<br />
320...400 2400...4800 200 / 220 65 33 KTA 3-400S-400A KTA 3-400S4-400A<br />
Ics Icu KTA 3-25 KTA 3-100 KTA 3-160S KTA 3-250S KTA 3-400S<br />
Rated normal breaking capacity<br />
Rated limiting breaking capacity<br />
I cu<br />
I cs<br />
Still functionally serviceable<br />
after test with O-t-CO.<br />
Suitable for normal operation<br />
after test with O-t-CO-t-CO<br />
O = break<br />
CO = restart and break<br />
t = defined pause
Product information: <strong>Circuit</strong> Breaker KTA 3<br />
Technical Data KTA 3-25 KTA 3-100 KTA 3-160S KTA 3-250S KTA 3-400S<br />
Rated insulating voltage<br />
IEC, SEV, VDE 0660 [V] 690 690 690 690 690<br />
UL, CSA [V] 600 600 – – –<br />
Rated frequency [Hz] 40...60 40...60 40...60 40...60 40...60<br />
Life<br />
mechanical [operating cycles] 100 000 30 000 15 000 10 000 8 000<br />
electrical [operating cycles] 100 000 >10 000 15 000 10 000 8 000<br />
Switching frequency [op. cycles/h] max. 30 max. 20 max.20 max. 20 max. 20<br />
Ambient temperature<br />
storage [°C] – 25...+ 80 – 25... + 80 – 20...+ 60 – 20... + 60 – 20...+ 60<br />
in operation [°C] – 25...+ 60 – 25... + 60 – 5... + 40 – 5... + 40 – 5...+ 40<br />
Resistance to climatic change C IV (IEC 68) C IV (IEC 68) (T2-3) IEC 68 (T2-3) IEC 68 (T2-3) IEC 68<br />
humid heat 40°C, 92%, 56 T. 40°C, 92%, 56 T. 40°C, 93% 40°C, 93% 40°C, 93%<br />
alternating climatic conditions 23°C, 83% 23°C, 83% 25°C/55°C, 93% 25°C/55°C, 93% 25°C/55°C, 93%<br />
40°C, 93%, 56 Z. 40°C, 93%, 56 Z.<br />
Degree of protection IP 20 IP 20 IP 00 IP 00 IP 00<br />
Impact resistance 30 G, 20 ms 30 G, 20 ms 5 G, 15 ms 5 G, 15 ms 5 G, 15 ms<br />
Vibration strength<br />
frequency range [Hz] 10... 150 10... 150 13... 100 13... 100 13... 100<br />
in all directions [G] >7.5 >7.5 1 1 1<br />
Thermal rated current I th<br />
IEC, SEV, VDE 0660 at 40 °C at 40 °C at 40 °C<br />
at 60 °C ambient temperature [A] 0.1...25 16...90 40...160 125...250 200...400<br />
Rated current I e 13 setting ranges 4 setting ranges 6 setting ranges 3 setting ranges 3 setting ranges<br />
[A] 0.1...25 16...90 at 40 °C: 160 at 40 °C: 250 at 40 °C: 400<br />
at 50 °C: 150 at 50 °C: 235 at 50 °C: 380<br />
at 60 °C: 140 at 60 °C: 220 at 60 °C: 360<br />
at 70 °C: 130 at 70 °C: 210 at 70 °C: 340<br />
Overload protection<br />
characteristic motor protection motor protection motor protection motor protection motor protection<br />
temperature compensation [°C] – 20... + 60 – 20... + 60 – 5.. + 40 – 5... + 40 – 5... + 40<br />
Magnetic release fixed setting fixed setting<br />
response current 11 x I e max. 14 x I e max. value setting range value setting range value setting range<br />
Weight [g] 290 1845 3-pole: 2100 3-pole: 4000 3-pole: 5400<br />
4-pole: 2700 4-pole: 5100 4-pole: 6800<br />
Dimensions [mm]<br />
KTA 3 - 25 KTA 3 - 100<br />
KTA 3 - 160S KTA 3 - 250S KTA 3 - 400S<br />
1) Mounting possibility on top hat rail EN 50 022-35 2) Auxiliary switch block for building-on KT 3-25-PA<br />
3) Shunt release KT 3-25-AA or undervoltage release KT 3-25-UA<br />
Mounting position / Blow fields<br />
KTA 3-25 KTA 3-160...KTA 3-400S<br />
KTA 3-100<br />
Dimensions in ( ) for 4-pole circuit breakers
Time / Current Characteristic<br />
Tripping time [s]<br />
Tripping time [s]<br />
Thermal release trip<br />
current:<br />
The adjustable inverse<br />
bimetal trip reliably protects<br />
motors against overloads.<br />
The curve shows the mean<br />
operating current at an<br />
ambient of 20 C starting from<br />
cold for KTA 3-25, KTA 3-100<br />
and 25 C for KTA 3-160S, KTA<br />
3-250S and KTA 3-400S.<br />
Careful testing and setting<br />
ensures effective motor<br />
protection even in the case of<br />
single-phasing.<br />
<strong>Circuit</strong>-breaker KTA 3-25 <strong>Circuit</strong>-breaker KTA 3-100<br />
Multiple of the set current I eF<br />
<strong>Circuit</strong>-breaker KTA 3-160S<br />
Multiple of the set current I eF<br />
Tripping time [s]<br />
Tripping time [s]<br />
Tripping time [s]<br />
<strong>Circuit</strong>-breaker KTA 3-400S<br />
Multiple of the set current I eF<br />
Multiple of the set current I eF<br />
<strong>Circuit</strong>-breaker KTA 3-250S<br />
Multiple of the set current I eF<br />
Magnetic release trip<br />
current:<br />
The instantaneous magnetic<br />
trip has a fixed operating<br />
current setting for KTA 3-25<br />
and KTA 3-100. This<br />
corresponds to 11 times (for<br />
KTA 3-25) and 14 times (for<br />
KTA 3-100) the highest setting<br />
of the thermal overload trip.<br />
The instantaneous magnetic<br />
trip for KTA 3-160S, KTA 3-<br />
250S and KTA 3-400S are<br />
adjustable.
Accessories: <strong>Circuit</strong> Breaker KTA 3-25<br />
Current limiter KTL 3-65-N<br />
u Improved switching capacity<br />
u No back-up fuse necessary<br />
u Reliable in function<br />
u Repulsion contacts close automatically<br />
u For single and group protection<br />
u When used compact bus-bars beside KTA 3-25<br />
KTL 3-65-N serves as supply block<br />
Auxiliary switch blocks<br />
for flush mounting<br />
u No extra space needed<br />
1 Normal contact designation<br />
2 Higher contact designation<br />
L Early-make contact<br />
add on lefthand side<br />
2-pole<br />
Use compact bus-bar with pitch<br />
54 mm<br />
Release control switch blocks<br />
for flush mounting<br />
u Indicate tripping of the circuit<br />
breaker<br />
u No extra space needed<br />
Technical Data KT 3-25-PE, KT 3-25-PA, KT 3-25-PF<br />
u For locking the START button<br />
u For locks ring diameter f 8 mm<br />
KTA 3-25 KT 3-25-...<br />
PF-10 PF-01<br />
Thermal rated current I th<br />
at 40 C ambient temperature 6 A<br />
at 60 C ambient temperature 4A<br />
Contact class according NEMA AC B 600 Standard Pilot Duty<br />
(UL / CSA-standards) DC R 300 Light Pilot Duty<br />
Back-up fuse gl, gL 16 A<br />
Undervoltage release / Shunt release<br />
KT 3-25-UA KT 3-25-AA<br />
add on<br />
righthand side<br />
Contact diagrams<br />
KTA 3-25 KT 3-25-... KTA 3-25 KT 3-25...<br />
UA-...V.. AA-... V..<br />
Technical Data KT 3-25-UA...V.. KT 3-25-AA...V..<br />
Operating voltage<br />
Pull-in 0.8...1.1 x U s 0.7... 1.1 x U s<br />
Drop-out 0.7...0.35 x U s –<br />
On-time 100% ED 100% ED<br />
Rated control voltage<br />
min.: 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz<br />
max.: 600 V 50 Hz 600 V 50 Hz<br />
Coil rating KT 3-25-UA...V.. KT 3-25-AA...V..<br />
Pull-in 8.5 VA, 6 W 8.5 VA, 6 W<br />
Hold 3 VA, 1.2 W 3 VA, 1.2 W<br />
Weight 104 g 100 g<br />
Locking device<br />
Contact diagrams<br />
KTA 3-25 KT 3-25-...<br />
KTA 3-25 KT 3-25-...<br />
Weight 11 g<br />
PE1-10 PE2-10 PE1-01 PE2-01 PE-L10<br />
PA-20 PA-02 PA-11<br />
Type designation<br />
KTL 3-65-N<br />
Technical Data<br />
Rated voltage 690 V<br />
Continuous current 65 A<br />
Weight 210 g<br />
Type designation<br />
KT 3-25-PE1-10<br />
KT 3-25-PE2-10<br />
KT 3-25-PE1-01<br />
KT 3-25-PE2-01<br />
KT 3-25-PE-L10<br />
Type designation<br />
KT 3-25-PA-20<br />
KT 3-25-PA-11<br />
KT 3-25-PA-02<br />
Type designation<br />
KT 3-25-PF-10<br />
KT 3-25-PF-01<br />
Rated current 230/240 V 400/415 V 500 V 690 V<br />
AC-15 2 A 1 A 0.8 A 0.5 A<br />
24 V 48 V 110 V 230 V<br />
DC-13 2 A 0.6 A 0.2 A 0.1 A<br />
Weight KT 3-25-PE 12 g<br />
KT 3-25-PA 35 g<br />
KT 3-25-PF 13 g<br />
Type designation<br />
KT 3-25-UA-...<br />
24 V 50/28 V 60<br />
110 V 50/127 V 60<br />
220...230 V 50/240...260 V 60<br />
240 V 50/277 V 60<br />
380...440 V 50/440..460 V 60<br />
400 V 50/480 V 60<br />
KT 3-25-AA-...<br />
24 V 50/28 V 60<br />
110 V 50/127 V 60<br />
220...230 V 50/240...260 V 60<br />
240 V 50/277 V 60<br />
380...440 V 50/440...460 V 60<br />
400 V 50/480 V 60<br />
Type designation<br />
KT 3-25-DSC
Accessories: <strong>Circuit</strong> <strong>Breakers</strong> KTA 3-25 and KTA 3-100<br />
Supply blocks Type designation<br />
KT 3-25-A2 KT 3-25-A3<br />
Compact bus-bars<br />
Accessories for KTA 3-100<br />
Auxiliary switch blocks<br />
for front mounting<br />
u No extra space<br />
needed<br />
Release control switch blocks<br />
for front mounting<br />
u Indicates tripping of<br />
the circuit breaker<br />
u No extra space<br />
needed<br />
Technical Data KT 3-100-PF, KT 3-100-PE<br />
u Pitch 45 mm for circuit breaker with internal<br />
auxiliary switch block<br />
42 g with 2 x 3 connecting ways<br />
94 g with 4 x 3 connecting ways<br />
119 g with 5 x 3 connecting ways<br />
u Pitch 54 mm for circuit breaker with addedon<br />
auxiliary switch block<br />
45 g with 2 x3 connecting ways<br />
104 g with 4 x 3 connecting ways<br />
135 g with 5 x 3 connecting ways<br />
Contact diagrams<br />
KTA 3-100 KT 3-100-...<br />
Rated current 230 V 400 V 500 V 690 V<br />
AC-15 3 A 2.5 A 1.5 A 0.75 A<br />
24 V 48 V 110 V 230 V 440 V<br />
DC-13 2 A 0.6 A 0.2 A 0.1 A 0.04 A<br />
Thermal rated current Ith at 40 C ambient temperature 10 A<br />
at 60 C ambient temperature<br />
Under-voltage release / Shunt release<br />
6 A<br />
for front mounting<br />
Supply block KT 3-25-A2 Supply block KT 3-25-A3<br />
1) Mounting possibility on top hat rail EN 50 022-35<br />
u Integrated short<br />
circuit indicator with<br />
isolated signalling<br />
KTA 3-100 KT 3-100-...<br />
PE-20 PE02 PE-11<br />
Sophisticated signalling:<br />
a) Overload release<br />
b) Short circuit release<br />
Contact diagrams<br />
KTA 3-100 KT 3-100-.. KTA 3-100 KT 3-100-...<br />
UA-......V.. AA.....V.<br />
b) Short circuit release<br />
Technical Data KT 3-100-UA...V... KT 3-100-AA...V..<br />
Operating voltage<br />
Pull-in 0.8...1.1 x U s 0.7...1.1 x u s<br />
Drop-out 0.7...0.35 x U s<br />
Rated control voltage<br />
min.: 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz<br />
max.: 600 V 50 Hz 600 V 50 Hz<br />
PF-20 PF-02 PF1-11 PF2-11<br />
KT 3-25-A2<br />
KT 3-25-A3<br />
Weight KT 3-25-A2 151 g<br />
KT 3-25-A3 36 g<br />
Type designation<br />
KT 3-25-DB-45-2<br />
KT 3-25-DB-45-4<br />
KT 3-25-DB-45-5<br />
KT 3-25-DB-54-2<br />
KT 3-25-DB-54-4<br />
KT 3-25-DB-54-5<br />
Type designation<br />
KT 3-100-PE-20<br />
KT 3-100-PE-02<br />
KT 3-100-PE-11<br />
Type designation<br />
KT 3-100-PF-20<br />
KT 3-100-PF-02<br />
KT 3-100-PF1-11<br />
KT 3-100-PF2-11<br />
Contact classe according NEMA AC B 600 Standard Pilot Duty<br />
(UL / CSA-standards) DC R 300 Light Pilot Duty<br />
Back-up fuse gl, gL 16 A<br />
Weight 31 g<br />
Type designation<br />
KT 3-100-UA-24 V 50<br />
KT 3-100-UA-110 V 50<br />
KT 3-100-UA-220 V 50<br />
KT 3-100-AA-24 V 50<br />
KT 3-100-AA-110 V 50<br />
KT 3-100-AA-220 V 50<br />
On-time 100% ED<br />
Coil rating<br />
Pull-in upon request<br />
Holding upon request<br />
Weight 94 g
Accessories: <strong>Circuit</strong> <strong>Breakers</strong> KTA 3-100 and KTA 3-160S(4)... KTA 3-400S(4)<br />
Lockable twist knob for KTA 3-100<br />
u For 3 padlocks f 4...8 mm<br />
u Lockable in 0-position<br />
Weight 17 g<br />
Components for KTA 3-160S(4)...KTA 3-400S(4)<br />
Auxiliary switch blocks<br />
for front mounting in the 1st contact circuit<br />
KT 3-160-PE-1W KT 3-400-PE-1W<br />
Auxiliary switch – and release<br />
control switch block<br />
for front mounting in the 1st contact<br />
circuit<br />
Release control switch block<br />
for front mounting in the 1st contact<br />
circuit<br />
Technical Data KT 3-160/400-PE/PE-PF/PF<br />
Contact diagrams<br />
KTA 3-160S KT 3-160-...<br />
KTA 3-250S KT 3-400-...<br />
KTA 3-400S KT 3-400-..<br />
PE-1W PE-2W<br />
KTA 3-160S KT 3-160-... KTA 3-160S KT 3-160-...<br />
KTA 3-250S KT 3-400-... KTA 3-250S KT 3-400-...<br />
KTA 3-400S KT 3-400-... KTA 3-400S KT 3-400-...<br />
PE-PF PF<br />
Thermal rated current I th<br />
at 40 C ambient temperature 5 A<br />
at 60 C ambient temperature 4 A<br />
Rated current I e 110 V 230/240 V 400/415 V<br />
AC-15 3 A 2 A 1 A<br />
48 V 110 V 230 V<br />
DC-13 0.5 A 0.2 A 0.1 A<br />
Under-voltage release / Shunt release<br />
for flush mounting in the<br />
third contact circuit<br />
KT 3-160-UA-... V.. KT 3-400-UA-... V..<br />
Colour Type designation<br />
black KT 3-100-KN<br />
red/yellow KT 3-100-KRY<br />
KT 3-160... Accessories for KTA 3-160S<br />
KT 3-400... Accessories for KTA 3-250S / KTA 3-400S<br />
Contact diagrams<br />
KTA 3-160S KT 3-160-... KTA 3-160S KT 3-160-...<br />
KTA 3-250S KT 3-250-... KTA 3-250S KT 3-250-...<br />
KTA 3-400S KT 3-400-.. KTA 3-400S KT 3-400-...<br />
UA-...V.. AA-...V..<br />
Technical Data KT 3-160-UA KT 3-400-UA KT 3-160-AA KT 3-400-AA<br />
Operating range<br />
switching on 0.85...1.1 x U s 0.85...1.1 x U s — —<br />
switching off 0.7...0.35 x U s 0.7...0.35 x U s 1.1...0.5 x U s 1.1...0.5 x U s<br />
Power absorbed<br />
AC 2.7 VA 4.5 VA 330 VA 380 VA<br />
DC – 2 W 330 W 380 W<br />
Weight 63 g 63 g 64 g 64 g<br />
Type designation<br />
KT 3-160-PE-1W<br />
KT 3-400-PE-1W<br />
KT 3-160-PE-2W<br />
KT 3-400-PE-2W<br />
KT 3-160-PE-PF<br />
KT 3-400-PE-PF<br />
KT 3-160-PF<br />
KT 3-400-PF<br />
Weight KT 3-160/400-PE-1W 34 g<br />
KT 3-160/400-PE-2W 60 g<br />
KT 3-160/400-PE-PF 52 g<br />
KT 3-160/400-PF 31 g<br />
Type designation<br />
KT 3-160-UA../KT 3-400-UA<br />
24 V 50/60<br />
110... 127 V 50/60<br />
208... 240 V 50/60<br />
380... 480 V 50/60<br />
24 VDC<br />
110... 127 VDC<br />
220... 250 VDC<br />
KT 3-160-AA-.../KT 3-400-AA<br />
24 V 50/60<br />
110...127 V 50/60<br />
208... 240 V 50/60<br />
380... 480 V 50/60<br />
24VDC<br />
110... 127 VDC<br />
220... 250 VDC
Accessories: <strong>Circuit</strong> <strong>Breakers</strong> KTA 3-160S(4)... KTA 3-400S(4)<br />
Lockable twist knob handle<br />
For KT 3-400-... declared value in ( )<br />
Locking device for toggle operator<br />
u Lockable with padlock<br />
u Prevents unauthorized operation<br />
Terminal cover<br />
Door-mounted handle with interlock<br />
Enclosures (For KTA 3-25)<br />
u Shock protection<br />
u For mounting in doors, covers,<br />
enclosures<br />
u Lockable with 3 padlocks f 6...8 mm in<br />
ON or OFF-position<br />
u To be mounted together with lockable<br />
twist knob and extention shaft<br />
Weight Lockable knob 250 g<br />
Extention shaft 100 g<br />
Lockable twist knob<br />
operating mechanism<br />
Door-mounted handle with<br />
interlock<br />
Extention shaft<br />
KT 3-400-HT<br />
Colour Type designation<br />
black/grey KT 3-160-HN<br />
red/yellow KT 3-160-HRY<br />
black/grey KT 3-400-HN<br />
red/yellow KT 3-400-HRY<br />
Weight 400 g<br />
Type designation<br />
KT 3-160-DS<br />
Weight 30 g KT 3-400-DS<br />
Type designation<br />
KT 3-160-HA<br />
KT 3-250-HA<br />
Weight 30 g KT 3-400-HA<br />
u Pre-stamped for 2 signal lamps and including terminals for ground and neutral conductors<br />
Technical data<br />
Degree of protection<br />
KT 3-25-KA IP 41<br />
KT 3-25-KAZ with seal and protection diaphragm IP 55<br />
Ambient temperature -25 C... 40 C<br />
Installation of unit<br />
<strong>Circuit</strong> breaker including auxiliary switch block<br />
and release control switch block snap-on<br />
Fitting<br />
Mounting holes 5 mm<br />
Outside sealed zone 2<br />
Cable entries<br />
Double-step cut-outs PG 16 (Ø 23 mm) or PG 21 (Ø 29 mm) 2 top. 2 bottom<br />
Colour Type designation<br />
red/yellow KT 3-400-HTRY<br />
red/yellow KT 3-400-HTRYS*<br />
Extention shaft<br />
KT 3-400-HT<br />
*Security switch for automotive industry<br />
Type [mm] with extention shaft<br />
by by<br />
reducing shifting<br />
a a min. a min. a max.<br />
KTA 3-160S(4) 171 201 284 301<br />
KTA 3-250S(4) 185 225 298 315<br />
KTA 3-400S(4) 185 225 298 315<br />
Type designation Weight<br />
KT 3-25-KA 250 g<br />
KT 3-25-KAZ 258 g<br />
Dimensions [mm]
SHORT CIRCUIT CO-ORDINATION SELECTION CHART<br />
Contactors : S + S CA3/4/6 <strong>Circuit</strong> <strong>Breakers</strong> : S+S KTA 3-25…400<br />
RATED OPERATIONAL VOLTAGE U e : 415 V, 50 Hz<br />
TEST VOLTAGE = 415+5% : 436 V, 50 HZ<br />
RATED CONDITIONAL S.C. CURRENT Iq : 65 kA (rms symmetrical)<br />
AS PER IEC 947-4-1 (1990)<br />
TYPE-2 DIRECT-ON-LINE STARTING<br />
NOM. MOTOR<br />
RATING/CURRENT<br />
CIRCUIT BREAKER CONTACTOR<br />
4-POLE 415V/1500 RPM MOTORS<br />
Rating Current Type Thermal Magn. Type I AC-3<br />
(kW) (A) (A) (A) (A)<br />
0.19 0.60 KTA 3-25 0.40-0.63 6.9 CA 4-5/CA 3-9 5.3/9<br />
0.25 0.80 0.63-1.00 11.0 CA 4-5/CA 3-9 5.3/9<br />
0.37 1.10 1.00-1.60 18.0 CA 4-5/CA 3-9 5.3/9<br />
0.55 1.50 1.00-1.60 18.0 CA 4-5/CA 3-9 5.3/9<br />
0.75 1.80 1.60-2.50 28.0 CA 4-5/CA 3-9 5.3/9<br />
1.10 2.60 2.50-4.00 44.0 CA 3-16 16<br />
1.50 3.40 2.50-4.00 44.0 CA 3-16 16<br />
2.20 4.80 4.00-6.30 69.0 CA 3-23 23<br />
3.00 6.50 6.3-10.00 110.0 CA 3-23 23<br />
4.00 8.20 6.3-10.00 110.0 CA 3-23 23<br />
3.00 6.50 KTA 3-25+KTL 6.30-10.0 110.0 CA 3-16 16<br />
4.00 8.20 6.30-10.0 110.0 CA 3-16 16<br />
5.50 11.00 10.0-16.0 176.0 CA 3-23 23<br />
7.50 14.00 10.0-16.0 176.0 CA 3-23 23<br />
9.00 17.00 16.0-20.0 220.0 CA 3-23 23<br />
11.00 21.00 20.0-25.0 275.0 CA 3-23 23<br />
15.00 28.00 KTA 3-100 25.0-40.0 560.0 CA 3-30 30<br />
18.50 34.00 25.0-40.0 560.0 CA 3-37 39<br />
22.00 40.00 25.0-40.0 560.0 CA 3-43 45<br />
30.00 55.00 40.0-63.0 882.0 CA 3-60 60<br />
37.00 66.00 63.0-90.0 1260 CA 3-72 72<br />
45.00 80.00 KTA-3-160S 80-100 1200 CA 6-85 85<br />
55.00 100.00 100-125 1500 CA 6-105 105<br />
75.00 135.00 125-160 1900 CA 6-140 140<br />
90.00 160.00 125-160 1900 CA 6-170 170<br />
110.00 200.00 KTA 3-250S 160-200 2400 CA 6-210 210<br />
132.00 230.00 200-250 3000 CA 6-250 250<br />
160.00 270.00 KTA 3-400S 250-320 3800 CA 6-300 300<br />
200.00 350.00 320-400 4800 CA 6-420 420<br />
TYPE-2 STAR-DELTA STARTING<br />
NOM. MOTOR RATING/ CIRCUIT BREAKER CONTACTOR CONTACTOR<br />
CURRENT Main & Delta Star<br />
4-POLE 415V/1500 RPM MOTORS<br />
Rating Line Phase<br />
(kW) (A) (A) Type Thermal Magn. Type I AC-3 Type I AC-3<br />
(A) (A) CA. (A) CA (A)<br />
1.50 3.40 2.00 KTA 3-25 2.50-4.00 44.0 3-16 16 3-9 9<br />
2.20 4.80 2.77 4.00-6.30 69.0 3-23 23 3-9 9<br />
3.00 6.50 3.75 KTA 3-25 + 6.30-10.0 110.0 3-16 16 3-9 9<br />
4.00 8.20 4.73 KTL 3-65 6.30-10.00 110.0 3-16 16 3-9 9<br />
5.50 11.00 6.35 10.0-16.0 176.0 3-23 23 3-9 9<br />
7.50 14.00 8.08 10.0-16.0 176.0 3-23 23 3-9 9<br />
9.00 17.00 9.81 16.0-20.0 220.0 3.23 23 3-9 9<br />
11.00 21.00 12.10 20.0-25.0 275.0 3-23 23 3-9 9<br />
15.00 28.00 16.20 KTA-3-100 25.0-40.0 560.0 3-30 30 3-12 12<br />
18.50 34.00 19.60 25.0-40.0 560.0 3-30 30 3-12 12<br />
22.00 40.00 23.10 25.0-40.0 560.0 3-30 30 3-16 16<br />
30.00 55.00 31.80 40.0-63.0 882.0 3-43 45 3-23 23<br />
37.00 66.00 38.10 63.0-90.0 1260 3-72 72 3-30 30<br />
45.00 80.00 46.20 KTA 3-160S 80-100 1200 6-85 85 3-30 30<br />
55.00 100.00 57.70 100-125 1500 6-85 85 3-37 39<br />
75.00 135.00 77.90 125-160 1900 6-140 140 3-60 60<br />
90.00 160.00 92.40 125-160 1900 6-140 140 3-60 60<br />
110.00 200.00 116.00 KTA 3-250S 160-200 2400 6-210 210 6-85 85<br />
132.00 230.00 133.00 200-250 3000 6-250 250 6-85 85<br />
160.00 270.00 156.00 KTA 3-400S 250-320 3800 6-300 300 6-105 105<br />
200.00 350.00 202.00 320-400 4800 6-420 420 6-140 140
Pub: S+S/MPCB/INDIA/001<br />
CALCUTTA<br />
Allen-Bradley India Limited<br />
III Floor,<br />
Shivam Chambers<br />
No. 53, Syed Amir Ali Avenue<br />
Calcutta-700 019<br />
Tel : (91)-33-2405274<br />
(91)-33-2407557<br />
(91)-33-2400650<br />
Fax: (91)-33-2405263<br />
MUMBAI<br />
Allen-Bradley India Limited<br />
C-312, Gokul Arcade<br />
Abasheb Garware<br />
Vile Parle (East)<br />
Mumbai-400 052<br />
Tel : (91)-22-8377044<br />
(91)-22-8377051<br />
(91)-22-8377108<br />
(91)-22-8208229<br />
(91)-22-8377820<br />
(91)-22-8378229<br />
Fax: (91)-22-8377049<br />
CHANDIGARH<br />
Tel : (91)-172-678526<br />
(91)-9814027002<br />
sprecher + schuh range of products:<br />
Our Offices in India :<br />
Registered Office :<br />
Factory and Northern<br />
Region Sales Office<br />
SAHIBABAD<br />
Allen-Bradley India Limited<br />
C-11, Industrial Area<br />
Site-IV, Sahibabad-201 010<br />
Tel : (91)-120-4777489-95, (91)-120-4771113<br />
Fax: (91)-120-4771115, (91)-120-4770822, (91)-98102-42014<br />
PUNE<br />
Allen-Bradley India Limited<br />
II Floor, Chaitraban<br />
Pune-Mumbai Road, Wakadewadi<br />
Pune-411 042<br />
Telefax : (91)-20-5512921-22<br />
(91)-20-5512323<br />
(91)-20-4001370 (D)<br />
VADODARA<br />
Allen-Bradley India Limited<br />
4, Shrey Nager, Vibhag-1,<br />
Behind Alembic Stores,<br />
Subhanpura, Vadodara-390 023<br />
Tel : (91)-265-386315<br />
Telefax: (91)-265-386110<br />
(91)-9824077871<br />
BANGALORE<br />
Allen-Bradley India Limited<br />
No. 105, Parvathi Plaza<br />
Richmond Road<br />
Bangalore-560 025<br />
Tel : (91)-80-2244818<br />
Resident Engineers at following locations:<br />
AHMEDABAD<br />
Tel : 9824060339<br />
(079)-5461374<br />
(91)-80-2243256<br />
(91)-80-2291585<br />
(91)-80-2246603<br />
Fax: (91)-80-2244743<br />
CHENNAI<br />
Allen-Bradley India Limited<br />
2 J, Second Floor<br />
Mount Chambers<br />
758, Mount Road<br />
Chennai-600 002<br />
Tel : (91)-44-8551872<br />
(91)-44-8594116<br />
(91)-44-8594117<br />
Fax: (91)-44-8551888<br />
SECUNDERABAD<br />
Allen-Bradley India Limited<br />
102 & 103, Hanuman Sharan<br />
Aprts, Park Avenue Colony<br />
Prender Ghast Road<br />
Secunderabad-500 003<br />
Tel : (91)-40-7841556<br />
Telefax: (91)-40-7841396<br />
● <strong>Motor</strong> <strong>Protection</strong> <strong>Circuit</strong> <strong>Breakers</strong> ● Thermistor <strong>Protection</strong> Relays<br />
● Contactors and Control Relays ● Electronic <strong>Motor</strong> <strong>Protection</strong> Relays<br />
● Thermal Overload Relays ● Electronic <strong>Motor</strong> Control and <strong>Protection</strong> System<br />
Bringing Together Leading Brands in Industrial <strong>Automation</strong><br />
Specifications subject to change.<br />
COIMBATORE<br />
Tel : (91)-422-498188<br />
Fax: (91)-422-493394