FIRE SAFETY

TABLE 3.14.: REQUIRED NUMBER OF MEANS OF EGRESS

CRITERIA

i. ANY BUILDING,

FLOOR, STOREY

ii. LOAD LESS THAN

500

NUMBER OF EXITS

MINIMUM 2 MEANS OF EGRESS

MINIMUM 2 EXITS

TABLE 3.15.a: REMOTENESS OF MEANS OF EGRESS

BUILDING

NUMBER OF EXITS

MEASUREMENT OF DISTANCE

22.05m

iii. MIDRISE,

SPRINKLERED

1/3 OF FLOOR

DIAGONAL

SHORTEST WALKING DISTANCE BETWEEN

EXITS

42m

68.78m

UAE Fire and Life Safety Code of Practice, Sep 2018, Chapter 1

Business:

An occupancy used for the transaction of business other than

mercantile, usually used for office, professional or service-type

transactions, including storage of records and accounts.

Group B: Offices.

Ground floor retail: Group C: commercial.

DM Regulations Feb 2013, Article 4

The vertical distance that is measured from the ground surface level to the highest point of the height of the building roof.

UAE Fire and Life Safety Code of Practice, Sep 2018, Chapter 1

The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having occupiable or usable floors between 15m to 23m from

the lowest grade or lowest level of Fire Services Access into that occupancy is categorized as Mid Rise Building.

Calculation:

To the highest occupied level ceiling: 22.05

Building falls under Mid Rise Category.

BUILDING USE: OFFICE (OCCUPANT LOAD FACTOR 9.32sqm/ PERSON)

OCCUPANT LOAD: 1020.02/9.32= 110 PEOPLE

50 - 500 PEOPLE = 2 EXITS

REQUIRED DISTANCE BETWEEN CORES= 68.78m/ (1/3) = 22.93m

BUILDING CORE DISTANCE= 42m > REQUIRED 22.93m

UAE Fire and Life Safety Code of Practice, Sep 2018, Chapter 3

The number of means of egress shall be sufficient to accommodate the occupant load and

complying with the travel distance requirements. Number of exits shall comply with table 3.4.

Building Category And Applied Code Low Rise / High Rise Implications Fire Exit Cores Number & Distance

EXIT ACCESS

EXIT

EXIT DISCHARGE

BASEMENT2 BASEMENT2 LEVEL - BASEMENT2 LEVEL - LEVEL TYPICAL - LEVEL TYPICAL - LEVEL TYPICAL - LEVEL DISCHARGE - (GROUND) DISCHARGE LEVEL- (GROUND) DISCHARGE LEVEL- (GROUND) LEVEL-

INWARD SWING INWARD SWING INWARD SWING INWARD SWING INWARD SWING INWARD SWING OUTWARD SWING OUTWARD SWING OUTWARD SWING

UAE Fire and Life Safety Code of Practice, Sep 2018, Chapter 3, Pg. 237

Means of Egress: A continuous and unobstructed way of travel from any point in a building or structure to a public way consisting of three separate

and distinct parts: (1) the exit access, (2) the exit, and (3) the exit discharge.

Means Of Egress

UAE Fire and Life Safety Code of Practice, Sep 2018, Chapter 3, Pg. 248

Door leaves required to be of the side-hinged or pivoted-swinging type shall swing in the direction of egress travel where

serving a room or area with an occupant load of 50 or more, or serving horizontal exit, or serving high hazard content

room or serving an exit enclosure.

Direction Of Egress & Discharge Level