BRITISH STANDARD
BS EN
50172:2004
BS
5266-8:2004
Emergency escape
lighting systems
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
The European Standard EN 50172:2004 has the status of a
British Standard
ICS 91.160.00
BS EN 50172:2004
National foreword
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
This British Standard, was
published under the authority
of the Standards Policy and
Strategy Committee on
20 December 2004
© BSI 20 December 2004
ISBN 0 580 45157 7
This British Standard is the official English language version of EN 50172:2004 and
implements it as duel numbered British Standard BS 5266-8:2004.
This part of the BS 5266 series partially supersedes BS 5266-1:1999, Emergency
lighting. Code of practice for the emergency lighting of premises other than cinemas and
certain other specified premises used for entertainment, which is currently under
revision to remove requirements conflicting with EN 50172:2004 as follows.
BS EN 50172:2004 specifies requirements whereas BS 5266-1 is a code of practice giving
recommendations.
The requirements of BS EN 50172 alter the duration period and frequency required for
self-contained luminaires (see 7.2).
A number of the requirements which are given in BS 5266-1:1999 are expanded,
particularly the size of open area that requires emergency lighting and the procedures
to reduce the impact of the failure of any single luminaire. Appropriate product
standards are also identified.
Compliance with this standard will assist users in meeting the requirements of the
Workplace Directive, the Construction Products Directive and the forthcoming
Regulatory Reform Order.
The UK participation in its preparation was entrusted by Technical Committee CPL/34,
Lamps and related equipment, to Subcommittee CPL/34/9, Emergency lighting, which
has the responsibility to:
— aid enquirers to understand the text;
— present to the responsible international/European committee any enquiries
on the interpretation, or proposals for change, and keep the UK interests
informed;
— monitor related international and European developments and promulgate
them in the UK.
A list of organizations represented on this subcommittee can be obtained on request to
its secretary.
Cross-references
The British Standards which implement international or European publications
referred to in this document may be found in the BSI Catalogue under the section
entitled “International Standards Correspondence Index”, or by using the “Search”
facility of the BSI Electronic Catalogue or of British Standards Online.
This publication does not purport to include all the necessary provisions of a contract.
Users are responsible for its correct application.
Compliance with a British Standard does not of itself confer immunity from
legal obligations.
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 12, an inside back cover and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
Amendments issued since publication
Amd. No. Date Comments
EUROPEAN STANDARD EN 50172
NORME EUROPÉENNE
EUROPÄISCHE NORM August 2004
ICS 91.160.00
English version
Emergency escape lighting systems
Systèmes d'éclairage de sécurité
Sicherheitsbeleuchtungsanlagen
This European Standard was approved by CENELEC on 2004-03-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2004 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50172:2004 E
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
EN 50172:2004 - 2 -
Foreword
This European Standard was prepared by the former CENELEC BTTF 62-8, Emergency lighting systems.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50172 on
2004-03-01.
For emergency lighting systems, it should be read in conjunction with EN 50171 and EN 1838.
Attention is drawn to the Council Directive 92/58/EEC of 24 June 1992 on the minimum requirements for
provision of safety and/or health signs at work.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2005-03-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2007-03-01
_____________
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
- 3 - EN 50172:2004
Contents
Page
1 Scope...........................................................................................................................................4
2 Normative references ..................................................................................................................4
3 Definitions ....................................................................................................................................4
4 Emergency escape lighting .........................................................................................................6
5 Emergency escape lighting design..............................................................................................7
6 Emergency escape lighting system records and log book ..........................................................8
7 Servicing and testing ...................................................................................................................9
Annex A (informative) A-deviations..................................................................................................11
EN 50172:2004 - 4 -
1 Scope
This European Standard specifies the provision of illumination of escape routes and safety signs in the
event of failure of the normal supply, and specifies the minimum provision of such emergency lighting
based on the size, type and usage of the premises. This standard relates to the provision of electric
emergency escape lighting in all work places and premises open to the public.
This European Standard does not cover private domestic premises but its provisions are applicable to
common access routes within multi-storey dwellings.
This European Standard is also applicable to standby lighting used as emergency escape lighting.
There are emerging way guidance techniques that, when applied to escape routes in addition to
conventional emergency lighting luminaires, can enhance its effectiveness in an emergency.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 81-1 Safety rules for the construction and installation of lifts and service lifts -
Part 1: Electric lifts
EN 1838:1999
Lighting applications - Emergency lighting
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
EN 13032 (series)
EN 50171
EN 50272-2
Light and lighting - Measurement and presentation of photometric data of
lamps and luminaires
Central power supply systems
Safety requirements for secondary batteries and battery installations
Part 2: Stationary batteries
EN 60529 Degrees of protection provided by enclosures (IP Code) (IEC 60529)
EN 60598-2-22:1998
EN 62034 1)
Luminaires - Part 2-22: Particular requirements - Luminaires for emergency
lighting (IEC 60598-2-22:1997, modified)
Automatic test system for battery powered emergency escape lighting
HD 384/HD 60364 series Electrical installations of buildings (IEC 60364 series, modified)
ISO 8528-12
3 Definitions
Reciprocating internal combustion engine driven alternating current generating
sets - Part 12: Emergency power supply to safety devices
For the purposes of this standard the following definitions apply:
3.1
premises
the whole or part of a building treated as a single unit for the purposes of applying this standard
1) At draft stage.
- 5 - EN 50172:2004
3.2
escape route
a route designated for escape to a place of safety in the event of an emergency
3.3
emergency escape route lighting
that part of emergency escape lighting provided to ensure that the means of escape can be effectively
identified and safely used at all times when the premises are occupied
3.4
open area (anti-panic)
areas of undefined escape routes in halls or premises larger than 60 m 2 floor area or smaller areas if
there is additional hazard such as use by a large number of people
3.5
place of safety
a place in which persons are in no danger
3.6
mounting height
the vertical distance between a luminaire and the floor
3.7
combined emergency luminaire
a luminaire containing two or more lamps, at least one of which is energized from the emergency lighting
supply and the other(s) from the normal lighting supply. A combined emergency luminaire is either
maintained or non-maintained
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
3.8
emergency exit
a way out that is used during an emergency
3.9
final exit
the terminal point of an escape route
3.10
luminaire
apparatus which distributes, filters or transforms the light transmitted from one or more lamps and which
includes all the parts necessary for supporting, fixing and protecting the lamps, but not the lamps
themselves, and which includes where necessary circuit auxiliaries together with the means for
connecting them to the supply
3.11
maintained emergency luminaire
luminaire in which the emergency lighting lamps are energized at all times when normal or emergency
lighting is required
[EN 60598-2-22:1998, 22.3.5]
3.12
non-maintained emergency luminaire
luminaire in which the emergency lighting lamps are in operation only when the supply to the normal
lighting fails
[EN 60598-2-22:1998, 22.3.6]
3.13
internally illuminated safety sign
a sign that is illuminated, when required, by an internal source
[EN 1838:1999, 3.11]
EN 50172:2004 - 6 -
3.14
externally illuminated safety sign
a sign that is illuminated, when required, by an external source
[EN 1838:1999, 3.10]
3.15
required battery duration
duration of emergency operation of the battery required for the function
3.16
rated duration of emergency operation
time, as claimed by the manufacturer, that the rated emergency lumen output is provided
[EN 60598-2-22:1998, 22.3.15]
4 Emergency escape lighting
4.1 General
The purpose of emergency escape lighting is to ensure the lighting is provided promptly, automatically
and for a suitable time in a specified area when the normal power supply to the normal lighting fails. The
installation shall ensure that emergency escape lighting fulfils the following functions:
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
a) to illuminate escape route signs;
b) to provide illumination onto and along such routes as to allow safe movement towards and through
the exits provided to a place of safety;
c) to ensure that fire alarm call points and fire equipment provided along escape routes can be readily
located and used;
d) to permit operations concerned with safety measures.
Emergency escape lighting shall be activated not only on complete failure of the supply to the normal
lighting but also on a localized failure such as a final circuit failure.
Emergency escape lighting is not designed to enable normal operations to be continued on the premises
in the event of failure of normal or standby lighting.
Full details of levels and measurement of illuminance and adaptation are specified in EN 1838 and
EN 13032.
The wiring rules of HD 384 / HD 60364 shall be complied with.
4.2 Identification and luminance of emergency exit signs
Where direct sight of an exit is not possible and doubt may exist as to its location, a directional sign (or
series of signs) shall be provided, placed such that a person moving towards it will be directed towards an
emergency exit.
An exit or directional sign shall be in view at all points along the escape route.
All signs marking exits and escape routes shall be uniform in colour and format, and their luminance shall
comply with EN 1838.
NOTE Maintained exit signs should be considered for applications where occupants may be unfamiliar with the building.
- 7 - EN 50172:2004
4.3 Escape route lighting
The objective of escape route lighting is to enable safe exit for occupants by providing appropriate visual
conditions and direction finding on escape routes and to ensure that fire fighting and safety equipment
can be readily located and used.
4.4 Open area (anti-panic) lighting
The objective of open area (anti-panic) lighting is to reduce the likelihood of panic and to enable safe
movement of occupants towards escape routes by providing appropriate visual conditions and direction
finding. It is used in areas of undefined escape routes in halls or premises larger than 60 m 2 floor area or
smaller areas if there is additional hazard such as use by a large number of people.
NOTE Condition BD3 or BD4 of HD 384 also defines areas that require emergency lighting.
4.5 Emergency lighting for high risk task area lighting
The objective of high-risk task area lighting is to ensure the safety of people involved in a potentially
dangerous process or situation and to enable proper shut down procedures for the safety of other
occupants of the premises.
4.6 Standby lighting
If standby lighting is used to provide emergency escape lighting, the installation shall comply with the
provisions of this standard and the appropriate product and wiring standards.
5 Emergency escape lighting system design
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
5.1 Plan of premises
In order to ensure that the emergency lighting system is engineered in accordance with EN 1838 plans
showing the layout of the building and of all existing or proposed escape routes, fire alarm call points and
fire fighting equipment and indicating the positions of all structural items which may offer obstruction to
escape shall be provided before commencing system design.
5.2 Failure of normal supply to part of premises
Emergency escape lighting shall operate, in the event of failure of any part of the normal lighting supply.
Non-maintained and combined non-maintained emergency luminaires have to operate in the event of
failure of a normal lighting final circuit. In all cases, arrangements shall be made to ensure that local
emergency escape lighting will operate in the event of failure of normal supply to the corresponding local
area.
5.3 System integrity
The provision of highly reliable emergency escape lighting is essential. The illumination by the emergency
escape lighting system of a compartment of the escape route shall be from two or more luminaires so that
the failure of one luminaire does not plunge the route into total darkness or make the directional finding
effect of the system ineffective. For the same reason, two or more luminaires shall be used in each open
area (anti-panic).
NOTE It is not normally possible to cater for an interruption of the normal lighting due solely to the failure of an individual lamp,
consideration should therefore be given to methods of eliminating any probable hazard which might arise due to the failure of this
lamp.
EN 50172:2004 - 8 -
5.4 Specific areas requiring emergency lighting
Where national regulations do not apply, the provisions of emergency escape lighting given in EN 1838
cover the routes and locations detailed in 4.2 to 4.5 of this standard. Other areas of hazard or areas that
may need access in a normal lighting failure also require emergency lighting and are defined in 5.4.1 and
5.4.2 of this standard.
5.4.1 External areas in the immediate vicinity of exits
To assist dispersal to a place of safety, the external areas in the immediate vicinity of final exits should be
illuminated in accordance with the illumination level for escape routes given in EN 1838.
5.4.2 Lift car
Lifts present a problem because the experience of being confined in the dark within a small space for an
indefinite period is not only unpleasant, but may cause harm to those who are nervous or suffer from
claustrophobia. Emergency lighting as specified for open area (anti-panic) lighting in EN 1838 shall
therefore be fitted in lifts in which persons may travel. The emergency lighting can either be selfcontained
or powered from a central supply in which case a fire protected supply will be required.
NOTE For further guidance refer to EN 81-1.
5.5 Emergency escape lighting equipment
5.5.1 Luminaires
Emergency escape lighting luminaires shall be designed and constructed in accordance with
EN 60598-2-22. They shall be selected to be appropriate for their location.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
NOTE If used in areas with risk of explosion, the luminaires shall comply with the relevant standards and the 94/9/EC Directive.
5.5.2 Central power supply systems
Battery powered central power supply systems shall be designed and constructed in accordance with
EN 50171 and the battery safety requirements of EN 50272-2 shall be complied with.
Reciprocating internal combustion engine driven alternating current generating sets: emergency power
supply to safety devices shall be constructed in accordance with ISO 8528-12.
5.5.3 Automatic emergency lighting testing systems
Automatic emergency lighting testing systems shall be designed, constructed and installed in accordance
with the relevant requirements of national standards or national regulations.
5.6 Categories of operation
The mode of operation and duration shall comply with the results of the risk assessment in accordance
with national regulations.
6 Emergency escape lighting system records and reporting
6.1 General
On completion of the work, drawings of the emergency escape lighting installation shall be provided and
retained on the premises. The drawings shall be made in accordance with Subclause 514.5.1 of
HD 384.5. In particular, they shall identify all luminaires and the main components, and shall be regularly
updated with any subsequent changes to the system. These drawings shall be signed by a competent
person to verify that the design meets the requirements of this standard.
- 9 - EN 50172:2004
In addition, a logbook conforming to 6.3 shall be provided for the recording of routine examinations, tests,
defects and alterations.
These shall be available as either a manual record or as a hard copy obtained from an automatic testing
device.
6.2 System record
On completion of a yearly inspection and test schedule as required in the periodic inspection a test
certificate should be supplied to the person responsible for the premises.
6.3 Log book (Reporting)
A log book shall be kept on the premises in the care of a responsible person appointed by the
occupier/owner and shall be readily available for examination by any duly authorized person.
The log book shall be used to record at least the following information:
a) date of commissioning of the system including any certificate relating to alterations;
b) date of each periodic inspection and test;
c) date and brief details of each service, inspection or test carried out;
d) dates and brief details of any defects and of remedial action taken;
e) date and brief details of any alteration to the emergency lighting installation;
f) if any automatic testing device is employed, the main characteristic and the mode of operation of that
device shall be described.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
NOTE 1 The logbook may also include pages relating to other safety records, e.g. fire alarms. Details of replacement components
of luminaires such as lamp type, battery and fusing may also be recorded in the logbook.
NOTE 2 An appropriate print out of data from an automatic testing device meets the requirements of this clause.
7 Servicing and testing
7.1 General
When automatic testing devices are used, the information shall be recorded monthly. For all other
systems, the tests shall be carried out as described in 7.2 and the results recorded.
Regular servicing is essential. The occupier/owner of the premises shall appoint a competent person to
supervise servicing of the system. This person shall be given sufficient authority to ensure the carrying
out of any work necessary to maintain the system in correct operation.
7.2 Routine inspections and tests
Where national regulations do not apply, the following shall be met.
7.2.1 General
Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of
testing of the emergency lighting system or during the subsequent recharge period, all full duration tests
shall wherever possible be undertaken preceding time of low risk to allow for battery recharge.
Alternatively, suitable temporary arrangements shall be made until the batteries have been recharged.
The following minimum inspections and tests shall be carried out at the intervals recommended in 7.2.2 to
7.2.4. The regulating authority may require specific tests.
EN 50172:2004 - 10 -
7.2.2 Daily
Indicators of central power supply shall be visually inspected for correct operation.
NOTE This is a visual inspection of indicators to identify that the system is in a ready condition and does not require a test of
operation.
7.2.3 Monthly
If automatic testing devices are used, the results of the short duration tests shall be recorded.
Tests shall be carried out as follows:
a) Switch on in the emergency mode each luminaire and each internally illuminated exit sign from its
battery by simulation of a failure of the supply to the normal lighting for a period sufficient to ensure
that each lamp is illuminated.
NOTE The period of simulated failure should be sufficient for the purpose of this clause whilst minimising damage to the
system components e.g. lamps.
During this period, all luminaires and signs shall be checked to ensure that they are present, clean
and functioning correctly.
At the end of this test period, the supply to the normal lighting should be restored and any indicator
lamp or device checked to ensure that it is showing that the normal supply has been restored.
b) In addition to a), for central battery systems, the correct operation of system monitors shall be
checked.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
c) In addition to a), for generating sets, refer to the requirement of ISO 8528-12.
7.2.4 Annually
If automatic testing devices are used, the results of the full rated duration test shall be recorded.
For all other systems the monthly inspection shall be carried out and the following additional tests made:
a) each luminaire and internally illuminated sign shall be tested as per 7.2.3 but for its full rated duration
in accordance with the manufacturer's information;
b) the supply of the normal lighting shall be restored and any indicator lamp or device checked to
ensure that it is showing that normal supply has been restored. The charging arrangements should
be checked for proper functioning;
c) the date of the test and its results shall be recorded in the system logbook;
d) in addition, for generating sets, refer to the requirements of ISO 8528-12.
- 11 - EN 50172:2004
Annex A
(informative)
A-deviations
A-deviation: National deviation due to regulations, the alteration of which is for the time being outside the
competence of the CENELEC national member.
This European Standard does not fall under any Directive of the EC.
In the relevant CENELEC countries these A-deviations are valid instead of the provisions of the European
Standard until they have been removed.
Clause
Deviation
4 and 5 Italy
The following national laws and regulations apply as regards emergency escape lighting.
Decreto del Ministero dell’Interno “Norme di sicurezza antincendi per la costruzione e
l’esercizio di autorimesse e simili” (01-02-1986)
This law deals with fire protection of garages and tower garages; in particular Clause 5
makes mandatory the emergency lighting installations for garages containing a number of
cars higher than 300.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
Decreto del Ministero dell’Interno n. 246 “Norme di sicurezza antincendi per gli edifici
di civile abitazione” (16-05-1987)
This law deals with fire protection of premises; in particular Clause 5 makes mandatory the
emergency lighting installations for premises higher 32 m.
Decreto del Ministero dell’interno “Norme di prevenzione incendi per l’edilizia
scolastica” (26-08-1992)
This law deals with fire protection of school premises; in particular Subclause 7.1 makes
mandatory the emergency lighting installations for schools having simultaneously a number
of people higher than 100.
Decreto del Ministero dell’interno “Approvazione della regola tecnica di prevenzione
incendi per la costruzione e l’esercizio delle attività turistico-alberghiere”
(09-04-1994)
This law deals with fire protection of hotels and guest houses; in particular Chapter II,
Clause 9 makes mandatory the emergency lighting installations for these premises with the
requirement of minimum operation time of emergency escape lighting.
Decreto del Ministero dell’interno “Approvazione della regola tecnica di prevenzione
incendi per la progettazione, la costruzione e l’esercizio dei locali di intrattenimento e
di pubblico spettacolo” (19-08-1996)
This law deals with fire protection of public show locations; in particular Chapter XIII,
Subclause 13.1 makes mandatory the emergency lighting installations for these premises
with the requirement of minimum operation time of emergency escape lighting.
Decreto del Ministero dell’interno “Norme di sicurezza per la costruzione e l’esercizio
di impianti sportivi” (18-03-1996)
This law deals with safety of sports installations; in particular it refers directly to Framework
Law No.168 of 1986.03.01.
Decreto del Ministero dell’interno “Approvazione della regola tecnica di prevenzione
incendi per la progettazione, la costruzione e l’esercizio delle strutture sanitarie
pubbliche e private” (18-09-2002)
This law deals with fire protection of medical locations; in particular Chapter II, Clause 6
makes mandatory the emergency lighting installations for these premises with the
requirement of minimum operation time of emergency escape lighting.
EN 50172:2004 - 12 -
4, 5 and
7
France
Emergency escape lighting in France is the concern of many statutory regulations.
The regulation changes according to the type (high-rise or not) and the purpose (public,
workers, private) of the premises
Regulation relating to security in public establishments: Arrêté du 25/06/1980 modified.
Regulation relating to security in workers establishments: Arrêté du 26/02/2003.
Regulation relating to the security in the high-rise buildings: Arrêté du 18/10/1977.
Regulation relating to security in residential buildings: Arrêté du 31/01/1986.
These regulations include different requirements on the following clauses:
4) The need for emergency escape lighting
4) Illumination for emergency escape lighting
5) Emergency escape lighting design
5) Choice of appropriate emergency lighting system
7) Emergency escape lighting system records and log book
Germany
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
4
4.2 and
4.4
5
5.4, 5.4.1
and 5.4.2
The requirements of the directive for places of work „Arbeitsstättenrichtlinie” ASR 7/4
"Sicherheitsbeleuchtung" (Emergency escape lighting) and the regulations of the
Professional/trade associations [Berufsgenossenschaften] „Unfallverhütungsvorschriften“
apply.
The necessity of providing safety signs or emergency lighting and their location in special
buildings and areas is governed by statutory building provisions of the Lands of the Federal
Republic of Germany, in particular concerning assembly places, sales areas and hotels, or
individually as a result of the planning permission.
In case of doubt the building supervisory board should be consulted.
The requirements of the directive for places of work „Arbeitsstättenrichtlinie” ASR 7/4
"Sicherheitsbeleuchtung" (Emergency escape lighting) and the regulations of the
Professional/trade associations [Berufsgenossenschaften] „Unfallverhütungsvorschriften“
apply.
The necessity of providing safety signs or emergency lighting and their location in special
buildings and areas is governed by statutory building provisions of the Lands of the Federal
Republic of Germany, in particular concerning assembly places, sales areas and hotels, or
individually as a result of the planning permission.
In case of doubt the building supervisory board should be consulted
__________
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
blank
BS EN
50172:2004
BS
5266-8:2004
BSI — British Standards Institution
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Licensed copy:RMJM, 07/09/2005, Uncontrolled Copy, © BSI
BSI
389 Chiswick High Road
London
W4 4AL
Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001.
Fax: +44 (0)20 8996 7001. Email: orders@bsi-global.com. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: info@bsi-global.com.
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001.
Email: membership@bsi-global.com.
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.