TRIMM, INC.<br />

<strong>TPA</strong>/<strong>GMT</strong> <strong>Fuse</strong> Panel<br />

Key Features<br />

<strong>TPA</strong> <strong>GMT</strong> panels rated up to 200 Amps per side.<br />

Accepts 3 – 50 Amp <strong>TPA</strong> fuses and<br />

.18 – 15 Amp <strong>GMT</strong> type fuses.<br />

1 rack space design saves space and 2 rack<br />

space designs offer more connections.<br />

4 <strong>TPA</strong> positions per side and up to 20 <strong>GMT</strong><br />

positions per side.<br />

Overview Why Specify this <strong>Trimm</strong> Panel?<br />

Multiple Options for <strong>GMT</strong> <strong>TPA</strong> <strong>Fuse</strong> <strong>Panels</strong>:<br />

<strong>Trimm</strong>’s <strong>TPA</strong> <strong>GMT</strong> power distribution units come in<br />

many different configurations. The 1 rack space panel<br />

has 5 <strong>GMT</strong> and 4 <strong>TPA</strong> positions on each side. The 2<br />

rack space panels have either 10 or 20 <strong>GMT</strong> positions<br />

and 4 <strong>TPA</strong> positions on each side. So whether you<br />

need 5, 10, or 20 <strong>GMT</strong>'s per side along with <strong>TPA</strong><br />

fuses, contact <strong>Trimm</strong>.<br />

Set Screw or Compression Lug <strong>TPA</strong> <strong>GMT</strong> <strong>Panels</strong>:<br />

<strong>Trimm</strong> has many different connection options for your<br />

<strong>TPA</strong> <strong>GMT</strong> panels. Set Screw inputs and outputs save<br />

installation time and cost because they do not require<br />

additional terminals or lugs to make connections.<br />

Compression lug inputs provide a proven connection<br />

for your higher amperage circuits.<br />

NEBS Level 3 and Safety Certified:<br />

All of <strong>Trimm</strong>’s <strong>TPA</strong> <strong>GMT</strong> power distribution units are<br />

certified to NEBS Level Three and the most stringent<br />

UL specifications. All of the certification has been<br />

completed by Nationally Recognized Testing<br />

Laboratories to independently verify compliance to the<br />

standards. NEBS Level Three certification is only<br />

given to equipment that has gone through a<br />

comprehensive series of rigorous tests to ensure the<br />

design can survive the toughest situations.<br />

<strong>TPA</strong> <strong>GMT</strong> <strong>Panels</strong> Provide Plenty of Power:<br />

<strong>TPA</strong> fuse positions accept fuses from 3 Amps all the<br />

way to 50 Amps. The <strong>TPA</strong> fuse can provide power to<br />

most switches and routers being used today as well as<br />

other power hungry equipment. <strong>GMT</strong> fuse positions<br />

accept fuses from .18 Amps to 15 Amps. The <strong>GMT</strong><br />

positions give you the ability to protect many smaller<br />

amperage circuits. Combining the two fuse types gives<br />

you the flexibility to protect both higher and lower<br />

amperage loads.<br />

Reliable Design:<br />

<strong>Trimm</strong> has been in business since 1922 and has<br />

shipped power distribution units all over the world. All<br />

panels are tested before leaving our facility to ensure it<br />

works when you install it. Choose <strong>Trimm</strong> as a supplier<br />

who has stood the test of time to get a <strong>TPA</strong> <strong>GMT</strong> fuse<br />

panel that arrives when needed.<br />

200 Amps Per Side for High Power Distribution:<br />

With up to 200 Amps per side, <strong>Trimm</strong>’s <strong>GMT</strong> <strong>TPA</strong> power<br />

distribution units allow you to fully utilize the available<br />

fuse positions. Today’s equipment requires more in a<br />

smaller space. <strong>Trimm</strong>’s panels protect your investment<br />

in power distribution by allowing you to protect up to 400<br />

Amps in two rack spaces.<br />

See next page for product specifications.<br />

TRIMM, INC.<br />

827D1 Rev. A<br />

407 Railroad St. Butner, NC 27509 Phone: 919-575-6100 Toll Free: 800-298-7466 Fax: 919-575-6200 www.trimminc.com


<strong>TPA</strong>/<strong>GMT</strong> <strong>Fuse</strong> Panel<br />

Technical Specifications<br />

Dimensions 19" W x (1.734" H or 3.484" H) x 11" D<br />

Rack Spaces 1 (1U) or 2 (2U)<br />

Mounting See ordering table<br />

Short Term Operating Temperature -5° C to +50° C<br />

Max. Recommended Ambient Up to +50° C<br />

Storage Temperature -40° C to +70° C<br />

Relative Humidity 0-95% noncondensing<br />

Part Number<br />

8271001001<br />

7570210503<br />

7570210502<br />

7570210501<br />

Part Number<br />

8271001001<br />

7570210153<br />

7570210502<br />

7570210501<br />

Input Type<br />

Comp. Lug<br />

(2 hole)<br />

Set screw<br />

Set screw<br />

Set screw<br />

Input Input <strong>GMT</strong> (load share) Output Type Output <strong>TPA</strong> Output <strong>GMT</strong><br />

1” AWG, 4/0 tongue max.<br />

N/A<br />

Barrier strip #8 stud 6 to 20 AWG #6 stud 10 to 20 AWG<br />

(1/4" stud x 5/8" spacing)<br />

(.500" tongue max.) (.312" tongue max.)<br />

4/0 to 4 AWG wire<br />

N/A<br />

Set screw 6 to 22 AWG wire 14 to 26 AWG wire<br />

0 to 6 AWG wire<br />

N/A<br />

Set screw 6 to 22 AWG wire 14 to 26 AWG wire<br />

0 to 6 AWG wire 22 to 6 AWG wire Set screw 6 to 22 AWG wire 14 to 26 AWG wire<br />

TRIMM, INC.<br />

407 Railroad St. Butner, NC 27509 Phone: 919-575-6100 Toll Free: 800-298-7466 Fax: 919-575-6200 www.trimminc.com<br />

Input<br />

Output<br />

7570210153 Back 8271001001 Back<br />

Bus Rating<br />

200 Amps<br />

200 Amps<br />

150 Amps<br />

150 Amps<br />

Voltage<br />

-/+ 24 - 48 VDC<br />

- 48 VDC<br />

- 48 VDC<br />

- 48 VDC<br />

<strong>Fuse</strong> Pos./Side Input Style<br />

4 <strong>TPA</strong> & 5 <strong>GMT</strong> Comp Lug<br />

4 <strong>TPA</strong> & 10 <strong>GMT</strong> Set Screw<br />

4 <strong>TPA</strong> & 20 <strong>GMT</strong> Set Screw<br />

4 <strong>TPA</strong> & 20 <strong>GMT</strong> Set Screw<br />

Voltage<br />

See ordering table<br />

Number of Buses 2 (A/B)<br />

Current<br />

See ordering table<br />

<strong>Fuse</strong> Rating<br />

15 Amps (<strong>GMT</strong>),<br />

50 Amps (<strong>TPA</strong>)<br />

Continuous Load Rating 10.5 A (<strong>GMT</strong>), 40 A (TPM)<br />

<strong>Fuse</strong> Positions See ordering table<br />

Certifications Safety and NEBS Level 3 Certified<br />

Ordering Information for <strong>TPA</strong> <strong>GMT</strong> <strong>Fuse</strong> <strong>Panels</strong><br />

Output Style<br />

Barrier Strip<br />

Set Screw<br />

Set Screw<br />

Set Screw<br />

<strong>TPA</strong> <strong>Fuse</strong><br />

Rack Size<br />

1U, 19"<br />

2U, 19" & 23"<br />

2U, 19" & 23"<br />

2U, 19" & 23"<br />

<strong>GMT</strong> <strong>Fuse</strong><br />

Input<br />

Combined<br />

Combined<br />

Combined<br />

Load-Share<br />

Ordering Information for <strong>GMT</strong> <strong>Fuse</strong>s<br />

Part Number Amps Part Number Amps Part Number Amps Part Number Amps<br />

0300097000 18/100 Amp 0300097003 3/4 Amp 0300097008 3 Amp 0300097010 10 Amp<br />

0300097001 1/4 Amp 0300097004 1 Amp 0300097013 3-1/2 Amp 0300097014 12 Amp<br />

0300097016 3/8 Amp 0300097005 1-1/3 Amp 0300097012 4 Amp 0300097015 15 Amp<br />

0300097002 1/2 Amp 0300097006 1-1/2 Amp 0300097009 5 Amp 0300097100 Dummy<br />

0300097065 65/100 Amp 0300097007 2 Amp 0300097011 7-1/2 Amp 0300097209 <strong>Fuse</strong> Cover<br />

Order part number 7500116741 to adapt the 8271001001 panel to a 23" rack. The part numbers in this table<br />

represent our top sellers. Please call or email sales@trimminc.com with any questions.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!