5 ⁄16″

1 3 ⁄4″

5 ⁄16″

Do not bend duct flanges inward as shown in Fig. 21. This

will affect airflow across heat exchangers and may cause limit

cycling or premature heat exchanger failure. Remove duct

flange completely or bend it inward a minimum of 210° as

shown in Fig. 21.

5 ⁄16″

1 3 ⁄4″

NOTE: For 140 size unit when installed in downflow orientation,

cut the white jumper wire off between terminals PL1-7 and PL1-9.

Do not cut white jumper between terminals PL1-7 and PL1-11.

Refer to Fig. 30 for location of jumper. Cut jumper close to

connector and remove wire to avoid a short circuit.

Step 3—Installation in Horizontal Applications

1 3 ⁄4″

1 3 ⁄4″

5 ⁄16″

Fig. 17—Leveling Legs

A89014

2. For each hole, install nut on bolt and then install bolt and nut

in hole. (Install flat washer if desired.)

3. Install another nut on other side of furnace base. (Install flat

washer if desired.)

4. Adjust outside nut to provide desired height, and tighten inside

nut to secure arrangement.

NOTE: Bottom closure must be used when leveling legs are used.

See Bottom Closure Panel section.

Step 2—Installation in Upflow or Downflow

Applications

NOTE: For downflow applications, this furnace is approved for

use on combustible flooring when special base (available from

manufacturer) Part No. KGASB0201ALL is used. Special base in

not required when this furnace is installed on manufacturer’s Coil

Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is

used.

1. Determine application being installed from Table 1.

2. Construct hole in floor per dimensions specified in Table 1

and Fig. 18.

3. Construct plenum to dimensions specified in Table 1 and Fig.

18.

4. If downflow subbase (KGASB) is used, install as shown in

Fig. 19.

If Coil Assembly Part No. CD5 or CK5 or Coil Box Part No.

KCAKC is used, install as shown in Fig. 20.

NOTE: Remove furnace perforated, discharge duct flanges when

they interfere with mating flanges on coil on downflow subbase.

To remove furnace perforated, discharge duct flange, use wide

duct pliers or duct flange tool or hand seamers to bend flange back

and forth until it breaks off. Be careful of sharp edges. (See Fig.

21.)

Downloaded from www.Manualslib.com manuals search engine

14

The entire length of furnace MUST be supported when

furnace is used in a horizontal position to ensure proper

draining. When suspended, bottom brace supports sides and

center blower shelf. When unit is supported from the ground,

blocks or pad should support sides and center blower shelf

area.

These furnaces can be installed horizontally in either horizontal

left or right discharge position. In a crawlspace, furnace can either

be hung from floor joist or installed on suitable blocks or pad.

Furnace can be suspended from each corner by hanger bolts and

angle iron supports. (See Fig. 22.) Cut hanger bolts (4 each 3/8-in.

all-thread rod) to desired length. Use 1 X 3/8-in. flat washers,

3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in

Fig. 22. Dimples are provided for hole locations. (See Fig. 2.)

AIR DUCTS

Step 1—General Requirements

The duct system should be designed and sized according to

accepted national standards such as those published by: Air

Conditioning Contractors Association (ACCA), Sheet Metal and

Air Conditioning Contractors National Association (SMACNA) or

American Society of Heating, Refrigerating and Air Conditioning

Engineers (ASHRAE) or consult The Air Systems Design Guidelines

reference tables available from your local distributor. The

duct system should be sized to handle the required system design

CFM at the design static pressure.

When a furnace is installed so that the supply ducts carry air

circulated by the furnace to areas outside the space containing the

furnace, the return air shall also be handled by a duct(s) sealed to

the furnace casing and terminating outside the space containing the

furnace.

Secure ductwork with proper fasteners for type of ductwork used.

Seal supply- and return-duct connections to furnace with code

approved tape or duct sealer.

Flexible connections should be used between ductwork and

furnace to prevent transmission of vibration. Ductwork passing

through unconditioned space should be insulated to enhance

system performance. When air conditioning is used, a vapor

barrier is recommended.

Maintain a 1-in. clearance from combustible materials to supply air

ductwork for a distance of 36-in. horizontally from the furnace.

See NFPA 90B or local code for further requirements.

For a furnace not equipped with a cooling coil, the outlet duct shall

be provided with a removable access panel. This opening shall be

accessible when the furnace is installed and shall be of such a size

that the heat exchanger can be viewed for possible openings using