Introduction<br />
<strong>Relay</strong> <strong>couplers</strong> – an overview<br />
Contact materials<br />
AgNi Au (silver-nickel hard gold plated)<br />
For dry loads, measuring and switching circuits, control inputs<br />
(1 mV – 10 V, 0.1 mA – 100 mA).<br />
AgNi 0.15 (fine-grain silver)<br />
Suitable for low to medium loads, AC and DC loads, resistive<br />
and inductive (solenoid valves, fans, heaters); not suitable for<br />
high inrush currents.<br />
AgNi 90/10 (silver-nickel)<br />
Suitable for all loads, constantly low contact-circuit resistances<br />
in the low load range, AC and DC loads, resistive and inductive<br />
(solenoid valves, fans, heaters); not suitable for capacitive inrush<br />
currents.<br />
Contact material<br />
10<br />
Hard gold plating<br />
htv<br />
AgNi 0.15<br />
AgNi 90/10<br />
AgSnO 2 90/10<br />
1 mA 10 mA 100 mA 1 A 10 A 100 A<br />
Load current<br />
AgSnO2 90/10 (silver-tin oxide)<br />
Suitable for all loads. Well suited to higher loads. Particularly well<br />
suited to high inrush currents with short rise times (lamp<br />
loads, capacitive loads, fluorescent tubes, switch-mode<br />
power supplies,etc.). Well suited to resistive, inductive and<br />
capacitive DC applications due to low of material transport.