OUTLINE DIMENSIONS<br />

Hot Water Outlet<br />

Protective Jacket<br />

Tank Cross<br />

Section<br />

1/2"<br />

Steel<br />

Pressure<br />

Vessel<br />

<strong>Co</strong>mbination <strong>Co</strong>ld<br />

Water Inlet & Drain<br />

18"<br />

Withdrawal<br />

Space<br />

Side View<br />

45 o<br />

T&P Relief Valve<br />

2" Foam Insulation<br />

Immersion Thermostat<br />

<strong>Co</strong>ntroller<br />

Boiler Water Inlet<br />

Heating <strong>Co</strong>il<br />

Boiler Water Outlet<br />

45 o<br />

10 o<br />

Top View<br />

Front View<br />

A<br />

T&P Relief Valve<br />

Hot Water Outlet<br />

<strong>Co</strong>mbination <strong>Co</strong>ld<br />

Water Inlet & Drain<br />

Thermostat<br />

Heating Dimensions (Inches) Inlet /<br />

Base Storage <strong>Co</strong>il First Hour Outlet Shipping<br />

<strong>Model</strong> Capacity Size Rating * Overall Overall Inlet <strong>Co</strong>il Thermostat T&P Valve Size Weight<br />

(Gallons) (Sq Ft) (Gallons) Diameter Height “A” “B” “C” “D” (Inches) (lbs.)<br />

T30-15 30 15 128 20 40.5 7 10 13 34 3/4 180<br />

T40-15 40 15 139 20 58.75 7 10 13 51 3 /4 230<br />

T65-20 65 20 165 26 48 8 10 14 40 3 /4 310<br />

T80-20 80 20 182 26 58 8 10 14 51 3 /4 340<br />

T120-20 120 20 188 28 69.25 8 11 17 62 3/4 420<br />

T120-40 120 (2) 20 306 28 69.25 8 11 17 62 1 1 /2 435<br />

TU40-20 40 20 152 26 33 7 8 14 24 3 /4 235<br />

* First hour ratings based on a 80 o F rise (40-120 o F) when supplied with 6 GPM of 200 o F boiler water.<br />

STANDARD EQUIPMENT<br />

■ 1/2" thick Hydrastone cement lined steel tank<br />

■ All copper-silicon non-ferrous tank openings<br />

■ Built-in copper heat trap to improve operating<br />

efficiency and prevent heat migration<br />

■ Removable design heating coil<br />

■ High efficiency copper fin tube heating coil<br />

■ Immersion adjustable thermostat to regulate the<br />

flow of boiler water through the heating coil<br />

■ ASME rated temperature and pressure relief valve<br />

set at 150psi, 210 o F, 200,000 BTU max<br />

■ 2" thick polyurethane foam insulation<br />

■ High impact colorized composite protective jacket<br />

OPTIONAL EQUIPMENT<br />

1. 1 1/2" male NPT inlet / outlet water connections<br />

2. Double wall copper heating coil with a leak<br />

detection port. (Available in 20 Sq. / Ft. coils only)<br />

3. Integrally welded seismic attachment points<br />

4. <strong>Electric</strong> back-up heating element in various<br />

wattages and voltages (consult factory)<br />

1"<br />

B<br />

C<br />

D