Nuclear Grade HEPA Filters - Flanders/CSC
Nuclear Grade HEPA Filters - Flanders/CSC
Nuclear Grade HEPA Filters - Flanders/CSC
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Nuclear</strong> <strong>Grade</strong> <strong>HEPA</strong> <strong>Filters</strong>: Round <strong>Filters</strong><br />
Gel Seal<br />
Gel Seal filters are supplied with a 5 /8 -inch<br />
x 11 /16 -inch deep channel on one face only. The<br />
channel is factory-filled with <strong>Flanders</strong>’ BLU-JEL ®<br />
sealant.<br />
Note: Designate R5 Case Style. Standard channel<br />
location is upstream. (Face of flange)<br />
Gasket Seal<br />
18<br />
Channel<br />
Gaskets are made from 1 /4-inch x 3 /4 -inch closed<br />
cell neoprene material. Gaskets may be located<br />
on either side of the upstream flange. Contact<br />
factory for downstream flange location.<br />
Note: Designate R1 (one flange) or R2 (2 flanges)<br />
Case Style and specify location of the gasket as<br />
face of flange, back of flange, face and back of<br />
flange or faces of both flanges in the model number.<br />
Detail any special placement requirements.<br />
Gasket Location<br />
Face of Flange Back of Flange<br />
lifting Bails<br />
Optional lifting bails are available for easy filterremoval<br />
in special applications.<br />
Note: Specify the “B” prefix in the filter modelnumber.<br />
Faceguards<br />
The standard faceguard materials<br />
are 23-gauge 4 x 4<br />
inch mesh, welded galvanized<br />
dipped steel or 18-gauge Type<br />
304 stainless steel. Faceguards<br />
protect the media, but are not a guarantee against<br />
damage caused by mishandling.<br />
Note: Specify faceguard location as upstream,<br />
downstream or both.<br />
Drilled Flanges<br />
Drilled flanges are available<br />
as an option. <strong>Flanders</strong>’<br />
standard pattern is<br />
eight (8) 5 /16-inch diameter<br />
holes equally spaced<br />
and centered on a 7 3 /8 -inch diameter bolt circle<br />
for sizes A and B, or a 11 5 /16 -diameter bolt circle<br />
for size C filters.<br />
Note: Use the ‘D’ prefix in the model number.<br />
Ul 586<br />
For UL 586 classifiication, filters must be submitted<br />
to Underwriters Laboratories for extensive testing<br />
including spot flame and exposure to heated air.<br />
A UL 586 classification listing is accepted by<br />
DOE for meeting the Heated Air and Spot Flame<br />
Test Requirement of <strong>Nuclear</strong> <strong>Grade</strong> <strong>HEPA</strong> filters.<br />
NOTE: UL labels are optional and are applied only<br />
if specified by the buyer.<br />
Model Numbers and Specification<br />
Note: To write a specification for Round <strong>Filters</strong>, use<br />
the Designating Charts on pages 21 and 22 for determining<br />
the model number. Fill in the numbered<br />
locations in the Suggested Specification Text on<br />
page 23 with the model number and other appropriate<br />
selections from the listing on page 17.