TECHNICAL MANUAL<br />
<strong>Floor</strong> <strong>Standing</strong><br />
B-<strong>Series</strong><br />
TM-YFS-0410-A<br />
®
Table of Contents<br />
1. Nomenclature ........................................................................................................ 1<br />
2. Features ................................................................................................................ 2<br />
3. Specifications ........................................................................................................ 3<br />
General Data ............................................................................................... 3<br />
Safety Devices ........................................................................................... 11<br />
4. Application Information ........................................................................................ 12<br />
Controllers ................................................................................................. 12<br />
5. Installation ........................................................................................................... 14<br />
6. Wiring Diagram .................................................................................................... 21<br />
7. Servicing & Maintenance .................................................................................... 27<br />
8. Troubleshooting .................................................................................................. 28<br />
9. Dimensional Data ................................................................................................ 32<br />
10. Exploded View & Part List ................................................................................... 36<br />
Note : Installation and maintenance are to be performed only by qualified personnel who are<br />
familiar with local codes and regulations, and experienced with this type of equipment.<br />
Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.<br />
Warning : Moving machinery and electrical power hazard. May cause severe personnel<br />
injury or death. Disconnect and lock off power before servicing equipment.<br />
®
®<br />
TM-YFS-0410-A<br />
1<br />
Y FS 150 B<br />
1. Nomenclacture<br />
<strong>Series</strong><br />
B : B <strong>Series</strong><br />
Capacity<br />
150 : 150,000 Btu/h<br />
Model Name<br />
FS : <strong>Floor</strong> <strong>Standing</strong><br />
Brand<br />
Y : York
2. Features<br />
Easy Maintenance<br />
The simple design concept has maintenance and servicing in mind. Access to the internal part of the unit<br />
can be from front side of the unit by removing a few screws.<br />
Easy and Flexible Installation<br />
The unit is highly compact and therefore it is very easy to select a location to install the unit such that<br />
only a small space is required.<br />
Three Speed Motor<br />
The unit has 3-speed direct driven centrifugal fan. The speed of the fan can be adjusted through the<br />
electronic controller.<br />
Filter Rack<br />
The fan coil unit has filter rack to hold the air filter. This ensures the air flow is clean and the filter is easily<br />
accessible for maintenance and cleaning.<br />
Electronic Controller<br />
Electronic Controller can display cool, dry and fan mode with auto, high, medium and low fan speed.<br />
The temperature settings range from 16 to 30 degrees Celsius. There is a sleep function for cool mode<br />
and programmable on/off timer 1 hour interval. The controller is built with 3 minutes restart delay timer<br />
for compressor protection.<br />
Safety Controls<br />
Manual/Auto reset high pressure and low pressure cut-outs to guard against compressor damage<br />
due to high discharge head pressure and system leakage respectively. Crankcase heater for each<br />
compressor to prevent liquid migration, which can damage compressor valve plates, during off-cycle<br />
and eases start-up.<br />
TM-YFS-0410-A<br />
2<br />
®
®<br />
TM-YFS-0410-A<br />
3<br />
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />
MODEL<br />
TOTAL COOLING CAPACITY<br />
TOTAL INPUT POWER<br />
TOTAL RUNNING CURRENT - 3Φ<br />
3. Specifications<br />
INDOOR UNIT<br />
YFS50B YFS60B<br />
OUTDOOR UNIT<br />
YSL50D YSL61D<br />
Btu/h 55,000 62,000<br />
W 16,115 18,166<br />
W 5,480 6,232<br />
A<br />
V/Ph/Hz<br />
8.97 10.20<br />
POWER SOURCE 380-415 / 3 / 50<br />
REFRIGERANT TYPE R-22<br />
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />
FAN<br />
HIGH<br />
l/s / CFM 880 / 1861 1000 / 2115<br />
AIR FLOW MEDIUM<br />
l/s / CFM 709 / 1500 898 / 1900<br />
LOW<br />
l/s / CFM 590 / 1248 810 / 1713<br />
TYPE<br />
CENTRIFUGAL<br />
INDOOR<br />
QUANTITY<br />
MATERIAL<br />
1<br />
G2 GALVANIZED STEEL Z275<br />
DRIVE DIRECT DRIVEN<br />
DIAMETER<br />
mm/in<br />
241 / 9.49<br />
LENGTH mm/in<br />
241 / 9.49<br />
SOUND PRESSURE LEVEL (H/M/L) dBA<br />
73 / 70 / 66 74 / 71 / 67<br />
AIR FLOW<br />
l/s / CFM 1605 / 3400 1770 / 3750<br />
TYPE PROPELLER<br />
QUANTITY 1<br />
OUTDOOR MATERIAL<br />
GLASS REINFORCED ACRYL STYRENE RESIN<br />
DRIVE DIRECT<br />
DIAMETER<br />
mm/in 609.6 / 24 609.6 / 24<br />
SOUND PRESSURE LEVEL<br />
dBA 58 65<br />
FAN MOTOR<br />
TYPE 3-SPEEDS MOTOR<br />
QUANTITY 1<br />
INDEX OF PROTECTION (IP) IP 20<br />
INSULATION GRADE CLASS B<br />
INDOOR POWER SOURCE<br />
V/Ph/Hz<br />
220-240V / 1PH / 50HZ<br />
RATED INPUT POWER<br />
W 810 976<br />
RATED RUNNING CURRENT<br />
A 3.4 4.1<br />
MOTOR OUTPUT<br />
W 315 600<br />
POLES 4 POLES<br />
TYPE INDUCTION<br />
QUANTITY 1<br />
INDEX OF PROTECTION (IP)<br />
IP24 -<br />
INSULATION GRADE<br />
B F<br />
OUTDOOR<br />
POWER SOURCE<br />
RATED INPUT POWER<br />
V/Ph/Hz<br />
W 239<br />
220-240/1/50<br />
335<br />
RATED RUNNING CURRENT<br />
A 1.04 1.6<br />
MOTOR OUTPUT<br />
W 145 335<br />
MOTOR SPEED<br />
RPM 8 8<br />
POLES 6<br />
INDOOR CONDENSATE DRAIN SIZE mm/in<br />
19.1 / 3/4<br />
TYPE<br />
PIPE<br />
CONNECTION SIZE<br />
LIQUID<br />
GAS<br />
mm/in<br />
mm/in<br />
9.5 / 3/8<br />
FLARE VALVE<br />
19.1 / 3/4<br />
12.7 / 1/2<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />
YFS50B<br />
YSL50D<br />
YFS60B<br />
YSL61D<br />
mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 mm/in 7.00 / 0.276 9.52 / 3/8<br />
mm/in 0.28 / 0.011 0.28 / 0.011<br />
mm/in<br />
ALUMINIUM (CORR. FIN)<br />
0.11 / 0.004<br />
ALUMINIUM (SLIT FIN)<br />
0.11 / 0.004<br />
m2 /ft2 0.84 / 9.04 0.87 / 9.36<br />
2 3<br />
18 16<br />
TYPE<br />
OIL TYPE DAPHNE SE56P EAL ARCTIC 22CC (POE)<br />
OIL AMOUNT cm3 MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
COIL<br />
MATERIAL COPPER TUBE<br />
TUBE DIAMETER 9.53 / 0.375<br />
THICKNESS 0.33 / 0.013<br />
INDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINIUM<br />
0.115 / 0.0045<br />
FIN<br />
FACE AREA 0.465 / 5<br />
ROW 3<br />
FIN PER INCH 12<br />
MATERIAL SEAMLESS INNER GROOVE COPPER<br />
TUBE DIAMETER<br />
THICKNESS<br />
OUTDOOR<br />
MATERIAL<br />
THICKNESS<br />
FIN<br />
FACE AREA<br />
ROW<br />
FIN PER INCH<br />
COMPRESSOR<br />
SCROLL<br />
/ fl.oz. 1400 / 47.3 1774 / 60<br />
INSULATION GRADE<br />
-<br />
OUTDOOR POWER SOURCE<br />
V/Ph/Hz<br />
380-415 / 3 / 50<br />
CAPACITOR<br />
µF<br />
NIL<br />
RATED INPUT POWER W 4244 5000<br />
RATED RUNNING CURRENT A 7.50 8.50<br />
LOCKED ROTOR AMP. A 66 74<br />
AIR QUALITY<br />
TYPE WASHABLE FILTERS<br />
TREATMENT 70 % EFFICIENCY<br />
INDOOR AIR FILTER<br />
QUANTITY<br />
LENGTH<br />
pc<br />
mm/in<br />
1<br />
900 / 35.43<br />
SIZE WIDTH mm/in<br />
550 / 21.65<br />
THICKNESS mm/in<br />
22 / 0.87<br />
UNIT HEIGHT<br />
UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />
mm/in<br />
1950 / 76.77<br />
DIMENSION WIDTH mm/in<br />
530 / 20.87<br />
() - PANEL DEPTH mm/in<br />
710 / 27.95<br />
INDOOR PACKING<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
mm/in<br />
mm/in<br />
2080 / 81.89<br />
550 / 21.65<br />
() - PANEL DEPTH mm/in<br />
950 / 37.40<br />
UNIT WEIGHT<br />
kg/lb 135 / 297.62 135 / 297.62<br />
UNIT<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
852 / 33.5<br />
1030 / 40.6<br />
428 / 16.9<br />
852 / 33.5<br />
1030 / 40.6<br />
428 / 16.9<br />
OUTDOOR<br />
PACKING<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
958 / 37.7<br />
1156 / 45.5<br />
502 / 19.8<br />
958 / 37.7<br />
1156 / 45.5<br />
502 / 19.8<br />
UNIT WEIGHT<br />
kg/lb 105 / 232 108 / 238<br />
CASING<br />
MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />
INDOOR UNIT<br />
FINISHING EPOXY POLYESTER POWER COATING<br />
COLOUR LIGHT GREY<br />
OUTDOOR UNIT<br />
MATERIAL<br />
COLOUR<br />
ELECTRO GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />
TM-YFS-0410-A<br />
4<br />
®
®<br />
TM-YFS-0410-A<br />
5<br />
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />
MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
MYSS72C<br />
YFS75B<br />
MYSS80C<br />
TOTAL COOLING CAPACITY<br />
Btu/h<br />
W<br />
70,000<br />
20,510<br />
77,000<br />
22,561<br />
TOTAL INPUT POWER<br />
W 8,737 9,409<br />
TOTAL RUNNING CURRENT - 3Φ<br />
A 14.30 15.40<br />
POWER SOURCE V/Ph/Hz<br />
380-415 / 3 / 50<br />
REFRIGERANT TYPE R-22<br />
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />
FAN<br />
HIGH l/s / CFM<br />
1080 / 2284<br />
AIR FLOW MEDIUM l/s / CFM<br />
946 / 2000<br />
LOW l/s / CFM<br />
850 / 1798<br />
TYPE CENTRIFUGAL<br />
INDOOR<br />
QUANTITY<br />
MATERIAL<br />
1<br />
G2 GALVANIZED STEEL Z275<br />
DRIVE DIRECT DRIVEN<br />
DIAMETER mm/in<br />
270 / 10.63<br />
LENGTH mm/in<br />
270 / 10.63<br />
SOUND PRESSURE LEVEL (H/M/L) dBA<br />
74 / 71 / 67<br />
AIR FLOW l/s / CFM<br />
2832 / 6000<br />
TYPE PROPELLER<br />
QUANTITY 1<br />
OUTDOOR MATERIAL ALUMINUM<br />
DRIVE DIRECT<br />
DIAMETER mm/in<br />
660 / 26<br />
SOUND PRESSURE LEVEL<br />
dBA 70 74<br />
FAN MOTOR<br />
TYPE 3-SPEEDS MOTOR<br />
QUANTITY 1<br />
INDEX OF PROTECTION (IP) -<br />
INSULATION GRADE CLASS B<br />
INDOOR POWER SOURCE V/Ph/Hz<br />
220-240V / 1Ph / 50Hz<br />
RATED INPUT POWER W<br />
1120<br />
RATED RUNNING CURRENT A<br />
4.7<br />
MOTOR OUTPUT W<br />
600<br />
POLES 4 POLES<br />
TYPE PERMANENT SPLIT CAPACITOR<br />
QUANTITY 1<br />
INDEX OF PROTECTION (IP) IP54<br />
OUTDOOR<br />
INSULATION GRADE<br />
POWER SOURCE V/Ph/Hz<br />
F<br />
220-240/1/50<br />
E<br />
RATED INPUT POWER<br />
W 740 596<br />
RATED RUNNING CURRENT<br />
A 3.8 2.5<br />
MOTOR OUTPUT<br />
W 145 480<br />
INDOOR CONDENSATE DRAIN SIZE mm/in<br />
19.1 / 3/4<br />
TYPE<br />
PIPE<br />
CONNECTION SIZE<br />
LIQUID<br />
GAS<br />
mm/in<br />
mm/in<br />
FLARE VALVE<br />
12.7 / ½<br />
25.4 / 1<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />
MYSS72C MYSS80C<br />
mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 2 2<br />
14 14<br />
cm3 MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
YFS75B<br />
COIL<br />
MATERIAL COPPER TUBE<br />
TUBE DIAMETER 9.53 / 0.375<br />
THICKNESS 0.33 / 0.013<br />
INDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINIUM<br />
0.115 / 0.0045<br />
FIN<br />
FACE AREA 0.465 / 5<br />
ROW 4<br />
FIN PER INCH 12<br />
MATERIAL SEAMLESS INNER SMOOTH COPPER<br />
TUBE DIAMETER 9.52 / 3/8<br />
THICKNESS 0.28 / 0.011<br />
OUTDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINUM<br />
0.11 / 0.004<br />
FIN<br />
FACE AREA 1.23 / 13.25<br />
ROW<br />
FIN PER INCH<br />
COMPRESSOR<br />
TYPE SCROLL<br />
OIL TYPE SONTEX 200LT/ MINERAL OIL<br />
OIL AMOUNT<br />
/ fl.oz. 1240.0 / 44 3000.0 / 101<br />
INSULATION GRADE<br />
F E<br />
OUTDOOR POWER SOURCE<br />
V/Ph/Hz<br />
380-415/3/50<br />
CAPACITOR µF<br />
NIL<br />
RATED INPUT POWER<br />
W 5800 7561<br />
RATED RUNNING CURRENT<br />
A 11.5 13.0<br />
LOCKED ROTOR AMP.<br />
A 97 102<br />
AIR QUALITY<br />
TYPE WASHABLE FILTERS<br />
TREATMENT 70 % EFFICIENCY<br />
INDOOR AIR FILTER<br />
QUANTITY<br />
LENGTH<br />
pc<br />
mm/in<br />
1<br />
900 / 35.43<br />
SIZE WIDTH mm/in<br />
550 / 21.65<br />
THICKNESS mm/in<br />
22 / 0.87<br />
UNIT HEIGHT<br />
UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />
mm/in<br />
1950 / 76.77<br />
DIMENSION WIDTH mm/in<br />
530 / 20.87<br />
() - PANEL DEPTH mm/in<br />
710 / 27.95<br />
INDOOR PACKING HEIGHT mm/in<br />
2080 / 81.89<br />
DIMENSION WIDTH<br />
() - PANEL DEPTH<br />
mm/in<br />
mm/in<br />
550 / 21.65<br />
950 / 37.40<br />
UNIT WEIGHT kg/lb<br />
142 / 33.05<br />
UNIT<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
946 / 37.2<br />
1300 / 51.2<br />
500 / 19.7<br />
OUTDOOR<br />
PACKING<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
1132 / 44.56<br />
1414 / 55.66<br />
664 / 26.14<br />
UNIT WEIGHT<br />
kg/lb 145 / 320<br />
CASING<br />
MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />
INDOOR UNIT<br />
FINISHING EPOXY POLYESTER POWER COATING<br />
COLOUR<br />
LIGHT GREY<br />
OUTDOOR UNIT<br />
MATERIAL<br />
COLOUR<br />
ELECTRO GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />
TM-YFS-0410-A<br />
6<br />
®
®<br />
TM-YFS-0410-A<br />
7<br />
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />
MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
YFS100B<br />
MYSS100B<br />
YFS125B<br />
MYSS125B<br />
TOTAL COOLING CAPACITY<br />
Btu/h<br />
W<br />
101,000<br />
29,593<br />
125,000<br />
36,625<br />
TOTAL INPUT POWER<br />
W 11,383 10,631<br />
TOTAL RUNNING CURRENT - 3Φ<br />
A 18.63 17.40<br />
POWER SOURCE V/Ph/Hz<br />
380-415 / 3 / 50<br />
REFRIGERANT TYPE R-22<br />
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />
FAN<br />
HIGH<br />
l/s / CFM 1759.7 / 3722 1942.2 / 4108<br />
AIR FLOW MEDIUM<br />
l/s / CFM 1418 / 3000 1702 / 3600<br />
LOW<br />
l/s / CFM 1180.1 / 2496 1519.5 / 3214<br />
TYPE<br />
CENTRIFUGAL<br />
INDOOR<br />
QUANTITY<br />
MATERIAL<br />
2<br />
G2 GALVANIZED STEEL Z275<br />
DRIVE DIRECT DRIVEN<br />
DIAMETER<br />
mm/in<br />
241 / 9.49<br />
LENGTH mm/in<br />
241 / 9.49<br />
SOUND PRESSURE LEVEL (H/M/L) dBA<br />
78 / 75 / 73<br />
AIR FLOW<br />
l/s / CFM 2926 / 6200 2926 / 6200<br />
TYPE PROPELLER<br />
QUANTITY 1<br />
OUTDOOR MATERIAL ALUMINUM<br />
DRIVE DIRECT<br />
DIAMETER mm/in<br />
660 / 26<br />
SOUND PRESSURE LEVEL<br />
dBA 65 65<br />
FAN MOTOR<br />
TYPE 3-SPEEDS MOTOR<br />
QUANTITY 2<br />
INDEX OF PROTECTION (IP) IP 20<br />
INSULATION GRADE<br />
CLASS B<br />
INDOOR POWER SOURCE V/Ph/Hz<br />
220-240V / 1Ph / 50Hz<br />
RATED INPUT POWER<br />
W 810 881<br />
RATED RUNNING CURRENT<br />
A 3.4 3.7<br />
MOTOR OUTPUT<br />
W 315 600<br />
POLES 4 POLES<br />
TYPE PERMANENT SPLIT CAPACITOR<br />
QUANTITY 1<br />
INDEX OF PROTECTION (IP) IP54<br />
OUTDOOR<br />
INSULATION GRADE<br />
POWER SOURCE V/Ph/Hz<br />
F<br />
380-415/3/50<br />
F<br />
RATED INPUT POWER<br />
W 660 820<br />
RATED RUNNING CURRENT<br />
A 1.5 1.2<br />
MOTOR OUTPUT<br />
W 470 520<br />
INDOOR CONDENSATE DRAIN SIZE mm/in<br />
19.1 / 3/4<br />
PIPE<br />
CONNECTION<br />
TYPE<br />
SIZE<br />
LIQUID<br />
GAS<br />
mm/in<br />
mm/in<br />
15.9 / 5/8<br />
28.6 / 1 1/8<br />
FLARE VALVE<br />
15.9 / 5/8<br />
34.9 / 1 3/8<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />
YFS100B<br />
MYSS100B<br />
YFS125B<br />
MYSS125B<br />
mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 0.836 / 9 0.883 / 9.5<br />
mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 1.76 / 19.00 1.76 / 19.00<br />
2 2<br />
12 16<br />
cm3 MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
COIL<br />
MATERIAL COPPER TUBE<br />
TUBE DIAMETER<br />
9.53 / 0.375<br />
THICKNESS 0.33 / 0.013<br />
INDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINIUM<br />
0.115 / 0.0045<br />
FIN<br />
FACE AREA<br />
ROW<br />
3<br />
FIN PER INCH 12<br />
MATERIAL SEAMLESS INNER SMOOTH COPPER<br />
TUBE DIAMETER 9.52 / 3/8<br />
THICKNESS<br />
0.28 / 0.011<br />
OUTDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINUM<br />
0.11 / 0.004<br />
FIN<br />
FACE AREA<br />
ROW<br />
FIN PER INCH<br />
COMPRESSOR<br />
TYPE SCROLL<br />
OIL TYPE SONTEX 200LT/ MINERAL OIL<br />
OIL AMOUNT<br />
/ fl.oz. 3253.1 / 110 3253.1 / 110<br />
INSULATION GRADE F<br />
OUTDOOR POWER SOURCE<br />
V/Ph/Hz<br />
380-415/3/50<br />
CAPACITOR µF<br />
NIL<br />
RATED INPUT POWER<br />
W 8607 9172<br />
RATED RUNNING CURRENT<br />
A 16.0 15.0<br />
LOCKED ROTOR AMP.<br />
A 125 110<br />
AIR QUALITY<br />
TYPE WASHABLE FILTERS<br />
TREATMENT 70 % EFFICIENCY<br />
INDOOR AIR FILTER<br />
QUANTITY<br />
LENGTH<br />
pc<br />
mm/in<br />
2<br />
478 / 21.65<br />
SIZE WIDTH mm/in<br />
900 / 35.43<br />
THICKNESS mm/in<br />
22 / 0.87<br />
UNIT HEIGHT<br />
UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />
mm/in<br />
1950 / 76.77<br />
DIMENSION WIDTH mm/in<br />
530 / 20.87<br />
() - PANEL DEPTH mm/in<br />
1180 / 46.46<br />
INDOOR PACKING HEIGHT mm/in<br />
2080 / 81.89<br />
DIMENSION WIDTH mm/in<br />
550 / 21.65<br />
() - PANEL DEPTH mm/in<br />
1370 / 53.94<br />
UNIT WEIGHT kg/lb<br />
190 / 418.87<br />
UNIT<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
946 / 37.2<br />
1116 / 43.9<br />
939 / 37.0<br />
946 / 37.2<br />
1116 / 43.9<br />
939 / 37.0<br />
OUTDOOR<br />
PACKING<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
1132 / 44.6<br />
1282 / 50.5<br />
1112 / 43.8<br />
1132 / 44.6<br />
1282 / 50.5<br />
1112 / 43.8<br />
UNIT WEIGHT<br />
kg/lb 164 / 361 224 / 493<br />
CASING<br />
MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />
INDOOR UNIT<br />
FINISHING EPOXY POLYESTER POWER COATING<br />
COLOUR<br />
LIGHT GREY<br />
OUTDOOR UNIT<br />
MATERIAL<br />
COLOUR<br />
ELECTRO GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />
TM-YFS-0410-A<br />
8<br />
®
®<br />
TM-YFS-0410-A<br />
9<br />
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />
MODEL<br />
TOTAL COOLING CAPACITY<br />
INDOOR<br />
OUTDOOR<br />
HIGH<br />
AIR FLOW MEDIUM<br />
LOW<br />
TYPE<br />
QUANTITY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER<br />
LENGTH<br />
SOUND PRESSURE LEVEL (H/M/L)<br />
AIR FLOW<br />
TYPE<br />
QUANTITY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER<br />
SOUND PRESSURE LEVEL<br />
TYPE<br />
QUANTITY<br />
INDEX OF PROTECTION (IP)<br />
INSULATION GRADE<br />
INDOOR POWER SOURCE<br />
RATED INPUT POWER<br />
RATED RUNNING CURRENT<br />
MOTOR OUTPUT<br />
POLES<br />
TYPE<br />
QUANTITY<br />
INDEX OF PROTECTION (IP)<br />
INSULATION GRADE<br />
OUTDOOR<br />
POWER SOURCE<br />
RATED INPUT POWER<br />
RATED RUNNING CURRENT<br />
MOTOR OUTPUT<br />
INDOOR CONDENSATE DRAIN SIZE<br />
TYPE<br />
PIPE<br />
LIQUID<br />
CONNECTION SIZE<br />
GAS<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
TOTAL INPUT POWER<br />
TOTAL RUNNING CURRENT - 3Φ<br />
POWER SOURCE<br />
REFRIGERANT TYPE<br />
REFRIGERANT CONTROL (EXPANSION DEVICE)<br />
Btu/h<br />
W<br />
W<br />
A<br />
V/Ph/Hz<br />
l/s / CFM<br />
l/s / CFM<br />
l/s / CFM<br />
mm/in<br />
mm/in<br />
dBA<br />
l/s / CFM<br />
mm/in<br />
dBA<br />
V/Ph/Hz<br />
W<br />
A<br />
W<br />
V/Ph/Hz<br />
W<br />
A<br />
W<br />
mm/in<br />
mm/in<br />
mm/in<br />
FAN<br />
FAN MOTOR<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />
YFS150B<br />
MYSS150C<br />
153,000<br />
44,829<br />
15,745<br />
25.77<br />
380-415 / 3 / 50<br />
R-22<br />
INDOOR TXV VALVE<br />
2160 / 4569<br />
1891 / 4000<br />
1700 / 3695<br />
CENTRIFUGAL<br />
2<br />
G2 GALVANIZED STEEL Z275<br />
DIRECT DRIVEN<br />
270 / 10.63<br />
270 / 10.63<br />
78 / 75 / 73<br />
4720 / 10000<br />
PROPELLER<br />
1<br />
ALUMINUM<br />
DIRECT<br />
762 / 30<br />
73<br />
3-SPEEDS MOTOR<br />
2<br />
IP 20<br />
CLASS B<br />
220-240V / 1Ph / 50Hz<br />
1120<br />
4.7<br />
600<br />
4 POLES<br />
INDUCTION<br />
1<br />
IP54<br />
F<br />
380-415 / 3 / 50<br />
820<br />
1.2<br />
520<br />
19.1 / 3/4<br />
FLARE VALVE<br />
15.9 / 5/8<br />
34.9 / 1 3/8
<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />
mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 mm/in<br />
mm/in<br />
mm/in<br />
m2 /ft2 cm3 MODEL<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
YFS150B<br />
MYSS150C<br />
COIL<br />
MATERIAL<br />
COPPER TUBE<br />
TUBE DIAMETER<br />
9.53 / 0.375<br />
THICKNESS<br />
0.33 / 0.013<br />
INDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINIUM<br />
0.115 / 0.0045<br />
FIN<br />
FACE AREA<br />
0.883 / 9.5<br />
ROW<br />
4<br />
FIN PER INCH<br />
12<br />
MATERIAL<br />
SEAMLESS INNER SMOOTH COPPER<br />
TUBE DIAMETER<br />
9.52 / 3/8<br />
THICKNESS<br />
0.28 / 0.011<br />
OUTDOOR<br />
MATERIAL<br />
THICKNESS<br />
ALUMINUM<br />
0.11 / 0.004<br />
FIN<br />
FACE AREA<br />
1.24 / 13.38<br />
ROW<br />
2<br />
FIN PER INCH<br />
14<br />
COMPRESSOR<br />
TYPE<br />
SCROLL<br />
OIL TYPE<br />
SONTEX 200LT/ MINERAL OIL<br />
OIL AMOUNT<br />
/ fl.oz.<br />
2513.8 / 85<br />
INSULATION GRADE<br />
F<br />
OUTDOOR POWER SOURCE<br />
V/Ph/Hz<br />
380-415/3/50<br />
CAPACITOR<br />
µF<br />
NIL<br />
RATED INPUT POWER<br />
W<br />
12502<br />
RATED RUNNING CURRENT<br />
A<br />
23.0<br />
LOCKED ROTOR AMP.<br />
A<br />
AIR QUALITY<br />
198<br />
TYPE<br />
WASHABLE FILTERS<br />
TREATMENT<br />
70 % EFFICIENCY<br />
INDOOR AIR FILTER<br />
QUANTITY<br />
LENGTH<br />
pc<br />
mm/in<br />
2<br />
478 / 21.65<br />
SIZE WIDTH mm/in<br />
900 / 35.43<br />
THICKNESS mm/in<br />
22 / 0.87<br />
UNIT HEIGHT<br />
UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />
mm/in<br />
1950 (76.77)<br />
DIMENSION WIDTH<br />
mm/in<br />
530 (20.87)<br />
() - PANEL DEPTH<br />
mm/in<br />
1180 (46.46)<br />
INDOOR PACKING HEIGHT<br />
mm/in<br />
2080 (81.89)<br />
DIMENSION WIDTH<br />
mm/in<br />
550 (21.65)<br />
() - PANEL DEPTH<br />
mm/in<br />
1370 (53.94)<br />
UNIT WEIGHT<br />
kg/lb<br />
200 / 440.92<br />
UNIT<br />
DIMENSION<br />
HEIGHT<br />
WIDTH<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
1041 / 41.0<br />
1116 / 43.9<br />
939 / 37.0<br />
OUTDOOR<br />
HEIGHT<br />
PACKING<br />
WIDTH<br />
DIMENSION<br />
DEPTH<br />
mm/in<br />
mm/in<br />
mm/in<br />
1132 / 44.6<br />
1282 / 50.5<br />
1112 / 43.8<br />
UNIT WEIGHT<br />
kg/lb<br />
258 / 568<br />
CASING<br />
MATERIAL<br />
ELECTRO-GALVANIZED MILD STEEL<br />
INDOOR UNIT<br />
FINISHING<br />
EPOXY POLYESTER POWER COATING<br />
COLOUR<br />
LIGHT GREY<br />
OUTDOOR UNIT<br />
MATERIAL<br />
COLOUR<br />
ELECTRO GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />
COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />
4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />
TM-YFS-0410-A<br />
®<br />
10
®<br />
11<br />
TM-YFS-0410-A<br />
Safety Device<br />
MODEL<br />
SAFETY DEVICE<br />
MODEL<br />
SAFETY DEVICE<br />
MODEL<br />
SAFETY DEVICE<br />
MODEL<br />
SAFETY DEVICE<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
HIGH PRESSURE SWITCH<br />
LOW PRESSURE SWITCH<br />
PHASE SEQUENCER, 1Φ <br />
DISCHARGE THERMOSTAT SETTING<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
HIGH PRESSURE SWITCH<br />
LOW PRESSURE SWITCH<br />
PHASE SEQUENCER<br />
DISCHARGE THERMOSTAT SETTING<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
HIGH PRESSURE SWITCH<br />
LOW PRESSURE SWITCH<br />
PHASE SEQUENCER<br />
DISCHARGE THERMOSTAT SETTING<br />
INDOOR UNIT<br />
OUTDOOR UNIT<br />
HIGH PRESSURE SWITCH<br />
LOW PRESSURE SWITCH<br />
PHASE SEQUENCER<br />
DISCHARGE THERMOSTAT SETTING<br />
YFS50B YFS60B<br />
YSL50D YSL61D<br />
TYPE<br />
NC NC<br />
OPEN kPa / psi 2937 / 426 2937 / 426<br />
CLOSE kPa / psi 2413 / 350 2413 / 350<br />
TYPE<br />
NC NC<br />
OPEN kPa / psi 124 / 18 124 / 18<br />
CLOSE kPa / psi 193 / 28 193 / 28<br />
<br />
°C / °F <br />
YFS75B<br />
MYSS72C MYSS80C<br />
TYPE<br />
AUTO RESET AUTO RESET<br />
OPEN Pa / psi 2937 / 426 2937 / 426<br />
CLOSE Pa / psi 2413 / 350 2413 / 350<br />
TYPE<br />
AUTO RESET AUTO RESET<br />
OPEN Pa / psi 124 / 18 124 / 18<br />
CLOSE Pa / psi 193 / 28 193 / 28<br />
OYLT OYLT<br />
°C / °F 125 / 257 125 / 257<br />
YFS100B YFS125B<br />
MYSS100B MYSS125B<br />
TYPE<br />
AUTO RESET AUTO RESET<br />
OPEN Pa / psi 2937 / 426 2937 / 426<br />
CLOSE Pa / psi 2413 / 350 2413 / 350<br />
TYPE<br />
AUTO RESET AUTO RESET<br />
OPEN Pa / psi 124 / 18 124 / 18<br />
CLOSE Pa / psi 193 / 28 193 / 28<br />
OYLT OYLT<br />
°C / °F 125 / 257 125 / 257<br />
TYPE<br />
OPEN Pa / psi<br />
CLOSE<br />
TYPE<br />
Pa / psi<br />
OPEN Pa / psi<br />
CLOSE Pa / psi<br />
°C / °F<br />
YFS150B<br />
MYSS150C<br />
AUTO RESET<br />
2937 / 426<br />
2413 / 350<br />
AUTO RESET<br />
124 / 18<br />
193 / 28<br />
OYLT<br />
125 / 257
Control Panel<br />
8<br />
9<br />
2<br />
5<br />
4. Application Information<br />
TEMP<br />
TIMER<br />
AUTO<br />
HIGH<br />
MED<br />
LOW<br />
SENSOR<br />
FAN<br />
SWING<br />
COOL<br />
DRY<br />
HEAT<br />
FAN<br />
ON/OFF<br />
MODE<br />
SLEEP<br />
1. “ON/OFF” switch 6. “Sleep” mode<br />
• Press to start the air conditioner unit. • Press button to activate the sleep<br />
• Press again to stop the unit. function can only be activated under<br />
“cool” mode operation.<br />
2. Temperature setting The set temperature will increase 0.5°C<br />
• Set the desired room temperature.<br />
after 30 minutes, 1°C after 1 hour and 2°C<br />
• Press button to increase or decrease the<br />
set temperature. Setting range are between<br />
after 2 hours.<br />
16°C to 30°C (60°F to 80°F).<br />
7. Air Swing<br />
3. Operation Modes<br />
• Press the “mode” button for select the type<br />
• Press button to activate the automatic air<br />
swing function.<br />
of operating mode.<br />
COOL, DRY, FAN<br />
8. Sensor<br />
• Infra red sensor to receive signals from<br />
wireless controller.<br />
4. Fan Speed selection. 9. LED Display<br />
• Press the button until the desired fan speed • To display the set temperature (in °C) and<br />
is achieved. timer delay setting (in hours).<br />
5. Timer. 10. Transmission source<br />
• Press the set button to select the switch • To transmit signals to the air conditioner.<br />
timer of the air conditioner unit (the setting<br />
range is between 1 to 10 hours).<br />
4<br />
1<br />
3<br />
6<br />
7<br />
TM-YFS-0410-A<br />
®<br />
12
®<br />
13<br />
TM-YFS-0410-A<br />
Operating State And Fault Table<br />
Wireless Remote Control (Universal Board)<br />
Cooling : LED Indicator Light Display<br />
POWER TIMER SLEEP<br />
POWER TIMER<br />
1 Time<br />
2 Times<br />
3 Times<br />
1 Time<br />
3 Times<br />
SLEEP<br />
ON / ON or OFF BLINKING<br />
Operation / Faulty Indication<br />
Cool Mode<br />
Timer On<br />
Sleep Mode On<br />
Compressor Overload<br />
Gas Leak<br />
Room Sensor Open or Short<br />
Indoor Coil Sensor Open or Short<br />
Outdoor Coil Sensor Open or Short
c) Ensure that the location is convenient for wiring and piping.<br />
5. Installations<br />
Indoor Unit<br />
Preliminary Site Survey<br />
a) Electrical supply and installation is to confirm to local authority’s (e.g. National Electricity Board)<br />
codes and regulations.<br />
b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be<br />
independent of welding transformers which can cause supply fluctuation.<br />
c) Ensure that the location is convenient for wiring and piping.<br />
Pipings<br />
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed<br />
or had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally,<br />
do not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect<br />
suction or liquid line into fittings.<br />
Operational Check<br />
After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is<br />
operating properly. Check that:<br />
a) Condenser fans are running, with warm air blowing off the condenser coil.<br />
b) Evaporator blowers are running and discharging cool air.<br />
c) Suction line inside condensing unit feels cool.<br />
d) Liquid line inside condensing unit feels warm.<br />
Electrical Connection<br />
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for<br />
field wiring regulations and ensure that these are complied with. Besides, observe the following general<br />
precautions:<br />
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing<br />
wiringwork.<br />
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit<br />
breaker for over-current protection should be provided in the exclusive line.<br />
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.<br />
d) All wiring must be firmly connected.<br />
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan<br />
motors.<br />
TM-YFS-0410-A<br />
®<br />
14
®<br />
15<br />
TM-YFS-0410-A<br />
Outdoor Unit<br />
Location For Installation Of The Condensing Units<br />
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve<br />
maximum cooling capacity, the location selected should fulfill the following requirements:-<br />
a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit<br />
cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for<br />
maintenance around the unit.<br />
b) Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacle which block air intake or<br />
discharge.<br />
c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering the<br />
condensing temperature.<br />
d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.<br />
e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.<br />
f) A place where the hot air discharge and operating sound level will not annoy the neighbours.<br />
g) The location must not be susceptible to dust or oil mist.<br />
CAUTION: If the condensing unit is operated in an atmosphere containing oils (including machine<br />
oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances<br />
may lead to failure of the unit.
Field Piping<br />
To ensure satisfactory operation and performance, the following points should be noted for the field<br />
piping arrangements of the complete refrigerant cycle.<br />
a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units<br />
(depending on whether the indoor unit is above or below the outdoor unit).<br />
b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit<br />
(evaporator) as possible.<br />
c) Field supplied sight glass must be assembled and mounted next to filter dryer.<br />
Maximum Pipe Length And Maximum Number Of Bends<br />
When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability<br />
drops asa result. As the number of bends increases, system piping resistance to the refrigerant flow<br />
increases, thus lowering the cooling capacity and the compressor may become defective. If the height<br />
difference between the evaporator and the condenser is excessive, the cooling capacity drops, the<br />
lubricating oil return is retarded, affecting the compressor efficiency adversely.<br />
Always choose the shortest piping path and follow the recommendations as shown below :-<br />
Model<br />
Max. Elevation, m<br />
(ft.)<br />
Max. Total Length, m<br />
(ft.)<br />
MYSS 100/125B 25 (82.0) 45 (147.6) 8<br />
MYSS 80/150C 25 (82.0) 45 (147.6) 8<br />
Note : If piping is more than 100ft, it is recommended to add in an accumulator.<br />
Max. of Bends<br />
CAUTION:<br />
1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height,<br />
length and/or the number of bends of the refrigerant piping system installed is beyond the<br />
limit above.<br />
2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe<br />
as far as possible.<br />
TM-YFS-0410-A<br />
®<br />
16
®<br />
17<br />
TM-YFS-0410-A<br />
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply<br />
before proceeding with the following troubleshooting procedures.<br />
The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which<br />
are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.<br />
No<br />
Fault<br />
onditions<br />
1 The air conditioner unit will not resume after<br />
power failure.<br />
2 The compressor does not operate 3 minutes<br />
after the air conditioner unit is started.<br />
3 The airflow is too slow or room cannot be<br />
cooled sufficiently.<br />
c<br />
Possib<br />
le<br />
causes<br />
/ corrective<br />
a<br />
ctions<br />
• The auto restart function is not functioning. Please<br />
turn on the unit with the wireless / wired controller.<br />
• Protection against frequent starting.<br />
• Wait for 3 or 4 minutes for the compressor to start<br />
operating by it self.<br />
• The air filter is dirty.<br />
• The doors and windows are opened.<br />
• The air suction and discharge of both indoor and<br />
outdoor units are clogged or blocked.<br />
• The regulated temperature or temperature setting<br />
is not low enough.<br />
4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,<br />
which might have adhered onto the coil, may<br />
cause odor.<br />
• Contact your nearest dealer.<br />
5 Condensation on the front air grille of the indoor<br />
unit.<br />
• This is caused by air humidity after an extended<br />
period of operation.<br />
• The set temperature is too low. Increase the<br />
temperature setting and operate the unit at high<br />
fan speed.<br />
6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest<br />
dealer. This might be due to tilted installation.<br />
7 Hissing airflow sound from the air conditioner<br />
unit during operation.<br />
• Liquid refrigerant flowing into the evaporator coil.<br />
8 The wireless controller display is dim. • The batteries are discharged.<br />
• The batteries are not correctly inserted.<br />
• The assembly is not good.<br />
9 Compressor operates continuously. • Dirty air filter. Clean the air filter.<br />
• Temperature setting too low (cooling). Use higher<br />
temperature setting.<br />
10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower<br />
temperature setting.
Guidelines Of Field-charging Air Conditioning Systems With Scroll Compressors<br />
These guidelines are intended for use with Scroll compressors only with R22, R407C, R134a, R404A,<br />
R507,and R410A refrigerants. They do not apply to reciprocating compressors or competitive Scroll<br />
compressors.<br />
Field -Charging - Some Precaution Points<br />
Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there is<br />
insufficient refrigerant in the system or if refrigerant is added too slowly. Operation with low suction<br />
pressure will quickly lead to very high discharge temperatures. While this process is happening, the<br />
scrolls are not being well lubricated - scrolls depend on the oil mist in the refrigerant for lubrication. A<br />
lack of lubrication leads to high friction between the scroll flanks and tips and generates additional heat.<br />
The combination of heat of compression and heat from increased friction is concentrated in a small<br />
localized discharge area where temperature scan quickly rise to more than 300°C. These extreme<br />
temperatures damage the Scroll spirals and the orbiting Scroll bearing. This damage can occur in less<br />
than one minute especially on larger compressors. Failure may occur in the first few hours or the<br />
damage done during field charging may show up some time later. Other typical field charging problems<br />
include undercharging, overcharging, moisture or air in the system etc. In time each one of these problems<br />
can cause compressor failure.<br />
Equipment<br />
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory<br />
job is:-<br />
Set of service gauges<br />
Hoses<br />
Vacuum pump<br />
Vacuum gauge<br />
ScalesThermometer<br />
Charging Hoses<br />
Most field-charging is done using standard service hoses. Hoses are made in different colors with<br />
different working pressures and with different leak rates but the most important point is the presence<br />
or absence of Shredder valve depressors. Shredder valve depressors severely restrict the flow through<br />
the service hoses.This slows evacuation and vapor charging dramatically. In most cases the Shredder<br />
depressor can be removed but it is simpler to have one set of hoses with and one set without Shredder<br />
depressors.<br />
Hose with Shredder valve Depressor Hose without Shredder valve Depressor<br />
Hose selection is important depending whether the system is being evacuated or charged. Charging<br />
liquid from the cylinder into the liquid line should be carried out using an open hose connected to an<br />
unrestricted fitting. This will reduce charging time.<br />
TM-YFS-0410-A<br />
®<br />
18
®<br />
19<br />
TM-YFS-0410-A<br />
Typical service valves<br />
found on the outdoor unit<br />
Shredder core<br />
Shredder valve with<br />
core in place<br />
Compressor Range Model lbs. kg.<br />
Quest ZR46 to ZR81 10 4.5<br />
Summit ZR84 to ZR144 16 7.3<br />
Specter ZR90 to ZR19M 17 7.7<br />
Shredder valves<br />
Most split systems have a suitable connection on the outdoor unit<br />
Shredder valve with core removed<br />
Shredder valves provide easy system access for pressure reading and addition of refrigerant. On<br />
small systems, they provide a reasonable connection for evacuation also. However, Shredder valves<br />
and the hoses connected to them can cause very severe pressure drops and can multiply evacuation<br />
time by a factor of 4 or 5. On the positive side, Shredder valves provide a restriction that slows the<br />
speed of liquid charging into the suction side. When a pressure drop is desirable (charging liquid into<br />
suction), connect via a Shredder valve. When a pressure drop is detrimental (evacuation), connect via<br />
an open fitting.<br />
How Much Refrigerant ?<br />
The proper refrigerant charge should follow the volume as recommended by manufacturer and recommendation<br />
should be followed by the installer. Refer to the table of Refrigerant Charge Level.<br />
If the installer cannot find the correct charge but the system must be started, refrigerant should be<br />
carefully added to the system until reasonable sub-cooling is measured in the liquid line and reasonable<br />
suction super-heat is measured at the compressor suction. Suction and discharge pressures<br />
must be monitored carefully during the charging process.<br />
Charge Limits<br />
Copeland Scroll compressors have the different charge limits for different compressor models as shown<br />
in table below. If the total charge exceeds these limits, the system should have a crank case heater<br />
and/or pump downcycle and/or accumulator to prevent liquid damage to the compressor. Some<br />
systems may require accumulators to limit liquid flood back even though the charge is lower than the<br />
published limit.
Charging Recommendations<br />
Charging liquid in a CONTROLLED manner into the suction side until the system is full .This recommendation<br />
does not hold true for reciprocating compressors where liquid charging into the suction side could cause<br />
severe damage.<br />
Charging Cylinder on Scale Close-up of Scale<br />
Carefully monitor the suction and discharge pressures - ensure that the suction pressure does not fall below 25<br />
psig (1.7 bar) at any time during the charging process.<br />
CAUTION : Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and<br />
Manifold valve "A" are both open.<br />
Charging Procedures - Three phase compressors<br />
There are many ways of charging liquid in a "controlled manner" into the<br />
suction side:-<br />
1. Use valve A on the manifold gauge set<br />
2. Use the valve on the refrigerant cylinder<br />
3. Charge through a Shredder valve<br />
4. Use a hose with a Shredder valve depressor<br />
5. Charge into the suction side at some distance from the compressor.<br />
6. All of the above<br />
A<br />
The fundamental procedure is the same as for single phase models but the compressor can run in the wrong<br />
direction on starting. If this happens reverse any two phases and start again. Short term reverse rotation will<br />
not damage the compressor.<br />
As compressors get larger the importance of correct field charging procedures grows exponentially. Unfortunately<br />
larger systems are often field charged which leads to many infant failures. All Specter compressors<br />
have internal discharge temperature protectors which are very effective in preventing dangerously high<br />
discharge temperatures during charging. The protection module will trip and lock the compressor out for 30<br />
minutes. It is not normally necessary to wait 30 minutes for the module to reset. When the compressor has<br />
cooled down the module can be reset by breaking the power supply to the control circuit. Very often the<br />
serviceman does not understand why the module tripped and uses a jumper wire to bypass it. He continues<br />
to charge the system and removes the jumper when charging is complete. The compressor may or may not<br />
run with the protector back in the circuit but it is certain that the compressor has been damaged and premature<br />
failure is inevitable.<br />
TM-YFS-0410-A<br />
®<br />
20
®<br />
21<br />
TM-YFS-0410-A<br />
Model : YFS 50/60/75B<br />
6. Wiring Diagrams<br />
L N<br />
E
Model : YFS 100/125/150B<br />
L<br />
N<br />
E<br />
TM-YFS-0410-A<br />
®<br />
22
®<br />
23<br />
TM-YFS-0410-A<br />
Model : YSF 50/60B - YSL 50/61D<br />
Indoor Unit
Model : YFS 75B - MYSS 72/80C<br />
Indoor Unit<br />
TM-YFS-0410-A<br />
®<br />
24
®<br />
25<br />
TM-YFS-0410-A<br />
Model : YFS 100B - MYSS 100B<br />
Indoor Unit
Model : YFS 125B - MYSS 125B, YFS 150B - MYSS 150B<br />
Indoor Unit<br />
TM-YFS-0410-A<br />
®<br />
26
®<br />
27<br />
TM-YFS-0410-A<br />
7. Servicing and Maintenance<br />
The design concept of the Condensing Unit is such that all servicing can be done from the front and<br />
side of the unit.<br />
Upon removal of front and side panel, all the electrical “terminal box”, fan and motor assembly and<br />
compressor are easily accessible.<br />
Under normal circumstances, these outdoor units only require a check and cleaning of air intake<br />
coil surfaces once quarterly. However, if a unit is installed in area subjected to much oil, mist and dust<br />
, the coil must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure<br />
sufficient heat exchange and proper operation. Otherwise, the systems life span might be shortened.<br />
CAUTION<br />
When the compressor is to be stopped for a long time, the crankcase heater should be energized<br />
for at least 6 hours before start of operation.<br />
Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the<br />
refrigeration cycle when performing a leakage test or an airtight test. These types of gases are<br />
extremely dangerous, because explosion can occur.<br />
It is recommended that nitrogen or refrigerant be charged for these types of tests.<br />
Caution For Use<br />
Bear the following points in mind to safeguard against malfunction and breakdown.<br />
Do not stick rods or other objects through the air outlet during operation since this may result to<br />
damage or injury<br />
The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped<br />
with a crankcase heater with the compressor).<br />
Make sure the air conditioner is properly grounded by checking the ground terminal.<br />
Maintenance<br />
For superb performance and lasting durability, please do not forget to conduct proper and regular<br />
maintenance.<br />
Cleaning The Outdoor Unit Heat Exchanger<br />
If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will<br />
become dirty impairing its function and reducing the performance of the air conditioned. Consult your<br />
local dealer about the cleaning of the heat exchanger.
8. Troubleshooting<br />
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply<br />
before proceeding with the following troubleshooting procedures.<br />
The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which<br />
are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.<br />
No<br />
Fault<br />
cond<br />
itio<br />
ns<br />
1 The air conditioner unit will not resume after<br />
power failure.<br />
2 The compressor does not operate 3 minutes<br />
after the air conditioner unit is started.<br />
3 The airflow is too slow or room cannot be<br />
cooled sufficiently.<br />
Possi<br />
ble<br />
causes<br />
/ corr<br />
ectiv<br />
e actio<br />
ns<br />
• The auto restart function is not functioning. Please<br />
turn on the unit with the wireless / wired controller.<br />
• Protection against frequent starting.<br />
• Wait for 3 or 4 minutes for the compressor to start<br />
operating by it self.<br />
• The air filter is dirty.<br />
• The doors and windows are opened.<br />
• The air suction and discharge of both indoor and<br />
outdoor units are clogged or blocked.<br />
• The regulated temperature or temperature setting<br />
is not low enough.<br />
4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,<br />
which might have adhered onto the coil, may<br />
cause odor.<br />
• Contact your nearest dealer.<br />
5 Condensation on the front air grille of the indoor<br />
unit.<br />
• This is caused by air humidity after an extended<br />
period of operation.<br />
• The set temperature is too low. Increase the<br />
temperature setting and operate the unit at high<br />
fan speed.<br />
6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest<br />
dealer. This might be due to tilted installation.<br />
7 Hissing airflow sound from the air conditioner<br />
unit during operation.<br />
• Liquid refrigerant flowing into the evaporator coil.<br />
8 The wireless controller display is dim. • The batteries are discharged.<br />
• The batteries are not correctly inserted.<br />
• The assembly is not good.<br />
9 Compressor operates continuously. • Dirty air filter. Clean the air filter.<br />
• Temperature setting too low (cooling). Use higher<br />
temperature setting.<br />
10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower<br />
temperature setting.<br />
TM-YFS-0410-A<br />
®<br />
28
®<br />
29<br />
TM-YFS-0410-A<br />
Diagnostic Guidelines<br />
By means of pressure reading :<br />
Circuit<br />
High side<br />
Low side<br />
High side<br />
Low side<br />
Data<br />
Too low<br />
High side<br />
Low side ●<br />
●<br />
A little low<br />
Pressure<br />
Normal<br />
A little high<br />
High side<br />
Low side ●<br />
High side<br />
Low side<br />
●<br />
●<br />
Too high<br />
●<br />
●<br />
●<br />
Probable cause<br />
1. Overcharged with refrigerant.<br />
2. Non-condensable gases in refrigerant circuit (e.g. air)<br />
3. Obstructed air-intake / discharge.<br />
4. Hot air short circuiting in outdoor unit.<br />
1. Poor compression / no compression (compressor<br />
defective)<br />
2. Reversing valve leaking.<br />
1. Undercharged with refrigerant.<br />
2. Refrigerant leakage.<br />
3. Air filter clogged / dirty (indoor unit).<br />
4. Indoor fan locked / seized.<br />
● 1. Outdoor fan blocked (cooling).<br />
2. Outdoor coil dirty (cooling).<br />
3. Non-condensable gases in refrigerant circuit (e.g. air)<br />
●<br />
1. Air intake temperature of indoor unit too high.
By means of diagnostic flow chart:<br />
Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting<br />
failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes<br />
“Insufficient cooling ”.<br />
i) Diagnosis of Electric Circuit<br />
TM-YFS-0410-A<br />
®<br />
30
®<br />
31<br />
TM-YFS-0410-A<br />
ii ) Diagnosis of Refrigerant Circuit / Application<br />
There might be some causes where the unit starts running but does not perform satisfactorily, i.e.<br />
insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s<br />
intake and discharge air as well as running current.
Indoor Unit<br />
Model : YFS 50/60/75B<br />
MODELS<br />
50B<br />
60B<br />
75B<br />
9. Dimensional Data<br />
A B C<br />
DIMENSION<br />
D E Liquid Suction<br />
203 304 203 266 209 3/8” 7/8”<br />
203 304 203 266 209 1/2” 7/8”<br />
186 338 186 292 220 1/1” 1-1/8”<br />
Model : YFS 100/125/150B<br />
MODELS<br />
100B<br />
125B<br />
150B<br />
A B C<br />
DIMENSION<br />
D Liquid Suction<br />
304 260 266 209 5/8” 1-1/8”<br />
304 260 266 209 3/4” 1-1/8”<br />
338 192 292 220 5/8” 1-3/8”<br />
TM-YFS-0410-A<br />
®<br />
32
®<br />
33<br />
TM-YFS-0410-A<br />
Outdoor Unit<br />
Model : YSL 50D<br />
Model : YSL 61D<br />
All Dimensions are in mm<br />
All Dimensions are in mm
Model : MYSS 72/80C<br />
Model : MYSS 100/125B (Standard Vertical Air Discharge)<br />
Dimension in mm<br />
Dimension in mm<br />
TM-YFS-0410-A<br />
®<br />
34
®<br />
35<br />
TM-YFS-0410-A<br />
Model : MYSS 100/125B<br />
Dimension in mm<br />
Model : MYSS 150C (Standard Vertical Discharge / Non-convertible)<br />
Dimension in mm
Indoor Unit<br />
Model : YFS 50/60B<br />
10. Exploded View & Part List<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 PAINT PANEL BASE YFS 50-75 13 BAFFLE COIL L/R YFS 50-100<br />
2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 50-75<br />
3 INSUL. PANEL DISCH YFS 50-60 15 FILTER FRAME BTM YFS 50-75<br />
4 INSUL. PANEL TOP YFS 50-75 16 INSUL. DRAIN PAN YFS 50-75<br />
5 INSUL. PANEL VERT L/R FRONT L/R 50/75 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />
6 INSUL. PANEL VERT L/R BACK YFS 50-75 18 ASSY COIL AL, 187PC,3R,12FPI YFS 50-60<br />
7 INSUL. PANEL BACK YFS 50-75 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />
8 INSUL. PANEL SIDE YFS 50-150 20 FILTER, 550 x 900 x 22, 70-75% APR YFS 50-75<br />
9 INSUL. PANEL HEADER YFS 50/60/100/125 21 FAN VANE<br />
10 INSUL. PANEL FRONT TOP YFS 50-75 22 CONTROL BOX<br />
11 PAINT GRILLE YFS 50-75 23 CONTROL BOX COVER<br />
12 PAINT FLANGE DISCH YFS 5/60/100/125 24 CONTROLLER, C3D-SLM EC(10m) YORK 1M<br />
TM-YFS-0410-A<br />
®<br />
36
®<br />
37<br />
TM-YFS-0410-A<br />
Model : YFS 100B<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 50-100<br />
2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 100<br />
3 INSUL. PANEL DISCH YFS 100-125 15 FILTER FRAME BTM YFS 100-150<br />
4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 100-150<br />
5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />
6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 12 TPC,3R,12FPI YFS 100<br />
7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />
7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />
8 INSUL. PANEL SIDE YFS 50-150<br />
9 INSUL. PANEL HEADER YFS 50/60/100/125<br />
10 INSUL. PANEL FRONT TOP YFS 100-150<br />
11 PAINT GRILLE YFS 100-150<br />
12 PAINT FLANGE DISCH YFS 5/60/100/125<br />
21 FAN VANE<br />
22 CONTROL BOX<br />
23 CONTROL BOX COVER<br />
24 CONTROLLER, C3D-SLM EC(10m) YORK 1M
Model : YFS 125B<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 125-150<br />
2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 125-150<br />
3 INSUL. PANEL DISCH YFS 100-125 15 FILTER FRAME BTM YFS 100-150<br />
4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 100-150<br />
5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />
6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 8 TPC,3R,12FPI YFS 125<br />
7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />
7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />
8 INSUL. PANEL SIDE YFS 50-150<br />
9 INSUL. PANEL HEADER YFS 50/60/100/125<br />
10 INSUL. PANEL FRONT TOP YFS 100-150<br />
11 PAINT GRILLE YFS 100-150<br />
12 PAINT FLANGE DISCH YFS 5/60/100/125<br />
21 FAN VANE<br />
22 CONTROL BOX<br />
23 CONTROL BOX COVER<br />
24 CONTROLLER, C3D-SLM EC(10m) YORK 1M<br />
TM-YFS-0410-A<br />
®<br />
38
®<br />
39<br />
TM-YFS-0410-A<br />
Model : YFS 150B<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 125-150<br />
2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 125-150<br />
3 INSUL. PANEL DISCH YFS 150 15 FILTER FRAME BTM YFS 125-150<br />
4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 125-150<br />
5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />
6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 10TPC,4R,12FPI YFS 150<br />
7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />
7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />
8 INSUL. PANEL SIDE YFS 50-150<br />
9 INSUL. PANEL HEADER YFS 150<br />
10 INSUL. PANEL FRONT TOP YFS 100-150<br />
11 PAINT GRILLE YFS 100-150<br />
12 PAINT FLANGE DISCH YFS 75-150<br />
21 FAN VANE YFS 50-150<br />
22 CONTROL BOX YFS 50-150<br />
23 CONTROL BOX COVER 50-150<br />
24 CONTROLLER, C3D-SLM EC(10m) YORK 1M
Outdoor Unit<br />
Model : MYSS 72/80C<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 ASSY, BASE PAN 19 CAP FOR FAN BLADE<br />
2 ASSY, COIL 20 GUARD, FAN<br />
3 STRUCTURE FRONT LEFT 21 PANEL, TOP<br />
4 ASSY, PARTITION 22 PANEL, SERVICE<br />
5 ASSY, COMPRESSOR 23 SCREW, TRUSSD HEAD PHILIP<br />
6 PLATE, VALVE 24 SCREW, TRUSSD HEAD PHILIP<br />
7 ASSY, ACCESS VALVE 1/4" 25 SCREW, TRUSSD HEAD PHILIP<br />
8 CLAMP, LIQUID TUBE 3/4" 26 SCREW, SELF TAPPING<br />
9 CLAMP, SUCTION TUBE 1" 35 SCREW, WOOD<br />
10 ASSY, TUBING 37 WASHER<br />
11 STRUCTURE, FRONT RIGHT 38 WASHER, SPRING<br />
12 STRUCTURE, BACK RIGHT 39 NUT HEXAGON<br />
13 ASSY, TERMINAL BOARD MAIN 40 WASHER, ISOLATOR<br />
14 PLATE, ORIFICE SUPPORT 41 WASHER<br />
15 PLATE, ORIFICE 42 WASHER, SPRING<br />
16 BRACKET FAN MOTOR 43 NUT, HEXAGON<br />
17 MOTOR 44 ISOLATOR, DURO 40<br />
18 BLADE, FAN 45 ISOLATOR SLEEVE<br />
TM-YFS-0410-A<br />
®<br />
40
®<br />
41<br />
TM-YFS-0410-A<br />
Model : MYSS 100/125B<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 ASSY, BASE PAN 17 MOTOR<br />
2 COMPRESSOR 18 PROPELLER FAN<br />
MYSS100B 19 FAN GUARD<br />
MYSS125B 20 COVER, TER. BOARD FRONT<br />
3 ASSY, STRUC. BACK L 21 HOISTING BRACKET<br />
4 ASSY, STRUC. BACK R 22 STRUC. TUBE SUPT.<br />
5 SUPT, ORIFICE PLATE MYSS100B<br />
6 ASSY, COIL L MYSS125B<br />
MYSS100B 23 SUPT, TUBE GAS<br />
MYSS125B MYSS100B<br />
7 ASSY, COIL R MYSS125B<br />
MYSS100B 24 CLAMP, TUBE GAS<br />
MYSS125B MYSS100B<br />
8 STRUC, FRONT L MYSS125B<br />
9 STRUC, FRONT R 25 SUPT, TUBE LIQUID<br />
10 STRUC, TOP L 26 CLAMP, TUBE LIQUID<br />
11 STRUC, TOP R 27 ASSY, ACCESS VALVE<br />
12 T/B PANEL PARTS NOT IN DIAGRAM<br />
13 COVER, TER. BOARD BACK PRESS SWITCH, 18PSI<br />
14 PANEL, TOP FRONT PRESS SWITCH, 426PSI<br />
15 ORIFICE PLATE MAGNECTIC CONTACTOR<br />
16 BRACKET, FAN MOTOR PHASE PROTECTOR PP1.03
Model : MYSS 150C<br />
NO. DESCRIPTION NO. DESCRIPTION<br />
1 ASSY, BASE PAN 14 TER. BOX COVER<br />
2 COMPRESSOR 15 PANEL, ORIFICE<br />
3 STRUC, PIPE SUPT. 16 FAN MOTOR BRACKET<br />
4 ASSY, ACCESS VALVE 17 MOTOR<br />
5 SUPT, TUBE LIQUID 18 FAN PROPELLER<br />
6 SUPT, GAS TUBE 19 FAN GUARD<br />
7 ASSY, COIL L 20 PANEL, SERVICE T<br />
8 ASSY, COIL R 21 PANEL, SERVICE B<br />
9 STRUC, COIL 22 ASSY, S. HOISTING BRACKET<br />
10 ASSY, STRUC. BACK L PARTS NOT IN DIAGRAM<br />
11 ASSY, STRUC. BACK R PRESS SWITCH, 18PSI<br />
12 CLAMP, TUBE LIQUID PRESSURE SWITCH, 426PSI<br />
13 CLAMP, GAS TUBE PHASE PROTECTOR, PP1.03<br />
TM-YFS-0410-A<br />
®<br />
42