TECHNICAL MANUAL<br />

<strong>Floor</strong> <strong>Standing</strong><br />

B-<strong>Series</strong><br />

TM-YFS-0410-A<br />

®


Table of Contents<br />

1. Nomenclature ........................................................................................................ 1<br />

2. Features ................................................................................................................ 2<br />

3. Specifications ........................................................................................................ 3<br />

General Data ............................................................................................... 3<br />

Safety Devices ........................................................................................... 11<br />

4. Application Information ........................................................................................ 12<br />

Controllers ................................................................................................. 12<br />

5. Installation ........................................................................................................... 14<br />

6. Wiring Diagram .................................................................................................... 21<br />

7. Servicing & Maintenance .................................................................................... 27<br />

8. Troubleshooting .................................................................................................. 28<br />

9. Dimensional Data ................................................................................................ 32<br />

10. Exploded View & Part List ................................................................................... 36<br />

Note : Installation and maintenance are to be performed only by qualified personnel who are<br />

familiar with local codes and regulations, and experienced with this type of equipment.<br />

Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.<br />

Warning : Moving machinery and electrical power hazard. May cause severe personnel<br />

injury or death. Disconnect and lock off power before servicing equipment.<br />

®


®<br />

TM-YFS-0410-A<br />

1<br />

Y FS 150 B<br />

1. Nomenclacture<br />

<strong>Series</strong><br />

B : B <strong>Series</strong><br />

Capacity<br />

150 : 150,000 Btu/h<br />

Model Name<br />

FS : <strong>Floor</strong> <strong>Standing</strong><br />

Brand<br />

Y : York


2. Features<br />

Easy Maintenance<br />

The simple design concept has maintenance and servicing in mind. Access to the internal part of the unit<br />

can be from front side of the unit by removing a few screws.<br />

Easy and Flexible Installation<br />

The unit is highly compact and therefore it is very easy to select a location to install the unit such that<br />

only a small space is required.<br />

Three Speed Motor<br />

The unit has 3-speed direct driven centrifugal fan. The speed of the fan can be adjusted through the<br />

electronic controller.<br />

Filter Rack<br />

The fan coil unit has filter rack to hold the air filter. This ensures the air flow is clean and the filter is easily<br />

accessible for maintenance and cleaning.<br />

Electronic Controller<br />

Electronic Controller can display cool, dry and fan mode with auto, high, medium and low fan speed.<br />

The temperature settings range from 16 to 30 degrees Celsius. There is a sleep function for cool mode<br />

and programmable on/off timer 1 hour interval. The controller is built with 3 minutes restart delay timer<br />

for compressor protection.<br />

Safety Controls<br />

Manual/Auto reset high pressure and low pressure cut-outs to guard against compressor damage<br />

due to high discharge head pressure and system leakage respectively. Crankcase heater for each<br />

compressor to prevent liquid migration, which can damage compressor valve plates, during off-cycle<br />

and eases start-up.<br />

TM-YFS-0410-A<br />

2<br />

®


®<br />

TM-YFS-0410-A<br />

3<br />

<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />

MODEL<br />

TOTAL COOLING CAPACITY<br />

TOTAL INPUT POWER<br />

TOTAL RUNNING CURRENT - 3Φ<br />

3. Specifications<br />

INDOOR UNIT<br />

YFS50B YFS60B<br />

OUTDOOR UNIT<br />

YSL50D YSL61D<br />

Btu/h 55,000 62,000<br />

W 16,115 18,166<br />

W 5,480 6,232<br />

A<br />

V/Ph/Hz<br />

8.97 10.20<br />

POWER SOURCE 380-415 / 3 / 50<br />

REFRIGERANT TYPE R-22<br />

REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />

FAN<br />

HIGH<br />

l/s / CFM 880 / 1861 1000 / 2115<br />

AIR FLOW MEDIUM<br />

l/s / CFM 709 / 1500 898 / 1900<br />

LOW<br />

l/s / CFM 590 / 1248 810 / 1713<br />

TYPE<br />

CENTRIFUGAL<br />

INDOOR<br />

QUANTITY<br />

MATERIAL<br />

1<br />

G2 GALVANIZED STEEL Z275<br />

DRIVE DIRECT DRIVEN<br />

DIAMETER<br />

mm/in<br />

241 / 9.49<br />

LENGTH mm/in<br />

241 / 9.49<br />

SOUND PRESSURE LEVEL (H/M/L) dBA<br />

73 / 70 / 66 74 / 71 / 67<br />

AIR FLOW<br />

l/s / CFM 1605 / 3400 1770 / 3750<br />

TYPE PROPELLER<br />

QUANTITY 1<br />

OUTDOOR MATERIAL<br />

GLASS REINFORCED ACRYL STYRENE RESIN<br />

DRIVE DIRECT<br />

DIAMETER<br />

mm/in 609.6 / 24 609.6 / 24<br />

SOUND PRESSURE LEVEL<br />

dBA 58 65<br />

FAN MOTOR<br />

TYPE 3-SPEEDS MOTOR<br />

QUANTITY 1<br />

INDEX OF PROTECTION (IP) IP 20<br />

INSULATION GRADE CLASS B<br />

INDOOR POWER SOURCE<br />

V/Ph/Hz<br />

220-240V / 1PH / 50HZ<br />

RATED INPUT POWER<br />

W 810 976<br />

RATED RUNNING CURRENT<br />

A 3.4 4.1<br />

MOTOR OUTPUT<br />

W 315 600<br />

POLES 4 POLES<br />

TYPE INDUCTION<br />

QUANTITY 1<br />

INDEX OF PROTECTION (IP)<br />

IP24 -<br />

INSULATION GRADE<br />

B F<br />

OUTDOOR<br />

POWER SOURCE<br />

RATED INPUT POWER<br />

V/Ph/Hz<br />

W 239<br />

220-240/1/50<br />

335<br />

RATED RUNNING CURRENT<br />

A 1.04 1.6<br />

MOTOR OUTPUT<br />

W 145 335<br />

MOTOR SPEED<br />

RPM 8 8<br />

POLES 6<br />

INDOOR CONDENSATE DRAIN SIZE mm/in<br />

19.1 / 3/4<br />

TYPE<br />

PIPE<br />

CONNECTION SIZE<br />

LIQUID<br />

GAS<br />

mm/in<br />

mm/in<br />

9.5 / 3/8<br />

FLARE VALVE<br />

19.1 / 3/4<br />

12.7 / 1/2<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.


<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />

YFS50B<br />

YSL50D<br />

YFS60B<br />

YSL61D<br />

mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 mm/in 7.00 / 0.276 9.52 / 3/8<br />

mm/in 0.28 / 0.011 0.28 / 0.011<br />

mm/in<br />

ALUMINIUM (CORR. FIN)<br />

0.11 / 0.004<br />

ALUMINIUM (SLIT FIN)<br />

0.11 / 0.004<br />

m2 /ft2 0.84 / 9.04 0.87 / 9.36<br />

2 3<br />

18 16<br />

TYPE<br />

OIL TYPE DAPHNE SE56P EAL ARCTIC 22CC (POE)<br />

OIL AMOUNT cm3 MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

COIL<br />

MATERIAL COPPER TUBE<br />

TUBE DIAMETER 9.53 / 0.375<br />

THICKNESS 0.33 / 0.013<br />

INDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINIUM<br />

0.115 / 0.0045<br />

FIN<br />

FACE AREA 0.465 / 5<br />

ROW 3<br />

FIN PER INCH 12<br />

MATERIAL SEAMLESS INNER GROOVE COPPER<br />

TUBE DIAMETER<br />

THICKNESS<br />

OUTDOOR<br />

MATERIAL<br />

THICKNESS<br />

FIN<br />

FACE AREA<br />

ROW<br />

FIN PER INCH<br />

COMPRESSOR<br />

SCROLL<br />

/ fl.oz. 1400 / 47.3 1774 / 60<br />

INSULATION GRADE<br />

-<br />

OUTDOOR POWER SOURCE<br />

V/Ph/Hz<br />

380-415 / 3 / 50<br />

CAPACITOR<br />

µF<br />

NIL<br />

RATED INPUT POWER W 4244 5000<br />

RATED RUNNING CURRENT A 7.50 8.50<br />

LOCKED ROTOR AMP. A 66 74<br />

AIR QUALITY<br />

TYPE WASHABLE FILTERS<br />

TREATMENT 70 % EFFICIENCY<br />

INDOOR AIR FILTER<br />

QUANTITY<br />

LENGTH<br />

pc<br />

mm/in<br />

1<br />

900 / 35.43<br />

SIZE WIDTH mm/in<br />

550 / 21.65<br />

THICKNESS mm/in<br />

22 / 0.87<br />

UNIT HEIGHT<br />

UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />

mm/in<br />

1950 / 76.77<br />

DIMENSION WIDTH mm/in<br />

530 / 20.87<br />

() - PANEL DEPTH mm/in<br />

710 / 27.95<br />

INDOOR PACKING<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

mm/in<br />

mm/in<br />

2080 / 81.89<br />

550 / 21.65<br />

() - PANEL DEPTH mm/in<br />

950 / 37.40<br />

UNIT WEIGHT<br />

kg/lb 135 / 297.62 135 / 297.62<br />

UNIT<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

852 / 33.5<br />

1030 / 40.6<br />

428 / 16.9<br />

852 / 33.5<br />

1030 / 40.6<br />

428 / 16.9<br />

OUTDOOR<br />

PACKING<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

958 / 37.7<br />

1156 / 45.5<br />

502 / 19.8<br />

958 / 37.7<br />

1156 / 45.5<br />

502 / 19.8<br />

UNIT WEIGHT<br />

kg/lb 105 / 232 108 / 238<br />

CASING<br />

MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />

INDOOR UNIT<br />

FINISHING EPOXY POLYESTER POWER COATING<br />

COLOUR LIGHT GREY<br />

OUTDOOR UNIT<br />

MATERIAL<br />

COLOUR<br />

ELECTRO GALVANIZED MILD STEEL<br />

LIGHT GREY<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />

TM-YFS-0410-A<br />

4<br />

®


®<br />

TM-YFS-0410-A<br />

5<br />

<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />

MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

MYSS72C<br />

YFS75B<br />

MYSS80C<br />

TOTAL COOLING CAPACITY<br />

Btu/h<br />

W<br />

70,000<br />

20,510<br />

77,000<br />

22,561<br />

TOTAL INPUT POWER<br />

W 8,737 9,409<br />

TOTAL RUNNING CURRENT - 3Φ<br />

A 14.30 15.40<br />

POWER SOURCE V/Ph/Hz<br />

380-415 / 3 / 50<br />

REFRIGERANT TYPE R-22<br />

REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />

FAN<br />

HIGH l/s / CFM<br />

1080 / 2284<br />

AIR FLOW MEDIUM l/s / CFM<br />

946 / 2000<br />

LOW l/s / CFM<br />

850 / 1798<br />

TYPE CENTRIFUGAL<br />

INDOOR<br />

QUANTITY<br />

MATERIAL<br />

1<br />

G2 GALVANIZED STEEL Z275<br />

DRIVE DIRECT DRIVEN<br />

DIAMETER mm/in<br />

270 / 10.63<br />

LENGTH mm/in<br />

270 / 10.63<br />

SOUND PRESSURE LEVEL (H/M/L) dBA<br />

74 / 71 / 67<br />

AIR FLOW l/s / CFM<br />

2832 / 6000<br />

TYPE PROPELLER<br />

QUANTITY 1<br />

OUTDOOR MATERIAL ALUMINUM<br />

DRIVE DIRECT<br />

DIAMETER mm/in<br />

660 / 26<br />

SOUND PRESSURE LEVEL<br />

dBA 70 74<br />

FAN MOTOR<br />

TYPE 3-SPEEDS MOTOR<br />

QUANTITY 1<br />

INDEX OF PROTECTION (IP) -<br />

INSULATION GRADE CLASS B<br />

INDOOR POWER SOURCE V/Ph/Hz<br />

220-240V / 1Ph / 50Hz<br />

RATED INPUT POWER W<br />

1120<br />

RATED RUNNING CURRENT A<br />

4.7<br />

MOTOR OUTPUT W<br />

600<br />

POLES 4 POLES<br />

TYPE PERMANENT SPLIT CAPACITOR<br />

QUANTITY 1<br />

INDEX OF PROTECTION (IP) IP54<br />

OUTDOOR<br />

INSULATION GRADE<br />

POWER SOURCE V/Ph/Hz<br />

F<br />

220-240/1/50<br />

E<br />

RATED INPUT POWER<br />

W 740 596<br />

RATED RUNNING CURRENT<br />

A 3.8 2.5<br />

MOTOR OUTPUT<br />

W 145 480<br />

INDOOR CONDENSATE DRAIN SIZE mm/in<br />

19.1 / 3/4<br />

TYPE<br />

PIPE<br />

CONNECTION SIZE<br />

LIQUID<br />

GAS<br />

mm/in<br />

mm/in<br />

FLARE VALVE<br />

12.7 / ½<br />

25.4 / 1<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.


<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />

MYSS72C MYSS80C<br />

mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 2 2<br />

14 14<br />

cm3 MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

YFS75B<br />

COIL<br />

MATERIAL COPPER TUBE<br />

TUBE DIAMETER 9.53 / 0.375<br />

THICKNESS 0.33 / 0.013<br />

INDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINIUM<br />

0.115 / 0.0045<br />

FIN<br />

FACE AREA 0.465 / 5<br />

ROW 4<br />

FIN PER INCH 12<br />

MATERIAL SEAMLESS INNER SMOOTH COPPER<br />

TUBE DIAMETER 9.52 / 3/8<br />

THICKNESS 0.28 / 0.011<br />

OUTDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINUM<br />

0.11 / 0.004<br />

FIN<br />

FACE AREA 1.23 / 13.25<br />

ROW<br />

FIN PER INCH<br />

COMPRESSOR<br />

TYPE SCROLL<br />

OIL TYPE SONTEX 200LT/ MINERAL OIL<br />

OIL AMOUNT<br />

/ fl.oz. 1240.0 / 44 3000.0 / 101<br />

INSULATION GRADE<br />

F E<br />

OUTDOOR POWER SOURCE<br />

V/Ph/Hz<br />

380-415/3/50<br />

CAPACITOR µF<br />

NIL<br />

RATED INPUT POWER<br />

W 5800 7561<br />

RATED RUNNING CURRENT<br />

A 11.5 13.0<br />

LOCKED ROTOR AMP.<br />

A 97 102<br />

AIR QUALITY<br />

TYPE WASHABLE FILTERS<br />

TREATMENT 70 % EFFICIENCY<br />

INDOOR AIR FILTER<br />

QUANTITY<br />

LENGTH<br />

pc<br />

mm/in<br />

1<br />

900 / 35.43<br />

SIZE WIDTH mm/in<br />

550 / 21.65<br />

THICKNESS mm/in<br />

22 / 0.87<br />

UNIT HEIGHT<br />

UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />

mm/in<br />

1950 / 76.77<br />

DIMENSION WIDTH mm/in<br />

530 / 20.87<br />

() - PANEL DEPTH mm/in<br />

710 / 27.95<br />

INDOOR PACKING HEIGHT mm/in<br />

2080 / 81.89<br />

DIMENSION WIDTH<br />

() - PANEL DEPTH<br />

mm/in<br />

mm/in<br />

550 / 21.65<br />

950 / 37.40<br />

UNIT WEIGHT kg/lb<br />

142 / 33.05<br />

UNIT<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

946 / 37.2<br />

1300 / 51.2<br />

500 / 19.7<br />

OUTDOOR<br />

PACKING<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

1132 / 44.56<br />

1414 / 55.66<br />

664 / 26.14<br />

UNIT WEIGHT<br />

kg/lb 145 / 320<br />

CASING<br />

MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />

INDOOR UNIT<br />

FINISHING EPOXY POLYESTER POWER COATING<br />

COLOUR<br />

LIGHT GREY<br />

OUTDOOR UNIT<br />

MATERIAL<br />

COLOUR<br />

ELECTRO GALVANIZED MILD STEEL<br />

LIGHT GREY<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />

TM-YFS-0410-A<br />

6<br />

®


®<br />

TM-YFS-0410-A<br />

7<br />

<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />

MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

YFS100B<br />

MYSS100B<br />

YFS125B<br />

MYSS125B<br />

TOTAL COOLING CAPACITY<br />

Btu/h<br />

W<br />

101,000<br />

29,593<br />

125,000<br />

36,625<br />

TOTAL INPUT POWER<br />

W 11,383 10,631<br />

TOTAL RUNNING CURRENT - 3Φ<br />

A 18.63 17.40<br />

POWER SOURCE V/Ph/Hz<br />

380-415 / 3 / 50<br />

REFRIGERANT TYPE R-22<br />

REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR TXV VALVE<br />

FAN<br />

HIGH<br />

l/s / CFM 1759.7 / 3722 1942.2 / 4108<br />

AIR FLOW MEDIUM<br />

l/s / CFM 1418 / 3000 1702 / 3600<br />

LOW<br />

l/s / CFM 1180.1 / 2496 1519.5 / 3214<br />

TYPE<br />

CENTRIFUGAL<br />

INDOOR<br />

QUANTITY<br />

MATERIAL<br />

2<br />

G2 GALVANIZED STEEL Z275<br />

DRIVE DIRECT DRIVEN<br />

DIAMETER<br />

mm/in<br />

241 / 9.49<br />

LENGTH mm/in<br />

241 / 9.49<br />

SOUND PRESSURE LEVEL (H/M/L) dBA<br />

78 / 75 / 73<br />

AIR FLOW<br />

l/s / CFM 2926 / 6200 2926 / 6200<br />

TYPE PROPELLER<br />

QUANTITY 1<br />

OUTDOOR MATERIAL ALUMINUM<br />

DRIVE DIRECT<br />

DIAMETER mm/in<br />

660 / 26<br />

SOUND PRESSURE LEVEL<br />

dBA 65 65<br />

FAN MOTOR<br />

TYPE 3-SPEEDS MOTOR<br />

QUANTITY 2<br />

INDEX OF PROTECTION (IP) IP 20<br />

INSULATION GRADE<br />

CLASS B<br />

INDOOR POWER SOURCE V/Ph/Hz<br />

220-240V / 1Ph / 50Hz<br />

RATED INPUT POWER<br />

W 810 881<br />

RATED RUNNING CURRENT<br />

A 3.4 3.7<br />

MOTOR OUTPUT<br />

W 315 600<br />

POLES 4 POLES<br />

TYPE PERMANENT SPLIT CAPACITOR<br />

QUANTITY 1<br />

INDEX OF PROTECTION (IP) IP54<br />

OUTDOOR<br />

INSULATION GRADE<br />

POWER SOURCE V/Ph/Hz<br />

F<br />

380-415/3/50<br />

F<br />

RATED INPUT POWER<br />

W 660 820<br />

RATED RUNNING CURRENT<br />

A 1.5 1.2<br />

MOTOR OUTPUT<br />

W 470 520<br />

INDOOR CONDENSATE DRAIN SIZE mm/in<br />

19.1 / 3/4<br />

PIPE<br />

CONNECTION<br />

TYPE<br />

SIZE<br />

LIQUID<br />

GAS<br />

mm/in<br />

mm/in<br />

15.9 / 5/8<br />

28.6 / 1 1/8<br />

FLARE VALVE<br />

15.9 / 5/8<br />

34.9 / 1 3/8<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.


<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />

YFS100B<br />

MYSS100B<br />

YFS125B<br />

MYSS125B<br />

mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 0.836 / 9 0.883 / 9.5<br />

mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 1.76 / 19.00 1.76 / 19.00<br />

2 2<br />

12 16<br />

cm3 MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

COIL<br />

MATERIAL COPPER TUBE<br />

TUBE DIAMETER<br />

9.53 / 0.375<br />

THICKNESS 0.33 / 0.013<br />

INDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINIUM<br />

0.115 / 0.0045<br />

FIN<br />

FACE AREA<br />

ROW<br />

3<br />

FIN PER INCH 12<br />

MATERIAL SEAMLESS INNER SMOOTH COPPER<br />

TUBE DIAMETER 9.52 / 3/8<br />

THICKNESS<br />

0.28 / 0.011<br />

OUTDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINUM<br />

0.11 / 0.004<br />

FIN<br />

FACE AREA<br />

ROW<br />

FIN PER INCH<br />

COMPRESSOR<br />

TYPE SCROLL<br />

OIL TYPE SONTEX 200LT/ MINERAL OIL<br />

OIL AMOUNT<br />

/ fl.oz. 3253.1 / 110 3253.1 / 110<br />

INSULATION GRADE F<br />

OUTDOOR POWER SOURCE<br />

V/Ph/Hz<br />

380-415/3/50<br />

CAPACITOR µF<br />

NIL<br />

RATED INPUT POWER<br />

W 8607 9172<br />

RATED RUNNING CURRENT<br />

A 16.0 15.0<br />

LOCKED ROTOR AMP.<br />

A 125 110<br />

AIR QUALITY<br />

TYPE WASHABLE FILTERS<br />

TREATMENT 70 % EFFICIENCY<br />

INDOOR AIR FILTER<br />

QUANTITY<br />

LENGTH<br />

pc<br />

mm/in<br />

2<br />

478 / 21.65<br />

SIZE WIDTH mm/in<br />

900 / 35.43<br />

THICKNESS mm/in<br />

22 / 0.87<br />

UNIT HEIGHT<br />

UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />

mm/in<br />

1950 / 76.77<br />

DIMENSION WIDTH mm/in<br />

530 / 20.87<br />

() - PANEL DEPTH mm/in<br />

1180 / 46.46<br />

INDOOR PACKING HEIGHT mm/in<br />

2080 / 81.89<br />

DIMENSION WIDTH mm/in<br />

550 / 21.65<br />

() - PANEL DEPTH mm/in<br />

1370 / 53.94<br />

UNIT WEIGHT kg/lb<br />

190 / 418.87<br />

UNIT<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

946 / 37.2<br />

1116 / 43.9<br />

939 / 37.0<br />

946 / 37.2<br />

1116 / 43.9<br />

939 / 37.0<br />

OUTDOOR<br />

PACKING<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

1132 / 44.6<br />

1282 / 50.5<br />

1112 / 43.8<br />

1132 / 44.6<br />

1282 / 50.5<br />

1112 / 43.8<br />

UNIT WEIGHT<br />

kg/lb 164 / 361 224 / 493<br />

CASING<br />

MATERIAL ELECTRO-GALVANIZED MILD STEEL<br />

INDOOR UNIT<br />

FINISHING EPOXY POLYESTER POWER COATING<br />

COLOUR<br />

LIGHT GREY<br />

OUTDOOR UNIT<br />

MATERIAL<br />

COLOUR<br />

ELECTRO GALVANIZED MILD STEEL<br />

LIGHT GREY<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />

TM-YFS-0410-A<br />

8<br />

®


®<br />

TM-YFS-0410-A<br />

9<br />

<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong><br />

MODEL<br />

TOTAL COOLING CAPACITY<br />

INDOOR<br />

OUTDOOR<br />

HIGH<br />

AIR FLOW MEDIUM<br />

LOW<br />

TYPE<br />

QUANTITY<br />

MATERIAL<br />

DRIVE<br />

DIAMETER<br />

LENGTH<br />

SOUND PRESSURE LEVEL (H/M/L)<br />

AIR FLOW<br />

TYPE<br />

QUANTITY<br />

MATERIAL<br />

DRIVE<br />

DIAMETER<br />

SOUND PRESSURE LEVEL<br />

TYPE<br />

QUANTITY<br />

INDEX OF PROTECTION (IP)<br />

INSULATION GRADE<br />

INDOOR POWER SOURCE<br />

RATED INPUT POWER<br />

RATED RUNNING CURRENT<br />

MOTOR OUTPUT<br />

POLES<br />

TYPE<br />

QUANTITY<br />

INDEX OF PROTECTION (IP)<br />

INSULATION GRADE<br />

OUTDOOR<br />

POWER SOURCE<br />

RATED INPUT POWER<br />

RATED RUNNING CURRENT<br />

MOTOR OUTPUT<br />

INDOOR CONDENSATE DRAIN SIZE<br />

TYPE<br />

PIPE<br />

LIQUID<br />

CONNECTION SIZE<br />

GAS<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

TOTAL INPUT POWER<br />

TOTAL RUNNING CURRENT - 3Φ<br />

POWER SOURCE<br />

REFRIGERANT TYPE<br />

REFRIGERANT CONTROL (EXPANSION DEVICE)<br />

Btu/h<br />

W<br />

W<br />

A<br />

V/Ph/Hz<br />

l/s / CFM<br />

l/s / CFM<br />

l/s / CFM<br />

mm/in<br />

mm/in<br />

dBA<br />

l/s / CFM<br />

mm/in<br />

dBA<br />

V/Ph/Hz<br />

W<br />

A<br />

W<br />

V/Ph/Hz<br />

W<br />

A<br />

W<br />

mm/in<br />

mm/in<br />

mm/in<br />

FAN<br />

FAN MOTOR<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />

YFS150B<br />

MYSS150C<br />

153,000<br />

44,829<br />

15,745<br />

25.77<br />

380-415 / 3 / 50<br />

R-22<br />

INDOOR TXV VALVE<br />

2160 / 4569<br />

1891 / 4000<br />

1700 / 3695<br />

CENTRIFUGAL<br />

2<br />

G2 GALVANIZED STEEL Z275<br />

DIRECT DRIVEN<br />

270 / 10.63<br />

270 / 10.63<br />

78 / 75 / 73<br />

4720 / 10000<br />

PROPELLER<br />

1<br />

ALUMINUM<br />

DIRECT<br />

762 / 30<br />

73<br />

3-SPEEDS MOTOR<br />

2<br />

IP 20<br />

CLASS B<br />

220-240V / 1Ph / 50Hz<br />

1120<br />

4.7<br />

600<br />

4 POLES<br />

INDUCTION<br />

1<br />

IP54<br />

F<br />

380-415 / 3 / 50<br />

820<br />

1.2<br />

520<br />

19.1 / 3/4<br />

FLARE VALVE<br />

15.9 / 5/8<br />

34.9 / 1 3/8


<strong>Floor</strong> <strong>Standing</strong> Type - YFS-B <strong>Series</strong> (Cont’d)<br />

mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 mm/in<br />

mm/in<br />

mm/in<br />

m2 /ft2 cm3 MODEL<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

YFS150B<br />

MYSS150C<br />

COIL<br />

MATERIAL<br />

COPPER TUBE<br />

TUBE DIAMETER<br />

9.53 / 0.375<br />

THICKNESS<br />

0.33 / 0.013<br />

INDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINIUM<br />

0.115 / 0.0045<br />

FIN<br />

FACE AREA<br />

0.883 / 9.5<br />

ROW<br />

4<br />

FIN PER INCH<br />

12<br />

MATERIAL<br />

SEAMLESS INNER SMOOTH COPPER<br />

TUBE DIAMETER<br />

9.52 / 3/8<br />

THICKNESS<br />

0.28 / 0.011<br />

OUTDOOR<br />

MATERIAL<br />

THICKNESS<br />

ALUMINUM<br />

0.11 / 0.004<br />

FIN<br />

FACE AREA<br />

1.24 / 13.38<br />

ROW<br />

2<br />

FIN PER INCH<br />

14<br />

COMPRESSOR<br />

TYPE<br />

SCROLL<br />

OIL TYPE<br />

SONTEX 200LT/ MINERAL OIL<br />

OIL AMOUNT<br />

/ fl.oz.<br />

2513.8 / 85<br />

INSULATION GRADE<br />

F<br />

OUTDOOR POWER SOURCE<br />

V/Ph/Hz<br />

380-415/3/50<br />

CAPACITOR<br />

µF<br />

NIL<br />

RATED INPUT POWER<br />

W<br />

12502<br />

RATED RUNNING CURRENT<br />

A<br />

23.0<br />

LOCKED ROTOR AMP.<br />

A<br />

AIR QUALITY<br />

198<br />

TYPE<br />

WASHABLE FILTERS<br />

TREATMENT<br />

70 % EFFICIENCY<br />

INDOOR AIR FILTER<br />

QUANTITY<br />

LENGTH<br />

pc<br />

mm/in<br />

2<br />

478 / 21.65<br />

SIZE WIDTH mm/in<br />

900 / 35.43<br />

THICKNESS mm/in<br />

22 / 0.87<br />

UNIT HEIGHT<br />

UNIT & PACKING DIMENSIONS, UNIT WEIGHT<br />

mm/in<br />

1950 (76.77)<br />

DIMENSION WIDTH<br />

mm/in<br />

530 (20.87)<br />

() - PANEL DEPTH<br />

mm/in<br />

1180 (46.46)<br />

INDOOR PACKING HEIGHT<br />

mm/in<br />

2080 (81.89)<br />

DIMENSION WIDTH<br />

mm/in<br />

550 (21.65)<br />

() - PANEL DEPTH<br />

mm/in<br />

1370 (53.94)<br />

UNIT WEIGHT<br />

kg/lb<br />

200 / 440.92<br />

UNIT<br />

DIMENSION<br />

HEIGHT<br />

WIDTH<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

1041 / 41.0<br />

1116 / 43.9<br />

939 / 37.0<br />

OUTDOOR<br />

HEIGHT<br />

PACKING<br />

WIDTH<br />

DIMENSION<br />

DEPTH<br />

mm/in<br />

mm/in<br />

mm/in<br />

1132 / 44.6<br />

1282 / 50.5<br />

1112 / 43.8<br />

UNIT WEIGHT<br />

kg/lb<br />

258 / 568<br />

CASING<br />

MATERIAL<br />

ELECTRO-GALVANIZED MILD STEEL<br />

INDOOR UNIT<br />

FINISHING<br />

EPOXY POLYESTER POWER COATING<br />

COLOUR<br />

LIGHT GREY<br />

OUTDOOR UNIT<br />

MATERIAL<br />

COLOUR<br />

ELECTRO GALVANIZED MILD STEEL<br />

LIGHT GREY<br />

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240.<br />

3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW:<br />

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB / 23.9°C WB OUTDOOR<br />

4) EER CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ARI 210/240.<br />

TM-YFS-0410-A<br />

®<br />

10


®<br />

11<br />

TM-YFS-0410-A<br />

Safety Device<br />

MODEL<br />

SAFETY DEVICE<br />

MODEL<br />

SAFETY DEVICE<br />

MODEL<br />

SAFETY DEVICE<br />

MODEL<br />

SAFETY DEVICE<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

HIGH PRESSURE SWITCH<br />

LOW PRESSURE SWITCH<br />

PHASE SEQUENCER, 1Φ <br />

DISCHARGE THERMOSTAT SETTING<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

HIGH PRESSURE SWITCH<br />

LOW PRESSURE SWITCH<br />

PHASE SEQUENCER<br />

DISCHARGE THERMOSTAT SETTING<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

HIGH PRESSURE SWITCH<br />

LOW PRESSURE SWITCH<br />

PHASE SEQUENCER<br />

DISCHARGE THERMOSTAT SETTING<br />

INDOOR UNIT<br />

OUTDOOR UNIT<br />

HIGH PRESSURE SWITCH<br />

LOW PRESSURE SWITCH<br />

PHASE SEQUENCER<br />

DISCHARGE THERMOSTAT SETTING<br />

YFS50B YFS60B<br />

YSL50D YSL61D<br />

TYPE<br />

NC NC<br />

OPEN kPa / psi 2937 / 426 2937 / 426<br />

CLOSE kPa / psi 2413 / 350 2413 / 350<br />

TYPE<br />

NC NC<br />

OPEN kPa / psi 124 / 18 124 / 18<br />

CLOSE kPa / psi 193 / 28 193 / 28<br />

<br />

°C / °F <br />

YFS75B<br />

MYSS72C MYSS80C<br />

TYPE<br />

AUTO RESET AUTO RESET<br />

OPEN Pa / psi 2937 / 426 2937 / 426<br />

CLOSE Pa / psi 2413 / 350 2413 / 350<br />

TYPE<br />

AUTO RESET AUTO RESET<br />

OPEN Pa / psi 124 / 18 124 / 18<br />

CLOSE Pa / psi 193 / 28 193 / 28<br />

OYLT OYLT<br />

°C / °F 125 / 257 125 / 257<br />

YFS100B YFS125B<br />

MYSS100B MYSS125B<br />

TYPE<br />

AUTO RESET AUTO RESET<br />

OPEN Pa / psi 2937 / 426 2937 / 426<br />

CLOSE Pa / psi 2413 / 350 2413 / 350<br />

TYPE<br />

AUTO RESET AUTO RESET<br />

OPEN Pa / psi 124 / 18 124 / 18<br />

CLOSE Pa / psi 193 / 28 193 / 28<br />

OYLT OYLT<br />

°C / °F 125 / 257 125 / 257<br />

TYPE<br />

OPEN Pa / psi<br />

CLOSE<br />

TYPE<br />

Pa / psi<br />

OPEN Pa / psi<br />

CLOSE Pa / psi<br />

°C / °F<br />

YFS150B<br />

MYSS150C<br />

AUTO RESET<br />

2937 / 426<br />

2413 / 350<br />

AUTO RESET<br />

124 / 18<br />

193 / 28<br />

OYLT<br />

125 / 257


Control Panel<br />

8<br />

9<br />

2<br />

5<br />

4. Application Information<br />

TEMP<br />

TIMER<br />

AUTO<br />

HIGH<br />

MED<br />

LOW<br />

SENSOR<br />

FAN<br />

SWING<br />

COOL<br />

DRY<br />

HEAT<br />

FAN<br />

ON/OFF<br />

MODE<br />

SLEEP<br />

1. “ON/OFF” switch 6. “Sleep” mode<br />

• Press to start the air conditioner unit. • Press button to activate the sleep<br />

• Press again to stop the unit. function can only be activated under<br />

“cool” mode operation.<br />

2. Temperature setting The set temperature will increase 0.5°C<br />

• Set the desired room temperature.<br />

after 30 minutes, 1°C after 1 hour and 2°C<br />

• Press button to increase or decrease the<br />

set temperature. Setting range are between<br />

after 2 hours.<br />

16°C to 30°C (60°F to 80°F).<br />

7. Air Swing<br />

3. Operation Modes<br />

• Press the “mode” button for select the type<br />

• Press button to activate the automatic air<br />

swing function.<br />

of operating mode.<br />

COOL, DRY, FAN<br />

8. Sensor<br />

• Infra red sensor to receive signals from<br />

wireless controller.<br />

4. Fan Speed selection. 9. LED Display<br />

• Press the button until the desired fan speed • To display the set temperature (in °C) and<br />

is achieved. timer delay setting (in hours).<br />

5. Timer. 10. Transmission source<br />

• Press the set button to select the switch • To transmit signals to the air conditioner.<br />

timer of the air conditioner unit (the setting<br />

range is between 1 to 10 hours).<br />

4<br />

1<br />

3<br />

6<br />

7<br />

TM-YFS-0410-A<br />

®<br />

12


®<br />

13<br />

TM-YFS-0410-A<br />

Operating State And Fault Table<br />

Wireless Remote Control (Universal Board)<br />

Cooling : LED Indicator Light Display<br />

POWER TIMER SLEEP<br />

POWER TIMER<br />

1 Time<br />

2 Times<br />

3 Times<br />

1 Time<br />

3 Times<br />

SLEEP<br />

ON / ON or OFF BLINKING<br />

Operation / Faulty Indication<br />

Cool Mode<br />

Timer On<br />

Sleep Mode On<br />

Compressor Overload<br />

Gas Leak<br />

Room Sensor Open or Short<br />

Indoor Coil Sensor Open or Short<br />

Outdoor Coil Sensor Open or Short


c) Ensure that the location is convenient for wiring and piping.<br />

5. Installations<br />

Indoor Unit<br />

Preliminary Site Survey<br />

a) Electrical supply and installation is to confirm to local authority’s (e.g. National Electricity Board)<br />

codes and regulations.<br />

b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be<br />

independent of welding transformers which can cause supply fluctuation.<br />

c) Ensure that the location is convenient for wiring and piping.<br />

Pipings<br />

Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed<br />

or had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally,<br />

do not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect<br />

suction or liquid line into fittings.<br />

Operational Check<br />

After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is<br />

operating properly. Check that:<br />

a) Condenser fans are running, with warm air blowing off the condenser coil.<br />

b) Evaporator blowers are running and discharging cool air.<br />

c) Suction line inside condensing unit feels cool.<br />

d) Liquid line inside condensing unit feels warm.<br />

Electrical Connection<br />

As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for<br />

field wiring regulations and ensure that these are complied with. Besides, observe the following general<br />

precautions:<br />

a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing<br />

wiringwork.<br />

b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit<br />

breaker for over-current protection should be provided in the exclusive line.<br />

c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.<br />

d) All wiring must be firmly connected.<br />

e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan<br />

motors.<br />

TM-YFS-0410-A<br />

®<br />

14


®<br />

15<br />

TM-YFS-0410-A<br />

Outdoor Unit<br />

Location For Installation Of The Condensing Units<br />

As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve<br />

maximum cooling capacity, the location selected should fulfill the following requirements:-<br />

a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit<br />

cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for<br />

maintenance around the unit.<br />

b) Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacle which block air intake or<br />

discharge.<br />

c) The location must be well ventilated, so that the unit can draw and distribute plenty of air thus lowering the<br />

condensing temperature.<br />

d) A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.<br />

e) A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.<br />

f) A place where the hot air discharge and operating sound level will not annoy the neighbours.<br />

g) The location must not be susceptible to dust or oil mist.<br />

CAUTION: If the condensing unit is operated in an atmosphere containing oils (including machine<br />

oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances<br />

may lead to failure of the unit.


Field Piping<br />

To ensure satisfactory operation and performance, the following points should be noted for the field<br />

piping arrangements of the complete refrigerant cycle.<br />

a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units<br />

(depending on whether the indoor unit is above or below the outdoor unit).<br />

b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit<br />

(evaporator) as possible.<br />

c) Field supplied sight glass must be assembled and mounted next to filter dryer.<br />

Maximum Pipe Length And Maximum Number Of Bends<br />

When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability<br />

drops asa result. As the number of bends increases, system piping resistance to the refrigerant flow<br />

increases, thus lowering the cooling capacity and the compressor may become defective. If the height<br />

difference between the evaporator and the condenser is excessive, the cooling capacity drops, the<br />

lubricating oil return is retarded, affecting the compressor efficiency adversely.<br />

Always choose the shortest piping path and follow the recommendations as shown below :-<br />

Model<br />

Max. Elevation, m<br />

(ft.)<br />

Max. Total Length, m<br />

(ft.)<br />

MYSS 100/125B 25 (82.0) 45 (147.6) 8<br />

MYSS 80/150C 25 (82.0) 45 (147.6) 8<br />

Note : If piping is more than 100ft, it is recommended to add in an accumulator.<br />

Max. of Bends<br />

CAUTION:<br />

1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height,<br />

length and/or the number of bends of the refrigerant piping system installed is beyond the<br />

limit above.<br />

2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe<br />

as far as possible.<br />

TM-YFS-0410-A<br />

®<br />

16


®<br />

17<br />

TM-YFS-0410-A<br />

When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply<br />

before proceeding with the following troubleshooting procedures.<br />

The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which<br />

are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.<br />

No<br />

Fault<br />

onditions<br />

1 The air conditioner unit will not resume after<br />

power failure.<br />

2 The compressor does not operate 3 minutes<br />

after the air conditioner unit is started.<br />

3 The airflow is too slow or room cannot be<br />

cooled sufficiently.<br />

c<br />

Possib<br />

le<br />

causes<br />

/ corrective<br />

a<br />

ctions<br />

• The auto restart function is not functioning. Please<br />

turn on the unit with the wireless / wired controller.<br />

• Protection against frequent starting.<br />

• Wait for 3 or 4 minutes for the compressor to start<br />

operating by it self.<br />

• The air filter is dirty.<br />

• The doors and windows are opened.<br />

• The air suction and discharge of both indoor and<br />

outdoor units are clogged or blocked.<br />

• The regulated temperature or temperature setting<br />

is not low enough.<br />

4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,<br />

which might have adhered onto the coil, may<br />

cause odor.<br />

• Contact your nearest dealer.<br />

5 Condensation on the front air grille of the indoor<br />

unit.<br />

• This is caused by air humidity after an extended<br />

period of operation.<br />

• The set temperature is too low. Increase the<br />

temperature setting and operate the unit at high<br />

fan speed.<br />

6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest<br />

dealer. This might be due to tilted installation.<br />

7 Hissing airflow sound from the air conditioner<br />

unit during operation.<br />

• Liquid refrigerant flowing into the evaporator coil.<br />

8 The wireless controller display is dim. • The batteries are discharged.<br />

• The batteries are not correctly inserted.<br />

• The assembly is not good.<br />

9 Compressor operates continuously. • Dirty air filter. Clean the air filter.<br />

• Temperature setting too low (cooling). Use higher<br />

temperature setting.<br />

10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower<br />

temperature setting.


Guidelines Of Field-charging Air Conditioning Systems With Scroll Compressors<br />

These guidelines are intended for use with Scroll compressors only with R22, R407C, R134a, R404A,<br />

R507,and R410A refrigerants. They do not apply to reciprocating compressors or competitive Scroll<br />

compressors.<br />

Field -Charging - Some Precaution Points<br />

Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there is<br />

insufficient refrigerant in the system or if refrigerant is added too slowly. Operation with low suction<br />

pressure will quickly lead to very high discharge temperatures. While this process is happening, the<br />

scrolls are not being well lubricated - scrolls depend on the oil mist in the refrigerant for lubrication. A<br />

lack of lubrication leads to high friction between the scroll flanks and tips and generates additional heat.<br />

The combination of heat of compression and heat from increased friction is concentrated in a small<br />

localized discharge area where temperature scan quickly rise to more than 300°C. These extreme<br />

temperatures damage the Scroll spirals and the orbiting Scroll bearing. This damage can occur in less<br />

than one minute especially on larger compressors. Failure may occur in the first few hours or the<br />

damage done during field charging may show up some time later. Other typical field charging problems<br />

include undercharging, overcharging, moisture or air in the system etc. In time each one of these problems<br />

can cause compressor failure.<br />

Equipment<br />

Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory<br />

job is:-<br />

Set of service gauges<br />

Hoses<br />

Vacuum pump<br />

Vacuum gauge<br />

ScalesThermometer<br />

Charging Hoses<br />

Most field-charging is done using standard service hoses. Hoses are made in different colors with<br />

different working pressures and with different leak rates but the most important point is the presence<br />

or absence of Shredder valve depressors. Shredder valve depressors severely restrict the flow through<br />

the service hoses.This slows evacuation and vapor charging dramatically. In most cases the Shredder<br />

depressor can be removed but it is simpler to have one set of hoses with and one set without Shredder<br />

depressors.<br />

Hose with Shredder valve Depressor Hose without Shredder valve Depressor<br />

Hose selection is important depending whether the system is being evacuated or charged. Charging<br />

liquid from the cylinder into the liquid line should be carried out using an open hose connected to an<br />

unrestricted fitting. This will reduce charging time.<br />

TM-YFS-0410-A<br />

®<br />

18


®<br />

19<br />

TM-YFS-0410-A<br />

Typical service valves<br />

found on the outdoor unit<br />

Shredder core<br />

Shredder valve with<br />

core in place<br />

Compressor Range Model lbs. kg.<br />

Quest ZR46 to ZR81 10 4.5<br />

Summit ZR84 to ZR144 16 7.3<br />

Specter ZR90 to ZR19M 17 7.7<br />

Shredder valves<br />

Most split systems have a suitable connection on the outdoor unit<br />

Shredder valve with core removed<br />

Shredder valves provide easy system access for pressure reading and addition of refrigerant. On<br />

small systems, they provide a reasonable connection for evacuation also. However, Shredder valves<br />

and the hoses connected to them can cause very severe pressure drops and can multiply evacuation<br />

time by a factor of 4 or 5. On the positive side, Shredder valves provide a restriction that slows the<br />

speed of liquid charging into the suction side. When a pressure drop is desirable (charging liquid into<br />

suction), connect via a Shredder valve. When a pressure drop is detrimental (evacuation), connect via<br />

an open fitting.<br />

How Much Refrigerant ?<br />

The proper refrigerant charge should follow the volume as recommended by manufacturer and recommendation<br />

should be followed by the installer. Refer to the table of Refrigerant Charge Level.<br />

If the installer cannot find the correct charge but the system must be started, refrigerant should be<br />

carefully added to the system until reasonable sub-cooling is measured in the liquid line and reasonable<br />

suction super-heat is measured at the compressor suction. Suction and discharge pressures<br />

must be monitored carefully during the charging process.<br />

Charge Limits<br />

Copeland Scroll compressors have the different charge limits for different compressor models as shown<br />

in table below. If the total charge exceeds these limits, the system should have a crank case heater<br />

and/or pump downcycle and/or accumulator to prevent liquid damage to the compressor. Some<br />

systems may require accumulators to limit liquid flood back even though the charge is lower than the<br />

published limit.


Charging Recommendations<br />

Charging liquid in a CONTROLLED manner into the suction side until the system is full .This recommendation<br />

does not hold true for reciprocating compressors where liquid charging into the suction side could cause<br />

severe damage.<br />

Charging Cylinder on Scale Close-up of Scale<br />

Carefully monitor the suction and discharge pressures - ensure that the suction pressure does not fall below 25<br />

psig (1.7 bar) at any time during the charging process.<br />

CAUTION : Manifold Gauge will show cylinder pressure rather than suction pressure if the cylinder valve and<br />

Manifold valve "A" are both open.<br />

Charging Procedures - Three phase compressors<br />

There are many ways of charging liquid in a "controlled manner" into the<br />

suction side:-<br />

1. Use valve A on the manifold gauge set<br />

2. Use the valve on the refrigerant cylinder<br />

3. Charge through a Shredder valve<br />

4. Use a hose with a Shredder valve depressor<br />

5. Charge into the suction side at some distance from the compressor.<br />

6. All of the above<br />

A<br />

The fundamental procedure is the same as for single phase models but the compressor can run in the wrong<br />

direction on starting. If this happens reverse any two phases and start again. Short term reverse rotation will<br />

not damage the compressor.<br />

As compressors get larger the importance of correct field charging procedures grows exponentially. Unfortunately<br />

larger systems are often field charged which leads to many infant failures. All Specter compressors<br />

have internal discharge temperature protectors which are very effective in preventing dangerously high<br />

discharge temperatures during charging. The protection module will trip and lock the compressor out for 30<br />

minutes. It is not normally necessary to wait 30 minutes for the module to reset. When the compressor has<br />

cooled down the module can be reset by breaking the power supply to the control circuit. Very often the<br />

serviceman does not understand why the module tripped and uses a jumper wire to bypass it. He continues<br />

to charge the system and removes the jumper when charging is complete. The compressor may or may not<br />

run with the protector back in the circuit but it is certain that the compressor has been damaged and premature<br />

failure is inevitable.<br />

TM-YFS-0410-A<br />

®<br />

20


®<br />

21<br />

TM-YFS-0410-A<br />

Model : YFS 50/60/75B<br />

6. Wiring Diagrams<br />

L N<br />

E


Model : YFS 100/125/150B<br />

L<br />

N<br />

E<br />

TM-YFS-0410-A<br />

®<br />

22


®<br />

23<br />

TM-YFS-0410-A<br />

Model : YSF 50/60B - YSL 50/61D<br />

Indoor Unit


Model : YFS 75B - MYSS 72/80C<br />

Indoor Unit<br />

TM-YFS-0410-A<br />

®<br />

24


®<br />

25<br />

TM-YFS-0410-A<br />

Model : YFS 100B - MYSS 100B<br />

Indoor Unit


Model : YFS 125B - MYSS 125B, YFS 150B - MYSS 150B<br />

Indoor Unit<br />

TM-YFS-0410-A<br />

®<br />

26


®<br />

27<br />

TM-YFS-0410-A<br />

7. Servicing and Maintenance<br />

The design concept of the Condensing Unit is such that all servicing can be done from the front and<br />

side of the unit.<br />

Upon removal of front and side panel, all the electrical “terminal box”, fan and motor assembly and<br />

compressor are easily accessible.<br />

Under normal circumstances, these outdoor units only require a check and cleaning of air intake<br />

coil surfaces once quarterly. However, if a unit is installed in area subjected to much oil, mist and dust<br />

, the coil must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure<br />

sufficient heat exchange and proper operation. Otherwise, the systems life span might be shortened.<br />

CAUTION<br />

When the compressor is to be stopped for a long time, the crankcase heater should be energized<br />

for at least 6 hours before start of operation.<br />

Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the<br />

refrigeration cycle when performing a leakage test or an airtight test. These types of gases are<br />

extremely dangerous, because explosion can occur.<br />

It is recommended that nitrogen or refrigerant be charged for these types of tests.<br />

Caution For Use<br />

Bear the following points in mind to safeguard against malfunction and breakdown.<br />

Do not stick rods or other objects through the air outlet during operation since this may result to<br />

damage or injury<br />

The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped<br />

with a crankcase heater with the compressor).<br />

Make sure the air conditioner is properly grounded by checking the ground terminal.<br />

Maintenance<br />

For superb performance and lasting durability, please do not forget to conduct proper and regular<br />

maintenance.<br />

Cleaning The Outdoor Unit Heat Exchanger<br />

If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will<br />

become dirty impairing its function and reducing the performance of the air conditioned. Consult your<br />

local dealer about the cleaning of the heat exchanger.


8. Troubleshooting<br />

When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply<br />

before proceeding with the following troubleshooting procedures.<br />

The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which<br />

are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.<br />

No<br />

Fault<br />

cond<br />

itio<br />

ns<br />

1 The air conditioner unit will not resume after<br />

power failure.<br />

2 The compressor does not operate 3 minutes<br />

after the air conditioner unit is started.<br />

3 The airflow is too slow or room cannot be<br />

cooled sufficiently.<br />

Possi<br />

ble<br />

causes<br />

/ corr<br />

ectiv<br />

e actio<br />

ns<br />

• The auto restart function is not functioning. Please<br />

turn on the unit with the wireless / wired controller.<br />

• Protection against frequent starting.<br />

• Wait for 3 or 4 minutes for the compressor to start<br />

operating by it self.<br />

• The air filter is dirty.<br />

• The doors and windows are opened.<br />

• The air suction and discharge of both indoor and<br />

outdoor units are clogged or blocked.<br />

• The regulated temperature or temperature setting<br />

is not low enough.<br />

4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,<br />

which might have adhered onto the coil, may<br />

cause odor.<br />

• Contact your nearest dealer.<br />

5 Condensation on the front air grille of the indoor<br />

unit.<br />

• This is caused by air humidity after an extended<br />

period of operation.<br />

• The set temperature is too low. Increase the<br />

temperature setting and operate the unit at high<br />

fan speed.<br />

6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest<br />

dealer. This might be due to tilted installation.<br />

7 Hissing airflow sound from the air conditioner<br />

unit during operation.<br />

• Liquid refrigerant flowing into the evaporator coil.<br />

8 The wireless controller display is dim. • The batteries are discharged.<br />

• The batteries are not correctly inserted.<br />

• The assembly is not good.<br />

9 Compressor operates continuously. • Dirty air filter. Clean the air filter.<br />

• Temperature setting too low (cooling). Use higher<br />

temperature setting.<br />

10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower<br />

temperature setting.<br />

TM-YFS-0410-A<br />

®<br />

28


®<br />

29<br />

TM-YFS-0410-A<br />

Diagnostic Guidelines<br />

By means of pressure reading :<br />

Circuit<br />

High side<br />

Low side<br />

High side<br />

Low side<br />

Data<br />

Too low<br />

High side<br />

Low side ●<br />

●<br />

A little low<br />

Pressure<br />

Normal<br />

A little high<br />

High side<br />

Low side ●<br />

High side<br />

Low side<br />

●<br />

●<br />

Too high<br />

●<br />

●<br />

●<br />

Probable cause<br />

1. Overcharged with refrigerant.<br />

2. Non-condensable gases in refrigerant circuit (e.g. air)<br />

3. Obstructed air-intake / discharge.<br />

4. Hot air short circuiting in outdoor unit.<br />

1. Poor compression / no compression (compressor<br />

defective)<br />

2. Reversing valve leaking.<br />

1. Undercharged with refrigerant.<br />

2. Refrigerant leakage.<br />

3. Air filter clogged / dirty (indoor unit).<br />

4. Indoor fan locked / seized.<br />

● 1. Outdoor fan blocked (cooling).<br />

2. Outdoor coil dirty (cooling).<br />

3. Non-condensable gases in refrigerant circuit (e.g. air)<br />

●<br />

1. Air intake temperature of indoor unit too high.


By means of diagnostic flow chart:<br />

Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting<br />

failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes<br />

“Insufficient cooling ”.<br />

i) Diagnosis of Electric Circuit<br />

TM-YFS-0410-A<br />

®<br />

30


®<br />

31<br />

TM-YFS-0410-A<br />

ii ) Diagnosis of Refrigerant Circuit / Application<br />

There might be some causes where the unit starts running but does not perform satisfactorily, i.e.<br />

insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s<br />

intake and discharge air as well as running current.


Indoor Unit<br />

Model : YFS 50/60/75B<br />

MODELS<br />

50B<br />

60B<br />

75B<br />

9. Dimensional Data<br />

A B C<br />

DIMENSION<br />

D E Liquid Suction<br />

203 304 203 266 209 3/8” 7/8”<br />

203 304 203 266 209 1/2” 7/8”<br />

186 338 186 292 220 1/1” 1-1/8”<br />

Model : YFS 100/125/150B<br />

MODELS<br />

100B<br />

125B<br />

150B<br />

A B C<br />

DIMENSION<br />

D Liquid Suction<br />

304 260 266 209 5/8” 1-1/8”<br />

304 260 266 209 3/4” 1-1/8”<br />

338 192 292 220 5/8” 1-3/8”<br />

TM-YFS-0410-A<br />

®<br />

32


®<br />

33<br />

TM-YFS-0410-A<br />

Outdoor Unit<br />

Model : YSL 50D<br />

Model : YSL 61D<br />

All Dimensions are in mm<br />

All Dimensions are in mm


Model : MYSS 72/80C<br />

Model : MYSS 100/125B (Standard Vertical Air Discharge)<br />

Dimension in mm<br />

Dimension in mm<br />

TM-YFS-0410-A<br />

®<br />

34


®<br />

35<br />

TM-YFS-0410-A<br />

Model : MYSS 100/125B<br />

Dimension in mm<br />

Model : MYSS 150C (Standard Vertical Discharge / Non-convertible)<br />

Dimension in mm


Indoor Unit<br />

Model : YFS 50/60B<br />

10. Exploded View & Part List<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 PAINT PANEL BASE YFS 50-75 13 BAFFLE COIL L/R YFS 50-100<br />

2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 50-75<br />

3 INSUL. PANEL DISCH YFS 50-60 15 FILTER FRAME BTM YFS 50-75<br />

4 INSUL. PANEL TOP YFS 50-75 16 INSUL. DRAIN PAN YFS 50-75<br />

5 INSUL. PANEL VERT L/R FRONT L/R 50/75 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />

6 INSUL. PANEL VERT L/R BACK YFS 50-75 18 ASSY COIL AL, 187PC,3R,12FPI YFS 50-60<br />

7 INSUL. PANEL BACK YFS 50-75 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />

8 INSUL. PANEL SIDE YFS 50-150 20 FILTER, 550 x 900 x 22, 70-75% APR YFS 50-75<br />

9 INSUL. PANEL HEADER YFS 50/60/100/125 21 FAN VANE<br />

10 INSUL. PANEL FRONT TOP YFS 50-75 22 CONTROL BOX<br />

11 PAINT GRILLE YFS 50-75 23 CONTROL BOX COVER<br />

12 PAINT FLANGE DISCH YFS 5/60/100/125 24 CONTROLLER, C3D-SLM EC(10m) YORK 1M<br />

TM-YFS-0410-A<br />

®<br />

36


®<br />

37<br />

TM-YFS-0410-A<br />

Model : YFS 100B<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 50-100<br />

2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 100<br />

3 INSUL. PANEL DISCH YFS 100-125 15 FILTER FRAME BTM YFS 100-150<br />

4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 100-150<br />

5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />

6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 12 TPC,3R,12FPI YFS 100<br />

7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />

7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />

8 INSUL. PANEL SIDE YFS 50-150<br />

9 INSUL. PANEL HEADER YFS 50/60/100/125<br />

10 INSUL. PANEL FRONT TOP YFS 100-150<br />

11 PAINT GRILLE YFS 100-150<br />

12 PAINT FLANGE DISCH YFS 5/60/100/125<br />

21 FAN VANE<br />

22 CONTROL BOX<br />

23 CONTROL BOX COVER<br />

24 CONTROLLER, C3D-SLM EC(10m) YORK 1M


Model : YFS 125B<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 125-150<br />

2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 125-150<br />

3 INSUL. PANEL DISCH YFS 100-125 15 FILTER FRAME BTM YFS 100-150<br />

4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 100-150<br />

5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />

6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 8 TPC,3R,12FPI YFS 125<br />

7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />

7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />

8 INSUL. PANEL SIDE YFS 50-150<br />

9 INSUL. PANEL HEADER YFS 50/60/100/125<br />

10 INSUL. PANEL FRONT TOP YFS 100-150<br />

11 PAINT GRILLE YFS 100-150<br />

12 PAINT FLANGE DISCH YFS 5/60/100/125<br />

21 FAN VANE<br />

22 CONTROL BOX<br />

23 CONTROL BOX COVER<br />

24 CONTROLLER, C3D-SLM EC(10m) YORK 1M<br />

TM-YFS-0410-A<br />

®<br />

38


®<br />

39<br />

TM-YFS-0410-A<br />

Model : YFS 150B<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 PAINT PANEL BASE YFS 100-150 13 BAFFLE COIL L/R YFS 125-150<br />

2 PAINT BASE FIXTURE L/R YFS 50-150 14 FILTER RAIL TOP YFS 125-150<br />

3 INSUL. PANEL DISCH YFS 150 15 FILTER FRAME BTM YFS 125-150<br />

4 INSUL. PANEL TOP YFS 100-150 16 INSUL. DRAIN PAN YFS 125-150<br />

5 INSUL. PANEL VERT L/R FRONT L/R 100/150 17 CHANNEL WELD PANEL GRILL YFS 50-150<br />

6 INSUL. PANEL VERT L/R BACK YFS 100-150 18 ASSY COIL AL, 10TPC,4R,12FPI YFS 150<br />

7a INSUL. PANEL BACK TOP YFS 100-150 19 BLOWER, DD241-241-200C C/W 10UF (AP/9x9)<br />

7b INSUL. PANEL BACK BTM YFS 100-150 20 FILTER, 478 x 900 x 22, 70-75% APR<br />

8 INSUL. PANEL SIDE YFS 50-150<br />

9 INSUL. PANEL HEADER YFS 150<br />

10 INSUL. PANEL FRONT TOP YFS 100-150<br />

11 PAINT GRILLE YFS 100-150<br />

12 PAINT FLANGE DISCH YFS 75-150<br />

21 FAN VANE YFS 50-150<br />

22 CONTROL BOX YFS 50-150<br />

23 CONTROL BOX COVER 50-150<br />

24 CONTROLLER, C3D-SLM EC(10m) YORK 1M


Outdoor Unit<br />

Model : MYSS 72/80C<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 ASSY, BASE PAN 19 CAP FOR FAN BLADE<br />

2 ASSY, COIL 20 GUARD, FAN<br />

3 STRUCTURE FRONT LEFT 21 PANEL, TOP<br />

4 ASSY, PARTITION 22 PANEL, SERVICE<br />

5 ASSY, COMPRESSOR 23 SCREW, TRUSSD HEAD PHILIP<br />

6 PLATE, VALVE 24 SCREW, TRUSSD HEAD PHILIP<br />

7 ASSY, ACCESS VALVE 1/4" 25 SCREW, TRUSSD HEAD PHILIP<br />

8 CLAMP, LIQUID TUBE 3/4" 26 SCREW, SELF TAPPING<br />

9 CLAMP, SUCTION TUBE 1" 35 SCREW, WOOD<br />

10 ASSY, TUBING 37 WASHER<br />

11 STRUCTURE, FRONT RIGHT 38 WASHER, SPRING<br />

12 STRUCTURE, BACK RIGHT 39 NUT HEXAGON<br />

13 ASSY, TERMINAL BOARD MAIN 40 WASHER, ISOLATOR<br />

14 PLATE, ORIFICE SUPPORT 41 WASHER<br />

15 PLATE, ORIFICE 42 WASHER, SPRING<br />

16 BRACKET FAN MOTOR 43 NUT, HEXAGON<br />

17 MOTOR 44 ISOLATOR, DURO 40<br />

18 BLADE, FAN 45 ISOLATOR SLEEVE<br />

TM-YFS-0410-A<br />

®<br />

40


®<br />

41<br />

TM-YFS-0410-A<br />

Model : MYSS 100/125B<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 ASSY, BASE PAN 17 MOTOR<br />

2 COMPRESSOR 18 PROPELLER FAN<br />

MYSS100B 19 FAN GUARD<br />

MYSS125B 20 COVER, TER. BOARD FRONT<br />

3 ASSY, STRUC. BACK L 21 HOISTING BRACKET<br />

4 ASSY, STRUC. BACK R 22 STRUC. TUBE SUPT.<br />

5 SUPT, ORIFICE PLATE MYSS100B<br />

6 ASSY, COIL L MYSS125B<br />

MYSS100B 23 SUPT, TUBE GAS<br />

MYSS125B MYSS100B<br />

7 ASSY, COIL R MYSS125B<br />

MYSS100B 24 CLAMP, TUBE GAS<br />

MYSS125B MYSS100B<br />

8 STRUC, FRONT L MYSS125B<br />

9 STRUC, FRONT R 25 SUPT, TUBE LIQUID<br />

10 STRUC, TOP L 26 CLAMP, TUBE LIQUID<br />

11 STRUC, TOP R 27 ASSY, ACCESS VALVE<br />

12 T/B PANEL PARTS NOT IN DIAGRAM<br />

13 COVER, TER. BOARD BACK PRESS SWITCH, 18PSI<br />

14 PANEL, TOP FRONT PRESS SWITCH, 426PSI<br />

15 ORIFICE PLATE MAGNECTIC CONTACTOR<br />

16 BRACKET, FAN MOTOR PHASE PROTECTOR PP1.03


Model : MYSS 150C<br />

NO. DESCRIPTION NO. DESCRIPTION<br />

1 ASSY, BASE PAN 14 TER. BOX COVER<br />

2 COMPRESSOR 15 PANEL, ORIFICE<br />

3 STRUC, PIPE SUPT. 16 FAN MOTOR BRACKET<br />

4 ASSY, ACCESS VALVE 17 MOTOR<br />

5 SUPT, TUBE LIQUID 18 FAN PROPELLER<br />

6 SUPT, GAS TUBE 19 FAN GUARD<br />

7 ASSY, COIL L 20 PANEL, SERVICE T<br />

8 ASSY, COIL R 21 PANEL, SERVICE B<br />

9 STRUC, COIL 22 ASSY, S. HOISTING BRACKET<br />

10 ASSY, STRUC. BACK L PARTS NOT IN DIAGRAM<br />

11 ASSY, STRUC. BACK R PRESS SWITCH, 18PSI<br />

12 CLAMP, TUBE LIQUID PRESSURE SWITCH, 426PSI<br />

13 CLAMP, GAS TUBE PHASE PROTECTOR, PP1.03<br />

TM-YFS-0410-A<br />