5. Circulate the system for at least<br />

24 hours to ensure complete<br />

mixing. Check the liquid concentration<br />

with a refractometer or<br />

other method to assure that the<br />

correct mixture is obtained.<br />

Note: If fluid mixing is a concern,<br />

the solution can be premixed in a<br />

separate tank before introduction<br />

into the system, or the inhibited<br />

glycol <strong>and</strong> the water can be added<br />

together through a “mixing tee."<br />

This will promote faster mixing of<br />

the inhibited glycol <strong>and</strong> water.<br />

6<br />

MAINTAINING <strong>DOWTHERM</strong> AND <strong>DOWFROST</strong> FLUIDS<br />

Free analytical service<br />

To help ensure that corrosion <strong>and</strong><br />

freeze protection are maintained<br />

in customer systems, Dow offers a<br />

free fluid analysis service. It is<br />

designed to assure the long term<br />

performance of <strong>DOWTHERM</strong><br />

<strong>and</strong> <strong>DOWFROST</strong> fluids <strong>and</strong> help<br />

minimize replacement fluid<br />

requirements as well as system<br />

maintenance <strong>and</strong> repair costs.<br />

Typically performed on an annual<br />

basis, the analysis includes determination<br />

of current inhibitor <strong>and</strong><br />

glycol levels plus Dow’s recommendations<br />

for maintaining<br />

proper corrosion protection.<br />

Dow has developed special Thermal<br />

<strong>Fluids</strong> Sampling Kits for use<br />

by customers participating in the<br />

analysis program. These kits<br />

permit easy <strong>and</strong> accurate labeling<br />

of fluid samples <strong>and</strong> safe shipment<br />

of samples to Dow for analysis.<br />

Kits may be obtained by calling 1-<br />

800-447-4369. Or write:<br />

Thermal <strong>Fluids</strong> Testing Lab<br />

The Dow Chemical Company<br />

Larkin Lab<br />

1691 North Swede Road<br />

Midl<strong>and</strong>, Michigan 48674<br />

How the service works<br />

After the system has been filled<br />

<strong>and</strong> circulated for several days, an<br />

initial four-ounce sample should<br />

be withdrawn <strong>and</strong> sent to Dow<br />

using one of the Thermal <strong>Fluids</strong><br />

Sampling Kits. After the system is<br />

in operation, it is recommended<br />

that samples be taken once a year.<br />

Before withdrawing the sample,<br />

the fluid should be well circulated<br />

in the system so the sample is<br />

representative. Remember to<br />

closely follow the sampling<br />

instructions included with the<br />

sample kit provided by Dow.<br />

Proper sampling is essential to<br />

ensure meaningful assessment of<br />

fluid condition.<br />

Approximately three weeks after<br />

the sample is received by Dow, a<br />

report will be sent to you detailing<br />

results of the analysis, discussing<br />

unusual or troublesome conditions<br />

(if any), <strong>and</strong> offering recommendations.<br />

Analytical tools for selftesting<br />

It may also be desirable to perform<br />

some simple, on-site analysis of<br />

your system to properly maintain<br />

the glycol concentration. A useful<br />

tool for this type of analysis is a<br />

Misco Products refractometer,<br />

model 7084VP (°F) <strong>and</strong> 7064VP<br />

(°C). These refractometers<br />

measure the glycol solution<br />

concentration of <strong>DOWTHERM</strong><br />

<strong>and</strong> <strong>DOWFROST</strong> fluids <strong>and</strong> give<br />

the freezing points of the fluids.<br />

The freezing point can be translated<br />

to glycol concentration from<br />

the tables on pages 7 <strong>and</strong> 10. This<br />

instrument requires only a few<br />

drops of fluid for testing <strong>and</strong><br />

requires no adjustment for fluid<br />

temperature. Diluted solutions<br />

with concentrations from 0 to<br />

60% glycol may be tested directly.<br />

Stronger concentrations require a<br />

simple dilution procedure prior to<br />

testing. Contact Misco Products at<br />

1-800-358-1100 <strong>and</strong> ask for the<br />

Dow discount.