<strong>Flanged</strong> <strong>joints</strong><br />

acc. to DIN EN 1092-2<br />

Bolt hole configuration<br />

4 holes 8 holes 12 holes 16 holes<br />

DN<br />

Number of bolts acc. to DIN EN 1092-2<br />

PN 10 PN 16 PN 25 PN 40<br />

40 4 4 4 4<br />

50 4 4 4 4<br />

65 4 4 8 8<br />

80 8 8 8 8<br />

100 8 8 8 8<br />

125 8 8 8 8<br />

150 8 8 8 8<br />

200 8 12 12 12<br />

250 12 12 12 12<br />

300 12 12 16 16<br />

(350) 16 16 16 16<br />

400 16 16 16 16<br />

500 20 20 20 20<br />

600 20 20 20 20<br />

700 24 24 24 –<br />

800 24 24 24 –<br />

900 28 28 28 –<br />

1000 28 28 28 –<br />

In principle, no bolt holes are allowed to come in the flange axis running perpendicular to the pipeline level.<br />