<strong>MCCB</strong><br />

DISCRIMINATION DATA<br />

STANDARD <strong>MCCB</strong> UPSTREAM DEVICE INSTANTANEOUS TRIP SET AT HIGH<br />

SKB 0<br />

SKB 3/4<br />

SKB 1/2<br />

kA@<br />

Product Rating<br />

1250 1600<br />

1000<br />

800<br />

600<br />

800<br />

630<br />

500<br />

400<br />

315<br />

(A) 415V 25 23 40 50 63 80 100 125 160 ALL 250<br />

8000 7400 8300 9200 9200 9200<br />

6300<br />

3000 4000 5000<br />

SKB 1/2 63 25 800 800 800 1600 1600 2500<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

3000 4000 5000<br />

2500<br />

80 25 1600 1600<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

5000<br />

4000<br />

3000<br />

2500<br />

100 25 1600 1600<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

3000 4000 5000<br />

125 25 1600 1600 2500<br />

SKB 3/4<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

3000 4000 5000<br />

2500<br />

160 25<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

5000<br />

3000 4000<br />

2500<br />

200 25<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

4000 5000<br />

315 50<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

5000<br />

400 50<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

6300<br />

500 50<br />

9200<br />

9200<br />

9200<br />

8300<br />

8000 7400<br />

630 50<br />

9200<br />

9200<br />

9200<br />

8300<br />

7400<br />

800 50<br />

9200<br />

9200<br />

9200<br />

SKB 0 1000 50<br />

9200 9200<br />

1250 50<br />

9200<br />

1600 50<br />

The above table gives fault current in amperes till which level the downstream breakers shall act prior to the upstream breaker<br />

Selection & Application<br />

TRANSFORMER PROTECTION<br />

Primary side<br />

For the protection of transformer with a circuit breaker connected<br />

to the primary side (LT primary) the no load inrush current of the<br />

transformer must be considered. The peak value of the first<br />

current wave often reaches 10-15 times the rated current and<br />

may sometimes reach as high as 20-25 times. However, the<br />

transient decays very quickly (in a few m.sec.). Thus the <strong>MCCB</strong><br />

selected should have a magnetic setting which will not be<br />

actuated by the momentary inrush current.<br />

Secondary side<br />

STANDARD <strong>MCCB</strong>s can be used for protection of transformer on<br />

the LT side (secondary side) as an outgoing protective device.<br />

Selection table For Transformer Protection<br />

<strong>MCCB</strong> Rating in Amperes<br />

Transformer SKB-5 SKB-6 SKB-7 SKB-1 SKB-2 SKB-2 SKB-3 SKB-4<br />

Rating (KVA) 10kA 16kA 25kA 25kA 25kA 35kA 35kA 50kA<br />

16 25 25 25 25 25 25<br />

25 40 40 40 40 40 40<br />

63 100 100 100 100 100 100<br />

100 160 160 160 160 160<br />

160 250 250 250 250 250<br />

200 315 315<br />

250 400 400<br />

315 500 500<br />

400 630 630<br />

500<br />

630<br />

750<br />

800 800<br />

GENERATOR Set Protection<br />

STANDARD <strong>MCCB</strong>s can be used for the effective protection and<br />

control of Diesel Generating set against overload and short circuits.<br />

The Current rating of <strong>MCCB</strong> to be selected is calculated as follows :<br />

kVA = 3 U e X Ie<br />

I e = kVA<br />

3x<br />

U e<br />

or<br />

Where,<br />

kVA = Rating of the DG Set<br />

U e = Rated Voltage<br />

I e = Rated Current<br />

The <strong>MCCB</strong> rating selected is greater than or equal to the rated<br />

current value<br />

The rated current of the transformer is calculated as follows :<br />

kVA x 1000<br />

I = Amps<br />

e<br />

3 x U e<br />

‘U e’<br />

is the Rated Voltage at the LT side<br />

The Breaking capacity of the breaker for protection can be<br />

calculated as :<br />

I e<br />

I = x 10 b<br />

Z%<br />

-3 Kiloamperes<br />

Where ‘I b’<br />

is the rated breaking capacity,<br />

‘I e ’ the rated current<br />

‘Z%’ is the percentage impedance of transformer<br />

(specified by the manufacturer)<br />

Selection Table for DG Set Protection<br />

SKB-0<br />

50kA<br />

1000<br />

1200<br />

DG Set Rating (KVA) <strong>MCCB</strong> Rating (Amperes)<br />

16<br />

25<br />

25<br />

40<br />

63<br />

100<br />

10<br />

160<br />

16<br />

250<br />

20<br />

315<br />

25<br />

400<br />

31<br />

500<br />

40<br />

630<br />

63<br />

1000<br />

750<br />

1200