Vertical Tanks, Pump Kits, Bulkheads<br />

PUMPING SYSTEMS<br />

The following kits are primarily designed to be used with a small<br />

capacity pump like Blackmer’s LGF1C (10 GPM) or LGF1PC (15<br />

GPM)<br />

For a pumping system to perform properly, you must have high<br />

quality equipment installed in accordance with the manufacturer’s<br />

recommendations and the following good installation practices:<br />

1. The tank should be installed with as much vertical distance from<br />

the bottom tank outlet to the pump inlet as practical. The<br />

minimum recommended distance from the bottom of the tank<br />

to the ground is 16” for good pump performance.<br />

2. Only bottom tank outlets should be used to supply gas to liquid<br />

pumps, and the size of these outlets should be no less than the<br />

inlet of the pump. There should be no restrictive fittings on the<br />

inlet side of the pump.<br />

3. The pump should be located as close to the tank outlet as<br />

practical. A LP gas pump can push gas for reasonable<br />

distances, but cannot suck gas. Liquid gas must be fed to the<br />

pump by gravity.<br />

4. All positive displacement pumps require a bypass line to return<br />

gas back to the tank. The Blackmer LGF1E and LGF1PE pumps<br />

have built in bypass valves. A line must be run between the<br />

pump and the tank to protect the pump against excessive<br />

differential pressure.<br />

CONYERS, GA (800) 241-5652<br />

APOPKA, FL (800) 432-1869<br />

GOLDSBORO, NC (800) 426-9293<br />

MANCHESTER TANK’S<br />

VERTICAL DISPENSER TANK<br />

• Very visible and great for advertising<br />

• Space saver design requires only 10’<br />

diameter area.<br />

• Portable base allows for easy<br />

relocation<br />

NOTE: Vertical dispenser tanks do not<br />

come painted from the factory.<br />

They are however primed, ready<br />

to paint.<br />

Gallons<br />

Item # W.C. LP Cap. Dia. Hgt. Wgt.<br />

M29014 660 528 3’6” 9’11 1/2” 2025#<br />

M22014 1150 920 4’0” 13’3” 2878#<br />

M29011 1250 1000 4’0” 14’2” 3500#<br />

M29016 1600 1280 4’0” 18’2” 4019#<br />

M23354 2000 1600 4’6” 18’7 1/2” 4540#<br />

M29005* 10’ “X” shape steel base 413#<br />

M22774* Crash posts and protective railing 305#<br />

*Not available on 2000 gallon tank<br />

- 67 -<br />

PUMPING SYSTEMS (CONTINUED)<br />

PUMPING SYSTEMS<br />

5. Proper electrical wiring connections and correct wire size are<br />

important for good pump performance. Be sure the motor<br />

terminals are connected correctly for the voltage and rotation<br />

being used. Listed below are general recommendations for<br />

the minimal wire size for more common wiring runs on 1 HP<br />

and 1 1/2 HP single phase motors. Please comply with the<br />

motor manufacturer’s requirements concerning this matter.<br />

Length of Run Voltage Wire Size<br />

Motor Size: 1 HP Single Phase<br />

100’ 115 #8<br />

100’ 230 #10<br />

200’ 115 #6<br />

200’ 230 #8<br />

Motor Size: 1 1/2 HP Single Phase<br />

100’ 115 #4<br />

100’ 230 #10<br />

200’ 115 #0<br />

200’ 230 #8<br />

LF1-A<br />

ECONOMY PUMP KIT<br />

This kit includes a manually operated liquid withdrawal valve<br />

with a 1” outlet. All fittings to the pump are 1”.<br />

LF1-B<br />

DELUXE PUMP KIT<br />

Deluxe kit includes Fisher’s 1 1/4” internal valve. All piping<br />

components are 1 1/4”.<br />

See appendix for material lists & schematics of these kits.<br />

BULKHEADS<br />

BULK PLANT BULKHEADS<br />

ITEM# COUPLINGS<br />

STH16X10 2” and 1 1/4”<br />

STH16X16 Two 2”<br />

STH16X16X10 Two 2”, One 1 1/4”<br />

STH24X16 3” and 2”<br />

STH24X16X10 3”, 2”, and 1 1/4”<br />

STH24X16X16 3” and Two 2”<br />