GREE COMMERCIAL AIR CONDITION <strong>HEAT</strong> <strong>RECOVERY</strong> D.C <strong>INVERTER</strong> <strong>MULTI</strong> <strong>VRF</strong><br />

F max ——the maximal frequency of the inverter compressor;<br />

F min ——the minimal frequency of the inverter compressor;<br />

q i ——the rated capacity of indoor unit;<br />

q iON ——the rated capacity of indoor unit which is running;<br />

q iOFF ——the rated capacity of indoor unit which is stopping;<br />

A i ——the correction of the outdoor and indoor temperature.<br />

B i ——the correction of the stopping indoor unit.<br />

2) Compressor Start Control<br />

Except the system receiving the stop signal,if the system start,it must run for 6min at least.Once the<br />

compressor stops,it starts after 3min later at least.<br />

The starting scheduling of cooling or dry code of indoor unit:<br />

During the starting, the inverter compressor must run at 45Hz for 40s, 55Hz for 80s, 70Hz for 80s,<br />

and 80Hz for 40s. In this course, if the high pressure lowers frequency, lowering frequency by discharge<br />

will quit initialization and they will run in their own ways respectively.<br />

42