(50Hz/R410A/Heat Pump)<br />

5CSL0-06B(Re<strong>pl</strong>aces: 5CSL0-06A)


Introduction<br />

Part 1 General information<br />

1. Model line up.....................................................................................10<br />

1.1 Indoor units ............................................................................................................10<br />

1.2 Outdoor units..........................................................................................................11<br />

2. Nomenclature....................................................................................14<br />

2.1 Indoor units(Global) ...............................................................................................14<br />

2.2 Outdoor units(Global).............................................................................................14<br />

2.3 Indoor units(Europe) ..............................................................................................15<br />

2.4 Outdoor units(Europe) ...........................................................................................15<br />

2.5 Decoration panel....................................................................................................15<br />

3. List <strong>of</strong> functions................................................................................16<br />

4. Features.............................................................................................17<br />

4.1 What's system.........................................................................................17<br />

4.2 Technologies ..........................................................................................................18<br />

4.3 Indoor units ............................................................................................................20<br />

4.4 Outdoor units .........................................................................................................33<br />

5. Control system..................................................................................36<br />

5.1 Individual control system(Accessory).....................................................................36<br />

5.2 Central control system(Accessory) ........................................................................52<br />

5.3 Control device(Accessory) .....................................................................................53<br />

6. Combination......................................................................................54<br />

6.1 Selection procedure ...............................................................................................54<br />

6.2 Combination <strong>of</strong> indoor unit and outdoor unit ..........................................................54<br />

6.3 Synchro operation Guide .......................................................................................57<br />

2 General information


Part 2 Product data<br />

1. Indoor units.......................................................................................60<br />

1.1 Ceiling cassette 4-way ...................................................................................60<br />

1.2 Ceiling & floor.................................................................................................82<br />

1.3 Ceiling suspended..........................................................................................94<br />

1.4 Ceiling concealed duct - High static pressure ..............................................105<br />

1.5 Console(Floor stand)....................................................................................125<br />

2. Outdoor unit....................................................................................133<br />

2.1 DC Inverter SingleA (1, 3 phase) ................................................................133<br />

2.2 DC Inverter Single A-Synchro (1, 3 phase)..................................................216<br />

2.3 Non inverter Single A (1, 3 phase) ...............................................................245<br />

General information 3


Part 3 Design and installation<br />

1. General installation guideline........................................................288<br />

1.1 Installation process & Guideline ...................................................................288<br />

1.2 Checking the drawing ...................................................................................289<br />

2. Guideline for each installation process........................................290<br />

2.1 Sleeve and inserting work.............................................................................290<br />

2.2 Refrigerant piping work .................................................................................292<br />

2.3 Drain piping work .........................................................................................298<br />

2.4 Insulation work ..............................................................................................304<br />

2.5 Electrical work...............................................................................................307<br />

2.6 Air tight test ...................................................................................................310<br />

2.7 Vacuum drying works....................................................................................312<br />

2.8 Additional charge <strong>of</strong> refrigerant.....................................................................316<br />

2.9 Trail test run operation ..................................................................................317<br />

3. Installation <strong>of</strong> indoor unit ..............................................................318<br />

3.1 Safety precautions ........................................................................................318<br />

3.2 Ceiling cassette 4-way ..................................................................................322<br />

3.3 Ceiling and floor, Ceiling suspended only .....................................................330<br />

3.4 Ceiling concealed duct - High static pressure...............................................341<br />

3.5 Console (Floor stand) ...................................................................................347<br />

4. Installation <strong>of</strong> outdoor Unit ...........................................................355<br />

4.1 Safety precautions ........................................................................................355<br />

4.2 Introduction ...................................................................................................359<br />

4.3 Foundation ....................................................................................................360<br />

4.4 Settlement <strong>of</strong> the outdoor unit.......................................................................362<br />

4.5 Selection <strong>of</strong> the best location ........................................................................362<br />

4.6 Clearance space ...........................................................................................364<br />

4.7 Outdoor unit piping........................................................................................367<br />

4.8 Outdoor unit installation requirments ............................................................368<br />

4.9 Outdoor unit cabin.........................................................................................372<br />

4 General information


Part 4 Accessories<br />

List <strong>of</strong> ap<strong>pl</strong>icable models<br />

1. Controller accessories...................................................................377<br />

1.1 Wireless remote controller ...................................................................................377<br />

1.2 Sim<strong>pl</strong>e remote controller ......................................................................................382<br />

1.3 Deluxe remote controller......................................................................................384<br />

1.4 Hotel use remote controller..................................................................................386<br />

1.5 Zone controller .....................................................................................................388<br />

1.6 Dry contact module ..............................................................................................391<br />

2. Mechanical accessories .......................................................................393<br />

2.1 Branch kit .............................................................................................................393<br />

2.2 Drain pump ..........................................................................................................395<br />

2.3 Air guide...............................................................................................................400<br />

2.4 Cassette cover .....................................................................................................401<br />

General information 5


Introduction 5CSL0-06B<br />

Introduction<br />

Preface<br />

New era brings the more sophisticated and advanced buildings which in turn demands for specialized and optimized direct<br />

expansion air conditioning systems. Also energy efficiency, environment friendly, low noise and low maintenance cost are<br />

the features which are essential for these systems.<br />

As a part <strong>of</strong> vertical integration LG makes all the key components in house, which gives an edge to LG to make better and<br />

latest technology products with best quality in optimized time.<br />

systems with are equipped with DC inverter technology and R410A refrigerant which is perfect solution to various<br />

installation locations.<br />

LG system consists <strong>of</strong> a single common outdoor unit for single indoor unit, such as ceiling cassette, ceiling and<br />

floor, ceiling suspended, ceiling concealed duct(H) and Console(Floor stand). Synchro operation is solution to customer<br />

with reasonable prices.<br />

It uses 2,3 or 4 indoor units with one outdoor unit.<br />

Each indoor units are running as one cycle with same mode(cooling or heating).<br />

It helps same air distribution all arround the middle or larger room(<strong>of</strong>fice or open <strong>pl</strong>aces) even in irregualr shaped spaces.<br />

The total capacity based on ODU for Synchro operation are the same as for the fixed combinations.<br />

This Engineering product data book incorporates information about the product itself, its installation and designing for<br />

system.<br />

The comprehensive study <strong>of</strong> this book will improve your knowledge about the system and its ap<strong>pl</strong>ication in details.<br />

LG Electronics Inc.<br />

Air Conditioning Company<br />

6 General information


5CSL0-06B<br />

Publication history<br />

Introduction<br />

Pub. No. Category Type Refrigerant Outdoor units Notes Published in<br />

5CSI0-03A<br />

5CSS0-04D<br />

5CSL0-01A<br />

5CSL0-02A<br />

Inverter Single<br />

Variable Single<br />

All models Added Europe model names Jul.2005<br />

All models<br />

Deletion :<br />

AUUW486C[UU48W UYC]<br />

AUUW606C[UU60W UYC]<br />

Change :<br />

AUUW4860[UU48W UYB]<br />

AUUW6060[UU60W UYB]<br />

New edition <strong>of</strong> EPDB<br />

- Engineering data addition<br />

- Design and installation<br />

guideline addition<br />

-Delete the models<br />

-Change the model names<br />

Feb.2006<br />

Oct.2007<br />

5CSL0-03A<br />

CAC<br />

Inverter Single<br />

Non-inverter<br />

R410A<br />

AUUW126C[UU12W UEC]<br />

AUUW186C[UU18W UEC]<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]<br />

AUUW366D[UU36W UED]<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW368D[UU37W UED]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

AUUH126C[UU12 ULC]<br />

AUUH186C[UU18 UEC]<br />

AUUH246D[UU24 UED]<br />

AUUH306D[UU30 UED]<br />

AUUH368D[UU37 UED]<br />

AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

- Added outdoor unit models.<br />

- Added indoor unit models :<br />

ATNH126ELFC[UT12 NEC]<br />

ATNH186ELFC[UT18 NEC]<br />

ATNH24GPLED[UT24NPD]<br />

ATNH30GPLED[UT30NPD]<br />

ATNH36GNLED[UT36NND]<br />

ATNH42GMLED[UT42NMD]<br />

ATNH48GMLED[UT48NMD]<br />

ATNH60GMLED[UT60 NMD]<br />

ABNH186HLAC[UB18 NHC]<br />

ABNH246HLAD[UB24 NHD]<br />

ABNH306GLAD[UB30 NGD]<br />

ABNH366GLAD[UB36 NGD]<br />

ABNH426RLAD[UB42 NRD]<br />

ABNH486RLAD[UB48 NRD]<br />

ABNH606RLAD[UB60 NRD]<br />

AVNH126ELAC[UV12 NEC]<br />

AVNH186BLAC[UV18 NBC]<br />

AVNH246BLAD[UV24 NBD]<br />

AVNH306BLAD[UV30 NBD]<br />

AVNH366KLAD[UV36 NKD]<br />

AVNH426LLAD[UV42 NLD]<br />

AVNH486LLAD[UV48 NLD]<br />

AVNH606LLAD[UV60 NLD]<br />

Jan.2008<br />

5CSL0-04A<br />

5CSL0-05A<br />

5CSL0-05B<br />

5CSL0-06A<br />

5CSL0-06B<br />

Inverter Single<br />

Inverter Single<br />

Non-inverter<br />

High efficiency<br />

Inverter<br />

Inverter Single A<br />

High Efficiency<br />

Single A<br />

Inverter Synchro<br />

Single A<br />

Inverter Single<br />

Non-inverter<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

AUUW096D[UU09W ULD]<br />

AUUW126D[UU12W ULD]<br />

AUUW186D[UU18W UED]<br />

AUUH126D[UU12 ULD]<br />

AUUH186D[UU18 UED]<br />

AUUW186DH[UU18WH UED]<br />

AUUW216DH[UU21WH U4D]<br />

AUUW246DH[UU24WH U4D]<br />

All Models<br />

-Added outdoor unit models.<br />

- Added outdoor unit models.<br />

- Added indoor unit models<br />

ATNH09GRLED[UT09 NRD]<br />

ATNH12GRLED[UT12 NRD]<br />

ATNH18GQLED[UT18 NQD]<br />

ABNH186HLAD[UB18 NHD]<br />

AVNH09GELAD[UV09 NED]<br />

AVNH12GELAD[UV12 NED]<br />

AVNH186BLAD[UV18 NBD]<br />

AQNH09GALA0[CQ09 NA0]<br />

AQNH12GALA0[CQ12 NA0]<br />

AQNH18GALA0[CQ18 NA0]<br />

ATNH18GPLED[UT18 NPD]<br />

ATNH21GNLED[UT21 NND]<br />

ATNH24GNLED[UT24 NND]<br />

- Delete the wrong notes about Synchro<br />

Combination<br />

- Add information about the Branch Kit<br />

- Correct the Capacity Table<br />

AUUW186D1[UU18W UED1] -Added outdoor unit model<br />

- - Change the model names<br />

Feb.2008<br />

Feb.2009<br />

Oct.2010<br />

Dec.2010<br />

Dec.2010<br />

General information 7


Introduction 5CSL0-06B<br />

Step by step Single A system selection process (reference)<br />

(1) Calculate or obtain the maximum heat load for the area(s) to be air conditioned<br />

(2)<br />

(3)<br />

(4)<br />

(5)<br />

Indoor unit specifications<br />

Outdoor unit specifications<br />

Capacity coefficient factor<br />

Air flow and temperature distributions<br />

Selection <strong>of</strong> BD unit and branch<br />

Selection <strong>of</strong> the control system<br />

CAUTION<br />

Control wiring method<br />

Description <strong>of</strong> devices<br />

Electrical wiring<br />

Electrical characteristics<br />

Field wiring<br />

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas<br />

or alkaline gas, are produced.<br />

2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze<br />

should be avoided and choose an outdoor unit with anti-corrosion treatment.<br />

8 General information


Part 1 General information<br />

1. Model line up.........................................................................................10<br />

1.1 Indoor units .................................................................................................................10<br />

1.2 Outdoor units...............................................................................................................11<br />

2. Nomenclature........................................................................................14<br />

2.1 Indoor units(Global).....................................................................................................14<br />

2.2 Outdoor units(Global)..................................................................................................14<br />

2.3 Indoor units(Europe) ...................................................................................................15<br />

2.4 Outdoor units(Europe).................................................................................................15<br />

2.5 Decoration panel.........................................................................................................15<br />

3. List <strong>of</strong> functions....................................................................................16<br />

4. Features.................................................................................................17<br />

4.1 What's system..............................................................................................17<br />

4.2 Technologies ...............................................................................................................18<br />

4.3 Indoor units .................................................................................................................20<br />

4.4 Outdoor units...............................................................................................................33<br />

5. Control system......................................................................................36<br />

5.1 Individual control system(Accessory)..........................................................................36<br />

5.2 Central control system(Accessory) .............................................................................52<br />

5.3 Control device(Accessory) ..........................................................................................53<br />

6. Combination..........................................................................................54<br />

6.1 Selection procedure ....................................................................................................54<br />

6.2 Combination <strong>of</strong> indoor unit and outdoor unit ...............................................................54<br />

6.3 Synchro operation Guide ............................................................................................57<br />

General information 9


Model line up<br />

1. Model line up<br />

1.1 Indoor units<br />

Category Type<br />

Ceiling<br />

cassette<br />

Ceiling<br />

concealed<br />

duct<br />

4way<br />

Ceiling & floor<br />

Ceiling suspended<br />

Console<br />

High<br />

static<br />

pressure<br />

* High Efficiency Indoor Units<br />

Chassis<br />

TR ATNH09GRLED<br />

[UT09 NRD]<br />

TQ<br />

TP<br />

TN<br />

TM<br />

BH<br />

BG<br />

BR<br />

VE<br />

VB<br />

VK<br />

VL<br />

QA<br />

5CSL0-06B<br />

2.5 3.5 5.0 6.0 7.1 8.0 10.0 12.5 14.0 15.0<br />

AVNH09GELAD<br />

[UV09 NED]<br />

AQNH09GALA0<br />

[CQ09 NA0]<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

AVNH12GELAD<br />

[UV12 NED]<br />

AQNH12GALA0<br />

[CQ12 NA0]<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

*ATNH18GPLED<br />

[UT18 NPD]<br />

ABNH186HLAD<br />

[UB18 NHD]<br />

UVNH186BLAD<br />

[UV18 NBD]<br />

AQNH18GALA0<br />

[CQ18 NA0]<br />

*ATNH21GNLED<br />

[UT21 NND]<br />

Model Name<br />

Capacity, kW<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

*ATNH24GNLED<br />

[UT24 NND]<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

UVNH246BLAD<br />

[UV24 NBD]<br />

ATNH30GPLED<br />

[UT30 NPD]<br />

ABNH306GLAD<br />

[UB30 NGD]<br />

UVNH306BLAD<br />

[UV30 NBD]<br />

ATNH36GNLED<br />

[UT36 NND]<br />

ABNH366GLAD<br />

[UB36 NGD]<br />

UVNH366KLAD<br />

[UV36 NKD]<br />

ATNH42GMLED<br />

[UT42 NMD]<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

UVNH426LLAD<br />

[UV42 NLD]<br />

ATNH48GMLED<br />

[UT48 NMD]<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

UVNH486LLAD<br />

[UV48 NLD]<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

UVNH606LLAD<br />

[UV60 NLD]<br />

10 General information


5CSL0-06B Model line up<br />

1.2 Outdoor units<br />

DC Inverter (1Ø)<br />

DC Inverter<br />

AUUW096D<br />

[UU09W ULD]<br />

AUUW126D<br />

[UU12W ULD]<br />

AUUW186D<br />

[UU18W UED]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong><br />

connectable indoor units<br />

kW 2.5 3.5 5.0<br />

Power sup<strong>pl</strong>y 1Ø, 220 - 240V, 50Hz<br />

Chassis<br />

DC Inverter<br />

AUUW246D<br />

[UU24W UED]<br />

AUUW306D<br />

[UU30W UED]<br />

AUUW186D1<br />

[UU18W UED1]<br />

AUUW366D<br />

[UU36W UED]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong><br />

connectable indoor units<br />

kW 7.1 8.0 10.0<br />

Power sup<strong>pl</strong>y 1Ø, 220 - 240V, 50Hz<br />

Chassis<br />

DC Inverter<br />

Synchro<br />

AUUW426D<br />

[UU42W U3D]<br />

AUUW486D<br />

[UU48W U3D]<br />

AUUW606D<br />

[UU60W U3D]<br />

No. <strong>of</strong> connectable indoor units 1~4<br />

Total capacity index <strong>of</strong><br />

connectable indoor units<br />

kW 12.5 14.0 15.0<br />

Power sup<strong>pl</strong>y 1Ø, 220 - 240V, 50Hz<br />

Chassis<br />

General information 11


Model line up<br />

DC Inverter (3Ø)<br />

DC Inverter<br />

Synchro<br />

AUUW428D<br />

[UU43W U3D]<br />

AUUW488D<br />

[UU49W U3D]<br />

AUUW608D<br />

[UU61W U3D]<br />

No. <strong>of</strong> connectable indoor units 1~4<br />

Total capacity index <strong>of</strong><br />

connectable indoor units<br />

kW 12.5 14.0 15.0<br />

Power sup<strong>pl</strong>y 3Ø, 380 - 415V, 50Hz<br />

Chassis<br />

DC Inverter<br />

AUUW368D<br />

[UU37W UED]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong><br />

connectable indoor units<br />

kW 10.0<br />

Power sup<strong>pl</strong>y 3Ø, 380 - 415V, 50Hz<br />

Chassis<br />

5CSL0-06B<br />

12 General information


5CSL0-06B Model line up<br />

DC Inverter High Efficiency models(1Ø)<br />

Non Inverter (1Ø, 3Ø)<br />

Heat pump<br />

AUUH368D<br />

[UU37 UED]<br />

AUUH488D<br />

[UU48 U3D]<br />

AUUH608D<br />

[UU60 U3D]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong> connectable<br />

indoor units<br />

kW 10.0 14.0 15.0<br />

Power sup<strong>pl</strong>y 3Ø, 380 - 415V, 50Hz<br />

Chassis<br />

Heat pump<br />

AUUH126D<br />

[UU12 ULD]<br />

AUUH186D<br />

[UU18 UED]<br />

AUUH246D<br />

[UU24 UED]<br />

AUUH306D<br />

[UU30 UED]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong> connectable<br />

indoor units<br />

kW 3.5 5.0 7.1 8.0<br />

Power sup<strong>pl</strong>y 1Ø, 220 - 240V, 50Hz<br />

Chassis<br />

DC Inverter super<br />

AUUW186DH<br />

[UU18WH UED]<br />

AUUW216DH<br />

[UU21WH U4D]<br />

AUUW246DH<br />

[UU24WH U4D]<br />

No. <strong>of</strong> connectable indoor units 1<br />

Total capacity index <strong>of</strong> connectable<br />

indoor units<br />

kW 5.0 6.0 7.1<br />

Power sup<strong>pl</strong>y 1Ø, 220 - 240V, 50Hz<br />

Chassis<br />

General information 13


Nomenclature<br />

2. Nomenclature<br />

Model number nomenclature<br />

2.1 Indoor unit(Global)<br />

A T N H 2 4 G N L E D<br />

2.2 Outdoor units(Global)<br />

A U U W 2 4 6 D H<br />

Serial number<br />

Functions<br />

A : Basic B : Low ambient<br />

C : Plasma filter E : Elevation grille<br />

F : Plasma filter + Elevation grille<br />

function circuit<br />

R : BLDC Motor + Plasma filter<br />

H : Plasma filter + Low ambient<br />

L : Plasma M : Plasma + Elevation grille<br />

Look<br />

L : Basic<br />

5CSL0-06B<br />

Chassis name<br />

Electrical ratings<br />

6: 1Ø, 220V-240V, 50Hz 8: 3Ø, 380V-415V, 50Hz G: 1Ø, 220-240V, 50/60 Hz<br />

Nominal cooling capacity in kW<br />

Ex) 24 -> 7.1 kW, 48 -> 14.0 kW<br />

Model type<br />

C : Cooling only H : Heat pump<br />

Indicates that this is a indoor unit for R410A<br />

ATN : Ceiling cassette type indoor unit<br />

ABN : Ceiling concealed duct type indoor unit<br />

AVN : Convertible, Ceiling and Floor type indoor unit<br />

UVN : Ceiling and Floor, Ceiling Suspended type indoor unit<br />

AQN : Console type indoor unit<br />

High efficiency model<br />

Serial number<br />

Electric standard (Phase, Volts, Freq)<br />

6:1Ø,220V-240V,50Hz<br />

8:3Ø,380V-415V,50Hz<br />

Nominal cooling capacity in kW<br />

09 : 2.5 kW<br />

12 : 3.5 kW<br />

18 : 5.0 kW<br />

24 : 7.1 kW<br />

30 : 8.0 kW<br />

36 : 10.0 kW<br />

42 : 12.5 kW<br />

48 : 14.0 kW<br />

60 : 15.0 kW<br />

Model type<br />

W : Inverter heat pump<br />

H : Heat pump<br />

Indicates that this is a<br />

R410A outdoor unit<br />

14 General information


5CSL0-06B Nomenclature<br />

2.3 Indoor unit(Europe)<br />

U T 2 4<br />

2.4 Outdoor units(Europe)<br />

U U 2 4 W H U4 D<br />

2.5 Decoration panel(For ceiling cassette models)<br />

P T - U M C<br />

N N D<br />

Serial number<br />

Chassis name<br />

Indoor unit<br />

Cooling / Heating capacity (kBtu/h)<br />

Type<br />

T : Cassette, B : Duct, V : Convertible, Q : Console<br />

Model type<br />

U : Universal model<br />

Serial number<br />

Outdoor unit chassis name<br />

High efficiency model<br />

Model type<br />

W : Inverter<br />

No mark for non-inverter model<br />

Cooling / heating capacity (kBtu/h)<br />

Type<br />

U : Outdoor units<br />

Model type<br />

U : Universal model<br />

Functions<br />

A : Basic C : Plasma air purifier<br />

Indoor unit chassis<br />

D : D Chassis E : E Chassis F : F Chassis<br />

H : H Chassis M : P, N, M Chassis<br />

Model type<br />

C : Cooling only H : Heat pump U : Universal<br />

Decoration panel <strong>of</strong> ceiling cassette type indoor unit<br />

General information 15


List <strong>of</strong> functions 5CSL0-06B<br />

3. List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

Ceiling Cassette<br />

4-way<br />

Ceiling & Floor<br />

Ceiling<br />

Suspended<br />

Ceiling Concealed<br />

Duct (High static)<br />

Console<br />

4 1 1 2 2<br />

- Manual Manual - Manual<br />

Auto Auto Auto - Auto<br />

X X - - X<br />

O O O - O<br />

4 / 5 / 4 3 / 4 / 3 3 / 4 / 3 3 / 3 / 3 4 / 5 / 4<br />

X X X - X<br />

- O O - O<br />

O O O - O<br />

O - - - X<br />

X X - - X<br />

Accessory X - X X<br />

O O O O O<br />

O - - Accessory X<br />

- - - O -<br />

O - Accessory - -<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

X X - X X<br />

X - X X X<br />

O O O O O<br />

O O* (Accessory) O* (Accessory) O O<br />

O O O X O<br />

O O* (Accessory) O (Accessory) O O<br />

X O O X O<br />

O O O O O<br />

O O* (Accessory) O (Accessory) O O<br />

O O* (Accessory) O (Accessory) O O<br />

O Accessory * Accessory O X<br />

O X X X Accessory<br />

X X X X X<br />

X X X X X<br />

X X X X X<br />

X X X X X<br />

Accessory O O Accessory O<br />

X X X X X<br />

Accessory Accessory Accessory Accessory ** Accessory **<br />

O O O O O<br />

X X X X X<br />

Accessory Accessory Accessory Accessory Accessory<br />

X X X X X<br />

- - X Accessory X<br />

Accessory Accessory Accessory Accessory X<br />

Note:<br />

* : Some <strong>of</strong> functions are slightly different depending upon models, refer individual function table on "PART 2. indoor units<br />

** : For ceiling concealed duct models, auto-run function <strong>of</strong> dry contact is not ap<strong>pl</strong>icabe. [If RF remote control use, auto-run function <strong>of</strong> dry contact is ap<strong>pl</strong>icable.(Refer to accessory PDB)]<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

16 General information


5CSL0-06B<br />

4. Features<br />

4.1 Whatʼs<br />

• Various IDU combination<br />

Cassette, consealed duct, convertible, console<br />

• Wide capacity range<br />

Indoor range : 2.5~15.0 kW<br />

Outdoor range : 2.5~15.0 kW<br />

• Convenient control<br />

Wired remote control<br />

Central controller<br />

• Long and high elevation piping<br />

• Wide operation range<br />

Cooling : -10~43 °CDB<br />

Heating : -15~24 °CDB<br />

Features<br />

General information 17


Features 5CSL0-06B<br />

4.2 Technologies<br />

Inverter Technology<br />

With the advancement <strong>of</strong> inverter technology comes more silent, economical and powerful air conditioning<br />

systems.<br />

Step-up Inverter by the PFC & the Sine Wave Control Technology (PFC :Power Factor Correction)<br />

The LG air conditioner is manufactured using the PFC and the sine wave technology. By the PFC contorl, raising the operating<br />

voltage from the existing DC 280V to DC 380V can be done. Thereby, it makes the operation smooth in a high-frequency<br />

area. The sine wave control enables s<strong>of</strong>t operation in a low frequency area, thereby expanding the product's operating<br />

range. This also markedly improves the product's energy efficiency.<br />

• Sine wave Control in BLDC Compressor<br />

Loss Full range<br />

Rectangle wave<br />

• PFC Control in Power Input<br />

V<br />

DC280V<br />

I<br />

Partial switching<br />

Powerful BLDC Compressor<br />

Sine wave<br />

The LG inverter air conditioner comes with a BLDC compressor<br />

that uses a strong neodymium magnet. Its compressor<br />

thus has improved efficiency compared with AC inverter.<br />

Notably, during partial-load operation (30-45 Hz), the efficiency<br />

<strong>of</strong> the compressor motor <strong>of</strong> the LG inverter air conditioner<br />

increases, as opposed to the existing AC motors, and<br />

the subcooling effects <strong>of</strong> the bigger condensor will further<br />

increase the product's energy consumption efficiency.<br />

V<br />

DC 380V<br />

(Boost up)<br />

Full range Sine wave switching<br />

I<br />

110Hz<br />

90Hz<br />

BLDC Fan motor<br />

BLDC fan motor <strong>of</strong>fers additional energy saving in operating<br />

mode. Compared with AC motors, BLDC fan motor can cut<br />

energy by 35%at full velocity. AC motor is operating at full<br />

velocity only, but BLDC Motor can change velocity according<br />

to load. Energy efficiency levels at low velocities in particular<br />

have been improved by 65%.<br />

65%<br />

Energy<br />

Saving<br />

35%<br />

Portial Load Full Load<br />

18 General information<br />

Motor Input<br />

Rectangle<br />

wave<br />

Load<br />

Sine<br />

wave<br />

AC Fan Motor<br />

DC Fan Motor


5CSL0-06B<br />

Top Class COP<br />

• DC Inverter Compressor<br />

• BLDC Fan Motor<br />

COP<br />

Cooling<br />

3.33<br />

*Testing Combinations<br />

Capacity<br />

Indoor<br />

3.70<br />

Outdoor<br />

Heating<br />

3.64<br />

3.21 3.21<br />

2.5kW 3.5kW 5.0kW<br />

3.62<br />

2.5kW 3.5kW 5.0kW<br />

UT09 NRD UT12 NRD UT18 NQD<br />

UU09W ULD UU12W ULD UU18W UED<br />

Temp<br />

Temp<br />

Temperature(°C)<br />

Setting<br />

Temperature<br />

Features<br />

Comfortable with Fast Cooling & Heating<br />

Performance<br />

When the air conditioner is initially activated to either heat<br />

or cool, the compressor will operate at maximum speed to<br />

reach the desired temperature quickly.<br />

Once the desired temperature is achieved, unlike conventional<br />

air conditioners that turn the compressor on and <strong>of</strong>f,<br />

LG inverter units constantly adjust and vary the compressor<br />

speed to maintain the desired temperature with minimal<br />

fluctuation to ensure that your comfort is not compromised.<br />

Conventional<br />

Setting Temp.<br />

General information 19<br />

Power<br />

Inverter<br />

Room Temp.<br />

Room Temp.<br />

On On On<br />

Off Off Off<br />

Power<br />

<br />

Power<br />

Input(W) ON ON<br />

ON<br />

<br />

Time<br />

Setting Temp.<br />

Time<br />

OFF OFF OFF<br />

Inverter<br />

(RED)<br />

Conventional<br />

(BLUE)<br />

Inverter<br />

(RED)<br />

Conventional<br />

(BLUE)


Features 5CSL0-06B<br />

4.3 Indoor units<br />

Ceiling Cassette – 4 way<br />

■ Compact design and easy installation<br />

■ Low noise<br />

■ Hygienic and easy-to-clean filter<br />

■ 2-thermistor(unit body and remote controller)<br />

■ Jet cool<br />

■ Plasma air purifying system(Accessory)<br />

■ High head drain pump(700mm)<br />

■ High-ceiling corresponding operation<br />

■ LCD wired remote controller<br />

■ Wireless remote controller(Accessory)<br />

• New Wired Remote Controller<br />

The wired remote controller with a large wide LCD screen<br />

featuring large font letters and a 4-direction key control<br />

enables the user more convenient control <strong>of</strong> operational conditions<br />

<strong>of</strong> the indoor unit.<br />

• 4 Vane Independent Operation<br />

Vane angle control satisfies both users who like direct wind<br />

or indirect wind. And also it prevents cold air draft.<br />

- This function can be controled with new wired remote controller<br />

(PQRCUSA0)<br />

900*900<br />

600*600<br />

• Big Font to see even from a<br />

distance<br />

• Large wide LCD for easy<br />

check<br />

• Easy installation<br />

Direct air flow Indirect air flow<br />

20 General information


5CSL0-06B<br />

All vane operation Individual vane operation Individual vane angle control<br />

• Wide Jet Air Flow<br />

Improved wide and narrow vane will provide comfortable temperature distribution without air flow dead zone.<br />

New<br />

Old<br />

• Elevation Grille (Accessory :PTEGMO)<br />

Easy filter cleaning with elevation grille<br />

- Installed inside main body<br />

- Auto horizontal level<br />

- 4 points support<br />

- Memory for user ʼs level<br />

- Max.4.5m length<br />

567mm<br />

80mm Wider!!<br />

4way<br />

4.5m<br />

Conventional<br />

3.5m<br />

Features<br />

4-Point Support Structure Auto Horizontal Control Memory for userês level Auto bottom detection<br />

General information 21


Features 5CSL0-06B<br />

• Slim & Compact size<br />

The indoor unit with slim and compact size enables successful<br />

installation in confined spaces.<br />

• Convenient Installation<br />

Easy installation with corner detachable decoration panel.<br />

Hanger adjust<br />

7.1 kW<br />

292 mm<br />

204 mm<br />

Model<br />

UT09<br />

UT12<br />

UT18<br />

UT24, UT30<br />

UT36<br />

UT42, UT48<br />

UT60<br />

Drain leakage<br />

check<br />

Hanger adjust<br />

Size<br />

214 mm<br />

214 mm<br />

256 mm<br />

204 mm<br />

246 mm<br />

288mm<br />

• One touch type Panel<br />

It provides easy installation with a one-touch detachable<br />

panel.<br />

• Extra high ceiling mode<br />

A 4.2m maximum high ceiling mode is available with the<br />

support <strong>of</strong> the indoor unit fan position control algorithm<br />

design. This setting <strong>of</strong>fers a reduction <strong>of</strong> droughts.<br />

• Independent Automatic Vane Control<br />

One motor per vane is adopted to control each <strong>of</strong> four vane<br />

independently, freely controlling air current according to situations.<br />

5 : 70°<br />

1 : 20°<br />

0 : 30°<br />

2 : 40°<br />

3 : 50°<br />

4 : 60°<br />

• Two Thermistor Control<br />

There may be a significant difference between the temperature<br />

taken at the installed product and indoor temperature.<br />

Two thermistor control provides option to control temperature<br />

by referring any <strong>of</strong> the two temperatures. With the help<br />

<strong>of</strong> the slide switch at the back <strong>of</strong> the LCD wired remote<br />

controller, selection <strong>of</strong> the desired thermistor for controlling<br />

the unit can be done. One thermistor is in the Indoor unit<br />

&the other one is in the LCD wired remote.<br />

22 General information


5CSL0-06B<br />

• Long Distance, High Elevation Piping<br />

LG air conditioners (cassette and concealed duct<br />

models)can be installed for long distance (up to 75m)and<br />

high elevation ap<strong>pl</strong>ications (up to 30m).<br />

• Weekly Program<br />

The operator can set an On/Off reservation <strong>of</strong> the air conditioner<br />

for a period <strong>of</strong> one week.<br />

LCD Wired Remote Controller<br />

• 24-Hour ON/OFF Timer in 1 hour intervals<br />

• TEST RUN Mode<br />

• Self-Diagnosis function<br />

• 3-Step Fan Speed selection<br />

• Operation Indication<br />

• Room Temperature Dis<strong>pl</strong>ay<br />

• Only 20mm thickness<br />

• Swirl Swing<br />

Swirl swing distributes air evenly throughout the room to<br />

ensure a more comfortable conditioned environment by<br />

adjusting the movement <strong>of</strong> the louvers.<br />

LG New Cassette<br />

Company A<br />

Vertical Temp. Differences Horizontal Temp. Differences<br />

Lover<br />

Lover<br />

Product<br />

Existing type<br />

Product<br />

Ceiling<br />

Ceiling<br />

pollutions<br />

Ceiling<br />

Ceiling pollutions prevention type<br />

Features<br />

• Design to Reduce the Ceiling Stains<br />

The new outlet design can reduce ceiling contamination<br />

from air current flowing along the ceiling.<br />

General information 23


Features 5CSL0-06B<br />

• Group Control<br />

1) Operation Summary<br />

- Where several products are linked, one specific control<br />

device can control a specific number <strong>of</strong> products.<br />

2) Specific Operation<br />

- Connecting line is linked to each <strong>of</strong> the indoor equipments<br />

for communication.<br />

A specific control device is connected to each <strong>of</strong> them<br />

and this control device can control the same function.<br />

- Group control function is enabled by dip switches in the<br />

wired remote control.<br />

At this time, the main system will not respond in order to<br />

prevent data collision.<br />

- While executing group control command, use the random<br />

data(0-3minutes) in the main body <strong>of</strong> indoor equipment<br />

for limiting starting current.<br />

- Control device can control up to 16 indoor equipments.<br />

• Cassette Cover<br />

(Accessory : PTDCQ / PTDCM)<br />

Maintains the ceiling elegance.<br />

- Covers the side area <strong>of</strong> cassette.<br />

- Gives elegant looks.<br />

- Light weight.<br />

- Suitable when false ceiling is unavailable.<br />

• Auto Changeover<br />

With reverse cycle models, the air conditioner will switch<br />

automatically from cooling to heating modes depending on<br />

the set temperature.<br />

• Initial Setting Temp :18 °C:<br />

(Memory the final setting temp)<br />

• Control <strong>of</strong> setting temp.<br />

Wired Remoted Controller:18~30 °C<br />

Reset Button in indoor unit: finally memorized temp.<br />

Wireless Remoted Controller: 23~27<br />

InsideTemp<br />

24 General information<br />

Temp<br />

+2<br />

+1<br />

+0.5<br />

Setting<br />

Temp<br />

-0.5<br />

-1<br />

-2<br />

COMP ON <strong>of</strong>f ON <strong>of</strong>f <strong>of</strong>f ON <strong>of</strong>f ON <strong>of</strong>f ON <strong>of</strong>f<br />

Indoor FAN Setting -Low Setting -Low Stop Setting Low stop Setting -Low stop Setting Low<br />

Cycle Cooling<br />

Heating<br />

Cooling


5CSL0-06B<br />

• World Best COP<br />

• DC Inverter Compressor<br />

• BLDC Fan Motor<br />

• Powerful BLDC Compressor<br />

The LG inverter air conditioner comes with a BLDC compressor that<br />

uses a strong neodymium magnet. Its compressor thus has improved<br />

efficiency compared with AC inverter. Notably, during partial-load operation<br />

(30-45 Hz), the efficiency <strong>of</strong> the compressor motor <strong>of</strong> the LG<br />

inverter air conditioner increases, as opposed to the existing AC<br />

motors, and the subcooling effects <strong>of</strong> the bigger condensor will further<br />

increase the product's energy consumption efficiency.<br />

• BLDC Fan motor<br />

BLDC fan motor <strong>of</strong>fers additional energy saving in operating mode.<br />

Compared with AC motors, BLDC fan motor can cut energy by 35%at<br />

full velocity. AC motor is operating at full velocity only, but BLDC Motor<br />

can change velocity according<br />

to load. Energy efficiency levels at low<br />

velocities in particular have been<br />

improved by 65%.<br />

Stator Rotor<br />

• Quick Cooling &Heating<br />

Inverter air conditioners can operate their compressors faster to give<br />

them more powerful performance. This results in being able to attain<br />

the desired temperature much faster in both heating and cooling<br />

modes than conventional air conditioners.<br />

Features<br />

• High efficiency Inverter Technology<br />

You may have heard the excitement about Inverter technology, LG Inverters are the pinnacle <strong>of</strong> energy efficiency due to the<br />

innovative operation. Rather than using a constant speed compressor, the LG Inverter system uses a variable speed compressor,<br />

which means the Cooling or Heating capacity <strong>of</strong> the Air Conditioning can be varied to suit Indoor conditions.<br />

This makes the LG Inverter Units more economical & efficient to operate, produce less noise than standard counterparts and<br />

contain most superior features on the market.<br />

*Testing Combinations<br />

Capacity 5.0kW 6.0kW 7.1kW<br />

INDOOR<br />

OUTDOOR<br />

UT18H<br />

UU18WH<br />

UT21H<br />

UU21WH<br />

General information 25<br />

UT24H<br />

UU24WH<br />

Motor Input<br />

Temp<br />

COP<br />

Cooling<br />

3.70<br />

65%<br />

Energy<br />

Saving<br />

AC Fan Motor<br />

DC Fan Motor<br />

35%<br />

Portial Load Full Load<br />

Load<br />

50%<br />

Time <strong>of</strong><br />

Conventional<br />

4.07<br />

Heating<br />

5.0kW 6.0kW 7.1kW<br />

Conventional<br />

4.22<br />

3.85 3.65<br />

INVERTER<br />

4.15<br />

Setting Temp.<br />

Time


Features 5CSL0-06B<br />

Ceiling & Floor<br />

■ Flexible installation (Ceiling & Floor)<br />

■ 4-way airflow direction control<br />

(Automatic vertical airflow & manual horizontal airflow)<br />

■ LCD wireless remote controller<br />

■ BLDC fan motor (UV09 NED, UV12 NED)<br />

Flexible installation<br />

It can be installed on the floor or ceiling according<br />

to your need.<br />

<br />

<br />

Vertical airflow & balanced temperature<br />

distribution<br />

The heat distribution graph shows an exam<strong>pl</strong>e <strong>of</strong><br />

even temperature distribution achieved by the autoswing<br />

airflow.<br />

Upward<br />

Downward<br />

Auto Changeover<br />

With reverse cycle models, the air conditioner will<br />

switch automatically from cooling to heating modes<br />

depending on the set temperature.<br />

- Initial Setting Temp: 18 °C:(Memory the final setting<br />

temp)<br />

- Control <strong>of</strong> setting temp.<br />

Wired Remoted Controller: 18~30°C<br />

Reset Button in indoor unit:finally memorized temp.<br />

Wireless Remoted Controller: 23~27°C<br />

InsideTemp<br />

26 General information<br />

Temp<br />

+2<br />

+1<br />

+0.5<br />

Setting<br />

Temp<br />

-0.5<br />

-1<br />

-2<br />

COMP ON <strong>of</strong>f ON <strong>of</strong>f <strong>of</strong>f ON <strong>of</strong>f ON <strong>of</strong>f ON <strong>of</strong>f<br />

Indoor FAN Setting -Low Setting -Low Stop Setting Low stop Setting -Low stop Setting Low<br />

Cycle Cooling<br />

Heating<br />

Cooling


5CSL0-06B<br />

Upgraded Function<br />

• One Touch Filter & Filter Cleaning Alarm Function<br />

• Power Wind Mode<br />

• Wired Remote Controller (Option)<br />

- 2 thermister control<br />

- Weekly Program<br />

- Group control.etc<br />

UV09, UV12<br />

UV18~UV60<br />

(PVRCUSZ0)<br />

Features<br />

New Wired Remote Controller (Option)<br />

The wired remote controller with a large wide LCD<br />

screen featuring large font letters and a 4-direction<br />

key control enables the user more convenient control<br />

<strong>of</strong> operational conditions <strong>of</strong> the indoor unit.<br />

UV09, UV12<br />

(PQRCUSA0)<br />

• Big Font to see even from a<br />

distance<br />

• Large wide LCD for easy<br />

check<br />

• Easy installation<br />

• 2 thermister control<br />

General information 27


Features 5CSL0-06B<br />

Ceiling Suspended<br />

1350 x 650 x 220 (UV36) 1750 x 650 x 220 (UV42 / UV48 / UV60)<br />

Customize size and weight<br />

• Weight : 65kg, 35kg<br />

• Volume : 100%, 68%<br />

Natural CHAOS wind<br />

• It swings at an angle, thus minimizing the difference in indoor temperatures and allowing air in every corner <strong>of</strong> the<br />

room.<br />

Auto air flow direction (up&down)<br />

• The air flow direction can be adjusted as desired by using the remote controller.<br />

• This is effective when you want to cool yourself directly<br />

One-touch air filter & filter chage alarm function<br />

• Easily change air filter when it is dirty.<br />

28 General information


5CSL0-06B<br />

Ceiling Concealed Duct – High static pressure<br />

■ Compact design and easy installation<br />

■ Phase control motor<br />

■ 2-thermistor control (unit body and remote controller)<br />

■ LCD wired remote controller<br />

■ Wireless remote controller(Accessory)<br />

■ High head drain pump(Accessory)<br />

■ Zone controller(Accessory)<br />

• E.S.P : External Static Pressure<br />

Always air volume and sound kept as design regardless <strong>of</strong><br />

E.S.P change using this technology, you can.<br />

• Optimize Duct work Installation<br />

• Keep Capacity & Sound level as desired<br />

• Sim<strong>pl</strong>ify model numbers<br />

The Phase control motor Technology gives benefit <strong>of</strong> saving<br />

money to Installer. Desired Air flowrate is obtained by controlling<br />

the phase <strong>of</strong> motor while installing the product and<br />

this makes your duct work system flexible.<br />

Air flow rate<br />

at 2mmAq<br />

Air flow rate<br />

at 10mmAq<br />

External static pressure(mmAq)<br />

Features<br />

• Quiet Operation & Easy Service<br />

A lightweight <strong>pl</strong>astic blower and housing makes air conditioning<br />

operation quiet and backup servicing more convenient.<br />

The new fan housing can be easily dismantled for convenient<br />

servicing and maintenance. The fan motor can be<br />

removed without the need to remove the com<strong>pl</strong>ete fan direct<br />

assembly.<br />

Conventional<br />

LG Fan and Housing<br />

General information 29


Features 5CSL0-06B<br />

• Central Controller<br />

Operation Summary<br />

LG units come with advanced control options, take for<br />

instance the Central Controller. Designed for the commercial<br />

ap<strong>pl</strong>ication, where multi<strong>pl</strong>e Air Conditioning units have<br />

been installed.<br />

You can control or fault find up to 16~2048 Air Conditioning<br />

units (via 8 separate controllers) individually or all together.<br />

1 2 3 4<br />

5 6 7 8<br />

9 10 11 12<br />

13 14 15 16<br />

On Of f<br />

1 2 16<br />

Controller<br />

#1<br />

1 2 3 4<br />

5 6 7 8<br />

9 10 11 12<br />

13 14 15 16<br />

On Of f<br />

1 2 16<br />

Controller<br />

#2<br />

1 2 3 4<br />

5 6 7 8<br />

9 10 11 12<br />

13 14 15 16<br />

On Of f<br />

Controller<br />

#8<br />

• Zone Controller<br />

This feature can be used to control the operation <strong>of</strong> the Air<br />

Conditioning Unit where each zone (maximum <strong>of</strong> 4 zones)<br />

has a separate thermostat and damper motor, your Air<br />

Conditioning Specialist can advise you if you require a VAV<br />

(Variable Air Volume) Installation in your home / <strong>of</strong>fice, as<br />

well as providing a quotation for Installation (including the<br />

sup<strong>pl</strong>y <strong>of</strong> thermostats and damper motors).<br />

Zone<br />

Control<br />

sub PCB<br />

ABZCA<br />

ROOM1<br />

Thermostat<br />

Damper Motor<br />

Damper Motor<br />

ROOM3<br />

Thermostat<br />

ROOM2<br />

Thermostat<br />

Damper Motor<br />

Damper Motor<br />

ROOM4<br />

Thermostat<br />

• Weekly Program<br />

The operator can set an On/Off reservation <strong>of</strong> the air conditioner<br />

for a period <strong>of</strong> one week.<br />

LCD Wired Remote Controller<br />

• 24-Hour ON/OFF Timer in<br />

1 hour intervals<br />

• TEST RUN Mode<br />

• Self-Diagnosis function<br />

• 3-Step Fan Speed selection<br />

• Operation Indication<br />

• Room Temperature Dis<strong>pl</strong>ay<br />

• Only 20mm thick<br />

• High Head Drain Pump<br />

Auxiliary Drain Pump automatically drains water. A standard<br />

drain-head height <strong>of</strong> up to 700mm is possible, creating the<br />

ideal solution for perfect water drainage.<br />

Drain Pipe Slope (1/50~1/100)<br />

Flexible Drain Hose<br />

Fixture<br />

Drain pipe<br />

(Accessory:ABDPG)<br />

• Long Distance, High Elevation Piping<br />

Our LG Air Conditioners(Cassette and Concealed duct<br />

model) are possible to be installed a long distance(Max<br />

75m) that is included High Elevation(30m)<br />

30 General information


5CSL0-06B<br />

Console (Floor stand)<br />

• Comfort Air Flow<br />

Features<br />

Different air flow <strong>of</strong> cooling & heating<br />

For cooling, the vane is adjusted upwards to let the cold air travel up. As for heating, the vane sends the heated air downwards<br />

to balance room temperature specially for floor.<br />

Quick floor heating<br />

Console air conditioners can operate faster to provide more powerful performance.<br />

The result is to attain the desired temperature much faster in floor heating mode than conventional air conditioners.<br />

27°C<br />

15°C<br />

Vertical<br />

Horizontal<br />

Lead Time for<br />

Heating<br />

(13°C 21°C)<br />

Average temp.(°C) 22.0[-1.0] 22.0[-1.0] 19.4[-3.6] 23.6[+0.6] 24.1[1.1]<br />

Vertical temp.<br />

difference (°C)<br />

Company D Company M Electric Heater LG LG<br />

Floor Heating Mode<br />

12 minutes<br />

30 second<br />

1.4<br />

[21.8~23.2]<br />

9 minutes<br />

40 second<br />

1.3<br />

[22.7~24.0]<br />

50 minutes<br />

4.9<br />

[15.7~20.6]<br />

EZ vane tap control Quiet operation (22dB)<br />

The indoor unit has a quiet operational noise level in the sleep mode to <strong>of</strong>fer<br />

calmness and comfort.<br />

• Healthy Air (3 stage air filter system)<br />

9 minutes<br />

30 second<br />

1.3<br />

[21.5~22.8]<br />

8 minutes<br />

40 second<br />

0.3<br />

[22.2~22.5]<br />

(Test Condition : Target Temp 23 °C,<br />

Indoor Room : 13 °C~, Outdoor Room :<br />

7 °C)<br />

1st Advanced pre filter : The antibacterial pre-filter primarily reduces large dust, mould and quilt<br />

dust.<br />

2nd Allergy Filter : Filter consists <strong>of</strong> enzyme that breaks down allergen, apatite, and organic/inorganic<br />

binder that attaches the enzyme to the filter. When the air passes the filter, allergen clings to the filter<br />

and like tiny pairs <strong>of</strong> scissors the enzymes cut allergen's protein to deactivate the allergen.<br />

3rd Plazma Ion Generator : The sterilized ion generating system, Ion Generator,<br />

emits around 1.2 million ions, and catches hazardous substances floating in the air, therefore<br />

proactively looking for and catching germs.<br />

General information 31


Features 5CSL0-06B<br />

• LG Unique design<br />

Console has been designed with the latest technologies to ensure optimum comfort.<br />

• EZ Installation & SVC<br />

6Way Pipe Installation<br />

It <strong>of</strong>fers 6way pipe so that fit various installation <strong>pl</strong>aces.<br />

Sliding-Type PCB at control box<br />

It can be installed different levels <strong>of</strong> user access which can be selected.<br />

It <strong>of</strong>fers even air distribution using upper and lower air diffuser.<br />

It has light weight but robust design.<br />

• Ez-Remote Controller<br />

User Friendly & Modern Design and<br />

Easy use!!<br />

- Comfortable to grab<br />

- Sliding type<br />

- Bigger size button<br />

- Highlighted some buttons with different<br />

colors<br />

- Easy to recognize functions with graphics<br />

• Full front panel<br />

• 3 dimensional round design<br />

32 General information


5CSL0-06B<br />

4.4 Outdoor units<br />

DC Inverter<br />

■ Inverter system<br />

- High efficiency<br />

- Low noise<br />

■ Meet EU New harmonics regulation<br />

■ New Design (12.5kW~)<br />

■ Long pipe / high elevation piping<br />

■ DC inverter full line up<br />

■ Energy saving using DC inverter<br />

Model name(1Ø) Model name(3Ø)<br />

Features<br />

2.5/3.5 kW 5.0 kW 7.1/8.0 kW 10.0 kW 12.5/14.0/15.0 kW<br />

AUUW096D[UU09W ULD], AUUW126D[UU12W ULD]<br />

AUUW186D[UU18W UED], AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED], AUUW366D[UU36W UED]<br />

AUUW426D[UU42W U3D], AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D], AUUW186D1[UU18W UED1]<br />

DC Inverter High efficiency<br />

Power sup<strong>pl</strong>y: 1Ø, 220-240V, 50Hz Power sup<strong>pl</strong>y: 3Ø, 380-415V, 50Hz<br />

■ Top class EER/COP<br />

■ New <strong>pl</strong>astic grille design, new ODU (6.0/7.1 kW)<br />

■ High efficiency technology<br />

■ Power operation and energy saving<br />

■ Low noise level<br />

5.0 kW 6.0/7.1 kW<br />

Model name(1Ø)<br />

AUUW186DH [UU18WH UED]<br />

AUUW216DH [UU21WH U4D]<br />

AUUW246DH [UU24WH U4D]<br />

Power sup<strong>pl</strong>y: 1Ø, 220-240V, 50Hz<br />

AUUW368D[UU37W UED]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

General information 33


Features 5CSL0-06B<br />

Non Inverter<br />

■ Reasonable solution<br />

■ Long pipe / high elevation piping up to 50m<br />

■ New Design (14.0/15.0 kW)<br />

■ Low noise level<br />

3.5 kW 5.0 kW 7.1/8.0 kW 10.0 kW 14.0/15.0 kW<br />

Model name(1Ø) Model name(3Ø)<br />

AUUH126D[UU12 ULD]<br />

AUUH186D[UU18 UED]<br />

AUUH246D[UU24 UED]<br />

AUUH306D[UU30 UED]<br />

AUUH368D[UU37 UED]<br />

AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

Power sup<strong>pl</strong>y: 1Ø, 220-240V, 50Hz Power sup<strong>pl</strong>y: 3Ø, 380-415V, 50Hz<br />

34 General information


5CSL0-06B<br />

DC Inverter - Synchro (1Ø, 3Ø)<br />

Model name (1Ø)<br />

AUUW426D [UU42W U3D]<br />

AUUW486D [UU48W U3D]<br />

AUUW606D [UU60W U3D]<br />

Power sup<strong>pl</strong>y: 1Ø, 220-240V, 50Hz<br />

(Ex. Duo simultaneous operation)<br />

Circuit<br />

breaker<br />

(Ex. Trio simultaneous operation)<br />

Circuit<br />

breaker<br />

(Ex. Quartet simultaneous operation)<br />

Circuit<br />

breaker<br />

Features<br />

One large room can be cooled simultaneously by duo, trio or quartet<br />

indoor units according to the environmental needs.<br />

■ Synchro op<strong>pl</strong>ication<br />

■ Connectable to 2~4 indoor units by sim<strong>pl</strong>e branch kit piping<br />

■ DC inverter system<br />

- High efficiency<br />

- Low noise<br />

- High reliability<br />

■ Long pipe / high elevation piping<br />

■ New Design<br />

■ New Harmonics Regulation<br />

Model name (3Ø)<br />

AUUW428D [UU43W U3D]<br />

AUUW488D [UU49W U3D]<br />

AUUW608D [UU61W U3D]<br />

Power sup<strong>pl</strong>y: 3Ø, 380-415V, 50Hz<br />

Branch kit(PMUB11A)<br />

Branch kit(PMUB111A)<br />

Branch kit(PMUB1111A)<br />

Only one remote controller<br />

Only one circuit breaker.<br />

Only one remote controller<br />

Only one circuit breaker.<br />

Only one remote controller<br />

Only one circuit breaker.<br />

General information 35


Control system 5CSL0-06B<br />

5. Control system<br />

5.1 Individual control system(Accessory)<br />

Wired<br />

remote<br />

controller<br />

Item Model name Image<br />

Function<br />

Ap<strong>pl</strong>icable model<br />

5.1.1 Wide Remote controller (PQRCUSA0)<br />

Wired<br />

remote<br />

controller<br />

Standard PVRCUSZ0<br />

Sim<strong>pl</strong>e type PQRCUCA0<br />

Deluxe type PQRCUDS0<br />

For hotel use<br />

PQRCFCS0<br />

• On/<strong>of</strong>f, fan speed, mode, tempeture<br />

• Room tempeture<br />

• Fan, <strong>pl</strong>asma, swirl swing<br />

• Automatic<br />

• ESP function<br />

• Reservation(sim<strong>pl</strong>e/weekly)<br />

• Sim<strong>pl</strong>e reservation<br />

• Timer function<br />

• Auto swing, child lock<br />

• On/<strong>of</strong>f<br />

• Fan speed<br />

• Mode<br />

• Set temperature<br />

• Room temp<br />

• ESP function<br />

• Wireless remocon receiver<br />

• On/<strong>of</strong>f, fan speed, mode,<br />

tempeture<br />

• Room tempeture<br />

• Fan, <strong>pl</strong>asma, swirl swing<br />

• Automatic<br />

• Vane control<br />

• ESP function<br />

• Reservation(sim<strong>pl</strong>e/weekly)<br />

• Sim<strong>pl</strong>e reservation<br />

• Timer function<br />

• Auto swing, child lock<br />

• On/<strong>of</strong>f<br />

• Fan speed<br />

• Set temperature<br />

• Room tempeture<br />

• ESP function<br />

• Wireless remocon receiver<br />

For UV Synchro<br />

Ceiling cassette<br />

Ceiling & floor<br />

Ceiling concealed duct<br />

Item Model name Image<br />

Function<br />

Ap<strong>pl</strong>icable model<br />

Picto type PQRCUSA0<br />

❈ For detail information, refer to the accessory part <strong>of</strong> design & installation book.<br />

• On/<strong>of</strong>f, fan speed, mode,<br />

tempeture<br />

• Room tempeture<br />

• Fan, <strong>pl</strong>asma, swirl swing<br />

• Automatic<br />

• Vane control<br />

• ESP function<br />

• Reservation(sim<strong>pl</strong>e/weekly)<br />

• Sim<strong>pl</strong>e reservation<br />

• Timer function<br />

• Auto swing, child lock<br />

• 4 Vane independent operation<br />

Ceiling cassette<br />

36 General information


5CSL0-06B<br />

5.1.2 Wide Remote controller (PQRCUSA0) installation guide<br />

1) When installing more than 2 units <strong>of</strong> air<br />

conditioner to one wired remote controller,<br />

<strong>pl</strong>ease connect as the right figure.<br />

• If it is not event communication indoor unit, set the unit<br />

as slave.<br />

• Check for event communication through the product<br />

manual.<br />

• Refer to regarding <strong>page</strong> on how to set the slave.<br />

(Only Single IDU/ODU operation Not for Synchro<br />

Operation)<br />

2) When installing more than 2 wired remote<br />

controllers to one air conditioner, <strong>pl</strong>ease<br />

connect as the right picture.<br />

• When installing more than 2 units <strong>of</strong> wired remote controller<br />

to one air conditioner, set one wired remote controller<br />

as master and the others all as slaves, as shown<br />

in the right picture.<br />

• Refer to Installer setting section on how to set<br />

master/slave.<br />

• You cannot control the group as shown in the right for<br />

some products.<br />

(Only Single IDU/ODU operation Not for Synchro<br />

Operation)<br />

GND<br />

Signal wire<br />

12V<br />

Control system<br />

General information 37<br />

GND<br />

Signal wire<br />

GND<br />

Signal wire GND<br />

12V<br />

B Y R B Y R<br />

Signal wire<br />

12V<br />

MASTER SLAVE<br />

<br />

<br />

❊ Some products do not use 'Group control'. It depends on the product type.


Control system 5CSL0-06B<br />

Installer Setting -How to enter installer setting mode<br />

Installer setting mode is to set the detail function <strong>of</strong> the remote controller.<br />

If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage.<br />

This must be set by an certificated installer, and any installation or change that is carried out by a non-certificated<br />

person should be responsible for the results. In this case, free service cannot be provided.<br />

1<br />

❈ Some contents may not be dis<strong>pl</strong>ayed depending on the product function.<br />

1<br />

2<br />

Press button for 4 secsonds to enter<br />

the installer setting mode. (When you<br />

enter the setting mode initially, Function<br />

code is dis<strong>pl</strong>ayed on the bottom <strong>of</strong> the<br />

LCD screen.)<br />

Function Code Value<br />

Repeat pressing button, the menu<br />

will change with the corresponding<br />

function code.<br />

Test Run → Address Setting → E.S.P.<br />

Value → Thermistor → Ceiling Height →<br />

Static Pressure → Group Setting →<br />

Override Setting → Dry Contact →<br />

Release 3Min. Delay → Zone State →<br />

Convert Temp. → Plasma → Electric<br />

heater → Humidifier → Elevation Grill →<br />

Ventilation Kit<br />

38 General information


5CSL0-06B<br />

<br />

No. Function Code Value<br />

1 Test Run 01 01:Set<br />

2 Address Setting 02 00~FF : Address<br />

<br />

01:VeryLow 0 ~ 255<br />

3 E.S.P. Value 03<br />

02:Low<br />

03:Med<br />

04:High<br />

05:Very High<br />

01:Remo<br />

4 Thermistor 04 02:Indoor<br />

03:2TH<br />

01:Med<br />

5 Ceiling Height 05<br />

02:Low<br />

03:High<br />

04:Very High<br />

01:V-H<br />

6 Static Pressure 06<br />

02:F-H<br />

03:V-L<br />

04:F-L<br />

7 Group Setting 07<br />

00:Slave<br />

01:Master<br />

8 Override Setting 08<br />

00:Slave<br />

01:Master<br />

9 Dry Contact 09<br />

00:OFF<br />

01:ON<br />

10<br />

Release 3 Min.<br />

Delay<br />

10 01:Set<br />

11 Zone State 11<br />

01:Variable<br />

02:Fixed<br />

12 Plasma 20<br />

13 Humidifier 22 00: Not Installed<br />

14 Elevation Grill 23 01: Installed<br />

15 Ventilation Kit 24<br />

❈ Some contents may not be dis<strong>pl</strong>ayed depending on the product function<br />

Function Code ESP step ESP value<br />

Control system<br />

General information 39


Control system 5CSL0-06B<br />

Installer Setting -Test Run Mode<br />

After installing the product, you must run a Test Run mode.<br />

For details related to this operation, refer to the product manual.<br />

1 2<br />

1<br />

2<br />

Keep pressing button setting for 4<br />

secs to enter installer setting mode until<br />

code dis<strong>pl</strong>ayed in timer segment.<br />

Function Code Set<br />

Press button to start.<br />

❈ 18˚C cooling, High Fan Speed, Airflow direction mode will be operated during 18 minutes with ignoring room temperature.<br />

❈ After running 18 minutes under test run mode, system will automatically turn OFF.<br />

❈ In case <strong>of</strong> duct type, the Airflow UP/DOWN function is not dis<strong>pl</strong>ayed.<br />

❈ During test run mode, receiving signal from wireless remote controller will release this operation.<br />

If you press any kind <strong>of</strong> button, Test Run mode will be released.<br />

40 General information


5CSL0-06B<br />

Installer Setting - Setting Address <strong>of</strong> Central Control<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

Press the button for 4<br />

seconds to enter the installer<br />

setting mode until timer segment<br />

dis<strong>pl</strong>ay "01:01".<br />

Repeat pressing button to select<br />

Function code 02.<br />

Function Code Group No<br />

Ex) Setting Address as 'F5'<br />

Set Group No. by pressing<br />

button.<br />

Indoor No.<br />

Move to Indoor No. setting option<br />

by pressing button.<br />

Set Indoor No. by pressing<br />

button.<br />

Press button to save or release.<br />

Press button to exit or system will<br />

automatically exit after 25 seconds<br />

without any input.<br />

Control system<br />

General information 41


Control system 5CSL0-06B<br />

Installer Setting -E.S.P.<br />

What is an E.S.P function?<br />

This is the function that decides the strength <strong>of</strong> the wind for each wind level and because this function is to make the<br />

installation easier, <strong>pl</strong>ease do not use this function when using the remote controller.<br />

If you set ESP incorrectly, the air conditioner may malfunction.<br />

This setting must be carried out by a certificated-technician.<br />

This function is used for only Duct product.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 03.<br />

Function Code ESP step ESP value<br />

Set ESP step by pressing button.<br />

(01: very low, 02: low, 03: medium, 04:<br />

high. 05: power)<br />

Move to ESP setting by pressing<br />

button.<br />

Press button to select ESP<br />

value(0~255).<br />

42 General information


5CSL0-06B<br />

6<br />

7<br />

❈ Weak and Power setting is not available for some products.<br />

Press button to save or release.<br />

Press button to exit or the system<br />

will automatically exit after 25 seconds<br />

without any input.<br />

Control system<br />

❈ Because the ESP value is already appropriately set when manufactured from the factory, it is recommended that<br />

you do not change the ESP value.<br />

General information 43


Control system 5CSL0-06B<br />

Installer Setting -Thermistor<br />

❈ Therefore system will use value that sensed from indoor unit or remote controller<br />

<br />

Temperature sensor location Function<br />

01 Remote controller Operation in indoor unit temperature sensor<br />

02 Indoor unit Operation in remote controller Temperature sensor<br />

03 2-Thermistor(2TH)<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 04.<br />

Function Code Thermistor setting<br />

Ex) Setting Thermistor as '2TH'.<br />

Set Thermistor mode by pressing<br />

button. (01: Remote Controller,<br />

02: Indoor, 03: 2TH)<br />

Press button to save or release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

Operation in lower temperature after comparing the temperature between the indoor unit<br />

and remote controller<br />

44 General information


5CSL0-06B<br />

Installer Setting -Ceiling Height Selection<br />

This function is to adjust FAN Airflow rate according to ceilingheight (only cassette model)<br />

<br />

Ceiling Height Level Description<br />

01 Low Decrease the indoor airflow rate 1 step from standard level<br />

02 Standard Set the indoor airflow rate as standard level<br />

03 High Increase indoor airflow rate 1 step from standard level<br />

04 Super high Increase indoor airflow rate 2 steps from standard level<br />

❈ Ceiling height setting is available only for some products.<br />

❈ Ceiling height <strong>of</strong> ʻSuper highʼ function may not exist depending on the indoor unit.<br />

❈ Refer to the product manual for more details.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 05.<br />

Function Code Ceiling height<br />

Ex) Setting Ceiling Height as 'Standard'.<br />

Select ceiling height value by pressing<br />

button.<br />

(01:Low, 02:Standard, 03:High,<br />

04:Super high)<br />

Press button to save or release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

Control system<br />

General information 45


Control system 5CSL0-06B<br />

Installer Setting -Static Pressure Setting<br />

This function is ap<strong>pl</strong>ied to only duct type. Setting this in other cases will cause malfunction.<br />

<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 06.<br />

Function Code Pressure<br />

Select static pressure by pressing<br />

button.<br />

(01:V-H, 02:F-H, 03:V-L, 04:F-L)<br />

Press button to save or<br />

release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

Pressure selection<br />

Zone state<br />

Function<br />

ESP standard value<br />

01 F-L Fixed Low<br />

02 F-H Fixed High<br />

03 V-L Variable Low<br />

04 V-H Variable High<br />

46 General information


5CSL0-06B<br />

Installer Setting-Group Setting<br />

This function is only for group control operation. Please donʼt set this function in case <strong>of</strong> non-group control.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay "01:01".<br />

Repeat pressing button to select<br />

Function code 07.<br />

Function Code Master/Slave value<br />

Ex) 'Master' Setting<br />

Select Master/ Slave by pressing<br />

button.<br />

(00: Slave, 01: Master)<br />

Press button to save or release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

Control system<br />

General information 47


Control system 5CSL0-06B<br />

Installer Setting -Mode Override Setting<br />

In case <strong>of</strong> More than 2 indoor units connected to 1 outdoor unit, they are assigned as Master indoor and Slave indoor.<br />

Therefore, they can operate together. (the setting code for this function is not dis<strong>pl</strong>ayed with un-equipped unit).<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay "01:01".<br />

Repeat pressing button to select<br />

Function code 08.<br />

Function Code Master/Slave<br />

Ex) Override 'Master' Setting<br />

Select Master/ Slave by pressing<br />

button.<br />

(00: Slave, 01 : Master)<br />

Press button to save or release<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

48 General information


5CSL0-06B<br />

Installer Setting-Dry Contact Mode Setting<br />

Control system<br />

This function allows the Dry contact-indoor unit operate under Auto Run mode or Manual mode with remote controller.<br />

* Please refer to dry contact manual for more details.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 09.<br />

Function Code Dry Contact setting value<br />

Ex) Setting Dry Contact Mode 'ON'<br />

Select Dry contact setting by<br />

pressing button.<br />

(00: OFF, 01: ON)<br />

Press button to save or release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

General information 49


Control system 5CSL0-06B<br />

Installer Setting-Zone State Setting<br />

This function is only available on some products.<br />

It is possible to setup Variable or Fixed option for Zone State <strong>of</strong> indoor. The initial setting is 'Variable'<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

Function code 11.<br />

Function Code Zone State fixing mode<br />

Ex) Setting Zone State as 'Fixed'.<br />

Select Zone State rate fixing mode by<br />

pressing button.<br />

(01: Variable, 02: Fixed)<br />

Press button to save or release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

50 General information


5CSL0-06B<br />

Installer Setting -Optional Function Setting<br />

Control system<br />

For the optional product such as PLASMA PURIFICATION/dehumidifier/ electric heater and ventilation, elevation grill.<br />

It is possible to set the items are installed or not<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Press button for 4 seconds<br />

to enter the installer setting<br />

mode until timer segment<br />

dis<strong>pl</strong>ay “01:01”.<br />

Repeat pressing button to select<br />

function code.<br />

(20: PLASMA PURIFICATION,<br />

21: DEHUMIDIFIER,<br />

22: ELECTRIC HEATER,<br />

23: ELEVATION GRILL,<br />

24: VENTILATION KIT)<br />

Function Code Existing condition<br />

Select existing condition<br />

<strong>of</strong> each mode by pressing<br />

button.<br />

(00: not installed,<br />

01 : installed)<br />

Press button to save or<br />

release.<br />

Press button to exit or<br />

system will automatically exit<br />

after 25 seconds without any<br />

input.<br />

General information 51


Control system 5CSL0-06B<br />

5.2 Central control system(Accessory)<br />

Central controller<br />

Item Model name Image Ap<strong>pl</strong>icable model<br />

Sim<strong>pl</strong>e central<br />

controller<br />

Sim<strong>pl</strong>e central<br />

controller<br />

(function controller<br />

available)<br />

Function controller<br />

Deluxe central<br />

controller<br />

(without schedule<br />

function)<br />

Deluxe central<br />

controller<br />

(with schedule<br />

function)<br />

PC based central<br />

controller<br />

(without schedule<br />

function)<br />

PC based central<br />

controller<br />

(with schedule<br />

function)<br />

PQCSA101S0<br />

PQCSB101S0<br />

PQCSC101S0<br />

PQCSW501A0<br />

PQCSW502A0<br />

PQCSS501A0<br />

PQCSS502A0<br />

❈ For detail information, refer to the network solution part <strong>of</strong> design & installation book.<br />

Ceiling cassette<br />

Ceiling & floor<br />

Ceiling concealed duct<br />

52 General information


5CSL0-06B<br />

5.3 Control device(Accessory)<br />

Control system<br />

Item Model name Image Ap<strong>pl</strong>ication model<br />

BMS_LW<br />

PDI<br />

(Power distributor indicator)<br />

Product<br />

interface units<br />

LonWorks<br />

for BMS<br />

PI485<br />

CNU<br />

Dry_contact<br />

PQNFB16A0<br />

PQNUD1S00<br />

PMNFP14A0<br />

PQNFG00A0<br />

PQDSA<br />

PQDSB<br />

❈ For detail information, refer to the network solution part <strong>of</strong> design & installation book.<br />

Ceiling cassette<br />

Ceiling & floor<br />

Ceiling concealed duct<br />

General information 53


Combination 5CSL0-06B<br />

6. Combination<br />

6.1 Outdoor units selection<br />

In general, outdoor unit may be selected as follows, though the location <strong>of</strong> the unit, and usage <strong>of</strong> the room, etc.<br />

should be considered.<br />

The combination <strong>of</strong> indoor and outdoor unit was to be decided that the sum <strong>of</strong> indoor unit capacity index should<br />

be smaller than the max. combination capacity <strong>of</strong> outdoor unit. Up to 2 ~ 4 indoor units can be connected to one<br />

outdoor unit. It is recommended to choose a large capacity outdoor unit if the installation space is large enough.<br />

6.2 Combination <strong>of</strong> indoor and outdoor unit<br />

Outdoor Units - 1Ø, 3Ø<br />

LGʼs system consist <strong>of</strong> one outdoor unit which can match with Four different indoor units as individual<br />

system.<br />

Category<br />

Standard Line up<br />

High efficiency Line up<br />

Outdoor unit Indoor unit<br />

1Ø 3Ø Type Model name<br />

Ceiling Cassette ATNH09GRLED[UT09 NRD]<br />

AUUW096D[UU09W ULD] - Ceiling & Floor AVNH09GELAD[UV09 NED]<br />

Console AQNH09GALA0[CQ09 NA0]<br />

Ceiling Cassette ATNH12GRLED[UT12 NRD]<br />

AUUW126D[UU12W ULD] - Ceiling & Floor AVNH12GELAD[UV12 NED]<br />

Console AQNH12GALA0[CQ12 NA0]<br />

Ceiling Cassette ATNH18GQLED[UT18 NQD]<br />

AUUW186D[UU18W UED] -<br />

Ceiling concealed duct<br />

Ceiling & Floor<br />

ABNH186HLAD[UB18 NHD]<br />

UVNH186BLAD[UV18 NBD]<br />

Console AQNH18GALA0[CQ18 NA0]<br />

Ceiling Cassette ATNH18GQLED[UT18 NQD]<br />

AUUW186D1[UU18W UED1] -<br />

Ceiling concealed duct<br />

Ceiling & Floor<br />

ABNH186HLAD[UB18 NHD]<br />

UVNH186BLAD[UV18 NBD]<br />

Console AQNH18GALA0[CQ18 NA0]<br />

Ceiling Cassette ATNH24GPLED[UT24 NPD]<br />

AUUW246D[UU24W UED] - Ceiling concealed duct ABNH246HLAD[UB24 NHD]<br />

Ceiling & Floor UVNH246BLAD[UV24 NBD]<br />

Ceiling Cassette ATNH30GPLED[UT30 NPD]<br />

AUUW306D[UU30W UED] - Ceiling concealed duct ABNH306GLAD[UB30 NGD]<br />

Ceiling & Floor UVNH306BLAD[UV30 NBD]<br />

Ceiling Cassette ATNH36GNLED[UT36 NND]<br />

AUUW366D[UU36W UED] AUUW368D[UU37W UED] Ceiling concealed duct ABNH366GLAD[UB36 NGD]<br />

Ceiling suspended UVNH366KLAD[UV36 NKD]<br />

Ceiling Cassette ATNH42GMLED[UT42 NMD]<br />

AUUW426D[UU42W U3D] AUUW428D[UU43W U3D] Ceiling concealed duct ABNH426RLAD[UB42 NRD]<br />

Ceiling suspended UVNH426LLAD[UV42 NLD]<br />

Ceiling Cassette ATNH48GMLED[UT48 NMD]<br />

AUUW486D[UU48W U3D] AUUW488D[UU49W U3D] Ceiling concealed duct ABNH486RLAD[UB48 NRD]<br />

Ceiling suspended UVNH486LLAD[UV48 NLD]<br />

Ceiling Cassette ATNH60GMLED[UT60 NMD]<br />

AUUW606D[UU60W U3D] AUUW608D[UU61W U3D] Ceiling concealed duct ABNH606RLAD[UB60 NRD]<br />

Ceiling suspended UVNH606LLAD[UV60 NLD]<br />

AUUW186DH [UU18WH UED] ATNH18GPLED [UT18 NPD]<br />

AUUW216DH [UU21WH U4D] - Ceiling Cassette ATNH21GNLED [UT21 NND]<br />

AUUW246DH [UU24WH U4D] ATNH24GNLED [UT24 NND]<br />

54 General information


5CSL0-06B<br />

Synchro Outdoor Unit – 1Ø, 3Ø<br />

(AUUW-D)[UU-W]<br />

Combination<br />

Synchro operation is solution to customer with reasonable prices.<br />

It uses 2, 3 or 4 indoor units with one outdoor unit.<br />

Each indoor units are running as one cycle with same mode(cooling or heating).<br />

It helps same air distribution all arround the middle or larger room(<strong>of</strong>fice or open <strong>pl</strong>aces) even in irregualr shaped<br />

spaces.<br />

The total capacity based on ODU for Synchro operation are the same as for the fixed combinations.<br />

Possible indoor units: indoor unit series<br />

IDU : INDOOR UNIT<br />

ODU : OUT DOOR INUT<br />

BD : BRANCH DISTRIBUTOR UNIT<br />

REMO : WIRED REMOTE CONTROLLER<br />

OUTDOOR<br />

UNITS<br />

AUUW426D[UU42W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW608D[UU61W U3D]<br />

Ap<strong>pl</strong>ied Accessiries<br />

Capacity (kW)<br />

Cooling Heating<br />

12.5 14.0<br />

14.0 16.0<br />

15.0 17.0<br />

Wired remote<br />

controller*<br />

BD unit<br />

Sim<strong>pl</strong>e central<br />

controller**<br />

Function<br />

controller**<br />

Duo<br />

Cassette Duct Ceiling & Floor<br />

UT24 NPD *2<br />

UT24 NPD *2<br />

UT30 NPD *2<br />

ODU<br />

PMUB11A<br />

Possible combination <strong>of</strong> indoor units<br />

Synchro<br />

Quartet<br />

Note:<br />

* When install ceiling and floor type synchro combinations, You must use wired remote controller "PVRCUSZ0"<br />

* In case <strong>of</strong> cassette or duct type synchro combinations, You can use only one wired remote controller included<br />

in the indoor units.<br />

** When using synchro operation,<br />

- Do not use wireless remote controller.<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central controller and function controller "PQCSB101S0 & PQCSC101S0" only.<br />

General information 55<br />

Trio<br />

ODU<br />

BD<br />

BD BD<br />

IDU IDU IDU IDU IDU IDU IDU IDU IDU<br />

REMO REMO REMO<br />

UB24 NHD *2<br />

UB24 NHD *2<br />

UB30 NGD *2<br />

UV24 NBD *2<br />

UV24 NBD *2<br />

UV30 NBD *2<br />

Cassette Duct Ceiling & Floor Cassette Duct Ceiling & Floor<br />

UT18 NQD *3<br />

UT18 NQD *3<br />

UT18 NQD *3<br />

UB18 NHD *3<br />

UB18 NHD *3<br />

UB18 NHD *3<br />

PVRCUSZO PVRCUSZO<br />

PMUB111A PMUB1111A<br />

PQCSB101S0<br />

PQCSC101S0<br />

UV18 NBD *3<br />

UV18 NBD *3<br />

UV18 NBD *3<br />

UT12 NRD *4<br />

UT12 NRD *4<br />

UT12 NRD *4<br />

ODU<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-


Combination 5CSL0-06B<br />

Non inverter Outdoor Units - 1Ø, 3Ø<br />

[AUUH-D] [UU-D]<br />

• Table <strong>of</strong> combination<br />

LGʼs system consist <strong>of</strong> one outdoor unit which can match with three different indoor units as individual<br />

system.<br />

The indoor units are ceiling cassette, ceiling concealed duct and ceiling & floor, Ceiling suspended, Console<br />

types.<br />

Outdoor unit Indoor unit<br />

1Ø 3Ø Type Model name<br />

AUUH126D[UU12 ULD] -<br />

Ceiling Cassette<br />

Ceiling & Floor<br />

ATNH12GRLED[UT12 NRD]<br />

AVNH12GELAD[UV12 NED]<br />

Ceiling Cassette ATNH18GQLED[UT18 NQD]<br />

AUUH186D[UU18 UED] - Ceiling concealed duct ABNH186HLAD[UB18 NHD]<br />

Ceiling & Floor UVNH186BLAD[UV18 NBD]<br />

Ceiling Cassette ATNH24GPLED[UT24 NPD]<br />

AUUH246D[UU24 UED] - Ceiling concealed duct ABNH246HLAD[UB24 NHD]<br />

Ceiling & Floor UVNH246BLAD[UV24 NBD]<br />

Ceiling Cassette ATNH30GPLED[UT30 NPD]<br />

AUUH306D[UU30 UED] - Ceiling concealed duct ABNH306GLAD[UB30 NGD]<br />

Ceiling & Floor UVNH306BLAD[UV30 NBD]<br />

Ceiling Cassette ATNH36GNLED[UT36 NND]<br />

- AUUH368D[UU37 UED] Ceiling concealed duct ABNH366GLAD[UB36 NGD]<br />

Ceiling suspended UVNH366KLAD[UV36 NKD]<br />

Ceiling Cassette ATNH48GMLED[UT48 NMD]<br />

- AUUH488D[UU48 U3D] Ceiling concealed duct ABNH486RLAD[UB48 NRD]<br />

Ceiling suspended UVNH486LLAD[UV48 NLD]<br />

Ceiling Cassette ATNH60GMLED[UT60 NMD]<br />

- AUUH608D[UU60 U3D] Ceiling concealed duct ABNH606RLAD[UB60 NRD]<br />

Ceiling suspended UVNH606LLAD[UV60 NLD]<br />

56 General information


5CSL0-06B<br />

6.3 Synchro Operation Guide<br />

6.3.1 Piping length guide<br />

Install the branch pipe so that pipe length and difference between high and low will not exceed below SPEC.<br />

h1<br />

L2<br />

L3<br />

L4<br />

L5<br />

Remote<br />

Controller<br />

Main (L1)<br />

Branch<br />

6.3.2 Additional refrigerant charging guide<br />

Indoor Unit Refrigerant Additional charging (kg)<br />

Duo<br />

Trio<br />

Quartet<br />

Model<br />

AUUW42-606(8)D<br />

Refrigerant = (L1-a) x B + (L2 + L3) x A<br />

Refrigerant = (L1-a) x B + (L2 + L3 + L4) x A<br />

Refrigerant = (L1-a) x B + (L2 + L3 + L4 + L5) x A<br />

a<br />

B<br />

7.5 0.04<br />

6.3.3 Electric Wiring method<br />

h2<br />

Pipe Length<br />

Total(L1+L2+L3+L4+L5)<br />

Main Pipe(L1)<br />

Branch Pipe - L2+L3+L4+L5<br />

Each Branch(L2, L3, L4, L5)<br />

In out (h1)<br />

In-In (h2)<br />

L1+L2,L1+L3,L1+L4,L1+L5<br />

L2-L3,L4-L5<br />

S Terminals on the indoor unit 4 1(L) 2(N) 3<br />

CN-REMO<br />

S Terminals on the indoor unit 3<br />

S Terminals on the indoor unit 2<br />

M Terminals on the indoor unit 1<br />

(380V-415V, 3N~)<br />

(220V-240V~)<br />

1(L) 2(N) 3<br />

1(L) 2(N) 3<br />

1(L) 2(N) 3<br />

CN-REMO<br />

CN-REMO<br />

CN-REMO<br />

Terminals on the<br />

Outdoor unit R S T N L N<br />

1(L) 2(N) 3<br />

Remote<br />

Controller<br />

POWER INPUT<br />

POWER INPUT<br />

Pipe Dia.<br />

(mm)<br />

Combination<br />

[Unit : m]<br />

Spec.<br />

Max 80<br />

General information 57<br />

Ø 6.35<br />

Ø 9.52<br />

A<br />

0.03 kg/m<br />

0.04 kg/m<br />

Max 50<br />

Max 40<br />

Max 15<br />

Max 30<br />

Max 1<br />

Max 70<br />

Max 10<br />

Fig.1 Piping length<br />

Fig.2 electric wiring


Combination 5CSL0-06B<br />

6.3.4 Main PCB Appearance<br />

(1) [DIP SW2] for [SETTING No. OF IDU] OR [LONG<br />

PIPE].<br />

1 TO 3 PIN SWITCHES RECOGNIZE IDU NORMAL-<br />

LY BEING UP AND DOWN ONE BY ONE.<br />

(2) [SW01B] for [AUTO-ADDRESSING]<br />

(3) [LED01G/LED02G] for SIGNALS<br />

Table 1. signals<br />

RED LED<br />

ON<br />

ON/OFF<br />

ON/OFF<br />

SLOW<br />

ON/OFF<br />

GREEN LED<br />

ON/OFF<br />

ON<br />

ON/OFF<br />

ON/OFF<br />

* ON / OFF : CONTINUOUS ON AND OFF.<br />

SLOW ON / OFF : AT A PERIOD OF 1.5s<br />

6.3.5 Auto addressing guide<br />

MEANS<br />

UNDERGOING<br />

SUCCEEDED<br />

FAILED<br />

CKECKING<br />

Addressing work assigns address to each indoor unit.<br />

When firstly installing product <strong>of</strong> ro<strong>pl</strong>acing the indoor unit<br />

PCB.<br />

It needs Auto Addressing for Synchro operation<br />

❈ Work procedure<br />

1) DIP SW2 correctly.(Ⓐ)<br />

2) Turn on main power.<br />

3) Press the SW01B for about 3 seconds within 3minutes<br />

After main power on.(Ⓑ)<br />

4) After step 3), the LED01H(green LED) rapidly flickers.When<br />

Addressing work is done, green LED is <strong>of</strong>f,<br />

else LED stops flickering and lights continuously.<br />

5) If you fail to perform the Addressing work, repeat step<br />

2),3).<br />

58 General information<br />

DIP SW2<br />

ON<br />

A<br />

B<br />

LED01H<br />

1 2 3 4 5<br />

SW01B LED01G/02G<br />

Table2.a DIP SW2 Setting<br />

ON<br />

Fig.3 ODU PCB<br />

DIP SW2 Indoor Unit No.<br />

1 2 3 4 5<br />

0 0 0 0 0<br />

ON<br />

1 2 3 4 5<br />

1 0 0 0 0<br />

ON<br />

1 2 3 4 5<br />

1 1 0 0 0<br />

ON<br />

1 2 3 4 5<br />

1 1 1 0 0<br />

ON<br />

1 2 3 4 5<br />

0 0 0 1 0<br />

1(Single)<br />

2(Duo)<br />

3(Trio)<br />

4(Quartet)<br />

Long Pipe


Part 2 Product data<br />

1. Indoor units............................................................................................60<br />

1.1 Ceiling cassette 4-way ..........................................................................................60<br />

1.2 Ceiling & floor........................................................................................................82<br />

1.3 Ceiling suspended ................................................................................................94<br />

1.4 Ceiling concealed duct - High static pressure.....................................................105<br />

1.5 Console(Floor stand) ..........................................................................................125<br />

2. Outdoor unit.........................................................................................133<br />

2.1 DC Inverter Single A (1, 3 phase) ......................................................................133<br />

2.2 DC Inverter Single A-Synchro (1, 3 phase).........................................................216<br />

2.3 Non inverter Single A (1, 3 phase) ......................................................................245<br />

CST 4 - Way 59


List <strong>of</strong> Functions 5CSL0-06B<br />

1. Indoor units<br />

1.1 Ceiling cassette 4-way<br />

1.1.1 List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

ATNH09GRLED<br />

[UT09 NRD]<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

4 4 4<br />

- - -<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

4/5/4 4/5/4 4/5/4<br />

X X X<br />

- - -<br />

O O O<br />

O O O<br />

- - -<br />

PTPKM0 PTPKM0 PTPKM0<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PQRCUSA0<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQWRHSF0 PQWRHSF0 PQWRHSF0<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

60 CST 4 - Way


5CSL0-06B<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

ATNH18GPLED<br />

[UT18 NPD]<br />

ATNH21GNLED<br />

[UT21 NND]<br />

List <strong>of</strong> Functions<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

4 4 4<br />

- - -<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

4/5/4 4/5/4 4/5/4<br />

X X X<br />

- - -<br />

O O O<br />

O O O<br />

- - -<br />

PTPKM0 PTPKM0 PTPKM0<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PQRCUSA0<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQWRHSF0 PQWRHSF0 PQWRHSF0<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

CST 4 - Way 61


List <strong>of</strong> Functions 5CSL0-06B<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

ATNH24GNLED<br />

[UT24 NND]<br />

ATNH30GPLED<br />

[UT30 NPD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

ATNH36GNLED<br />

[UT36 NND]<br />

4 4 4<br />

- - -<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

4/5/4 4/5/4 4/5/4<br />

X X X<br />

- - -<br />

O O O<br />

O O O<br />

- - -<br />

PTPKM0 PTPKM0 PTPKM0<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PQRCUSA0<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQWRHSF0 PQWRHSF0 PQWRHSF0<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

62 CST 4 - Way


5CSL0-06B<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

ATNH42GMLED<br />

[UT42 NMD]<br />

ATNH48GMLED<br />

[UT48 NMD]<br />

List <strong>of</strong> Functions<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

4 4 4<br />

- - -<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

4/5/4 4/5/4 4/5/4<br />

X X X<br />

- - -<br />

O O O<br />

O O O<br />

- - -<br />

PTPKM0 PTPKM0 PTPKM0<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PQRCUSA0<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQWRHSF0 PQWRHSF0 PQWRHSF0<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

CST 4 - Way 63


Specifications 5CSL0-06B<br />

1.1.2 Specifications<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions Body mm<br />

(WxHxD) Decorative Panel mm<br />

Weight Body kg<br />

Air Filter<br />

Decorative Panel kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling Cassette - 4way<br />

Model<br />

Decoration panel<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 ATNH09GRLED<br />

[UT09 NRD]<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

PT-UQC PT-UQC PT-UQC<br />

1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.3 0.3 0.3<br />

BLDC BLDC BLDC<br />

Turbo Turbo Turbo<br />

40*1 40*1 40*1<br />

8.5 / 7.0 / 6.0 9.5 / 8.0 / 7.0 13 / 12 / 11<br />

- - -<br />

Direct Drive Direct Drive Direct Drive<br />

2R x 8C x 18FPI 2R x 8C x 18FPI 2R x 10C x 18FPI<br />

570*214*570 570*214*570 570*256*570<br />

700*30*700 700*30*700 700*30*700<br />

14 14 15<br />

3 3 3<br />

Long life filter Long life filter Long life filter<br />

36/33/30 38/35/32 41/39/36<br />

6.35 6.35 6.35<br />

9.52 9.52 12.7<br />

32 / 25 32 / 25 32 / 25<br />

1.4 1.7 2.4<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor Thermistor<br />

R410A R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Note :<br />

Conversion Formula<br />

1. Capacities are based on the following conditions:<br />

kcal/h = kW × 859.8<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

CFM = CMM × 35.3<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

64 CST 4 - Way


5CSL0-06B<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions Body mm<br />

(WxHxD) Decorative Panel mm<br />

Weight Body kg<br />

Air Filter<br />

Decorative Panel kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling Cassette - 4way<br />

Model<br />

Decoration panel<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 *ATNH18GPLED<br />

[UT18 NPD]<br />

*ATNH21GNLED<br />

[UT21 NND]<br />

Specifications<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

PT-UMC PT-UMC PT-UMC<br />

1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.60 0.60 0.60<br />

BLDC BLDC BLDC<br />

Turbo Fan Turbo Fan Turbo Fan<br />

124*1 124*1 60*1<br />

17 / 15 / 13 19 / 16 / 14 17 / 15 / 13<br />

- - -<br />

Direct Drive Direct Drive Direct Drive<br />

2R x 8C x 19 2R x 10C x 19 2R x 8C x 19<br />

840*204*840 840*246*840 840*204*840<br />

950*25*950 950*25*950 950*25*950<br />

21 23.5 21<br />

5 5 5<br />

Long life filter Long life filter Long life filter<br />

39 / 37 / 34 38 / 36 / 34 39 / 37 / 34<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

32 / 25 32 / 25 32 / 25<br />

2.1 2.7 2.1<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor Thermistor<br />

R410A R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Note :<br />

Conversion Formula<br />

1. Capacities are based on the following conditions:<br />

kcal/h = kW × 859.8<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

CFM = CMM × 35.3<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

4. "*" means high efficient indoor unit<br />

CST 4 - Way 65


Specifications 5CSL0-06B<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions Body mm<br />

(WxHxD) Decorative Panel mm<br />

Weight Body kg<br />

Air Filter<br />

Decorative Panel kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling Cassette - 4way<br />

Model<br />

Decoration panel<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 *ATNH24GNLED<br />

[UT24 NND]<br />

ATNH30GPLED<br />

[UT30 NPD]<br />

ATNH36GNLED<br />

[UT36 NND]<br />

PT-UMC PT-UMC PT-UMC<br />

1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.60 0.60 0.60<br />

BLDC BLDC BLDC<br />

Turbo Fan Turbo Fan Turbo Fan<br />

124*1 60*1 124*1<br />

21 / 18 / 16 19 / 17 / 15 24 / 22 / 19<br />

- - -<br />

Direct Drive Direct Drive Direct Drive<br />

2R x 10C x19 2R x 8C x19 2R x 10C x 19<br />

840*246*840 840*204*840 840*246*840<br />

950*25*950 950*25*950 950*25*950<br />

23 21 23.5<br />

5 5 5<br />

Long life filter Long life filter Long life filter<br />

40 / 38 / 36 43 / 40 / 37 43 / 40 / 37<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

32 / 25 32 / 25 32 / 25<br />

2.7 2.5 2.7<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor Thermistor<br />

R410A R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Note :<br />

Conversion Formula<br />

1. Capacities are based on the following conditions:<br />

kcal/h = kW × 859.8<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

CFM = CMM × 35.3<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

4. "*" means high efficient indoor unit<br />

66 CST 4 - Way


5CSL0-06B<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions Body mm<br />

(WxHxD) Decorative Panel mm<br />

Weight Body kg<br />

Air Filter<br />

Decorative Panel kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling Cassette - 4way<br />

Model<br />

Decoration panel<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 ATNH42GMLED<br />

[UT42 NMD]<br />

ATNH48GMLED<br />

[UT48 NMD]<br />

Specifications<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

PT-UMC PT-UMC PT-UMC<br />

1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.72 0.72 0.72<br />

BLDC BLDC BLDC<br />

Turbo Fan Turbo Fan Turbo Fan<br />

124*1 124*1 124*1<br />

30 / 28 / 26 34 / 32 / 30 34 / 32 / 30<br />

- - -<br />

Direct Drive Direct Drive Direct Drive<br />

2R x 12C x 21 2R x12C x 21 2R x 12C x 21<br />

840*288*840 840*288*840 840*288*840<br />

950*25*950 950*25*950 950*25*950<br />

26 26 26<br />

5 5 5<br />

Long life filter Long life filter Long life filter<br />

46 / 44 / 40 49 / 47 / 43 49 / 47 / 43<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

32 / 25 32 / 25 32 / 25<br />

3.6 4.4 5.5<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor Thermistor<br />

R410A R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Note :<br />

Conversion Formula<br />

1. Capacities are based on the following conditions:<br />

kcal/h = kW × 859.8<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

CFM = CMM × 35.3<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

CST 4 - Way 67


Dimensions 5CSL0-06B<br />

1.1.3 Dimensions<br />

ATNH09GRLED[UT09 NRD]<br />

ATNH12GRLED[UT12 NRD]<br />

8<br />

Part Name Remark<br />

Decoration panel<br />

PT-UQC<br />

air suction grille<br />

150<br />

86<br />

Ø70<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Drain pipe connection<br />

517<br />

378.6<br />

4-R20<br />

172<br />

3<br />

Ø70<br />

Power sup<strong>pl</strong>y connection<br />

Fresh air connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

1<br />

570<br />

517<br />

523<br />

ATNH12GRLED[UT12 NRD]<br />

1 / 220-240 / 50<br />

ATNH09GRLED[UT09 NRD]<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

Model name<br />

378.6<br />

380(Air outlet hole)<br />

700<br />

6.35<br />

9.52<br />

32/25<br />

6.35<br />

9.52<br />

32/25<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

68 CST 4 - Way<br />

2<br />

461<br />

570<br />

5<br />

4<br />

380(Air outlet hole)<br />

473<br />

700<br />

55<br />

22.5<br />

214<br />

53<br />

84.5 59.5<br />

34.5<br />

142.5<br />

30 19<br />

570<br />

6<br />

CHASSIS CODE: TR<br />

2.5/3.5 kW


5CSL0-06B<br />

ATNH18GQLED[UT18 NQD]<br />

8<br />

150<br />

86<br />

Ø70<br />

Part Name Remark<br />

Decoration panel<br />

PT-UQC<br />

air suction grille<br />

517<br />

378.6<br />

4-R20<br />

172<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Drain pipe connection<br />

3<br />

1<br />

570<br />

517<br />

523<br />

Ø70<br />

Power sup<strong>pl</strong>y connection<br />

Fresh air connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

378.6<br />

380(Air outlet hole)<br />

700<br />

2<br />

ATNH18GQLED[UT18 NQD]<br />

1/ 220-240 / 50<br />

Model name<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

6.35<br />

12.7<br />

32/25<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

Dimensions<br />

CST 4 - Way 69<br />

461<br />

570<br />

5<br />

4<br />

380(Air outlet hole)<br />

473<br />

700<br />

55<br />

22.5<br />

256<br />

76 94<br />

95.5<br />

125 59.5<br />

30 19<br />

142.5<br />

570<br />

6<br />

CHASSIS CODE: TQ<br />

5.0 kW


Dimensions 5CSL0-06B<br />

*ATNH18GPLED[UT18 NPD]<br />

ATNH24GPLED[UT24 NPD]<br />

ATNH30GPLED[UT30 NPD]<br />

8<br />

Ø70<br />

61.5<br />

66<br />

618<br />

Part Name Remark<br />

Decoration panel<br />

PT-UMC<br />

air suction grille<br />

787<br />

4-R20<br />

292<br />

Air discharge grille<br />

Gas pipe connection<br />

1<br />

Liquid pipe connection<br />

Drain pipe connection<br />

684<br />

840<br />

671<br />

500(Air outlet hole)<br />

618<br />

950<br />

2<br />

Ø70<br />

Power sup<strong>pl</strong>y connection<br />

Fresh air connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

ATNH30GPLED<br />

[UT30 NPD]<br />

1 / 200-240 / 50<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

*ATNH18GPLED<br />

[UT18 NPD]<br />

3<br />

70 CST 4 - Way<br />

Model name<br />

1 / 200-240 / 50<br />

1 / 200-240 / 50<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

787<br />

840<br />

500(Air outlet hole)<br />

734<br />

950<br />

54<br />

9.52<br />

15.88<br />

32 / 25<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

32 / 25<br />

9.52<br />

15.88<br />

32 / 25<br />

6<br />

4 5<br />

204<br />

40<br />

1. Unit should be installed in com<strong>pl</strong>ance with the installation manual in the<br />

product box.<br />

2. Unit shall be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. The unit is powered from the outdoor unit. So power cable should be<br />

connected with the outdoor unit.<br />

* High efficiency indoor uni.<br />

25<br />

99<br />

82<br />

60<br />

65<br />

60 80<br />

840<br />

108<br />

7<br />

TP<br />

6.0/7.0 kW


5CSL0-06B<br />

*ATNH21GNLED[UT21 NND]<br />

*ATNH24GNLED[UT24 NND]<br />

ATNH36GNLED[UT36 NND]<br />

8<br />

Ø70<br />

79.5<br />

65.5<br />

Part Name Remark<br />

Decoration panel<br />

PT-UMC<br />

air suction grille<br />

618<br />

787<br />

292 No.<br />

4-R20<br />

1<br />

2<br />

Air discharge grille<br />

Gas pipe connection<br />

3<br />

4<br />

1<br />

Liquid pipe connection<br />

Drain pipe connection<br />

5<br />

6<br />

Ø70<br />

Power sup<strong>pl</strong>y connection<br />

Fresh air connection<br />

7<br />

8<br />

500(Air outlet hole)<br />

618<br />

950<br />

2<br />

684<br />

840<br />

671<br />

ATNH36GNLED<br />

[UT36 NND]<br />

1 / 200-240 / 50<br />

ATNH24GNLED<br />

[UT24 NND]<br />

ATNH21GNLED<br />

[UT21 NND]<br />

Model name<br />

3<br />

Dimensions<br />

CST 4 - Way 71<br />

1 / 200-240 / 50<br />

1 / 200-240 / 50<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

787<br />

840<br />

500(Air outlet hole)<br />

734<br />

950<br />

54<br />

9.52<br />

15.88<br />

32 / 25<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

32 / 25<br />

9.52<br />

15.88<br />

32 / 25<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

6<br />

4 5<br />

25<br />

246<br />

60<br />

82<br />

99<br />

65 40<br />

1. Unit should be installed in com<strong>pl</strong>ance with the installation manual in the<br />

product box.<br />

2. Unit shall be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. The unit is powered from the outdoor unit. So power cable should be<br />

connected with the outdoor unit.<br />

* High efficiency indoor uni.<br />

80<br />

840<br />

108 60<br />

7<br />

6.0/7.1/10.0 kW


Dimensions 5CSL0-06B<br />

ATNH42GMLED[UT42 NMD]<br />

ATNH48GMLED[UT48 NMD]<br />

ATNH60GMLED[UT60 NMD]<br />

8<br />

Ø70<br />

109<br />

66<br />

Part Name Remark<br />

Decoration panel<br />

PT-UMC<br />

air suction grille<br />

787<br />

618<br />

4-R20<br />

292<br />

Air discharge grille<br />

Gas pipe connection<br />

1<br />

Liquid pipe connection<br />

Drain pipe connection<br />

840<br />

684<br />

500(Air outlet hole)<br />

618<br />

950<br />

2<br />

671<br />

Ø70<br />

Power sup<strong>pl</strong>y connection<br />

Fresh air connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

ATNH48GMLED<br />

UT48 NMD]<br />

ATNH42GMLED<br />

[UT42 NMD]<br />

Model name<br />

1 / 220-240 / 50<br />

1 / 220-240 / 50<br />

1 / 220-240 / 50<br />

78<br />

3<br />

9.52<br />

15.88<br />

32 / 25<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

32 / 25<br />

9.52<br />

15.88<br />

32 / 25<br />

72 CST 4 - Way<br />

REFER TO EACH<br />

787<br />

840<br />

500(Air outlet hole)<br />

734<br />

950<br />

54<br />

4 5<br />

6<br />

40<br />

25<br />

135<br />

183<br />

288<br />

70<br />

148<br />

110 60 80<br />

840<br />

7<br />

TM<br />

12.5/14.0/15.0 kW


5CSL0-06B<br />

1.1.4 Piping diagrams<br />

Heating<br />

Cooling<br />

Th2<br />

Heat exchanger<br />

Turbo fan<br />

Th1 : Thermistor for suction air temp.<br />

Th2 : Thermistor for liquid line temp.<br />

Th3 : Thermistor for gas line temp.<br />

■ Refrigerant pipe connection port diameters<br />

Piping diagrams<br />

CST 4 - Way 73<br />

Th3<br />

Th1<br />

Gas pipe connection port<br />

(flare connection)<br />

Liquid pipe connection port<br />

(flare connection)<br />

Model Gas Liquid<br />

ATNH09GRLED[UT09 NRD]<br />

ATNH12GRLED[UT12 NRD]<br />

Ø9.52 Ø6.35<br />

ATNH18GQLED[UT18 NQD] Ø12.7 Ø6.35<br />

ATNH18GPLED[UT18 NPD]<br />

ATNH21GNLED[UT21 NND]<br />

ATNH24GNLED[UT24 NND]<br />

ATNH24GPLED[UT24 NPD]<br />

ATNH30GPLED[UT30 NPD] Ø15.88 Ø9.52<br />

ATNH36GNLED[UT36 NND]<br />

ATNH42GMLED[UT42 NMD]<br />

ATNH48GMLED[UT48 NMD]<br />

ATNH60GMLED[UT60 NMD]<br />

[Unit:mm]


Wiring diagrams 5CSL0-06B<br />

1.1.5 Wiring diagrams<br />

1) Wiring diagrams<br />

CONNECTOR NUMBER LOCATION POINT FUNCTION<br />

2) PCB<br />

CN-POWER AC POWER SUPPLY AC POWER LINE INPUT FOR INDOOR CONTROLLER<br />

CN-MOTOR1 FAN MOTOR OUTPUT MOTOR OUTPUT OF BLDC<br />

CN-D/PUMP DRAIN PUMP OUTPUT AC OUTPUT FOR DRAIN PUMP<br />

CN-DISP DISPLAY DISPLAY OF INDOOR STATUS<br />

CN-VANE1 / VANE2 STEP MOTOR STEP MOTOR OUTPUT<br />

CN-FLOAT FLOAT SWITCH INPUT FLOAT SWITCH SENSING<br />

CN-PIPE/IN SUCTION PIPE SENSOR PIPE IN THERMISTOR<br />

CN-PIPE/OUT DISCHARGE PIPE SENSOR PIPE OUT THERMISTOR<br />

CN-ROOM ROOM SENSOR ROOM AIR THERMISTOR<br />

CN-REMO REMOTE CONTROLLER REMOTE CONTROL LINE<br />

CN-CC DRY CONTACT DRY CONTACT LINE<br />

CN_D/PUMP<br />

CN_POWER<br />

CN_MOTOR<br />

CN_FLOAT CN_DISPLAY<br />

CN_VANE2 CN_VANE1<br />

CN_OPTION<br />

CN_REMO<br />

CN_ROOM<br />

CN_PIPE/IN<br />

CN_PIPE/OUT<br />

74 CST 4 - Way<br />

SW01


5CSL0-06B<br />

Air flow and temperature distributions (reference data)<br />

1.1.6 Air flow and temperature distributions (reference data)<br />

Model : 2.5kW/3.5kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

Temperature [°C]<br />

0.5<br />

1.0<br />

1.5<br />

2.0<br />

Cooling Heating<br />

2.7m<br />

0m<br />

2.5m 1.5m 0m<br />

1.5m 2.5m<br />

24<br />

22<br />

20<br />

18<br />

2.0<br />

1.5<br />

1.0<br />

0.5<br />

2m<br />

1m<br />

2.7m<br />

0m<br />

2.5m 1.5m 0m<br />

1.5m 2.5m<br />

Model : 5.0kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

24<br />

0.5<br />

1.0<br />

1.5<br />

22<br />

2.0<br />

18<br />

20<br />

18<br />

2.0<br />

18<br />

20<br />

20<br />

1.5<br />

4m 3m 2m 1m 0m 1m 2m<br />

22<br />

1.0<br />

0.5<br />

22<br />

24<br />

24<br />

3m<br />

3m<br />

2m<br />

1m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

Temperature [°C]<br />

CST 4 - Way 75<br />

0.5<br />

2.0<br />

1.5<br />

1.0<br />

2.0<br />

1.5<br />

2.7m<br />

0m<br />

2.5m 1.5m 0m<br />

1.5m 2.5m<br />

24<br />

21<br />

27<br />

30<br />

33<br />

1.0<br />

0.5<br />

2m<br />

1m<br />

2.7m<br />

0m<br />

2.5m 1.5m 0m<br />

1.5m 2.5m<br />

Cooling Heating<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

21<br />

24<br />

0.5<br />

27<br />

1.0<br />

1.5<br />

2.0<br />

4m 3m 2m 1m 0m 1m 2m<br />

30<br />

33<br />

2.0<br />

33<br />

33<br />

1.5<br />

30<br />

30<br />

1.0<br />

0.5<br />

27<br />

27<br />

24<br />

24<br />

21<br />

3m<br />

21<br />

3m<br />

2m<br />

1m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m


Air flow and temperature distributions (reference data)<br />

Model : 6.0kW/7.1kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

24<br />

1.0<br />

4m 3m 2m 1m 0m 1m 2m<br />

Model : 8.0kW<br />

23<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

1.0<br />

Temperature [°C]<br />

Cooling Heating<br />

2.0<br />

2.0<br />

1.5 1.5<br />

1.5<br />

18<br />

20<br />

22<br />

18<br />

20<br />

22<br />

1.0<br />

23<br />

24<br />

3m<br />

3m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

33 33<br />

30 30<br />

4m 3m 2m 1m 0m 1m 2m<br />

Cooling Heating<br />

3.0<br />

2.5<br />

3.0<br />

2.5<br />

2.0<br />

2.0<br />

1.5<br />

1.0<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

23<br />

22<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

2.7m<br />

2m<br />

1m<br />

5CSL0-06B<br />

76 CST 4 - Way<br />

22<br />

24<br />

0.5<br />

1.0<br />

2.0 2.0<br />

18 18<br />

2.7m<br />

33 33<br />

20<br />

20<br />

2m<br />

22<br />

23<br />

3m<br />

3m<br />

0m<br />

4m 5m<br />

1m<br />

0m<br />

4m 5m<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

Temperature [°C]<br />

24<br />

22<br />

27<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.0<br />

30 30<br />

27 27<br />

1.0<br />

0.5<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

27<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.0<br />

24<br />

3m<br />

3m<br />

3m<br />

3m<br />

24<br />

22<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

22<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m 5m


5CSL0-06B Air flow and temperature distributions (reference data)<br />

Model : 10.0kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

Model : 12.5kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

2.0<br />

1.0<br />

Temperature [°C]<br />

3.0<br />

4.0<br />

Cooling Heating<br />

Cooling Heating<br />

4.0<br />

3.0<br />

2.0<br />

1.0<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

24<br />

1.0<br />

Temperature [°C]<br />

22<br />

1.5<br />

20<br />

3.0<br />

2.5<br />

3.0<br />

2.5<br />

2.0<br />

2.0<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

18<br />

18<br />

1.5<br />

20<br />

1.0<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

23<br />

22<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

22<br />

3m<br />

3m<br />

24<br />

2.7m<br />

2m<br />

1m<br />

18 18<br />

2.7m<br />

33 33<br />

20<br />

20<br />

2m<br />

22<br />

23<br />

3m<br />

3m<br />

0m<br />

4m 5m<br />

1m<br />

0m<br />

4m 5m<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

Temperature [°C]<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

CST 4 - Way 77<br />

24<br />

22<br />

24<br />

22<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.0<br />

1.0<br />

4.0<br />

33 33<br />

30 30<br />

27 27<br />

4.0<br />

3.0 3.0<br />

2.0<br />

30 30<br />

27 27<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

2.0<br />

1.0<br />

1.0<br />

3m<br />

3m<br />

3m<br />

22<br />

3m<br />

24<br />

24<br />

22<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m


Air flow and temperature distributions (reference data)<br />

Model : 14.0kW/15.0kW<br />

Discharge angle: 40°<br />

Air velocity [m/s]<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

23.9<br />

22.4<br />

0.5<br />

1<br />

21.0<br />

1.5<br />

20.3<br />

23.9<br />

2.5<br />

2<br />

19.2<br />

18.2<br />

Cooling Heating<br />

2.5<br />

2<br />

18.2<br />

19.2<br />

1.5<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

20.3<br />

23.9<br />

1<br />

3m<br />

21.0<br />

3m<br />

0.5<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

22.4<br />

23.9<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

Discharge angle: 50°<br />

Air velocity [m/s]<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

Temperature [°C]<br />

5m 4m 3m 2m 1m 0m 1m 2m<br />

5CSL0-06B<br />

78 CST 4 - Way<br />

25.3<br />

28.6<br />

27.4<br />

0.5<br />

30.8<br />

1<br />

31.4<br />

2<br />

1.5<br />

0.5<br />

32.8<br />

2.5<br />

34.3<br />

2.5<br />

2<br />

1.5<br />

0.5<br />

34.3<br />

32.8<br />

1<br />

0.5<br />

3m<br />

31.4 30.8<br />

3m<br />

28.6<br />

27.4<br />

3.2m<br />

2m<br />

1m<br />

0m<br />

4m 5m<br />

3.2m<br />

2m<br />

25.3<br />

1m<br />

0m<br />

4m 5m


5CSL0-06B Sound levels<br />

1.1.7 Sound levels<br />

Overall<br />

1.5m<br />

Sound pressure level<br />

Sound Pressure Level (dB re 20uPa)<br />

Octave Band Sound Pressure Level (dB re 20 Pa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

s<br />

20<br />

NC-25<br />

Approximate<br />

Hearing<br />

NC-20<br />

Threshold<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Ceiling<br />

ATNH09GRLED [UT09 NRD]<br />

ATNH12GRLED [UT12 NRD]<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20uPa)<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Notes:<br />

- Sound measured at 1.5m below<br />

the center <strong>of</strong> the unit.<br />

- Data is valid at free field condition<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Octave Band Center Frequency (Hz)<br />

CST 4 - Way 79<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

ATNH30GPLED [UT30 NPD] *ATNH21GNLED [UT21 NND]<br />

* High Efficiency Indoor units<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

ATNH18GQLED [UT18 NQD] ATNH24GPLED [UT24 NPD]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20uPa)<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

Approximate<br />

Hearing<br />

NC-20<br />

Threshold<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

*ATNH18GPLED [UT18 NPD]<br />

*ATNH24GNLED [UT24 NND]<br />

ATNH36GNLED [UT36 NND]<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

20<br />

NC-25<br />

Approximate<br />

Hearing<br />

NC-20<br />

Threshold<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)


Sound levels<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

ATNH42GMLED [UT42 NMD] ATNH48GMLED[UT48 NMD]<br />

ATNH60GMLED[UT60 NMD]<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

20<br />

NC-25<br />

Approximate<br />

Hearing<br />

NC-20<br />

Threshold<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

5CSL0-06B<br />

80 CST 4 - Way<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


5CSL0-06B<br />

1.1.8 Controller<br />

■ Wired remote controller<br />

1. Operation indication screen<br />

2. Set temperature button<br />

3. Wireless remote controller Receiver<br />

• Some products don't receive the wireless signals.<br />

4. Ventilation button<br />

5. Operation mode selection button<br />

6. Subfunction button<br />

7. Function setting button<br />

1<br />

2<br />

3<br />

4 10<br />

5<br />

6<br />

7<br />

8<br />

Controller<br />

CST 4 - Way 81<br />

9<br />

11<br />

12<br />

13<br />

14<br />

15<br />

8. Exit button<br />

9. On/ Off button<br />

10. Room temperature button<br />

11. Fan speed button<br />

12. Air flow button<br />

13. Reservation/ Time setting button<br />

14. Setting/ Cancel button<br />

15. Up, Down, Left, Right button<br />

Note<br />

❈ Dis<strong>pl</strong>ay temperature can be different from actual room temperature if the remote controller is installed at the <strong>pl</strong>ace where<br />

sun-rays are falling directly or the <strong>pl</strong>ace nearby heat source.<br />

❈ The actual product can be different from above contents depending upon model type.


List <strong>of</strong> functions 5CSL0-06B<br />

1.2 Ceiling and floor<br />

1.2.1 List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Deluxe wired remote controller<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

AVNH09GELAD<br />

AVNH12GELAD<br />

UVNH186BLAD<br />

[UV09 NED]<br />

[UV12 NED]<br />

[UV18 NBD]<br />

1 1 1<br />

Manual Manual Manual<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

3 / 4 / 3 3 / 4 / 3 3 / 4 / 3<br />

X X X<br />

O O O<br />

O O O<br />

- - -<br />

X X X<br />

X X X<br />

O O O<br />

- - -<br />

- - -<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

- - -<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PVRCUSZ0<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PVRCUSZ0<br />

O O O<br />

O O O<br />

PQRCUSA0 PQRCUSA0 PVRCUSZ0<br />

PQRCUSA0 PQRCUSA0 PVRCUSZ0<br />

PQRCUSA0 PQRCUSA0 PVRCUSZ0<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

O O O<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

82 Ceiling & Floor


5CSL0-06B<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Deluxe wired remote controller<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

UVNH246BLAD<br />

[UV24 NBD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

UVNH306BLAD<br />

[UV30 NBD]<br />

1 1<br />

Manual Manual<br />

Auto Auto<br />

X X<br />

O O<br />

3 / 4 / 3 3 / 4 / 3<br />

X X<br />

O O<br />

O O<br />

- -<br />

X X<br />

X X<br />

O O<br />

- -<br />

- -<br />

- -<br />

PVRCUSZ0 PVRCUSZ0<br />

O O<br />

O O<br />

O O<br />

O O<br />

X X<br />

- -<br />

O O<br />

PVRCUSZ0 PVRCUSZ0<br />

O O<br />

PVRCUSZ0 PVRCUSZ0<br />

O O<br />

O O<br />

PVRCUSZ0 PVRCUSZ0<br />

PVRCUSZ0 PVRCUSZ0<br />

PVRCUSZ0 PVRCUSZ0<br />

X X<br />

X X<br />

X X<br />

X X<br />

O O<br />

X X<br />

PQDSB PQDSB<br />

O O<br />

X X<br />

PMNFP14A0 PMNFP14A0<br />

X X<br />

X X<br />

PQRSTA0 PQRSTA0<br />

List <strong>of</strong> functions<br />

Ceiling & Floor 83


Specifications 5CSL0-06B<br />

1.2.2 Specifications<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions (WxHxD) Body mm<br />

Weight Body kg<br />

Air Filter<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling & Floor<br />

Model<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 AVNH09GELAD<br />

[UV09 NED]<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

AVNH12GELAD<br />

[UV12 NED]<br />

UVNH186BLAD<br />

[UV18 NBD]<br />

1 / 220-240 / 50 1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

BLDC BLDC Induction<br />

Cross Flow Fan Cross Flow Fan Cross Flow Fan<br />

20.0*1 20.0*1 30.0*1<br />

7.6 / 6.9 / 6.2 9.2 / 7.6 / 6.2 13.5 / 12 / 11<br />

- - 1.5/370<br />

Direct Drive Direct Drive Direct Drive<br />

2R x 12C x 20 2R x 12C x 20 2R x 12C x 18<br />

900*200*490 900*200*490 1,200*205*615<br />

13.7 13.7 30.0<br />

Long life filter Long life filter Long life filter<br />

40 / 36 / 31 40 / 36 / 31 43 / 40 / 37<br />

6.35 6.35 6.35<br />

9.52 9.52 12.7<br />

20/16 20/16 20/16<br />

0.93 1.3 1.54<br />

Thermistor<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

84 Ceiling & Floor


5CSL0-06B<br />

Indoor unit type Ceilling & Floor<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor<br />

Drive<br />

μF/Vac<br />

Coil Row x Column x FPI mm<br />

Dimensions (WxHxD) Body mm<br />

Weight<br />

Air Filter<br />

Body kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Connectable outdoor unit<br />

l/h<br />

Power and transmission interunit cable No.x mm2 Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Specifications<br />

Model UVNH246BLAD [UV24 NBD] UVNH306BLAD [UV30 NBD]<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

Induction Induction<br />

Cross Flow Fan Cross Flow Fan<br />

35*1 42.5*1<br />

15 / 13.5 / 12 18 / 16 / 14<br />

1.5/370 1.5/370<br />

Direct Drive Direct Drive<br />

2R x 12C x 20 2R x 12C x 20<br />

1,200*205*615 1,200*205*615<br />

30 30<br />

Long life filter Long life filter<br />

45 / 42 / 39 45 / 42 / 39<br />

9.52 9.52<br />

15.88 15.88<br />

20/16 20/16<br />

3.2 3.5<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Ceiling & Floor 85


Dimensions 5CSL0-06B<br />

1.2.3 Dimensions<br />

AVNH09GELAD[UV09 NED]<br />

AVNH12GELAD[UV12 NED]<br />

1<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

86 Ceiling & Floor<br />

AVNH12GELAD[UV12 NED]<br />

1 / 220-240 / 50<br />

AVNH09GELAD[UV09 NED]<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

6.35<br />

9.52<br />

20 / 16<br />

6.35<br />

9.52<br />

20 / 16<br />

2.5/3.2 kW


5CSL0-06B<br />

UVNH186BLAD[UV18 NBD]<br />

UVNH246BLAD[UV24 NBD]<br />

UVNH306BLAD[UV30 NBD]<br />

1<br />

UVNH306BLAD<br />

[UV30 NBD]<br />

1 / 220-240 / 50<br />

UVNH246BLAD<br />

[UV24 NBD]<br />

UVNH186BLAD<br />

[UV18 NBD]<br />

Model name<br />

Dimensions<br />

Ceiling & Floor 87<br />

1 / 220-240 / 50<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

20/16<br />

9.52<br />

15.88<br />

20/16<br />

6.35<br />

12.7<br />

20/16<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

5<br />

5.0/7.1/8.0 kW


Piping diagrams 5CSL0-06B<br />

1.2.4 Piping diagrams<br />

Heating<br />

Cooling<br />

Th2<br />

Heat exchanger<br />

C.F.F<br />

Th1 : Thermistor for suction air temp.<br />

Th2 : Thermistor for liquid line temp.<br />

Th3 : Thermistor for gas line temp.<br />

Th3<br />

[Unit:mm]<br />

88 Ceiling & Floor<br />

Th1<br />

Gas pipe connection port<br />

(flare connection)<br />

Liquid pipe connection port<br />

(flare connection)<br />

Model Gas Liquid<br />

AVNH09GELAD[UV09 NED]<br />

AVNH12GELAD[UV12 NED]<br />

Ø9.52 Ø6.35<br />

UVNH186BLAD[UV18 NBD] Ø12.7 Ø6.35<br />

UVNH246BLAD[UV24 NBD]<br />

UVNH306BLAD[UV30 NBD]<br />

Ø15.88 Ø9.52


5CSL0-06B<br />

1.2.5 Wiring diagrams<br />

1) Wiring diagrams<br />

Models : AVNH09GELAD[UV09 NED], AVNH12GELAD[UV12 NED]<br />

Wiring diagrams<br />

Models : UVNH186BLAD[UV18 NBD], UVNH246BLAD [UV24 NBD], UVNH306BLAD [UV30 NBD]<br />

Connector Number Location Connector Number Location<br />

CN-POWER AC power sup<strong>pl</strong>y CN-TH2 Discharge pipe sensor<br />

CN-MOTOR BLDC fan motor output CN-TH1 Pipe and room sensor<br />

CN-DPUMP Drain pump output CN-HVB Air cleaner<br />

CN-AC/DC AC/DC connector CN-DOOR Step motor<br />

CN-DISPLAY Dis<strong>pl</strong>ay CN-UD1 Step motor<br />

CN-FLOAT Float switch input CN-CC Central control<br />

Ceiling & Floor 89


Wiring diagrams<br />

2) PCB<br />

CN_ CENTRAL<br />

CONTROL<br />

CN_ WRITE<br />

CN_ DISPLAY<br />

CN_ OPTION<br />

CN-POWER<br />

CN_ REMO<br />

CN_ PIPE/OUT<br />

SW01<br />

CN_ PIPE/IN CN_ ROOM<br />

CN_ vain 1<br />

1<br />

CN_ vain 2<br />

2<br />

CN_ DOOR CN_ MOTOR1<br />

CN_ MOTOR2<br />

<br />

CN_ POWER<br />

CN-MOTOR CN-DISP CN-REMO<br />

CN-FLOAT<br />

CN-PIPE1<br />

CN-ROOM<br />

5CSL0-06B<br />

CVT 1:Communication 2:Cycle 3:Group control 4:Dry Contact 5:Install 6:Heater link 7:Ventilator link 8:Extra<br />

Off (Factory Set) On H/P Master Manual Ceiling Off Off -<br />

On Off C/O Slave Auto Bottom On On -<br />

<br />

CN-CC<br />

CN-PIPE2<br />

90 Ceiling & Floor


5CSL0-06B<br />

Air flow and temperature distributions (reference data)<br />

1.2.6 Air flow and temperature distributions (reference data)<br />

Models : 5.0 kW - installation on ceilling<br />

Cooling Heating<br />

Discharge angle:45° Discharge angle:50°<br />

8m<br />

8m<br />

8m<br />

8m<br />

Air velocity [m/s]<br />

Air velocity [m/s]<br />

7m<br />

6m<br />

Temperature [˚C]<br />

7m<br />

7m<br />

6m<br />

6m<br />

Temperature [˚C]<br />

7m<br />

6m<br />

5m<br />

5m<br />

5m<br />

5m<br />

24<br />

24<br />

4m<br />

4m<br />

0.5<br />

4m<br />

4m<br />

0.5<br />

3m<br />

3m<br />

1.0<br />

3m<br />

22<br />

3m<br />

Models : 5.0 kW - installation on floor or wall<br />

2m<br />

2m<br />

1.5<br />

2m<br />

2m<br />

1.0<br />

22<br />

1.5<br />

2.0<br />

1m<br />

1m<br />

2.0<br />

1m<br />

18<br />

20<br />

1m<br />

Cooling Heating<br />

Discharge angle:45° Discharge angle:50°<br />

18<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

Air velocity [m/s]<br />

Ceiling & Floor 91<br />

8m<br />

8m<br />

8m<br />

8m<br />

Air velocity [m/s]<br />

7m<br />

6m<br />

Temperature [˚C]<br />

7m<br />

7m<br />

6m<br />

6m<br />

Temperature [˚C]<br />

21<br />

7m<br />

6m<br />

5m<br />

5m<br />

5m<br />

5m<br />

24<br />

4m<br />

4m<br />

4m<br />

4m<br />

24<br />

0.5<br />

3m<br />

0.5<br />

3m<br />

3m<br />

3m<br />

27<br />

2m<br />

2m<br />

2m<br />

2m<br />

1.0<br />

27<br />

1.0<br />

1m<br />

1m<br />

1m<br />

30<br />

1.5<br />

33<br />

2.0<br />

1.5<br />

1m<br />

2.0<br />

33<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m


Sound levels<br />

1.2.7 Sound levels<br />

Overall<br />

Sound Pressure Level (dB re 20 Pa )<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

Microphone<br />

1m<br />

1m<br />

20<br />

NC-25<br />

NC-20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Notes:<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

Sound pressure level<br />

AVNH09GELAD[UV09 NED]<br />

AVNH12GELAD[UV12 NED] UVNH186BLAD [UV18 NBD] UVNH246BLAD [UV24 NBD]<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

UVNH306BLAD [UV30 NBD]<br />

Octave Band Center Frequency (Hz)<br />

5CSL0-06B<br />

92 Ceiling & Floor<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

20<br />

NC-25<br />

NC-20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000


5CSL0-06B Controller<br />

1.2.8 Controller<br />

■ Wireless remote controller<br />

The remote controller transmits the signals to the system.<br />

CANCEL<br />

ON OFF SET<br />

AUTO CLEAN<br />

Cooling operation<br />

Auto operation<br />

Healthy dehumidification operation<br />

Heating operation<br />

Signal transmitter<br />

5 1<br />

6<br />

3<br />

4<br />

2<br />

7<br />

11<br />

8<br />

13<br />

14<br />

Operation mode<br />

10<br />

9<br />

12<br />

15<br />

Flip-up door<br />

(opened)<br />

• Cooling model( ), Heat pump model( )<br />

1. Start/Stop btton<br />

Operation starts when this button is pressed<br />

and stops when the button is pressed again.<br />

2. Operation mode selection button<br />

Used to select the operation mode.<br />

3. Room temperature setting buttons<br />

Used to select the room temperature.<br />

4. Indoor fanspeed selector<br />

Used to select fan speed in four steps<br />

low, medium, high and CHAOS.<br />

5. Jet cool<br />

Used to start or stop the speed cooling/heating.<br />

(Speed cooling/heating operates super high fan<br />

speed.)<br />

6. Chaos swing button<br />

Used to stop or start louver movement and set<br />

the desired up/down airflow direction.<br />

7. On/Off timer buttons<br />

Used to set the time <strong>of</strong> starting and stopping<br />

operation.<br />

8. Time setting buttons<br />

Used to adjust the time.<br />

9. Timer set/Cancel button<br />

Used to set the timer when the desired time is<br />

obtained and to cancel the Timer operation.<br />

10. Sleep mode auto button<br />

Used to set sleep mode auto operation.<br />

11. Air circulation button<br />

Used to circulate the room air without cooling or<br />

heating.<br />

12. Room temperature checking button<br />

Used to check the room temperature.<br />

13. PLASMA(Optional)<br />

Used to start or stop the <strong>pl</strong>asma-purification<br />

function.<br />

14. Reset button<br />

Initialize remote controller.<br />

15. 2nd F button<br />

Used prior to using modes printed in blue at the<br />

bottom <strong>of</strong> buttons.<br />

Ceiling & Floor 93<br />

(Heat Pump)


List <strong>of</strong> functions 5CSL0-06B<br />

1.3 Ceiling suspended<br />

1.3.1 List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Deluxe wired remote controller<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

UVNH366KLAD<br />

[UV36 NKD]<br />

UVNH426LLAD<br />

[UV42 NLD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

UVNH486LLAD<br />

[UV48 NLD]<br />

UVNH606LLAD<br />

[UV60 NLD]<br />

1 1 1 1<br />

Manual Manual Manual Manual<br />

Auto Auto Auto Auto<br />

- - - -<br />

O O O O<br />

3 / 4 / 3 3 / 4 / 3 3 / 4 / 3 3 / 4 / 3<br />

X X X X<br />

O O O O<br />

O O O O<br />

- - - -<br />

- - - -<br />

- - - -<br />

O O O O<br />

- - - -<br />

- - - -<br />

- - - -<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

- - - -<br />

X X X X<br />

O O O O<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

O O O O<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

O O O O<br />

O O O O<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

PVRCUSZ0 PVRCUSZ0 PVRCUSZ0 PVRCUSZ0<br />

X X X X<br />

X X X X<br />

X X X X<br />

X X X X<br />

O O O O<br />

X X X X<br />

PQDSB PQDSB PQDSB PQDSB<br />

O O O O<br />

X X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X X<br />

X X X X<br />

PQRSTA0 PQRSTA0 PQRSTA0 PQRSTA0<br />

94 Ceiling suspended


5CSL0-06B<br />

1.3.2 Specifications<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions (WxHxD) Body mm<br />

Weight Body kg<br />

Air Filter<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Refrigerant<br />

Refrigerant Control<br />

Indoor unit type Ceiling suspended<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 Specifications<br />

Model UVNH366KLAD [UV36 NKD] UVNH426LLAD [UV42 NLD]<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.97 0.67*2<br />

Induction Induction<br />

sirocco sirocco<br />

94.5 63*4<br />

29 / 27 / 24 32 / 30 / 28<br />

4.0 / 440 4.0 / 440<br />

Direct Drive Direct Drive<br />

3R*14C*19 3R*14C*19<br />

1,350*630*220 1,750*630*220<br />

35 45<br />

Long life filter Long life filter<br />

44 / 42 / 40 48 / 45 / 42<br />

9.52 9.52<br />

15.88 15.88<br />

20 / 17 20 / 17<br />

3.5 4.5<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Ceiling suspended 95


Specifications 5CSL0-06B<br />

Indoor unit type Ceiling suspended<br />

Model UVNH486LLAD [UV48 NLD] UVNH606LLAD [UV60 NLD]<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

Capacitor<br />

Drive<br />

μF/Vac<br />

Coil Row x Column x FPI mm<br />

Dimensions (WxHxD) Body mm<br />

Weight<br />

Air Filter<br />

Body kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate<br />

Safety devices<br />

Temperature Sensor<br />

Refrigerant<br />

Refrigerant Control<br />

Connectable outdoor unit<br />

l/h<br />

Power and transmission interunit cable No.x mm2 Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

0.67*2 0.67*2<br />

Induction Induction<br />

sirocco sirocco<br />

63*4 63*4<br />

36 / 34 / 32 40 / 38 / 36<br />

4.0 / 440 4.0 / 440<br />

Direct Drive Direct Drive<br />

3R*14C*19 3R*14C*19<br />

1,750*630*220 1,750*630*220<br />

45 45<br />

Long life filter Long life filter<br />

54 / 52 / 50 56 / 54 / 52<br />

9.52 9.52<br />

15.88 15.88<br />

20 / 17 20 / 17<br />

5.8 6.2<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

96 Ceiling suspended


5CSL0-06B<br />

1.3.3 Dimensions<br />

UVNH366KLAD[UV36 NKD]<br />

1<br />

Model name UVNH366KLAD[UV36 NKD]<br />

1 / 220-240 / 50<br />

9.52<br />

15.88<br />

20 / 17<br />

Dimensions<br />

Ceiling suspended 97<br />

Refer to each combination table<br />

10.0 kW


Dimensions 5CSL0-06B<br />

UVNH426LLAD[UV42 NLD]<br />

UVNH486LLAD[UV48 NLD]<br />

UVNH606LLAD[UV60 NLD]<br />

1<br />

UVNH606LLAD<br />

[UV60 NLD]<br />

1 / 220-240 / 50<br />

UVNH486LLAD<br />

[UV48 NLD]<br />

1 / 220-240 / 50<br />

UVNH426LLAD<br />

[UV42 NLD]<br />

1 / 220-240 / 50<br />

Model name<br />

9.52<br />

15.88<br />

20 / 17<br />

9.52<br />

15.88<br />

20 / 17<br />

9.52<br />

15.88<br />

20 / 17<br />

98 Ceiling suspended<br />

Refer to each combination table<br />

12.5/14.0/15.0 kW


5CSL0-06B<br />

1.3.4 Piping diagrams<br />

Heating<br />

Cooling<br />

Th2<br />

Heat exchanger<br />

C.F.F<br />

Th1 : Thermistor for suction air temp.<br />

Th2 : Thermistor for liquid line temp.<br />

Th3 : Thermistor for gas line temp.<br />

■ Refrigerant pipe connection port diameters<br />

Piping diagrams<br />

Ceiling suspended 99<br />

Th3<br />

Th1<br />

Gas pipe connection port<br />

(flare connection)<br />

Liquid pipe connection port<br />

(flare connection)<br />

Model Gas Liquid<br />

UVNH366KLAD[UV36 NKD]<br />

UVNH426LLAD[UV42 NLD]<br />

UVNH486LLAD[UV48 NLD]<br />

UVNH606LLAD[UV60 NLD]<br />

Ø15.88 Ø9.52<br />

[Unit:mm]


Wiring diagrams 5CSL0-06B<br />

1.3.5 Wiring diagrams<br />

1) Wiring diagrams<br />

Connector Number Location Connector Number Location<br />

CN-POWER AC power sup<strong>pl</strong>y CN-TH2 Discharge pipe sensor<br />

CN-MOTOR BLDC fan motor output CN-TH1 Pipe and room sensor<br />

CN-DPUMP Drain pump output CN-HVB Air cleaner<br />

CN-AC/DC AC/DC connector CN-DOOR Step motor<br />

CN-DISPLAY Dis<strong>pl</strong>ay CN-UD1 Step motor<br />

CN-FLOAT Float switch input CN-CC Central control<br />

2) PCB<br />

CN-POWER<br />

CN-MOTOR CN-DISP CN-REMO<br />

CN-FLOAT<br />

< UV36 NKD, UV42 NLD, UV48 NLD, UV60 NLD ><br />

CN-PIPE1<br />

CN-ROOM<br />

CN-CC<br />

CN-PIPE2<br />

100 Ceiling suspended


5CSL0-06B<br />

Air flow and temperature distributions (reference data)<br />

1.3.6 Air flow and temperature distributions (reference data)<br />

2.7m<br />

2m<br />

1m<br />

1<br />

0.5<br />

0.25<br />

3<br />

<br />

Air Flow Direction :10 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

2.5<br />

0.25<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

0.25<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

1<br />

0.25<br />

0.5<br />

4<br />

3.5<br />

0.25<br />

3<br />

2.5<br />

2<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

Models : 10.0 kW<br />

Models : 12.5 kW<br />

0.5<br />

0.25<br />

0.5<br />

0.25<br />

3<br />

3.5<br />

3<br />

1.5<br />

2<br />

1.5<br />

1<br />

1<br />

0.5<br />

0.5<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :45 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

2.5<br />

2<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

1.5<br />

1<br />

0.5<br />

0.25<br />

Ceiling suspended 101<br />

2.7m<br />

2m<br />

1m<br />

2.7m<br />

2m<br />

1m<br />

15<br />

32<br />

30<br />

28<br />

17<br />

16<br />

26<br />

19<br />

24<br />

21<br />

31<br />

22<br />

12<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :10 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

2.7m<br />

2m<br />

1m<br />

30<br />

28<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :45 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

0.25<br />

0.5<br />

2.7m<br />

34<br />

18<br />

2.5<br />

2<br />

1<br />

0.5 2m<br />

30<br />

28<br />

26<br />

1.5<br />

0.25<br />

1m<br />

14<br />

16<br />

18<br />

24<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

23<br />

20<br />

22<br />

20<br />

22<br />

20<br />

25<br />

24<br />

12<br />

29<br />

18<br />

26<br />

12<br />

27<br />

14<br />

14<br />

18<br />

16<br />

16<br />

28


Air flow and temperature distributions (reference data) 5CSL0-06B<br />

2.7m<br />

2m<br />

1m<br />

<br />

Air Flow Direction :10 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

0.25<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

0.5<br />

0.25<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

0.25<br />

0.5<br />

3<br />

3.5<br />

3<br />

0.25<br />

2.5<br />

2.5<br />

2<br />

0m<br />

0.5<br />

0.25<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

2.7m<br />

2m<br />

1m<br />

Models : 14.0 kW<br />

Models : 15.0 kW<br />

0.5<br />

0.25<br />

0.25<br />

0.5<br />

3.5<br />

3.5<br />

3<br />

1.5<br />

2<br />

1.5<br />

1<br />

1<br />

0.5<br />

0.5<br />

0.5<br />

0.25<br />

30 28<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :45 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

0m<br />

0.25<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

102 Ceiling suspended<br />

2.7m<br />

2m<br />

1m<br />

2.7m<br />

2m<br />

1m<br />

14<br />

32<br />

30<br />

18<br />

28<br />

16<br />

26<br />

18<br />

24<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :10 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

3<br />

2.5<br />

2 1.5 1<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

<br />

Air Flow Direction :45 °(downward)<br />

Air Velocity Distribution(m/s) Temperature Distribution(°C)<br />

0.25<br />

2.5<br />

2<br />

1.5<br />

1<br />

0.5<br />

0.5<br />

2.7m<br />

2m<br />

1m<br />

14<br />

32<br />

30<br />

28<br />

16<br />

26<br />

18<br />

12 16<br />

0m<br />

12<br />

0m 1m 2m 3m 4m 5m 6m 7m 8m<br />

24<br />

20<br />

20<br />

22<br />

30<br />

22<br />

18<br />

22<br />

22<br />

24<br />

20<br />

12<br />

24<br />

20<br />

28<br />

14<br />

14<br />

26<br />

16<br />

26<br />

26<br />

18<br />

18


5CSL0-06B<br />

1.3.7 Sound levels<br />

Overall<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

Microphone<br />

1m<br />

1m<br />

Sound Pressure Level<br />

Sound Pressure Level (dB re 20μPa )<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

10<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

UVNH366KLAD[UV36 NKD] UVNH426LLAD[UV42 NLD]<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

20<br />

NC-25<br />

NC-20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

Notes:<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

UVNH486LLAD[UV48 NLD] UVNH606LLAD[UV60 NLD]<br />

Sound Pressure Level (dB re 20μPa )<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound levels<br />

Ceiling suspended 103<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


Controller 5CSL0-06B<br />

1.3.8 Controller<br />

■ Wireless remote controller<br />

The remote controller transmits the signals to the system.<br />

CANCEL<br />

ON OFF SET<br />

AUTO CLEAN<br />

Cooling operation<br />

Auto operation<br />

Healthy dehumidification operation<br />

Heating operation<br />

Signal transmitter<br />

5 1<br />

6<br />

3<br />

4<br />

2<br />

7<br />

11<br />

8<br />

13<br />

14<br />

Operation mode<br />

10<br />

9<br />

12<br />

15<br />

Flip-up door<br />

(opened)<br />

• Cooling model( ), Heat pump model( )<br />

1. Start/Stop btton<br />

Operation starts when this button is pressed<br />

and stops when the button is pressed again.<br />

2. Operation mode selection button<br />

Used to select the operation mode.<br />

3. Room temperature setting buttons<br />

Used to select the room temperature.<br />

4. Indoor fanspeed selector<br />

Used to select fan speed in four steps<br />

low, medium, high and CHAOS.<br />

5. Jet cool<br />

Used to start or stop the speed cooling/heating.<br />

(Speed cooling/heating operates super high fan<br />

speed.)<br />

6. Chaos swing button<br />

Used to stop or start louver movement and set<br />

the desired up/down airflow direction.<br />

7. On/Off timer buttons<br />

Used to set the time <strong>of</strong> starting and stopping<br />

operation.<br />

8. Time setting buttons<br />

Used to adjust the time.<br />

9. Timer set/Cancel button<br />

Used to set the timer when the desired time is<br />

obtained and to cancel the Timer operation.<br />

10. Sleep mode auto button<br />

Used to set sleep mode auto operation.<br />

11. Air circulation button<br />

Used to circulate the room air without cooling or<br />

heating.<br />

12. Room temperature checking button<br />

Used to check the room temperature.<br />

13. PLASMA(Optional)<br />

Used to start or stop the <strong>pl</strong>asma-purification<br />

function.<br />

14. Reset button<br />

Initialize remote controller.<br />

15. 2nd F button<br />

Used prior to using modes printed in blue at the<br />

bottom <strong>of</strong> buttons.<br />

104 Ceiling suspended<br />

(Heat Pump)


5CSL0-06B<br />

1.4 Ceiling concealed duct – high static pressure<br />

1.4.1 List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Deluxe wired remote controller<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

ABNH186HLAD<br />

[UB18 NHD]<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

List <strong>of</strong> functions<br />

ABNH306GLAD<br />

[UB30 NGD]<br />

2 2 2<br />

- - -<br />

- - -<br />

- - -<br />

- - -<br />

3 / 3 / 3 3 / 3 / 3 3 / 3 / 3<br />

- - -<br />

- - -<br />

- - -<br />

- - -<br />

- - -<br />

X X X<br />

O O O<br />

ABDPG ABDPG ABDPG<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

X X X<br />

O O O<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQDSB** PQDSB** PQDSB**<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

ABZCA ABZCA ABZCA<br />

PQRSTA0 PQRSTA0 PQRSTA0<br />

Duct (H) 105


List <strong>of</strong> functions 5CSL0-06B<br />

Category<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Air flow Auto swing(up & down)<br />

Airflow steps(fan/cool/heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Air purifying Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Installation<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Reliability Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Convenience Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Deluxe wired remote controller<br />

Sim<strong>pl</strong>e wired remote controller<br />

Individual control<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

CAC network<br />

Sim<strong>pl</strong>e central control(LGAP)<br />

function<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Special function kit<br />

Zone control<br />

Others Thermistor<br />

ABNH366GLAD<br />

[UB36 NGD]<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

2 2 2 2<br />

- - - -<br />

- - - -<br />

- - - -<br />

- - - -<br />

3 / 3 / 3 3 / 3 / 3 3 / 3 / 3 3 / 3 / 3<br />

- - - -<br />

- - - -<br />

- - - -<br />

- - - -<br />

- - - -<br />

X X X X<br />

O O O O<br />

ABDPG ABDPG ABDPG ABDPG<br />

O O O O<br />

- - - -<br />

- - - -<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

X X X X<br />

X X X X<br />

O O O O<br />

O O O O<br />

X X X X<br />

O O O O<br />

X X X X<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

X X X X<br />

X X X X<br />

X X X X<br />

X X X X<br />

X X X X<br />

X X X X<br />

PQDSB** PQDSB** PQDSB** PQDSB**<br />

O O O O<br />

X X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X X<br />

ABZCA ABZCA ABZCA ABZCA<br />

AQTTA AQTTA AQTTA AQTTA<br />

106 Duct (H)


5CSL0-06B<br />

1.4.2 Specifications<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

External Static Pressure mmAq<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Columns x FPI mm<br />

Dimensions(WxHxD) Body mm<br />

Weight Body kg<br />

Air Filter<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Ceilling Concealed Duct - High Static<br />

Model<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 ABNH186HLAD<br />

[UB18 NHD]<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

Specifications<br />

0.92 0.92<br />

Induction Induction<br />

Sirocco Fan Sirocco Fan<br />

118*2 118*2<br />

16.5/14.5/13.0 18.0/16.5/14.0<br />

8 8<br />

6/370 6/370<br />

Direct Drive Direct Drive<br />

3R x 10C x 21 3R x 10C x 21<br />

880*260*450 880*260*450<br />

35 35<br />

Long life filter Long life filter<br />

36/34/32 38/36/34<br />

6.35 9.52<br />

12.7 15.88<br />

32/25 32/25<br />

2.0 2.5<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Duct (H) 107


Specifications 5CSL0-06B<br />

Indoor unit type Ceilling Concealed Duct - High Static<br />

Model ABNH306GLAD [UB30 NGD] ABNH366GLAD [UB36 NGD]<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

External Static Pressure mmAq<br />

Capacitor<br />

Drive<br />

μF/Vac<br />

Coil Row x Columns x FPI mm<br />

Dimensions(WxHxD) Body mm<br />

Weight<br />

Air Filter<br />

Body kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Connectable outdoor unit<br />

l/h<br />

Power and transmission interunit cable No.x mm2 Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

1.34 1.42<br />

Induction Induction<br />

Sirocco Fan Sirocco Fan<br />

211*2 272*2<br />

26.5 / 23.0 / 20.0 32.0 / 29.0 / 26.0<br />

10 10<br />

6/370 6/370<br />

Direct Drive Direct Drive<br />

3R x 12C x 21 3R x 12C x 21<br />

1,180*298*450 1,180*298*450<br />

38 38<br />

Long life filter Long life filter<br />

40/38/35 42/39/36<br />

9.52 9.52<br />

15.88 15.88<br />

32/25 32/25<br />

3.3 4.0<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

108 Duct (H)


5CSL0-06B<br />

Indoor unit type Ceilling Concealed Duct - High Static<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

External Static Pressure mmAq<br />

Capacitor<br />

Drive<br />

μF/Vac<br />

Coil Row x Columns x FPI mm<br />

Dimensions(WxHxD) Body mm<br />

Weight<br />

Air Filter<br />

Body kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Connectable outdoor unit<br />

l/h<br />

Power and transmission interunit cable No.x mm2 Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Specifications<br />

Model ABNH426RLAD [UB42 NRD] ABNH486RLAD [UB48 NRD]<br />

1 / 220-240 / 50 1 / 220-240 / 50<br />

Refer to each combination table<br />

3.65 3.65<br />

Induction Induction<br />

Sirocco Fan Sirocco Fan<br />

357*2 357*2<br />

36/32/38 40/35/30<br />

10 15<br />

15/450 15/450<br />

Direct Drive Direct Drive<br />

3R x 13C x 19 3R x 13C x 19<br />

1,230*380*590 1,230*380*590<br />

60 60<br />

Long life filter Long life filter<br />

42/40/38 44/42/40<br />

9.52 9.52<br />

15.88 15.88<br />

32/25 32/25<br />

5.0 6.0<br />

Fuse, Thermal protector for fan motor<br />

Thermistor Thermistor<br />

R410A R410A<br />

EEV(Outdoor Unit) EEV(Outdoor Unit)<br />

Single A Single A<br />

4*0.75(Including Earth) 4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Duct (H) 109


Specifications 5CSL0-06B<br />

Indoor unit type Ceilling Concealed Duct - High Static<br />

Model ABNH606RLAD [UB60 NRD]<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L) cmm<br />

External Static Pressure mmAq<br />

Capacitor<br />

Drive<br />

μF/Vac<br />

Coil Row x Columns x FPI mm<br />

Dimensions(WxHxD) Body mm<br />

Weight<br />

Air Filter<br />

Body kg<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Connectable outdoor unit<br />

l/h<br />

Power and transmission interunit cable No.x mm2 Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

1/220-240 / 50<br />

Refer to each combination table<br />

3.65<br />

Induction<br />

Sirocco Fan<br />

357*2<br />

50/45/40<br />

15<br />

15/450<br />

Direct Drive<br />

4Rx13Cx19<br />

1,230*380*590<br />

62<br />

Long life filter<br />

46/44/42<br />

9.52<br />

15.88<br />

32/25<br />

6.5<br />

Fuse, Thermal protector for fan motor<br />

Thermistor<br />

R410A<br />

EEV(Outdoor Unit)<br />

Single A<br />

4*0.75(Including Earth)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

110 Duct (H)


5CSL0-06B<br />

1.4.3 Dimensions<br />

ABNH186HLAD[UB18 NHD]<br />

ABNH246HLAD[UB24 NHD]<br />

ABNH246HLAD[UB24 NHD]<br />

1 / 220-240 / 50<br />

Model name ABNH186HLAD[UB18 NHD]<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

6.35<br />

12.7<br />

32/25<br />

Dimensions<br />

Duct (H) 111<br />

9.52<br />

15.88<br />

32/25<br />

5.0/7.1 kW


Dimensions 5CSL0-06B<br />

ABNH306GLAD[UB30 NGD]<br />

ABNH366GLAD[UB36 NGD]<br />

ABNH366GLAD[UB36 NGD]<br />

1 / 220-240 / 50<br />

Model name ABNH306GLAD[UB30 NGD]<br />

1/ 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

32 / 35<br />

9.52<br />

15.88<br />

32 / 35<br />

112 Duct (H)<br />

8.0/10.0 kW


5CSL0-06B<br />

ABNH426RLAD[UB42 NRD]<br />

ABNH486RLAD[UB48 NRD]<br />

ABNH606RLAD[UB60 NRD]<br />

ABNH426RLAD[UB42 NRD]<br />

ABNH486RLAD[UB48 NRD]<br />

ABNH606RLAD[UB60 NRD]<br />

Model name<br />

Dimensions<br />

Duct (H) 113<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

COMBINATION TABLE<br />

9.52<br />

15.88<br />

32/25<br />

12.5/14.0/15.0 kW


Piping diagrams 5CSL0-06B<br />

1.4.4 Piping diagrams<br />

Heating<br />

Cooling<br />

Th2<br />

Heat exchanger<br />

Sirocco Fan<br />

Th1 : Thermister for suction air temp.<br />

Th2 : Thermister for liquid line temp.<br />

Th3 : Thermister for gas line temp.<br />

■ Refrigerant pipe connection port diameters<br />

M<br />

Th3<br />

114 Duct (H)<br />

Th1<br />

Gas pipe connection port<br />

(flare connection)<br />

Liquid pipe connection port<br />

(flare connection)<br />

Model Gas Liquid<br />

ABNH186HLAD[UB18 NHD]<br />

ABNH246HLAD[UB24 NHD]<br />

ABNH306GLAD[UB30 NGD]<br />

Ø12.7 Ø6.35<br />

ABNH366GLAD[UB36 NGD]<br />

ABNH426RLAD[UB42 NRD]<br />

Ø15.88 Ø9.52<br />

ABNH486RLAD[UB48 NRD]<br />

ABNH606RLAD[UB60 NRD]<br />

[Unit:mm]


5CSL0-06B<br />

1.4.5 Wiring diagrams<br />

1) Wiring diagrams<br />

Models : ABNH186HLAD[UB18 NHD], ABNH246HLAD[UB24 NHD]<br />

Models : ABNH306GLAD[UB30 NGD], ABNH366GLAD[UB36 NGD]<br />

Connector Number Location<br />

CN-POWER AC power sup<strong>pl</strong>y<br />

CN-MOTOR BLDC fan motor outpup<br />

CN-D/PUMP Drain pump output<br />

CN-DISP RF-remote control<br />

CN-FLOAT Float switch input<br />

CN-ZONE Zone control output<br />

CN-CC Central control ouput<br />

Connector Number Location<br />

CN-PIPE1 Pipe sensor<br />

CN-PIPE2 Dischage pipe sensor<br />

CN-REMO Remote control<br />

CN-ROOM Room sensor<br />

CN-AIRC Air clean<br />

CN-PTC PTC heater<br />

CN-OUT Ventilation/Electric heater<br />

Wiring diagrams<br />

Duct (H) 115


Wiring diagrams 5CSL0-06B<br />

Models: ABNH426RLAD [UB42 NRD], ABNH486RLAD [UB48 NRD], ABNH606RLAD [UB60 NRD]<br />

Connector Number Location<br />

CN-POWER AC power sup<strong>pl</strong>y<br />

CN-MOTOR BLDC fan motor outpup<br />

CN-D/PUMP Drain pump output<br />

CN-DISP RF-remote control<br />

CN-FLOAT Float switch input<br />

CN-ZONE Zone control output<br />

CN-CC Central control ouput<br />

Connector Number Location<br />

CN-PIPE1 Pipe sensor<br />

CN-PIPE2 Dischage pipe sensor<br />

CN-REMO Remote control<br />

CN-ROOM Room sensor<br />

CN-AIRC Air clean<br />

CN-PTC PTC heater<br />

CN-OUT Ventilation/Electric heater<br />

116 Duct (H)


5CSL0-06B<br />

2) PCB<br />

CN-ZONE<br />

CN-FLOAT<br />

CN-PIPE2<br />

CN-ZONE<br />

CN-FLOAT<br />

CN-CC CN-ROOM<br />

CN-FLOAT<br />

CN-REMO<br />

CN-PIPE2<br />

CN-REMO<br />

CN-ROOM<br />

CN-CC CN-PIPE2<br />

CN-PIPE1<br />

CN-STEP<br />

CN-DPUMP CN-POWER<br />

CN-MOTOR<br />

<br />

CN-MOTOR<br />

CN-DPUMP<br />

<br />

Wiring diagrams<br />

CN-POWER<br />

Duct (H) 117


External pressure setting for tuning 5CSL0-06B<br />

1.4.6 External pressure setting for<br />

(ESP Control) provide required constant air volume irrespective <strong>of</strong> ESP charge.<br />

(1) Open the rear cover <strong>of</strong> the wired remote-controller to set the mode.<br />

(2) Select one <strong>of</strong> three selectable modes as follows.<br />

■ Without zone system<br />

1. Position V-H, F-H:<br />

• This position sets the maximum ESP as a default set.<br />

2. Position V-L:<br />

• This position sets the minimum ESP as a default set.<br />

■ With zone system<br />

1. Position V-H:<br />

• Maximum ESP setting & Fan speed is varied according to the state <strong>of</strong> dampers by micom.<br />

2. Position F-H:<br />

• Maximum ESP setting & Fan speed doesn't vary according to the opening & closing <strong>of</strong> dampers.<br />

3. Position V-L:<br />

• Minimum ESP setting & Fan speed is varied according to the state <strong>of</strong> dampers by micom.<br />

Static pressure RECOMMENDATION : NORMAL SET ±2<br />

Static pressure guide (Unit : mmAq)<br />

MODELS MIN NORMAL SET MAX<br />

UB18,UB24 0 4 8<br />

UB30,UB36 0 4 10<br />

UB42,UB48,UB60 0 8 15<br />

(3) Move the slide switch to set position.<br />

(4) Close the rear cover and check if it works normally.<br />

CAUTION<br />

V-L<br />

F-H<br />

V-H<br />

Zone state / Default E.S.P<br />

• Select the position after checking duct work and ESP <strong>of</strong> the unit.<br />

• Maunfactured in the position F-H.<br />

TH R13H R12H OP5R16H OP4<br />

CO1H<br />

118 Duct (H)<br />

R14H<br />

SW TH<br />

OP3 OP2 OP1<br />

REMO<br />

MAIN<br />

2TH<br />

OP7<br />

R18H<br />

R17H<br />

OP6<br />

LO<br />

STAND<br />

HI R03S<br />

SW HIGH<br />

R19H<br />

R11H<br />

C070 R04S<br />

R02S<br />

R01S<br />

R15H


5CSL0-06B<br />

How to Set ESP on the remote controller?<br />

Procedure <strong>of</strong> RPM change:<br />

Ex) External static pressure is 4mmAq for model name "ABNH246HLAD".<br />

• To protect the unit, compressor is designed to be <strong>of</strong>f during ESP setting.<br />

1<br />

2<br />

3<br />

Push the "On/Off" button.<br />

The unit will start.<br />

Push the "Timer" and "Wind" button simultaneously for more than<br />

3 seconds.<br />

Timer<br />

Push the "Up" <strong>of</strong> "Down" button for ESP adjustment.<br />

And, adjust the number which you want.(In this exam<strong>pl</strong>e, the number is "190".<br />

Refer to the table on the next <strong>page</strong>.)<br />

Shift the fan speed mode by pressing the fan speed button.<br />

And then, adjust numbers <strong>of</strong> next steps by repeating the stage 3.<br />

(In this exam<strong>pl</strong>e, the numbers are "220" and "235" respectively.<br />

Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.<br />

Then, wind data is memorized by the EEPROM <strong>of</strong> the main PCB.<br />

External pressure setting for tuning<br />

AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION<br />

Room Temp<br />

HI AUTO Heater Preheat<br />

MED JET Defrost Humidify<br />

LO<br />

Filter Out door<br />

Time ZONE 1 2 3 4<br />

Timer Operation unit Program set<br />

On Off<br />

Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23<br />

AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION<br />

Room Temp<br />

HI AUTO Heater Preheat<br />

MED JET Defrost Humidify<br />

LO<br />

Filter Out door<br />

Time ZONE 1 2 3 4<br />

Timer Operation unit Program set<br />

On Off<br />

Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23<br />

AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION<br />

Room Temp<br />

HI AUTO Heater Preheat<br />

MED JET Defrost Humidify<br />

LO<br />

Filter Out door<br />

Time ZONE 1 2 3 4<br />

Timer Operation unit Program set<br />

On Off<br />

Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23<br />

Note: The range <strong>of</strong> selection is from 1~254. Since, the dis<strong>pl</strong>ay is two digit only.<br />

If the range selection is above 100 then the third digit will appear in the screen as shown.(setting value)<br />

4<br />

5<br />

Timer<br />

AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION<br />

Room Temp<br />

HI AUTO Heater Preheat<br />

MED JET Defrost Humidify<br />

LO<br />

Filter Out door<br />

Time ZONE 1 2 3 4<br />

Timer Operation unit Program set<br />

On Off<br />

Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23<br />

Duct (H) 119


External pressure setting for tuning 5CSL0-06B<br />

Table 1<br />

[ Notes ]<br />

Static Pressure(mmAq)<br />

Model Name Step CMM<br />

ABNH186HLAD<br />

[UB18 NHD]<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

ABNH306GLAD<br />

[UB30 NGD]<br />

ABNH366GLAD<br />

[UB36 NGD]<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

0 2 4 6 8<br />

Setting Value<br />

10 12 14 15<br />

High 16.5 235 230 225 215 180 - - - -<br />

Med 14.5 245 238 235 230 215 - - - -<br />

Low 13 254 252 248 245 240 - - - -<br />

High 18 220 205 190 50 1 - - - -<br />

Med 16.5 235 230 220 200 100 - - - -<br />

Low 14 250 240 235 230 210 - - - -<br />

High 26.5 153 150 150 148 130 1 - - -<br />

Med 23 173 173 175 175 170 155 - - -<br />

Low 20 190 190 190 190 190 190 - - -<br />

High 32 230 230 225 220 150 1 - - -<br />

Med 29 240 238 237 235 230 220 - - -<br />

Low 26.5 245 245 243 243 240 240 - - -<br />

High 36 238 235 230 225 220 215 - - -<br />

Med 32 253 250 245 240 235 230 - - -<br />

Low 28 255 255 255 255 250 248 - - -<br />

High 40 230 225 220 215 205 200 190 180 160<br />

Med 35 250 245 240 235 230 220 215 210 200<br />

Low 30 255 255 255 250 245 240 235 230 225<br />

High 50 185 180 174 162 154 140 90 5 1<br />

Med 45 210 205 199 191 189 180 155 138 110<br />

Low 40 230 225 219 215 210 205 193 180 171<br />

1. To get the desired Airflow & ESP combination from the table set the matching value from the table. Value<br />

other than that in table will not give the combinations <strong>of</strong> airflow & ESP which are mentioned in the table.<br />

2. Table data is based at 230V. According to the fluctuation <strong>of</strong> voltage, air flow rate varies.<br />

3) Duct work must be designed within the range <strong>of</strong> on installing the unit.<br />

4) If duct work is designed under External Static Pressure adjust the External Static Pressure ap<strong>pl</strong>ying<br />

air damper.<br />

120 Duct (H)


5CSL0-06B<br />

Table 2<br />

[ Notes ]<br />

External pressure setting for tuning<br />

Static Pressure(mmAq)<br />

Model Name Step 0 2 4 6 8<br />

CMM<br />

10 12 14 15<br />

Setting<br />

Value<br />

ABNH186HLAD<br />

[UB18 NHD]<br />

High<br />

Med<br />

180<br />

215<br />

22<br />

18.5<br />

21<br />

17.8<br />

19.8<br />

17.1<br />

18.3<br />

16.2<br />

16.5<br />

14.5<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Low 240 16.1 15.6 15.1 14.2 13 - - - -<br />

ABNH246HLAD<br />

[UB24 NHD]<br />

High<br />

Med<br />

1<br />

100<br />

24<br />

21.3<br />

22.5<br />

19.9<br />

20.8<br />

18.7<br />

19<br />

17.2<br />

18<br />

16.5<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Low 210 17 16.1 15.4 14.7 14 - - - -<br />

ABNH306GLAD<br />

[UB30 NGD]<br />

High<br />

Med<br />

1<br />

155<br />

34.2<br />

27<br />

33.1<br />

26.3<br />

31.7<br />

26.1<br />

29.9<br />

25.8<br />

27.7<br />

24.8<br />

26.5<br />

23<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Low 190 21 20.8 20.6 20.4 20.4 20 - - -<br />

High 1 42 40 38 35.5 33.5 32 - - -<br />

ABNH366GLAD<br />

[UB36 NGD]<br />

Med<br />

Low<br />

220<br />

240<br />

39<br />

34<br />

37<br />

32.5<br />

35<br />

31<br />

33<br />

29.5<br />

31<br />

27<br />

29<br />

26.5<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

High 215 44.5 43.4 41 39.4 37.5 36.4 - - -<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

Med<br />

Low<br />

230<br />

248<br />

41<br />

37<br />

40.2<br />

36.1<br />

37.6<br />

34.6<br />

35<br />

31.5<br />

33.8<br />

29.1<br />

32.7<br />

27.9<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

High 200 49 47.4 44.9 43.3 41.7 40 38.6 37 35.4<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

Med<br />

Low<br />

220<br />

240<br />

44<br />

38<br />

42.4<br />

37.2<br />

40.2<br />

35<br />

39.2<br />

32.4<br />

36.7<br />

31.6<br />

35<br />

30<br />

34.6<br />

28.6<br />

33<br />

27<br />

32.2<br />

26.2<br />

High 140 59 57.4 55.8 53.4 51.7 50 46.6 42.9 40.6<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

Med<br />

Low<br />

180<br />

205<br />

53<br />

47<br />

51.4<br />

45.8<br />

49.8<br />

43.8<br />

47.4<br />

42.1<br />

45.9<br />

40.7<br />

45<br />

40<br />

42.6<br />

37.8<br />

39.6<br />

35<br />

38.3<br />

33.4<br />

1) The above table shows the correlation <strong>of</strong> External Static Pressure & Air Flow.<br />

2) When installing, the value <strong>of</strong> motor step needs to be set according to E.S.P. <strong>of</strong> the table 2.<br />

3) Duct work must be designed within the range <strong>of</strong> on installing the unit.<br />

4) If duct work is designed under External Static Pressure adjust the External Static Pressure ap<strong>pl</strong>ying<br />

air damper.<br />

Duct (H) 121


Sound levels 5CSL0-06B<br />

1.4.7 Sound levels<br />

overall<br />

DISCHARGE SUCTION<br />

DUCT<br />

2m<br />

1.5m<br />

1m<br />

1m<br />

Sound pressure level<br />

Sound Pressure Level (dB re 20μPa )<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

DUCT<br />

Notes:<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

ABNH186HLAD[UB18 NHD] ABNH246HLAD[UB24 NHD] ABNH306GLAD[UB30 NGD]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

ABNH366GLAD[UB36 NGD] ABNH426RLAD[UB42 NRD] ABNH486RLAD[UB48 NRD]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

122 Duct (H)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20μPa )<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


5CSL0-06B<br />

Sound Pressure Level (dB re 20μPa )<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

ABNH606RLAD[UB60 NRD]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound levels<br />

Duct (H) 123


Controller 5CSL0-06B<br />

1.4.8 Controller<br />

Wired remote controller<br />

3<br />

Signal receiver<br />

5<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION<br />

Room Temp<br />

HI AUTO Heater Preheat<br />

MED JET Defrost Humidify<br />

LO<br />

Filter Out door<br />

Time ZONE 1 2 3 4<br />

Timer Operation unit<br />

Program set<br />

On Off<br />

Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23<br />

Timer Cancel<br />

Program Week Holiday<br />

Hour<br />

Min<br />

SET/CLR<br />

1. Operation dis<strong>pl</strong>ay<br />

Dis<strong>pl</strong>ays the operation conditions.<br />

2. On/Off button<br />

Operation starts when this button is pressed, and<br />

stops when the button is pressed again.<br />

3. Set temperature button<br />

Used to set the temperature when the desired temperature<br />

is obtained.<br />

4. FAN operation button<br />

Used to circulate room air without cooling or heating.<br />

5. Electric heater button(Optional)<br />

Used to set the electric heater.<br />

6. Fan speed button<br />

Used to set desired fan speed.<br />

7. Operation mode selection button<br />

Used to select the operation mode.<br />

• Auto operation or Auto changeover mode.<br />

• Cooling operation mode.<br />

• S<strong>of</strong>t dry operation mode.<br />

• Heating operation mode.(except cooling model)<br />

8. Timer cancel button<br />

Used to cancel the timer.<br />

Plasma<br />

RESET<br />

124 Duct (H)<br />

1<br />

2<br />

6<br />

7<br />

4<br />

15<br />

16<br />

17<br />

9. Timer set button<br />

Used to set the timer when the desired time is<br />

obtained.<br />

10. Week button<br />

Used to set a day <strong>of</strong> the week.<br />

11. Program button<br />

Used to set the weekly timer.<br />

12. Holiday button<br />

Used to set a holiday <strong>of</strong> the week.<br />

13. Time set button<br />

Used to set the time <strong>of</strong> the day and change the<br />

time in the weekly timer Function.<br />

14. Set and clear button<br />

Used to set and clear the weekly timer.<br />

15. Room temperature checking button<br />

Used to check the room temperature.<br />

16. Plasma air clean button(Accessory)<br />

17. Reset button<br />

Used to set the current time and clear the setting<br />

time.<br />

❈ Dis<strong>pl</strong>ay temperature can be different from actual room temperature if the remote controller is installed at the <strong>pl</strong>ace where<br />

sun-rays are falling directly or the <strong>pl</strong>ace nearby heat source.


5CSL0-06B<br />

1.5 Console (Floor stand)<br />

1.5.1 List <strong>of</strong> functions<br />

Category<br />

Air flow<br />

Air purifying<br />

Installation<br />

Reliability<br />

Convenience<br />

Individual<br />

control<br />

CAC network<br />

function<br />

Special<br />

function kit<br />

Others<br />

Function<br />

Air sup<strong>pl</strong>y outlet<br />

Airflow direction control(left & right)<br />

Airflow direction control(up & down)<br />

Auto swing(left & right)<br />

Auto swing(up & down)<br />

Airflow steps(fan / cool / heat)<br />

Chaos swing<br />

Chaos wind(auto wind)<br />

Jet cool(Power wind)<br />

Swirl wind<br />

Deodorizing filter<br />

Plasma air purifier<br />

Prefilter(washable / anti-fungus)<br />

Drain pump<br />

E.S.P. control<br />

Electric heater(operation)<br />

High ceiling operation<br />

Hot start<br />

Self diagnosis<br />

S<strong>of</strong>t dry operation<br />

Auto changeover<br />

Auto cleaning<br />

Auto operation(artificial intelligence)<br />

Auto restart operation<br />

Child lock<br />

Forced operation<br />

Group control<br />

Sleep mode<br />

Timer(on/<strong>of</strong>f)<br />

Timer(weekly)<br />

Two thermistor control<br />

Standard wired remote controller<br />

Picto wired remote controlxer<br />

Deluxe wired remote controlxer<br />

Sim<strong>pl</strong>e wired remote controller<br />

Wired remote controller(for hotel use)<br />

Wireless remote controller(sim<strong>pl</strong>e)<br />

Wireless LCD remote control<br />

General central control(Non LGAP)<br />

Dry contact<br />

Network Soluation(LGAP)<br />

PDI(power distribution indicator)<br />

PI 485<br />

CTIE<br />

Zone control<br />

Thermistor<br />

AQNH09GALA0<br />

[CQ09 NA0]<br />

AQNH12GALA0<br />

[CQ12 NA0]<br />

Note:<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

List <strong>of</strong> functions<br />

AQNH18GALA0<br />

[CQ18 NA0]<br />

2 2 2<br />

Manual Manual Manual<br />

Auto Auto Auto<br />

X X X<br />

O O O<br />

4/5/4 4/5/4 4/5/4<br />

X X X<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

X X X<br />

O O O<br />

X X X<br />

- - -<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

X X X<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

X X X<br />

PQRCUSA1 PQRCUSA1 PQRCUSA1<br />

X X X<br />

X X X<br />

X X X<br />

X X X<br />

PQWRHSF0 PQWRHSF0 PQWRHSF0<br />

X X X<br />

PQDSB PQDSB PQDSB<br />

O O O<br />

X X X<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

X X X<br />

X X X<br />

X X X<br />

Console 125


Specifications 5CSL0-06B<br />

1.5.2 Specifications<br />

Power Sup<strong>pl</strong>y Ø/V/Hz<br />

Cooling Capacity kW<br />

Heating Capacity kW<br />

Current Nominal running current A<br />

Fan Motor Type<br />

Fan Type<br />

Motor Output x Number <strong>of</strong> Unit<br />

Air Flow Rate(H/M/L/Sleep) cmm<br />

Capacitor μF/Vac<br />

Drive<br />

Coil Row x Column x FPI mm<br />

Dimensions (WxHxD) Body mm<br />

Weight Body kg<br />

Air Filter<br />

Sound Level (H/M/L) dB(A)+3<br />

Piping Liquid mm<br />

Connections Gas mm<br />

Drain(OD/ID) mm<br />

Dehumidification Rate l/h<br />

Safety devices<br />

Temperature Sensor<br />

Referigerant<br />

Referigerant Control<br />

Indoor unit type Console (Floor stand)<br />

Model<br />

Connectable outdoor unit<br />

Power and transmission interunit cable No.x mm2 AQNH09GALA0<br />

[CQ09 NA0]<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Cooling/heating capacity <strong>of</strong> indoor unit can be lower when it is connected to variable outdoor.<br />

3. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

AQNH12GALA0<br />

[CQ12 NA0]<br />

AQNH18GALA0<br />

[CQ18 NA0]<br />

1 / 220-240V / 50 1 / 220-240V / 50 1 / 220-240V / 50<br />

Refer to each combination table<br />

0.14 0.14 0.18<br />

BLDC BLDC BLDC<br />

Turbo Turbo Turbo<br />

48 x 1 48 x 1 48 x 1<br />

8.5/6.7/5.0/4.0 9.0/6.9/5.2/4.6 11.0/9.5/8.0/6.5<br />

- - -<br />

Direct Direct Direct<br />

2 x 19 x 19 2 x 19 x 19 2 x 19 x 19<br />

700 x 600 x 210 700 x 600 x 210 700 x 600 x 210<br />

13.8 13.8 13.8<br />

Long Life Filter Long Life Filter Long Life Filter<br />

38/32/27/22 39/32/27/23 44/39/35/32<br />

6.35 6.35 6.35<br />

9.52 9.52 12.7<br />

16.7/9.7 16.7/9.7 16.7/9.7<br />

1.2 1.4 2<br />

Fuse, Thermal Protector for Fan Motor<br />

Thermistor Thermistor Thermistor<br />

R410A, 1000g R410A, 1000g R410A, 1300g<br />

EEV (ODU) EEV (ODU) EEV (ODU)<br />

AUUW096D AUUW126D AUUW186D<br />

4 x 0.75 4 x 0.75 4 x 0.75<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

126 Console


5CSL0-06B<br />

1.5.3 Dimensions<br />

Console (Floor stand)<br />

AQNH09GALA0[CQ09 NA0]<br />

AQNH12GALA0[CQ12 NA0]<br />

AQNH18GALA0[CQ18 NA0]<br />

666<br />

45<br />

95<br />

2<br />

210<br />

700<br />

1<br />

AQNH18GALA0<br />

[CQ18 NA0]<br />

1 / 220-240 / 50<br />

AQNH12GALA0<br />

[CQ12 NA0]<br />

1 / 220-240 / 50<br />

REFER TO EACH<br />

AQNH09GALA0<br />

[CQ09 NA0]<br />

1 / 220-240 / 50<br />

Model name<br />

600<br />

584<br />

COMBINATION TABLE<br />

6.35<br />

9.52<br />

16.7/9.7<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

mm<br />

Power sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Piping Liquid<br />

Connections Gas<br />

Drain(OD/ID)<br />

3<br />

Dimensions<br />

Console 127<br />

6.35<br />

12.7<br />

16.7/9.7<br />

6.35<br />

9.52<br />

16.7/9.7<br />

1<br />

90<br />

125<br />

80<br />

18<br />

639<br />

82.5<br />

150<br />

140<br />

120<br />

160<br />

80<br />

68.5<br />

37<br />

37<br />

100<br />

CHASSIS CODE: QA<br />

2.5/3.5/5.0 kW


Piping diagrams 5CSL0-06B<br />

1.5.4 Piping diagrams<br />

Heating<br />

Cooling<br />

Th2<br />

Heat exchanger<br />

Turbo fan<br />

Th1 : Thermistor for suction air temp.<br />

Th2 : Thermistor for liquid line temp.<br />

Th3 : Thermistor for gas line temp.<br />

■ Refrigerant pipe connection port diameters<br />

128 Console<br />

Th3<br />

Th1<br />

Gas pipe connection port<br />

(flare connection)<br />

Liquid pipe connection port<br />

(flare connection)<br />

Model Gas Liquid<br />

AQNH09GALA0[CQ09 NA0]<br />

AQNH12GALA0[CQ12 NA0]<br />

Ø9.52 Ø6.35<br />

AQNH18GALA0[CQ18 NA0] Ø12.7 Ø6.35<br />

[Unit:mm]


5CSL0-06B<br />

1.5.5 Wiring diagrams<br />

1) Wiring diagrams<br />

2) PCB<br />

■ Main PCB<br />

CN_PWR<br />

■ Dis<strong>pl</strong>ay PCB<br />

CN_MOTOR<br />

CN_VANE2<br />

SW01 CN_DISPLAY CN_OPTION<br />

CN_VANE1<br />

CN_CC<br />

CN_ROOM<br />

CN_PIPE/IN<br />

CN_PIPE/OUT<br />

CN_REMO<br />

Wiring diagrams<br />

Console 129


Air flow and temperature distributions (reference data) 5CSL0-06B<br />

1.5.6 Air flow and temperature distributions (reference data)<br />

Models : 2.5 kW/3.5 kW<br />

Air velocity [m/s]<br />

2.7m<br />

2m<br />

1m<br />

3.0<br />

2.0<br />

0m<br />

2.0<br />

1.0<br />

0m 1m 2m 3m 4m 5m<br />

Temperature [°C]<br />

2.7m<br />

2m<br />

1m<br />

Models : 5.0 kW<br />

18<br />

20<br />

20<br />

0m<br />

18<br />

0m 1m 2m 3m 4m 5m<br />

Air velocity [m/s]<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

2.0<br />

0.5<br />

0m 1m 2m 3m 4m 5m<br />

Temperature [°C]<br />

2.7m<br />

2m<br />

1m<br />

23<br />

19<br />

16<br />

2.5<br />

17<br />

1.0<br />

17<br />

2.0<br />

1.5<br />

18<br />

18<br />

Cooling Heating<br />

0.5<br />

0m<br />

0m 1m 2m 3m 4m 5m<br />

1.0<br />

22<br />

0.5<br />

24<br />

0.5<br />

Air velocity [m/s]<br />

Temperature [°C]<br />

2.7m<br />

130 Console<br />

2.7m<br />

2m<br />

1m<br />

2m<br />

1m<br />

33<br />

3.0<br />

33<br />

30<br />

2.0<br />

0m<br />

2.0<br />

1.0<br />

0m 1m 2m 3m 4m 5m<br />

27<br />

30<br />

0m<br />

0m 1m 2m 3m 4m 5m<br />

Cooling Heating<br />

19<br />

23<br />

Air velocity [m/s]<br />

2.7m<br />

2m<br />

1m<br />

0m<br />

0m 1m 2m 3m 4m 5m<br />

Temperature [°C]<br />

2.7m<br />

2m<br />

1m<br />

32<br />

0.5<br />

34<br />

2.5<br />

2.0<br />

1.5<br />

0.5<br />

32<br />

1.0<br />

1.0<br />

32<br />

30<br />

0m<br />

0m 1m 2m 3m 4m 5m<br />

1.0<br />

30<br />

0.5<br />

0.5<br />

0.5<br />

0.5<br />

24<br />

0.5<br />

28


5CSL0-06B<br />

1.5.7 Sound levels<br />

Overall<br />

Microphone<br />

1m<br />

1m<br />

Sound Pressure Level<br />

Octave Band Sound Pressure Level (dB re 20μPa )<br />

AQNH09GALA0[CQ09 NA0]<br />

AQNH12GALA0[CQ12 NA0]<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

High<br />

Middle<br />

Low<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Octave Band Sound Pressure Level (dB re 20μPa )<br />

AQNH18GALA0[CQ18 NA0]<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

Notes:<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound levels<br />

Console 131<br />

High<br />

Middle<br />

Low<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


Controller 5CSL0-06B<br />

1.5.8 Controller<br />

The controls will look like the following. ON/OFF BUTTON<br />

Used to turn <strong>of</strong>f/on the unit.<br />

(Optional1)<br />

(Optional2)<br />

(Optional3)<br />

Operation Mode<br />

Cooling Operation<br />

Auto Operation or Auto Changeover<br />

Healthy Dehumidification Operation<br />

Heating Operation (Only heat pump)<br />

Air Circulation<br />

Signal transmitter<br />

OPERATION MODE SELECTION BUTTON<br />

Used to select the operation mode.<br />

ROOM TEMPERATURE SETTING BUTTONS<br />

Used to select the room temperature.<br />

INDOOR FAN SPEED SELECTION BUTTON<br />

Used to select fan speed in six steps low, medium-low,<br />

medium, medium-high, high and natural wind.<br />

HORIZONTAL VANE CONTROL BUTTON<br />

Used to set the desired vertical airflow direction.<br />

VERTICAL LOUVER CONTROL BUTTON(Optional)<br />

Used to set the desired horizontal airflow direction.<br />

AUTO CLEAN BUTTON<br />

Used to set auto clean.<br />

ENERGY SAVING COOLING BUTTON<br />

Used to save Energy.<br />

ROOM TEMPERATURE CHECKING BUTTON<br />

Used to check the room temperature.<br />

TIMER BUTTON(before adjusting)<br />

Used to set the current time and the time <strong>of</strong> starting / stopping.<br />

TIME ADJUSTING BUTTONS<br />

Used to adjust the time.<br />

TIMER SET/CLEAR BUTTON(after adjusting)<br />

Used to set and to cancel the timer operation.<br />

RESET BUTTON<br />

Used prior to resetting time.<br />

PLASMA BUTTON(Optional)<br />

Used to start or stop the <strong>pl</strong>asma-purification.<br />

LED LUMINOSITY BUTTON(Optional)<br />

Used to adjust LED luminosity.<br />

132 Console


5CSL0-06B<br />

Power sup<strong>pl</strong>y<br />

2. Outdoor<br />

2.1 DC Inverter SINGLE A (1Ø, 3Ø) , High Efficiency models(1Ø)<br />

2.1.1 Power sup<strong>pl</strong>y<br />

Type Outdoor unit Capacity (kW) Circuit breaker capacity Power sup<strong>pl</strong>y<br />

1Phase<br />

Inverter<br />

External wiring procedure<br />

AUUW096D[UU09W ULD] 2.5<br />

AUUW126D[UU12W ULD] 3.5<br />

AUUW186D [UU18W UED] 5.0<br />

AUUW186D1[UU18W UED1] 5.0<br />

AUUW246D[UU24W UED] 7.1<br />

- The power sup<strong>pl</strong>y work is needed only to the outdoor unit. The power sup<strong>pl</strong>y to the indoor unit is conducted through the<br />

transmission wiring. Therefore, the power sup<strong>pl</strong>y work can be carried out at just one <strong>pl</strong>ace <strong>of</strong> the outdoor unit. It will<br />

contribute to sim<strong>pl</strong>ify the work procedure and to save cost.<br />

- Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Circuit breaker<br />

Circuit breaker<br />

Power sup<strong>pl</strong>y<br />

Earth<br />

Power sup<strong>pl</strong>y<br />

Earth<br />

Outdoor unit<br />

Outdoor unit<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 133<br />

15A<br />

20A<br />

AUUW306D[UU30W UED] 8.0 30A<br />

AUUW366D[UU36W UED] 10.0<br />

AUUW426D[UU42W U3D] 12.5<br />

AUUW486D[UU48W U3D] 14.0 40A<br />

AUUW606D[UU60W U3D] 15.0<br />

AUUW368D[UU37W UED] 10.0 20A<br />

3Phase AUUW428D[UU43W U3D] 12.5<br />

Inverter AUUW488D[UU49W U3D] 14.0 25A<br />

AUUW608D[UU61W U3D] 15.0<br />

High AUUW186DH[UU18WH UED] 5.0<br />

1Ø, 220-240V, 50Hz<br />

3Ø, 380-415V, 50Hz<br />

Efficiency AUUW216DH[UU21WH U4D] 6.0 30A 1Ø, 220-240V, 50Hz<br />

Inverter AUUW246DH[UU24WH U4D] 7.1


List <strong>of</strong> functions 5CSL0-06B<br />

2.1.2 List <strong>of</strong> functions<br />

DC Inverter Single A (1Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Convenience Auto operation(Artificial intelligence)<br />

Auto Restart Operation<br />

CAC Network Central control(LGAP)<br />

Function PDI(Power Distribution Indicator)<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Convenience Auto operation(Artificial intelligence)<br />

Auto Restart Operation<br />

CAC Network Central control(LGAP)<br />

Function PDI(Power Distribution Indicator)<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

AUUW096D<br />

[UU09W ULD]<br />

AUUW126D<br />

[UU12W ULD]<br />

AUUW186D<br />

[UU18W UED]<br />

AUUW186D1<br />

[UU18W UED1]<br />

AUUW246D<br />

[UU24W UED]<br />

ˇ O O O O O<br />

- - - - O<br />

- - - - -<br />

- - - - -<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O O O<br />

(program logic) (program logic) (program logic) (program logic) (program logic)<br />

- - - - -<br />

AUUW306D<br />

[UU30W UED]<br />

AUUW366D<br />

[UU36W<br />

UED]<br />

AUUW426D<br />

[UU42W<br />

U3D]<br />

AUUW486D<br />

[UU48W<br />

U3D]<br />

AUUW606D<br />

[UU60W<br />

U3D]<br />

O O O O O<br />

O O O O O<br />

- - - - -<br />

- - - - -<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

O O O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O O O<br />

(program logic) (program logic) (program logic) (program logic) (program logic)<br />

- - - - -<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

134 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

DC Inverter Single A (3Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Auto operation(Artificial intelligence)<br />

Convenience<br />

Auto Restart Operation<br />

Central control(LGAP)<br />

CAC Network<br />

PDI(Power Distribution Indicator)<br />

Function<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

DC Inverter High Efficiency models (1Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Convenience Auto-changeover<br />

Auto Restart Operation<br />

CAC Network Central control(LGAP)<br />

Function PDI(Power Distribution Indicator)<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

AUUW368D<br />

[UU37W UED]<br />

AUUW428D<br />

[UU43W U3D]<br />

AUUW488D<br />

[UU49W U3D]<br />

List <strong>of</strong> functions<br />

AUUW608D<br />

[UU61W U3D]<br />

O O O O<br />

O O O O<br />

O - - -<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O O<br />

(program logic) (program logic) (program logic) (program logic)<br />

- - - -<br />

AUUW186DH<br />

[UU18WH UED]<br />

AUUW216DH<br />

[UU21WH U4D]<br />

AUUW246DH<br />

[UU24WH U4D]<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O<br />

(program logic) (program logic) (program logic)<br />

- - -<br />

Notes<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate<br />

package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 135


Specifications 5CSL0-06B<br />

2.1.3 Specifications<br />

DC Inverter Single A (1Ø)<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Cassette<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Cassette<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Ceiling & floor<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Ceiling & floor<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

ATNH09GRLED<br />

[UT09 NRD]<br />

AUUW096D<br />

[UU09W ULD]<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

AUUW126D<br />

[UU12W ULD]<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

AUUW186D<br />

[UU18W UED]<br />

1.0 ~ 2.5 ~ 2.75 1.36 ~ 3.4 ~ 3.74 2.0 ~ 5.0 ~ 5.5<br />

1.2 ~ 3.0 ~ 3.3 1.60 ~ 4.0 ~ 4.4 2.2 ~ 5.5 ~ 6.05<br />

0.75 1.06 1.56<br />

0.81 1.1 1.52<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

AUUW186D1<br />

[UU18W UED1]<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

AUUW246D<br />

[UU24W UED]<br />

ATNH30GPLED<br />

[UT30 NPD]<br />

AUUW306D<br />

[UU30W UED]<br />

2.0 ~ 5.0 ~ 5.5 2.84 ~ 7.1 ~ 7.81 3.2 ~ 8.0 ~ 8.8<br />

2.2 ~ 5.5 ~ 6.05 3.2 ~ 8.0 ~ 8.8 3.6 ~ 9.0 ~ 9.9<br />

1.56 2.15 2.65<br />

1.52 2.34 2.8<br />

AVNH09GELAD<br />

[UV09 NED]<br />

AUUW096D<br />

[UU09W ULD]<br />

AVNH12GELAD<br />

[UV12 NED]<br />

AUUW126D<br />

[UU12W ULD]<br />

UVNH186BLAD<br />

[UV18 NBD]<br />

AUUW186D<br />

[UU18W UED]<br />

1.0 ~ 2.5 ~ 2.75 1.32 ~ 3.3 ~ 3.63 1.92 ~ 4.8 ~ 5.28<br />

1.2 ~ 3.0 ~ 3.3 1.52 ~ 3.8 ~ 4.18 2.04 ~ 5.1 ~ 5.61<br />

0.75 1.09 1.49<br />

0.83 1.18 1.49<br />

UVNH186BLAD<br />

[UV18 NBD]<br />

AUUW186D1<br />

[UU18W UED1]<br />

UVNH246BLAD<br />

[UV24 NBD]<br />

AUUW246D<br />

[UU24W UED]<br />

UVNH306BLAD<br />

[UV30 NBD]<br />

AUUW306D<br />

[UU30W UED]<br />

1.92 ~ 4.8 ~ 5.28 2.8 ~ 7.0 ~ 7.7 3.04 ~ 7.6 ~ 8.36<br />

2.04 ~ 5.1 ~ 5.61 3.08 ~ 7.7 ~ 8.47 3.36 ~ 8.4 ~ 9.24<br />

1.49 2.3 2.68<br />

1.49 2.74 2.99<br />

136 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Specifications<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Duct<br />

ABNH186HLAD<br />

ABNH186HLAD<br />

ABNH246HLAD<br />

ABNH306GLAD<br />

[UB18 NHD]<br />

[UB18 NHD]<br />

[UB24 NHD]<br />

[UB30 NGD]<br />

Outdoor Units<br />

AUUW186D<br />

AUUW186D1<br />

AUUW246D<br />

AUUW306D<br />

[UU18W UED]<br />

[UU18W UED1]<br />

[UU24W UED]<br />

[UU30W UED]<br />

Nominal Capacity Cooling kW 1.98 ~ 4.95 ~ 5.44 1.98 ~ 4.95 ~ 5.44 2.84 ~ 7.1 ~ 7.81 3.2 ~ 8.0 ~ 8.8<br />

(Min~Rated~Max) Heating kW 2.4 ~ 6.0 ~ 6.6 2.4 ~ 6.0 ~ 6.6 3.2 ~ 8.0 ~ 8.8 3.6 ~ 9.0 ~ 9.9<br />

Nominal Input Cooling kW<br />

1.54 1.54 2.62 2.65<br />

(Min~Rated~Max) Heating kW<br />

1.66 1.66 2.75 2.49<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Console<br />

AQNH09GALA0<br />

AQNH12GALA0<br />

AQNH18GALA0<br />

AQNH18GALA0<br />

[CQ09 NA0]<br />

[CQ12 NA0]<br />

[CQ18 NA0]<br />

[CQ18 NA0]<br />

Outdoor Units<br />

AUUW096D<br />

AUUW126D<br />

AUUW186D<br />

AUUW186D1<br />

[UU09W ULD]<br />

[UU12W ULD]<br />

[UU18W UED]<br />

[UU18W UED1]<br />

Nominal Capacity Cooling kW 1.3 ~ 2.55 ~ 3.4 1.36 ~ 3.5 ~ 3.74 2.0 ~ 4.6 ~ 5.5 2.0 ~ 4.6 ~ 5.5<br />

(Min~Rated~Max) Heating kW 1.36 ~ 3.1 ~ 4.2 1.6 ~ 4.0 ~ 4.4 2.2 ~ 5.0 ~ 6.0 2.2 ~ 5.0 ~ 6.0<br />

Nominal Input Cooling kW<br />

0.635 1.06 1.49 1.49<br />

(Min~Rated~Max) Heating kW<br />

0.74 1.08 1.46 1.46<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Cassette<br />

ATNH36GNLED ATNH42GMLED ATNH48GMLED ATNH60GMLED<br />

[UT36 NND]<br />

[UT42 NMD]<br />

[UT48 NMD]<br />

[UT60 NMD]<br />

Outdoor Units<br />

AUUW366D<br />

AUUW426D<br />

AUUW486D<br />

AUUW606D<br />

[UU36W UED] [UU42W U3D] [UU48W U3D] [UU60W U3D]<br />

Nominal Capacity Cooling kW 4.0 ~ 10.0 ~ 11.0 5.0 ~ 12.5 ~ 13.8 5.48 ~ 13.9~ 15.7 5.92 ~ 14.6 ~ 16.3<br />

(Min~Rated~Max) Heating kW 4.4 ~ 11.0 ~ 12.1 5.6 ~ 14.0 ~ 15.4 6.4 ~ 15.5 ~ 17.6 6.8 ~ 16.9 ~ 18.7<br />

Nominal Input Cooling kW<br />

3.12 3.89 4.61 5.40<br />

(Min~Rated~Max) Heating kW<br />

3.23 3.87 4.54 5.50<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Ceiling & floor<br />

UVNH366KLAD UVNH426LLAD UVNH486LLAD UVNH606LLAD<br />

[UV36 NKD]<br />

[UV42 NLD]<br />

[UV48 NLD]<br />

[UV60 NLD]<br />

Outdoor Units<br />

AUUW366D<br />

AUUW426D<br />

AUUW486D<br />

AUUW606D<br />

[UU36W UED] [UU48W U3D] [UU48W U3D] [UU60W U3D]<br />

Nominal Capacity Cooling kW 3.8 ~ 9.5 ~ 10.5 5.0 ~ 12.5 ~ 13.8 5.32 ~ 13.3 ~ 14.6 5.72 ~ 14.4 ~ 15.7<br />

(Min~Rated~Max) Heating kW 4.2 ~ 10.5 ~ 11.6 5.6 ~ 13.6 ~ 15.4 6.4 ~ 15.3 ~ 17.6 6.8 ~ 16.8 ~ 18.7<br />

Nominal Input Cooling kW<br />

3.32 4.00 4.00 5.30<br />

(Min~Rated~Max) Heating kW<br />

3.27 3.98 3.98 5.50<br />

Nominal Capacity and Nominal Input<br />

Indoor Units - Duct<br />

ABNH366GLAD ABNH426RLAD ABNH486RLAD ABNH606RLAD<br />

[UB36 NGD]<br />

[UB42 NRD]<br />

[UB48 NRD]<br />

[UB60 NRD]<br />

Outdoor Units<br />

AUUW366D<br />

AUUW486D<br />

AUUW486D<br />

AUUW606D<br />

[UU36W UED] [UU48W U3D] [UU48W U3D] [UU60W U3D]<br />

Nominal Capacity Cooling kW 4.0 ~ 9.8 ~ 11.0 5.0 ~ 12.5 ~ 13.8 5.6 ~ 14.0 ~ 15.4 5.92 ~ 14.8 ~ 16.3<br />

(Min~Rated~Max) Heating kW 4.48 ~ 11.2 ~ 12.3 5.6 ~ 14.0 ~ 15.4 6.6 ~ 16.4 ~ 18.2 6.8 ~ 16.8 ~ 18.7<br />

Nominal Input Cooling kW<br />

3.25 4.15 4.65 5.26<br />

(Min~Rated~Max) Heating kW<br />

3.28 3.73 4.54 4.57<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 137


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

A<br />

AUUW096D<br />

[UU09W ULD]<br />

AUUW126D<br />

[UU12W ULD]<br />

AUUW186D<br />

[UU18W UED]<br />

3.42/3.87 5.0/5.1 7.1/7.2<br />

- - -<br />

1, 220-240, 50 1, 220-240, 50 1, 220-240, 50<br />

3*2.5 3*2.5 3*2.5<br />

4*0.75 4*0.75 4*0.75<br />

770*540*245 770*540*245 870*655*320<br />

32 32 46<br />

Rotary Rotary e-Scroll<br />

1 1 1<br />

5RS102XAA21 5RS102XAA21 5CS130XCC03<br />

BLDC BLDC BLDC<br />

320 320 480<br />

FV50S (PVE) FV50S (PVE) RB68A (POE)<br />

1,000 1,000 1,300<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

17 17 18<br />

2R,24C 2R,24C 2R,28C<br />

7 7 7<br />

Reversing cycle Reversing cycle Reversing cycle<br />

SIC-67FV-D843-1 SIC-67FV-D843-1 EHDS82ALG<br />

0.043 0.043 0.084<br />

- - -<br />

Propeller Propeller Propeller<br />

400 400 460<br />

Side Discharge Side Discharge Side Discharge<br />

32 32 50<br />

48/42 48/42 51/45<br />

6.35 6.35 6.35<br />

9.52 9.52 12.7<br />

15/10 15/10 40/30<br />

20 20 20<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

AUUW186D1<br />

[UU18W UED1]<br />

7.1/7.1<br />

(CST/CVT/Console)<br />

7.01/7.42<br />

(Duct)<br />

-<br />

1, 220-240, 50<br />

3*2.5<br />

4*0.75<br />

870*655*320<br />

52<br />

Rotary<br />

1<br />

GJT240DAA<br />

BLDC<br />

900<br />

FVC68D<br />

1,500<br />

R410A<br />

EEV<br />

18<br />

2R, 28C<br />

7<br />

Reversing cycle<br />

EAU52759301<br />

0.084<br />

-<br />

Propeller<br />

460<br />

Side Discharge<br />

50<br />

51/45<br />

6.35<br />

12.7<br />

40/30<br />

20(Over 5.0m)<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

138 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Specifications<br />

AUUW246D<br />

AUUW306D<br />

AUUW366D<br />

[UU24W UED]<br />

[UU30W UED]<br />

[UU36W UED]<br />

10.0/10.7 12.0/13.0 14.0/14.2<br />

- - -<br />

1, 220-240, 50 1, 220-240, 50 1, 220-240, 50<br />

3*2.5 3*2.5 3*2.5<br />

4*0.75 4*0.75 4*0.75<br />

870*808*320 870*808*320 870*1,060*320<br />

60 60 75<br />

Rotary Rotary Rotary<br />

1 1 1<br />

5KD240XAE21 5KD240XAE21 5JD420XAD22<br />

BLDC BLDC BLDC<br />

900 900 1,300<br />

FV50S(PVE) FV50S(PVE) FV50S(PVE)<br />

2,000 2,000 2,500<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

18 18 18<br />

2R,36C 2R,36C 2R,24C X 2<br />

7 7 7<br />

Reversing cycle Reversing cycle Reversing cycle<br />

SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-67FV-D843-1<br />

0.124 0.124 0.043 x 2<br />

- - -<br />

Propeller Propeller Propeller<br />

520 520 400<br />

Side Discharge Side Discharge Side Discharge<br />

58 58 32 X 2<br />

52/46 52/46 56/52<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

50/30 50/30 50/30<br />

35 35 50<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 139


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

AUUW426D<br />

AUUW486D<br />

AUUW606D<br />

[UU42W U3D]<br />

[UU48W U3D]<br />

[UU60W U3D]<br />

17.7/16.7 20.5/20.5 24.7/23.5<br />

- - -<br />

1, 220-240, 50 1, 220-240, 50 1, 220-240, 50<br />

3*5.0 3*5.0 3*5.0<br />

4*0.75 4*0.75 4*0.75<br />

950*1,380*330 950*1,380*330 950*1,380*330<br />

103 103 103<br />

Rotary Rotary Rotary<br />

1 1 1<br />

5JD420XAD22 5JD420XAD22 5JD420XAD22<br />

BLDC BLDC BLDC<br />

1,300 1,300 1,300<br />

FV50S(PVE) FV50S(PVE) FV50S(PVE)<br />

3,600 3,600 3,600<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

17 17 17<br />

2R,32C x 2 2R,32C x 2 2R,32C x 2<br />

7 7 7<br />

Reversing cycle Reversing cycle Reversing cycle<br />

SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3<br />

0.124 X 2 0.124 X 2 0.124 X 2<br />

- - -<br />

Propeller Propeller Propeller<br />

526 526 526<br />

Side Discharge Side Discharge Side Discharge<br />

55 X 2 55 X 2 55(1,942) X 2<br />

55/51 55/51 55/51<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

75/30 75/30 75/30<br />

40 40 40<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

140 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

DC Inverter Single A (3Ø)<br />

Specifications<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

ATNH36GNLED ATNH42GMLED ATNH48GMLED ATNH60GMLED<br />

[UT36 NND]<br />

[UT42 NMD]<br />

[UT48 NMD]<br />

[UT60 NMD]<br />

Outdoor Units<br />

AUUW368D<br />

AUUW428D<br />

AUUW488D<br />

AUUW608D<br />

[UU37W UED] [UU43W U3D] [UU49W U3D] [UU61W U3D]<br />

Nominal Capacity Cooling kW 4.0 ~ 10.0 ~ 11.0 5.0 ~ 12.5 ~ 13.8 5.48 ~ 13.8~ 15.7 5.92 ~ 14.7 ~ 16.3<br />

(Min~Rated~Max) Heating kW 4.4 ~ 11.0 ~ 12.1 5.6 ~ 14.0 ~ 15.4 6.4 ~ 15.9 ~ 17.6 6.8 ~ 17.0 ~ 18.7<br />

Nominal Input Cooling kW<br />

3.12 3.89 4.58 5.63<br />

(Min~Rated~Max) Heating kW<br />

3.23 3.87 4.66 5.64<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

UVNH366KLAD UVNH426LLAD UVNH486LLAD UVNH606LLAD<br />

[UV36 NKD]<br />

[UV42 NLD]<br />

[UV48 NLD]<br />

[UV60 NLD]<br />

Outdoor Units<br />

AUUW368D<br />

AUUW428D<br />

AUUW488D<br />

AUUW608D<br />

[UU37W UED] [UU43W U3D] [UU49W U3D] [UU61W U3D]<br />

Nominal Capacity Cooling kW 3.8 ~ 9.5 ~ 10.5 5.0 ~ 12.5 ~ 13.8 5.32 ~ 13.3 ~ 14.6 5.72 ~ 14.4 ~ 15.7<br />

(Min~Rated~Max) Heating kW 4.2 ~ 10.5 ~ 11.6 5.6 ~ 13.6 ~ 15.4 6.4 ~ 15.3 ~ 17.6 6.8 ~ 16.8~ 18.7<br />

Nominal Input Cooling kW<br />

3.32 4.00 4.41 5.30<br />

(Min~Rated~Max) Heating kW<br />

3.27 3.98 4.76 5.50<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

ABNH366GLAD ABNH426RLAD ABNH486RLAD ABNH606RLAD<br />

[UB36 NGD]<br />

[UB42 NRD]<br />

[UB48 NRD]<br />

[UB60 NRD]<br />

Outdoor Units<br />

AUUW368D<br />

AUUW428D<br />

AUUW488D<br />

AUUW608D<br />

[UU37W UED] [UU43W U3D] [UU49W U3D] [UU61W U3D]<br />

Nominal Capacity Cooling kW 4.0 ~ 10.0 ~ 11.0 5.0 ~ 12.5 ~ 13.8 5.6 ~ 14.0 ~ 15.4 5.92 ~ 14.8 ~ 16.3<br />

(Min~Rated~Max) Heating kW 4.48 ~ 11.2 ~ 12.3 5.6 ~ 14.0 ~ 15.4 6.6 ~ 16.7 ~ 18.2 6.8 ~ 17.0 ~ 18.7<br />

Nominal Input Cooling kW<br />

3.51 4.15 4.65 5.26<br />

(Min~Rated~Max) Heating kW<br />

3.49 3.82 4.57 4.70<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 141


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

AUUW368D<br />

AUUW428D<br />

AUUW488D<br />

[UU37W UED]<br />

[UU43W U3D]<br />

[UU49W U3D]<br />

3.7/3.9 4.09/4.28 4.98/5.23<br />

- - -<br />

3 ,380-415 , 50 3 ,380-415 , 50 3 ,380-415 , 50<br />

5 x 2.5 5 x 2.5 5 x 2.5<br />

4*0.75 4*0.75 4*0.75<br />

870*1,060*320 950*1,380*330 950*1,380*330<br />

80 103 103<br />

Rotary Rotary Rotary<br />

1 1 1<br />

5KD240XBA21 5JD420XBB22 5JD420XBB22<br />

BLDC BLDC BLDC<br />

900 1,300 1,300<br />

FV50S (PVE) FV50S (PVE) FV50S (PVE)<br />

2,650 3,600 3,600(127)<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

18 17 17<br />

2R,24C 2R,32C 2R,32C<br />

7 7 7<br />

Reversing cycle Reversing cycle Reversing cycle<br />

SIC - 67FV-D843-1 SIC - 72FW- 8F1124-3 SIC - 72FW- 8F1124-3<br />

0.043*2 0.124*2 0.124*2<br />

- - -<br />

Propeller Propeller Propeller<br />

2/400 2/526 2/526<br />

Side Discharge Side Discharge Side Discharge<br />

32*2 55*2 55*2<br />

54/50 55/51 55/51<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

50/30 75/30 75/30<br />

45 40 40<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

142 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

AUUW608D<br />

[UU61W U3D]<br />

5.91/5.79<br />

-<br />

3 ,380-415 , 50<br />

5 x 2.5<br />

4*0.75<br />

950*1,380*330<br />

103<br />

Rotary<br />

1<br />

5JD420XBB22<br />

BLDC<br />

1,300<br />

FV50S (PVE)<br />

3,600(127)<br />

R410A<br />

EEV<br />

17<br />

2R,32C<br />

7<br />

Reversing cycle<br />

SIC - 72FW- 8F1124-3<br />

0.124*2<br />

-<br />

Propeller<br />

2/526<br />

Side Discharge<br />

55*2<br />

55/51<br />

9.52<br />

15.88<br />

75/30<br />

40<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Specifications<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 143


Specifications 5CSL0-06B<br />

DC Inverter High Efficiency models (1Ø)<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

AUUW186DH<br />

[UU18WH UED]<br />

ATNH21GNLED<br />

[UT21 NND]<br />

AUUW216DH<br />

[UU21WH U4D]<br />

ATNH24GPLED<br />

[UT24 NPD]<br />

AUUW246DH<br />

[UU24WH U4D]<br />

2.0 ~ 5.0 ~ 5.5 2.8 ~ 6.0 ~ 8.0 2.8 ~ 7.0 ~ 8.4<br />

2.2 ~ 5.5 ~ 6.05 3.2 ~ 7.0 ~ 9.0 3.2 ~ 8.0 ~ 9.4<br />

1.35 1.56 1.92<br />

1.35 1.66 1.93<br />

144 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, v, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Quantity<br />

Model<br />

Motor Type<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge(at 7.5m) g<br />

Type<br />

Control<br />

Heat exchanger Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Tube Size (OD) mm<br />

Defrosting Method<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Type<br />

Fan No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level (H/L) Sound Press,1m dB(A)+3<br />

Piping connections Liquid mm<br />

Gas mm<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Specifications<br />

AUUW186DH<br />

AUUW216DH<br />

AUUW246DH<br />

[UU18WH UED] [UU21WH U4D] [UU24WH U4D]<br />

5.0/5.5 6.9/7.4 8.5/8.6<br />

- - -<br />

1, 220-240, 50 1, 220-240, 50 1, 220-240, 50<br />

3*2.5 3*2.5 3*2.5<br />

4*0.75 4*0.75 4*0.75<br />

870*808*320 950*834*330 950*834*330<br />

52 52 52<br />

Rotary Rotary Rotary<br />

1 1 1<br />

5KD240XAE21 5KD240XAE21 5KD240XAE21<br />

BLDC BLDC BLDC<br />

900 900 900<br />

FV50S(PVE) FV50S(PVE) FV50S(PVE)<br />

1,500 1,500 1,500<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

18 17 17<br />

2R,36C 2R,38C 2R,38C<br />

7 7 7<br />

Reversing cycle Reversing cycle Reversing cycle<br />

SIC-72FW-F1124 SIC-72FW-F1124 SIC-72FW-F1124<br />

0.124 0.124 0.124<br />

- - -<br />

BLDC BLDC BLDC<br />

528 528 528<br />

Side Side Side<br />

50 58 58<br />

52/46 55/49 55/49<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

40/30 50/30 50/30<br />

20 40 40<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 145


Dimensions<br />

2.1.4 Dimensions<br />

OUTDOOR UNIT<br />

AUUW096D[UU09W ULD]<br />

AUUW126D[UU12W ULD]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

6<br />

Earth screw<br />

SVC valve cover<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

Technical Specification<br />

AUUW126D[UU12W ULD]<br />

1/ 220-240 / 50<br />

AUUW096D[UU09W ULD]<br />

1/ 220-240 / 50<br />

Model name<br />

Simultaneous operation<br />

Refer to combination table<br />

Refer to combination table<br />

6.35<br />

9.52<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

146 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

6.35<br />

9.52<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Note<br />

CHASSIS CODE: UL<br />

OUTDOOR UNIT<br />

76, Seongsan-dong, Changwon City, Gyeongnam,<br />

641-713, Korea<br />

www.lge.com/airconditioner


5CSL0-06B Dimensions<br />

OUTDOOR UNIT<br />

AUUW186D [UU18W UED]<br />

AUUW186D1[UU18W UED1]<br />

Part Name Remark<br />

870<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

160<br />

546<br />

6<br />

340<br />

360<br />

Earth screw<br />

SVC valve cover<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

10<br />

54.6<br />

Technical Specification<br />

AUUW186D1[UU18W UED1]<br />

1/ 220-240 / 50<br />

AUUW186D[UU18W UED]<br />

1/ 220-240 / 50<br />

Model name<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Simultaneous operation Refer to combination table<br />

301<br />

Heating Capacity<br />

320<br />

6.35<br />

12.7<br />

6.35<br />

12.7<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 147<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Ø531<br />

4<br />

Note<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

1<br />

513<br />

630<br />

655<br />

2<br />

319<br />

3<br />

5<br />

50<br />

80<br />

25<br />

CHASSIS CODE: UE<br />

OUTDOOR UNIT<br />

76, Seongsan-dong, Changwon City, Gyeongnam,<br />

641-713, Korea<br />

www.lge.com/airconditioner


Dimensions<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

6<br />

Earth screw<br />

SVC valve cover<br />

AUUW246D[UU24W UED] AUUW306D[UU30W UED]<br />

1/ 220-240 / 50<br />

1/ 220-240 / 50<br />

Simultaneous operation<br />

Refer to combination table<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

148 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

9.52<br />

15.88<br />

9.52<br />

15.88<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Note<br />

1<br />

OUTDOOR UNIT


5CSL0-06B Dimensions<br />

AUUW366D[UU36W UED]<br />

AUUW368D[UU37W UED]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

6<br />

Earth screw<br />

SVC valve cover<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

AUUW366D[UU36W UED] AUUW368D[UU37W UED]<br />

1/ 220-240 / 50<br />

3/ 380-415 / 50<br />

Simultaneous operation<br />

_Refer<br />

to combination table<br />

9.52<br />

9.52<br />

15.88<br />

15.88<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 149<br />

Note<br />

OUTDOOR UNIT


Dimensions<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

4<br />

Supporter<br />

AUUW606D[UU60W U3D]<br />

1/ 220-240 / 50<br />

AUUW486D[UU48W U3D]<br />

AUUW426D[UU42W U3D]<br />

Model name<br />

1/ 220-240 / 50<br />

1/ 220-240 / 50<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

9.52<br />

15.88<br />

Simultaneous operation<br />

Refer to combination table<br />

9.52<br />

15.88<br />

Heating Capacity<br />

9.52<br />

15.88<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

150 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Note<br />

490<br />

OUTDOOR UNIT


5CSL0-06B Dimensions<br />

OUTDOOR UNIT<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

Technical Specification<br />

Model name<br />

4<br />

Supporter<br />

AUUW608D[UU61W U3D]<br />

3/ 380-415 / 50<br />

AUUW488D[UU49W U3D]<br />

3/ 380-415 / 50<br />

AUUW428D[UU43W U3D]<br />

3/ 380-415 / 50<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Simultaneous operation<br />

Refer to combination table<br />

Heating Capacity<br />

9.52<br />

15.88<br />

9.52<br />

15.88<br />

9.52<br />

15.88<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Note<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 151<br />

490<br />

CHASSIS CODE: U3<br />

OUTDOOR UNIT<br />

76, Seongsan-dong, Changwon City, Gyeongnam,<br />

641-713, Korea<br />

www.lge.com/airconditioner


Dimensions<br />

OUTDOOR UNIT<br />

AUUW186DH[UU18WH UED]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

6<br />

Earth screw<br />

SVC valve cover<br />

Technical Specification<br />

AUUW186DH[UU18WH UED]<br />

1/ 220-240 / 50<br />

Simultaneous 4.04 operation<br />

Refer to combination 13,800 table<br />

9.52<br />

15.88<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

152 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Note<br />

1<br />

CHASSIS CODE: UE1<br />

76, Seongsan-dong, Changwon City, Gyeongnam,<br />

641-713, Korea<br />

www.lge.com/airconditioner


5CSL0-06B Dimensions<br />

OUTDOOR UNIT<br />

AUUW216DH [UU21WH U4D]<br />

AUUW246DH [UU24WH U4D]<br />

Remark<br />

Part Name<br />

Air discharge grille<br />

Item No.<br />

1<br />

Gas pipe connection<br />

2<br />

Liquid pipe connection<br />

Power & transmission connection<br />

3<br />

4<br />

Earth screw<br />

5<br />

Technical Specification<br />

AUUW216DH [UU21WH U4D] AUUW246DH [UU24WH U4D]<br />

1/ 220-240 / 50<br />

1/ 220-240 / 50<br />

Simultaneous operation<br />

Refer to combination table<br />

9.52<br />

9.52<br />

15.88<br />

15.88<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 153<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Note<br />

CHASSIS CODE: U4<br />

76, Seongsan-dong, Changwon City, Gyeongnam,<br />

641-713, Korea<br />

www.lge.com/airconditioner


Piping diagrams<br />

2.1.5 Piping diagrams<br />

Models : AUUW096D[UU09W ULD], AUUW126D[UU12W ULD]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 9.52mm)<br />

Liquid<br />

(Ø 6.35mm)<br />

EEV<br />

Accumulator<br />

5CSL0-06B<br />

154 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

Th4<br />

Th3<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2


5CSL0-06B Piping diagrams<br />

Models : AUUW186D[UU18W UED]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 9.52mm)<br />

Liquid<br />

(Ø 6.35mm)<br />

EEV<br />

Accumulator<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 155<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

OUTDOOR UNIT<br />

Th4<br />

Th3<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2


Piping diagrams 5CSL0-06B<br />

Models : AUUW186D1[UU18W UED1]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 12.7mm)<br />

Liquid<br />

(Ø 6.35mm)<br />

E.E.V.<br />

Accumulator<br />

r<br />

156 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

OUTDOOR UNIT<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2<br />

Th5 Thermistor for condenser middle pipe temperature CN_TH4<br />

Th4<br />

Heat<br />

Exchanger<br />

Th5<br />

Th3


5CSL0-06B<br />

Models : AUUW246D[UU24W UED], AUUW306D[UU30W UED]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

EEV<br />

Accumulator<br />

r<br />

Piping diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 157<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

Th4<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2<br />

Th3


Piping diagrams 5CSL0-06B<br />

Models : AUUW366D[UU36W UED], AUUW426D[UU42W U3D], AUUW486D[UU48W U3D], AUUW606D[UU60W U3D],<br />

AUUW428D[UU43W U3D], AUUW488D[UU49W U3D], AUUW608D[UU61W U3D]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

EEV<br />

Accumulator<br />

r<br />

Th1<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2<br />

158 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Th2<br />

Th3<br />

Th4


5CSL0-06B<br />

Models : AUUW368D[UU37W UED]<br />

Field piping<br />

Gas Ø15.88mm<br />

Field piping<br />

Liquid Ø9.52mm<br />

Accumulator<br />

Low Pressure<br />

Switch<br />

Solenoid<br />

valve<br />

Th1<br />

Inverter<br />

Compressor<br />

Reversing<br />

Valve<br />

Oil<br />

Separator<br />

Piping diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 159<br />

Th2<br />

High Pressure Switch<br />

EEV<br />

.<br />

Th3<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_EEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH3<br />

Th2 Thermistor for discharge pipe temperature CN_TH3<br />

Th3 Thermistor for condenser pipe temperature CN_TH2<br />

Th4 Thermistor for outdoor air temperature CN_TH2<br />

Th4


Piping diagrams 5CSL0-06B<br />

Models: AUUW186DH[UU18WH UED], , AUUW216DH [UU21WH U4D], AUUW246DH [UU24WH U4D]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

E.E.V.<br />

Accumulator<br />

r<br />

160 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN-EEV<br />

Th1 Thermistor for suction pipe temperature CN-TH3<br />

Th2 Thermistor for discharge pipe temperature CN-TH3<br />

Th3 Thermistor for condenser pipe temperature CN-TH2<br />

Th4 Thermistor for outdoor air temperature CN-TH2<br />

Th5 Thermistor for condenser middle pipe temperature CN-TH4<br />

Th4<br />

Heat<br />

Exchanger<br />

Th5<br />

Th3


5CSL0-06B<br />

2.1.6 Wiring diagrams<br />

Models : AUUW096D[UU09W ULD], AUUW126D[UU12W ULD]<br />

Notes:<br />

BL<br />

RD<br />

YL<br />

PSCM<br />

Phase current<br />

detector<br />

IPM<br />

BLUE<br />

RED<br />

YELLOW<br />

BK<br />

OR<br />

GN/YL<br />

SMPS<br />

CN_MOTOR<br />

BLACK<br />

ORANGE<br />

GREEN/YELLOW<br />

4WAY<br />

DC LINK<br />

VOLTAGE<br />

ERROR<br />

DISPLAY<br />

CN_EEV<br />

EEPROM<br />

Wiring diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 161<br />

BR<br />

WH<br />

CURRENT<br />

DETECTOR<br />

CN_CENTRAL<br />

BROWN<br />

WHITE<br />

FIELD WIRING<br />

EMC<br />

CN_TH1(PIPE/AIR)<br />

CN_TH1(DIS/SUC)<br />

CN_FLASH(WRITER)<br />

CN_LGMV


Wiring diagrams 5CSL0-06B<br />

Models : AUUW186D[UU18W UED]<br />

Notes:<br />

BL<br />

RD<br />

YL<br />

PSCM<br />

Phase current<br />

detector<br />

BLUE<br />

RED<br />

YELLOW<br />

IPM<br />

PSC OUT<br />

DC LINK<br />

VOLTAGE<br />

SMPS<br />

BK<br />

OR<br />

GN/YL<br />

CN_MOTOR<br />

DIP SW<br />

BLACK<br />

ORANGE<br />

GREEN/YELLOW<br />

4WAY<br />

EEPROM<br />

ERROR<br />

DISPLAY<br />

CN_CENTRAL<br />

CN_EEV<br />

CURRENT<br />

DETECTOR<br />

CN_COM<br />

162 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

BR<br />

WH<br />

BROWN<br />

WHITE<br />

FIELD WIRING<br />

EMC<br />

CN_TH1(SUC/DIS)<br />

COMMUNICATION<br />

PART<br />

CN_TH2(AIR/PIPE)<br />

CN_FLASH(WRITER)<br />

CN_LGMV


5CSL0-06B<br />

Models : AUUW186D1[UU18W UED1]<br />

CN-PFC-OUT<br />

CN-MOTOR1<br />

CN-PFC-IN CN_4WAY<br />

CN_EEV1<br />

CN_CENTRAL CN_COM<br />

CN_TH3<br />

CN_TH2<br />

CN_TH4<br />

CN_FLASH<br />

CN_LGMV<br />

CN_CP(N)<br />

CN_CP(L)<br />

Wiring diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 163


Wiring diagrams 5CSL0-06B<br />

Models : AUUW246D[UU24W UED], AUUW306D [UU30W UED], AUUW186DH [UU18WH UED]<br />

CN-PFC-OUT<br />

DC LINK VOLTAGE<br />

PFC MODULE<br />

PHASE CURRENT<br />

DETECTOR<br />

IPM<br />

CN-PFC-IN<br />

SMPS<br />

CN-MOTOR1<br />

ERROR<br />

DISPLAY CURRENT<br />

CN 4WAY CN_H/P DETECTOR EMC<br />

DIP SW<br />

CN_LEV1<br />

CN_CENTRAL<br />

CN_COM<br />

CN_TH3<br />

CN_TH2<br />

CN_FLASH(WRITER)<br />

CN_LGMV<br />

COMMUNICATION PART<br />

164 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW366D[UU36W UED]<br />

DC LINK VOLTAGE<br />

PFC MODULE<br />

PHASE CURRENT<br />

DETECTOR<br />

CN-PFC-OUT<br />

IPM<br />

CN-PFC-IN<br />

ERROR<br />

DISPLAY CURRENT<br />

CN 4WAY CN_H/P DETECTOR EMC<br />

CN-MOTOR1 DIP SW CN_LEV1<br />

SMPS<br />

CN-MOTOR2<br />

EEPROM<br />

CN_COM<br />

CN_TH3<br />

CN_TH2<br />

Wiring diagrams<br />

CN_FLASH(WRITER)<br />

CN_LGMV<br />

COMMUNICATION PART<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 165


Wiring diagrams 5CSL0-06B<br />

Models : AUUW426D[UU42W U3D], AUUW486D[UU48W U3D], AUUW606D[UU60W U3D]<br />

CN-<br />

4WAY<br />

CN-H/PRESS<br />

CENTRAL<br />

CONTROLLER<br />

POWER SUPPLY<br />

MAIN PCB ASSY<br />

CN-POWER<br />

CN-COMM<br />

CN-EEV1<br />

CN-COM(INV)<br />

CN-JIG_PC<br />

CN-CENTRAL<br />

CN-TH1<br />

CN-TH2<br />

CN-WRITER<br />

CN-FLASH<br />

CN-<br />

MAIN(COM)<br />

CN-<br />

MOTOR2<br />

CN-<br />

MOTOR1<br />

INVERTER PCB ASSY<br />

CN_ POWER<br />

CN(N) CN(L)<br />

166 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW368D [UU37W UED]<br />

CN_14-2(IU+)<br />

CN_14-4(IV+)<br />

CN_14-3(IV-)<br />

CN_IPM<br />

CN_GATE2<br />

CN_GATE1<br />

CN_14-1(IU-)<br />

TAB1<br />

CN_TH2<br />

CN_TH3<br />

CN_IPM(N)<br />

CN_LEV1<br />

CN_PRESS<br />

CN_IPM(P) CN_COIL(IN)<br />

CN_OIL/S<br />

CN_T<br />

CN_S<br />

CN_R<br />

CN_FAN(A)<br />

CN_POWER<br />

CN_FAN(B)<br />

CN_N<br />

Wiring diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 167<br />

CN_PWR<br />

CN_INV/HT<br />

CN_4WAY<br />

CN_PHASE<br />

CN_COM


Wiring diagrams 5CSL0-06B<br />

Models : AUUW428D[UU43W U3D], AUUW488D[UU49W U3D], AUUW608D[UU61W U3D]<br />

CN-<br />

C/FAN<br />

CN-<br />

4WAY<br />

CENTRAL<br />

CONTROLLER<br />

POWER SUPPLY<br />

CN-H/PRESS<br />

MAIN PCB ASSY<br />

CN-POWER<br />

CN-COMM<br />

CN-EEV1<br />

CN-COM(INV)<br />

CN-JIG_PC<br />

CN-CENTRAL<br />

CN-TH1<br />

CN-TH2<br />

CN-WRITER<br />

CN-FLASH<br />

CN_COMP<br />

CN_<br />

COM(INV)<br />

CN-MOTOR1<br />

CN-MOTOR2<br />

INVERTER PCB ASSY<br />

CN-L2(S)<br />

CN-L1(R)<br />

CN_<br />

AC220V<br />

168 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

to inverter<br />

driver<br />

R2<br />

S2<br />

T-N<br />

T2<br />

Noise filter PCB<br />

To Ceramic resistor<br />

Phase detector_main<br />

Wiring diagrams<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 169<br />

R1<br />

S1<br />

T1<br />

N1<br />

From main power


Wiring diagrams 5CSL0-06B<br />

Models: AUUW216DH [UU21WH U4D], AUUW246DH [UU24WH U4D]<br />

CN-PFC-OUT<br />

CN-MOTOR1<br />

MAIN PCB ASSY<br />

CN-PFC-IN CN 4WAY CN_PRESS<br />

CN_EEV<br />

CN_CENTRAL CN_COM<br />

CN_TH3<br />

CN_TH2<br />

CN_TH4<br />

CN_FLASH<br />

CN_LGMVC<br />

CN_CP(N)<br />

CN_CP(L)<br />

170 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

2.1.7 Capacity tables<br />

Models : AUUW096D + ATNH09GRLED, AVNH09GELAD, AQNH09GALA0<br />

[UU09W ULD] + [UT09 NRD], [UV09 NED], [CQ09 NAD]<br />

• Cooling Capacity<br />

Model ATNH09GRLED[UT09 NRD]<br />

AFR 8.5<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 2.70 2.46 0.55 2.58 2.38 0.57 2.42 2.28 0.77 2.35 2.21 0.86 2.24 2.14 0.94 2.18 2.07 0.92<br />

16.0 22.0 2.86 2.49 0.74 2.74 2.42 0.75 2.59 2.33 0.90 2.51 2.25 0.97 2.41 2.19 1.01 2.35 2.12 0.96<br />

18.0 25.0 3.03 2.51 0.80 2.91 2.44 0.81 2.75 2.36 0.95 2.67 2.29 0.99 2.57 2.23 1.03 2.51 2.16 0.96<br />

19.0 27.0 3.11 2.54 0.81 2.99 2.47 0.82 2.83 2.39 0.96 2.75 2.31 0.99 2.65 2.26 1.03 2.59 2.19 0.96<br />

22.0 30.0 3.36 2.59 0.81 3.24 2.52 0.83 3.08 2.45 0.98 3.00 2.38 1.04 2.90 2.33 1.05 2.84 2.26 0.97<br />

24.0 32.0 3.53 2.64 0.81 3.41 2.57 0.84 3.24 2.51 1.00 3.17 2.44 1.06 3.06 2.39 1.07 3.00 2.32 0.99<br />

Model AVNH09GELAD[UV09 NED]<br />

AFR 7.6<br />

Indoor Air<br />

Temperature<br />

Model AQNH09GALA0[CQ09 NAD]<br />

AFR 8.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 2.70 2.55 0.55 2.58 2.47 0.57 2.42 2.37 0.77 2.35 2.29 0.86 2.24 2.22 0.94 2.18 2.14 0.92<br />

16.0 22.0 2.86 2.58 0.74 2.74 2.50 0.75 2.59 2.41 0.90 2.51 2.33 0.97 2.41 2.27 1.01 2.35 2.19 0.96<br />

18.0 25.0 3.03 2.60 0.80 2.91 2.53 0.81 2.75 2.45 0.95 2.67 2.37 0.99 2.57 2.31 1.03 2.51 2.24 0.96<br />

19.0 27.0 3.11 2.63 0.81 2.99 2.56 0.82 2.83 2.47 0.96 2.75 2.39 0.99 2.65 2.34 1.03 2.59 2.27 0.96<br />

22.0 30.0 3.36 2.68 0.81 3.24 2.61 0.83 3.08 2.54 0.98 3.00 2.47 1.04 2.90 2.42 1.05 2.84 2.35 0.97<br />

24.0 32.0 3.53 2.73 0.81 3.41 2.67 0.84 3.24 2.60 1.00 3.17 2.52 1.06 3.06 2.48 1.07 3.00 2.41 0.99<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

2.12 2.00 0.83<br />

2.28 2.06 0.84<br />

2.45 2.10 0.82<br />

2.53 2.13 0.81<br />

2.78 2.21 0.81<br />

2.94 2.27 0.83<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

2.12 2.07 0.83<br />

2.28 2.13 0.84<br />

2.45 2.18 0.82<br />

2.53 2.21 0.81<br />

2.78 2.29 0.81<br />

2.94 2.35 0.83<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 3.33 3.08 0.53 3.19 2.98 0.55 2.99 2.86 0.74 2.90 2.76 0.83 2.78 2.68 0.91 2.70 2.58 0.89<br />

16.0 22.0 3.54 3.12 0.72 3.39 3.02 0.73 3.20 2.91 0.88 3.10 2.82 0.94 2.98 2.74 0.98 2.90 2.65 0.93<br />

18.0 25.0 3.74 3.15 0.78 3.60 3.06 0.78 3.40 2.95 0.92 3.31 2.86 0.96 3.18 2.79 1.00 3.10 2.70 0.93<br />

19.0 27.0 3.85 3.17 0.79 3.70 3.09 0.79 3.50 2.99 0.93 3.40 2.89 0.96 3.28 2.83 1.00 3.20 2.74 0.93<br />

22.0 30.0 4.15 3.24 0.79 4.01 3.16 0.81 3.81 3.07 0.95 3.71 2.98 1.01 3.58 2.92 1.01 3.51 2.83 0.94<br />

24.0 32.0 4.36 3.30 0.78 4.21 3.22 0.81 4.01 3.14 0.97 3.91 3.05 1.03 3.79 2.99 1.04 3.71 2.91 0.96<br />

TC SHC PI<br />

2.62 2.50 0.80<br />

2.83 2.57 0.81<br />

3.03 2.63 0.79<br />

3.13 2.67 0.78<br />

3.43 2.76 0.78<br />

3.63 2.84 0.80<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 171


Capacity tables 5CSL0-06B<br />

Models : AUUW096D + ATNH09GRLED, AVNH09GELAD, AQNH09GALA0<br />

[UU09W ULD] + [UT09 NRD], [UV09 NED], [CQ09 NAD]<br />

• Heating Capacity<br />

Model ATNH09GRLED[UT09 NRD]<br />

AFR 8.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 2.35 1.30 2.51 1.32 2.80 1.26 3.08 1.17 3.36 1.11 3.57 1.08 3.67 1.03<br />

18 2.33 1.32 2.50 1.36 2.81 1.29 3.08 1.21 3.33 1.14 3.53 1.10 3.66 1.04<br />

20 2.31 1.34 2.50 1.39 2.81 1.33 3.07 1.24 3.30 1.16 3.50 1.12 3.66 1.04<br />

21 2.30 1.36 2.50 1.41 2.81 1.35 3.06 1.26 3.28 1.17 3.50 1.13 3.64 1.04<br />

22 2.30 1.37 2.50 1.43 2.81 1.37 3.05 1.27 3.26 1.18 3.50 1.13 3.61 1.04<br />

24 2.28 1.39 2.48 1.45 2.77 1.39 3.04 1.28 3.25 1.19 3.44 1.13 3.59 1.05<br />

Model AVNH09GELAD[UV09 NED]<br />

AFR 7.6<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 2.35 1.33 2.51 1.36 2.80 1.29 3.08 1.20 3.36 1.13 3.57 1.11 3.67 1.05<br />

18 2.33 1.35 2.50 1.39 2.81 1.33 3.08 1.24 3.33 1.16 3.53 1.13 3.66 1.06<br />

20 2.31 1.38 2.50 1.42 2.81 1.36 3.07 1.27 3.30 1.19 3.50 1.15 3.66 1.07<br />

21 2.30 1.39 2.50 1.45 2.81 1.38 3.06 1.29 3.28 1.20 3.50 1.15 3.64 1.07<br />

22 2.30 1.40 2.50 1.47 2.81 1.40 3.05 1.30 3.26 1.21 3.50 1.16 3.61 1.07<br />

24 2.28 1.43 2.48 1.49 2.77 1.42 3.04 1.32 3.25 1.22 3.44 1.16 3.59 1.08<br />

Model AQNH09GALA0[CQ09 NAD]<br />

AFR 8.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 2.99 1.33 3.19 1.35 3.56 1.29 3.92 1.20 4.27 1.13 4.55 1.10 4.67 1.05<br />

18 2.96 1.35 3.19 1.39 3.57 1.32 3.92 1.23 4.24 1.16 4.49 1.13 4.65 1.06<br />

20 2.94 1.37 3.19 1.42 3.57 1.36 3.91 1.27 4.20 1.18 4.46 1.14 4.66 1.07<br />

21 2.93 1.39 3.19 1.44 3.57 1.38 3.90 1.28 4.17 1.20 4.46 1.15 4.63 1.07<br />

22 2.93 1.40 3.19 1.46 3.57 1.40 3.89 1.30 4.14 1.20 4.46 1.16 4.59 1.07<br />

24 2.90 1.43 3.15 1.48 3.53 1.42 3.86 1.31 4.14 1.21 4.38 1.16 4.57 1.07<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

172 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW126D + ATNH12GRLED, AVNH12GELAD, AQNH12GALA0<br />

[UU12W ULD] + [UT12 NRD], [UV12 NED], [CQ12 NAD]<br />

• Cooling Capacity<br />

Model ATNH12GRLED[UT12 NRD]<br />

AFR 9.5<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 3.67 3.39 0.77 3.51 3.28 0.81 3.29 3.14 1.08 3.19 3.04 1.21 3.05 2.95 1.33 2.97 2.84 1.30<br />

16.0 22.0 3.89 3.43 1.05 3.73 3.33 1.06 3.52 3.20 1.28 3.42 3.10 1.37 3.28 3.02 1.43 3.19 2.92 1.36<br />

18.0 25.0 4.12 3.46 1.13 3.96 3.36 1.14 3.74 3.25 1.34 3.64 3.15 1.40 3.50 3.07 1.45 3.41 2.97 1.36<br />

19.0 27.0 4.23 3.49 1.15 4.07 3.40 1.16 3.85 3.29 1.36 3.74 3.18 1.40 3.61 3.11 1.46 3.53 3.01 1.36<br />

22.0 30.0 4.57 3.56 1.15 4.41 3.47 1.18 4.19 3.37 1.39 4.08 3.28 1.47 3.94 3.21 1.48 3.86 3.12 1.37<br />

24.0 32.0 4.80 3.63 1.14 4.63 3.54 1.19 4.41 3.45 1.41 4.31 3.35 1.50 4.17 3.29 1.51 4.08 3.20 1.40<br />

Model AVNH12GELAD[UV12 NED]<br />

AFR 9.2<br />

Indoor Air<br />

Temperature<br />

Model AQNH12GALA0[CQ12 NAD]<br />

AFR 9.0<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 3.56 3.40 0.79 3.40 3.29 0.83 3.20 3.16 1.11 3.10 3.05 1.24 2.96 2.96 1.37 2.88 2.85 1.34<br />

16.0 22.0 3.78 3.44 1.08 3.62 3.34 1.09 3.41 3.22 1.31 3.32 3.11 1.41 3.18 3.03 1.47 3.10 2.93 1.40<br />

18.0 25.0 4.00 3.47 1.16 3.84 3.37 1.17 3.63 3.26 1.38 3.53 3.16 1.44 3.40 3.08 1.49 3.31 2.98 1.40<br />

19.0 27.0 4.11 3.50 1.18 3.95 3.41 1.19 3.74 3.30 1.40 3.63 3.19 1.44 3.50 3.12 1.50 3.42 3.02 1.40<br />

22.0 30.0 4.44 3.57 1.18 4.28 3.48 1.21 4.06 3.38 1.43 3.96 3.29 1.51 3.83 3.22 1.52 3.75 3.13 1.41<br />

24.0 32.0 4.65 3.64 1.17 4.49 3.55 1.22 4.28 3.46 1.45 4.18 3.37 1.54 4.04 3.30 1.55 3.96 3.21 1.44<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

2.89 2.75 1.17<br />

3.11 2.83 1.18<br />

3.33 2.89 1.15<br />

3.44 2.93 1.14<br />

3.77 3.04 1.14<br />

4.00 3.12 1.17<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

2.80 2.76 1.20<br />

3.02 2.84 1.22<br />

3.23 2.90 1.19<br />

3.34 2.94 1.18<br />

3.66 3.05 1.18<br />

3.88 3.14 1.20<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 3.67 3.47 0.79 3.51 3.36 0.83 3.29 3.22 1.11 3.19 3.11 1.24 3.05 3.02 1.36 2.97 2.91 1.33<br />

16.0 22.0 3.89 3.52 1.07 3.73 3.41 1.08 3.52 3.29 1.31 3.42 3.18 1.40 3.28 3.09 1.46 3.19 2.99 1.39<br />

18.0 25.0 4.12 3.55 1.16 3.96 3.45 1.17 3.74 3.33 1.37 3.64 3.23 1.43 3.50 3.15 1.48 3.41 3.05 1.39<br />

19.0 27.0 4.23 3.58 1.17 4.07 3.48 1.18 3.85 3.37 1.39 3.74 3.26 1.43 3.61 3.19 1.49 3.53 3.09 1.39<br />

22.0 30.0 4.57 3.65 1.17 4.41 3.56 1.20 4.19 3.46 1.42 4.08 3.36 1.50 3.94 3.29 1.51 3.86 3.19 1.40<br />

24.0 32.0 4.80 3.72 1.16 4.63 3.63 1.21 4.41 3.54 1.45 4.31 3.44 1.53 4.17 3.37 1.54 4.08 3.28 1.43<br />

TC SHC PI<br />

2.89 2.82 1.19<br />

3.11 2.90 1.21<br />

3.33 2.96 1.18<br />

3.44 3.01 1.17<br />

3.77 3.12 1.17<br />

4.00 3.20 1.20<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 173


Capacity tables 5CSL0-06B<br />

Models : AUUW126D + ATNH12GRLED, AVNH12GELAD, AQNH12GALA0<br />

[UU12W ULD] + [UT12 NRD], [UV12 NED], [CQ12 NAD]<br />

• Heating Capacity<br />

Model ATNH12GRLED[UT12 NRD]<br />

AFR 9.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 3.13 1.77 3.34 1.80 3.73 1.71 4.11 1.60 4.47 1.50 4.76 1.47 4.89 1.39<br />

18 3.10 1.79 3.34 1.84 3.74 1.76 4.10 1.64 4.44 1.54 4.70 1.50 4.88 1.41<br />

20 3.08 1.82 3.34 1.89 3.74 1.81 4.09 1.68 4.40 1.57 4.67 1.52 4.88 1.42<br />

21 3.07 1.84 3.34 1.92 3.74 1.83 4.08 1.71 4.37 1.59 4.67 1.53 4.85 1.42<br />

22 3.07 1.86 3.34 1.94 3.74 1.86 4.07 1.73 4.34 1.60 4.67 1.54 4.81 1.42<br />

24 3.04 1.89 3.30 1.97 3.70 1.88 4.05 1.74 4.33 1.61 4.59 1.54 4.79 1.43<br />

Model AVNH12GELAD[UV12 NED]<br />

AFR 9.2<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 2.97 1.89 3.18 1.93 3.55 1.83 3.90 1.71 4.25 1.61 4.53 1.57 4.65 1.49<br />

18 2.95 1.92 3.17 1.98 3.55 1.89 3.90 1.76 4.22 1.65 4.47 1.61 4.63 1.51<br />

20 2.93 1.96 3.17 2.02 3.55 1.94 3.89 1.81 4.18 1.69 4.44 1.63 4.64 1.52<br />

21 2.92 1.97 3.17 2.05 3.55 1.97 3.88 1.83 4.15 1.70 4.44 1.64 4.61 1.52<br />

22 2.91 2.00 3.17 2.08 3.55 1.99 3.87 1.85 4.12 1.72 4.43 1.65 4.57 1.52<br />

24 2.89 2.03 3.14 2.11 3.51 2.02 3.85 1.87 4.12 1.73 4.36 1.65 4.55 1.53<br />

Model AQNH12GALA0[CQ12 NAD]<br />

AFR 9.0<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 3.13 1.73 3.34 1.77 3.73 1.68 4.11 1.57 4.47 1.48 4.76 1.44 4.89 1.37<br />

18 3.10 1.76 3.34 1.81 3.74 1.73 4.10 1.61 4.44 1.51 4.70 1.47 4.88 1.38<br />

20 3.08 1.79 3.34 1.85 3.74 1.78 4.09 1.65 4.40 1.54 4.67 1.49 4.88 1.39<br />

21 3.07 1.81 3.34 1.88 3.74 1.80 4.08 1.67 4.37 1.56 4.67 1.50 4.85 1.39<br />

22 3.07 1.83 3.34 1.91 3.74 1.83 4.07 1.70 4.34 1.57 4.67 1.51 4.81 1.39<br />

24 3.04 1.86 3.30 1.93 3.70 1.85 4.05 1.71 4.33 1.58 4.59 1.51 4.79 1.40<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

174 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW186D + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD, AQNH18GALA0<br />

[UU18W UED]+ [UT18 NQD], [UV18 NBD], [UB18 NHD], [CQ18 NAD]<br />

• Cooling Capacity<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 5.10 1.14 5.16 4.93 1.19 4.84 4.73 1.60 4.70 4.57 1.78 4.49 4.43 1.95 4.37 4.28 1.92<br />

16.0 22.0 5.72 5.16 1.54 5.49 5.01 1.56 5.17 4.82 1.88 5.02 4.67 2.02 4.82 4.54 2.11 4.69 4.39 2.00<br />

18.0 25.0 6.06 5.21 1.67 5.82 5.06 1.68 5.50 4.89 1.98 5.35 4.74 2.06 5.14 4.62 2.14 5.02 4.48 2.00<br />

19.0 27.0 6.22 5.25 1.69 5.98 5.11 1.70 5.67 4.95 2.00 5.50 4.79 2.06 5.31 4.68 2.14 5.18 4.54 2.00<br />

22.0 30.0 6.72 5.36 1.69 6.48 5.23 1.73 6.16 5.08 2.04 6.00 4.93 2.16 5.80 4.83 2.18 5.67 4.69 2.02<br />

24.0 32.0 7.05 5.46 1.68 6.81 5.33 1.75 6.49 5.19 2.08 6.33 5.05 2.20 6.13 4.95 2.22 6.00 4.82 2.06<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Indoor Air<br />

Temperature<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.33 4.51 1.12 5.10 4.36 1.17 4.79 4.18 1.58 4.64 4.04 1.76 4.44 3.92 1.93 4.32 3.78 1.89<br />

16.0 22.0 5.66 4.57 1.52 5.43 4.43 1.54 5.12 4.27 1.86 4.97 4.13 2.00 4.76 4.01 2.08 4.64 3.88 1.98<br />

18.0 25.0 5.99 4.61 1.65 5.76 4.48 1.66 5.44 4.32 1.95 5.29 4.19 2.03 5.09 4.09 2.11 4.97 3.96 1.98<br />

19.0 27.0 6.16 4.65 1.66 5.92 4.52 1.68 5.60 4.37 1.97 5.44 4.23 2.03 5.25 4.14 2.11 5.13 4.01 1.97<br />

22.0 30.0 6.65 4.74 1.66 6.41 4.62 1.71 6.09 4.49 2.02 5.94 4.36 2.13 5.74 4.27 2.15 5.61 4.15 1.99<br />

24.0 32.0 6.98 4.83 1.65 6.74 4.71 1.72 6.42 4.59 2.06 6.26 4.46 2.17 6.06 4.38 2.19 5.94 4.26 2.04<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

4.24 4.14 1.72<br />

4.57 4.26 1.74<br />

4.90 4.35 1.70<br />

5.06 4.42 1.68<br />

5.55 4.58 1.68<br />

5.88 4.70 1.72<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.18 4.46 1.09 4.95 4.32 1.13 4.65 4.15 1.52 4.51 4.01 1.70 4.31 3.88 1.87 4.19 3.75 1.83<br />

16.0 22.0 5.50 4.52 1.47 5.27 4.39 1.49 4.97 4.22 1.80 4.82 4.09 1.93 4.62 3.98 2.01 4.51 3.84 1.91<br />

18.0 25.0 5.81 4.56 1.59 5.59 4.43 1.60 5.28 4.28 1.89 5.14 4.15 1.97 4.94 4.05 2.04 4.82 3.92 1.91<br />

19.0 27.0 5.97 4.60 1.61 5.75 4.48 1.63 5.44 4.33 1.91 5.28 4.19 1.97 5.10 4.10 2.05 4.98 3.97 1.91<br />

22.0 30.0 6.45 4.69 1.61 6.22 4.58 1.65 5.91 4.45 1.95 5.76 4.32 2.06 5.57 4.23 2.08 5.45 4.11 1.93<br />

24.0 32.0 6.77 4.78 1.60 6.54 4.67 1.67 6.23 4.55 1.99 6.08 4.42 2.10 5.88 4.34 2.12 5.76 4.22 1.97<br />

TC SHC PI<br />

4.07 3.63 1.64<br />

4.39 3.73 1.66<br />

4.70 3.81 1.62<br />

4.86 3.87 1.61<br />

5.33 4.01 1.61<br />

5.64 4.12 1.65<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

4.20 3.67 1.70<br />

4.52 3.77 1.72<br />

4.84 3.85 1.68<br />

5.01 3.91 1.66<br />

5.49 4.05 1.66<br />

5.81 4.16 1.70<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 175


Capacity tables 5CSL0-06B<br />

Model AQNH18GALA0[CQ18 NAD]<br />

AFR 11.0<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 4.80 1.14 5.16 4.65 1.19 4.84 4.46 1.60 4.70 4.31 1.79 4.49 4.18 1.96 4.37 4.03 1.92<br />

16.0 22.0 5.72 4.86 1.55 5.49 4.72 1.56 5.17 4.54 1.89 5.02 4.40 2.03 4.82 4.28 2.11 4.69 4.13 2.01<br />

18.0 25.0 6.06 4.91 1.67 5.82 4.77 1.68 5.50 4.61 1.98 5.35 4.47 2.07 5.14 4.35 2.14 5.02 4.22 2.01<br />

19.0 27.0 6.22 4.95 1.69 5.98 4.81 1.71 5.67 4.66 2.00 5.50 4.51 2.07 5.31 4.41 2.15 5.18 4.27 2.00<br />

22.0 30.0 6.72 5.05 1.69 6.48 4.92 1.74 6.16 4.78 2.05 6.00 4.65 2.17 5.80 4.55 2.18 5.67 4.42 2.02<br />

24.0 32.0 7.05 5.14 1.68 6.81 5.02 1.75 6.49 4.89 2.09 6.33 4.76 2.21 6.13 4.67 2.23 6.00 4.54 2.07<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

4.24 3.90 1.72<br />

4.57 4.01 1.75<br />

4.90 4.10 1.70<br />

5.06 4.16 1.69<br />

5.55 4.31 1.69<br />

5.88 4.43 1.73<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

176 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW186D + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD, AQNH18GALA0<br />

[UU18W UED]+ [UT18 NQD], [UV18 NBD], [UB18 NHD], [CQ18 NAD]<br />

• Heating Capacity<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Indoor Air<br />

Temperature<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.31 2.44 4.60 2.49 5.13 2.36 5.65 2.20 6.15 2.08 6.55 2.03 6.73 1.93<br />

18 4.26 2.48 4.59 2.55 5.14 2.43 5.64 2.27 6.11 2.13 6.47 2.07 6.70 1.95<br />

20 4.24 2.52 4.59 2.61 5.14 2.50 5.63 2.33 6.05 2.17 6.43 2.10 6.72 1.96<br />

21 4.22 2.54 4.59 2.65 5.14 2.53 5.61 2.36 6.01 2.19 6.43 2.11 6.67 1.96<br />

22 4.22 2.57 4.59 2.69 5.14 2.57 5.60 2.39 5.97 2.21 6.42 2.12 6.62 1.96<br />

24 4.18 2.62 4.54 2.72 5.08 2.60 5.57 2.41 5.96 2.23 6.31 2.13 6.58 1.97<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 3.99 2.39 4.26 2.44 4.76 2.31 5.24 2.16 5.70 2.04 6.08 1.99 6.24 1.89<br />

18 3.95 2.43 4.25 2.50 4.77 2.38 5.23 2.22 5.66 2.09 6.00 2.03 6.22 1.91<br />

20 3.93 2.47 4.25 2.56 4.77 2.45 5.22 2.28 5.61 2.13 5.96 2.06 6.23 1.92<br />

21 3.92 2.49 4.25 2.59 4.77 2.48 5.21 2.31 5.57 2.15 5.96 2.07 6.19 1.92<br />

22 3.91 2.52 4.25 2.63 4.77 2.52 5.19 2.34 5.53 2.17 5.95 2.08 6.14 1.92<br />

24 3.87 2.56 4.21 2.67 4.71 2.55 5.16 2.36 5.53 2.18 5.85 2.09 6.10 1.93<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.70 2.67 5.01 2.71 5.60 2.58 6.16 2.41 6.71 2.27 7.15 2.21 7.34 2.10<br />

18 4.65 2.71 5.01 2.78 5.61 2.65 6.16 2.47 6.66 2.33 7.06 2.26 7.31 2.13<br />

20 4.62 2.75 5.01 2.85 5.61 2.73 6.14 2.54 6.60 2.37 7.01 2.29 7.33 2.14<br />

21 4.61 2.78 5.01 2.89 5.61 2.77 6.12 2.57 6.56 2.40 7.01 2.31 7.28 2.14<br />

22 4.60 2.81 5.01 2.93 5.61 2.81 6.11 2.61 6.51 2.41 7.00 2.32 7.22 2.14<br />

24 4.56 2.86 4.96 2.97 5.54 2.84 6.07 2.63 6.50 2.43 6.89 2.32 7.18 2.15<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 177


Capacity tables 5CSL0-06B<br />

Model AQNH18GALA0[CQ18 NAD]<br />

AFR 11.0<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.27 2.42 4.56 2.47 5.09 2.34 5.60 2.19 6.10 2.06 6.50 2.01 6.67 1.91<br />

18 4.23 2.46 4.55 2.53 5.10 2.41 5.60 2.25 6.06 2.12 6.42 2.05 6.65 1.93<br />

20 4.20 2.50 4.55 2.59 5.10 2.48 5.58 2.31 6.00 2.16 6.37 2.08 6.66 1.94<br />

21 4.19 2.53 4.55 2.63 5.10 2.52 5.57 2.34 5.96 2.18 6.37 2.10 6.62 1.95<br />

22 4.18 2.56 4.55 2.67 5.10 2.55 5.55 2.37 5.92 2.20 6.36 2.11 6.56 1.95<br />

24 4.14 2.60 4.51 2.70 5.04 2.59 5.52 2.39 5.91 2.21 6.26 2.11 6.53 1.96<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

178 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW186D1 + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD, AQNH18GALA0<br />

[UU18W UED1]+ [UT18 NQD], [UV18 NBD], [UB18 NHD], [CQ18 NAD]<br />

• Cooling Capacity<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 5.10 1.14 5.16 4.93 1.19 4.84 4.73 1.60 4.70 4.57 1.78 4.49 4.43 1.95 4.37 4.28 1.92<br />

16.0 22.0 5.72 5.16 1.54 5.49 5.01 1.56 5.17 4.82 1.88 5.02 4.67 2.02 4.82 4.54 2.11 4.69 4.39 2.00<br />

18.0 25.0 6.06 5.21 1.67 5.82 5.06 1.68 5.50 4.89 1.98 5.35 4.74 2.06 5.14 4.62 2.14 5.02 4.48 2.00<br />

19.0 27.0 6.22 5.25 1.69 5.98 5.11 1.70 5.67 4.95 2.00 5.50 4.79 2.06 5.31 4.68 2.14 5.18 4.54 2.00<br />

22.0 30.0 6.72 5.36 1.69 6.48 5.23 1.73 6.16 5.08 2.04 6.00 4.93 2.16 5.80 4.83 2.18 5.67 4.69 2.02<br />

24.0 32.0 7.05 5.46 1.68 6.81 5.33 1.75 6.49 5.19 2.08 6.33 5.05 2.20 6.13 4.95 2.22 6.00 4.82 2.06<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Indoor Air<br />

Temperature<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.33 4.51 1.12 5.10 4.36 1.17 4.79 4.18 1.58 4.64 4.04 1.76 4.44 3.92 1.93 4.32 3.78 1.89<br />

16.0 22.0 5.66 4.57 1.52 5.43 4.43 1.54 5.12 4.27 1.86 4.97 4.13 2.00 4.76 4.01 2.08 4.64 3.88 1.98<br />

18.0 25.0 5.99 4.61 1.65 5.76 4.48 1.66 5.44 4.32 1.95 5.29 4.19 2.03 5.09 4.09 2.11 4.97 3.96 1.98<br />

19.0 27.0 6.16 4.65 1.66 5.92 4.52 1.68 5.60 4.37 1.97 5.44 4.23 2.03 5.25 4.14 2.11 5.13 4.01 1.97<br />

22.0 30.0 6.65 4.74 1.66 6.41 4.62 1.71 6.09 4.49 2.02 5.94 4.36 2.13 5.74 4.27 2.15 5.61 4.15 1.99<br />

24.0 32.0 6.98 4.83 1.65 6.74 4.71 1.72 6.42 4.59 2.06 6.26 4.46 2.17 6.06 4.38 2.19 5.94 4.26 2.04<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

4.24 4.14 1.72<br />

4.57 4.26 1.74<br />

4.90 4.35 1.70<br />

5.06 4.42 1.68<br />

5.55 4.58 1.68<br />

5.88 4.70 1.72<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.18 4.46 1.09 4.95 4.32 1.13 4.65 4.15 1.52 4.51 4.01 1.70 4.31 3.88 1.87 4.19 3.75 1.83<br />

16.0 22.0 5.50 4.52 1.47 5.27 4.39 1.49 4.97 4.22 1.80 4.82 4.09 1.93 4.62 3.98 2.01 4.51 3.84 1.91<br />

18.0 25.0 5.81 4.56 1.59 5.59 4.43 1.60 5.28 4.28 1.89 5.14 4.15 1.97 4.94 4.05 2.04 4.82 3.92 1.91<br />

19.0 27.0 5.97 4.60 1.61 5.75 4.48 1.63 5.44 4.33 1.91 5.28 4.19 1.97 5.10 4.10 2.05 4.98 3.97 1.91<br />

22.0 30.0 6.45 4.69 1.61 6.22 4.58 1.65 5.91 4.45 1.95 5.76 4.32 2.06 5.57 4.23 2.08 5.45 4.11 1.93<br />

24.0 32.0 6.77 4.78 1.60 6.54 4.67 1.67 6.23 4.55 1.99 6.08 4.42 2.10 5.88 4.34 2.12 5.76 4.22 1.97<br />

TC SHC PI<br />

4.07 3.63 1.64<br />

4.39 3.73 1.66<br />

4.70 3.81 1.62<br />

4.86 3.87 1.61<br />

5.33 4.01 1.61<br />

5.64 4.12 1.65<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

4.20 3.67 1.70<br />

4.52 3.77 1.72<br />

4.84 3.85 1.68<br />

5.01 3.91 1.66<br />

5.49 4.05 1.66<br />

5.81 4.16 1.70<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 179


Capacity tables 5CSL0-06B<br />

Model AQNH18GALA0[CQ18 NAD]<br />

AFR 11.0<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 4.80 1.14 5.16 4.65 1.19 4.84 4.46 1.60 4.70 4.31 1.79 4.49 4.18 1.96 4.37 4.03 1.92<br />

16.0 22.0 5.72 4.86 1.55 5.49 4.72 1.56 5.17 4.54 1.89 5.02 4.40 2.03 4.82 4.28 2.11 4.69 4.13 2.01<br />

18.0 25.0 6.06 4.91 1.67 5.82 4.77 1.68 5.50 4.61 1.98 5.35 4.47 2.07 5.14 4.35 2.14 5.02 4.22 2.01<br />

19.0 27.0 6.22 4.95 1.69 5.98 4.81 1.71 5.67 4.66 2.00 5.50 4.51 2.07 5.31 4.41 2.15 5.18 4.27 2.00<br />

22.0 30.0 6.72 5.05 1.69 6.48 4.92 1.74 6.16 4.78 2.05 6.00 4.65 2.17 5.80 4.55 2.18 5.67 4.42 2.02<br />

24.0 32.0 7.05 5.14 1.68 6.81 5.02 1.75 6.49 4.89 2.09 6.33 4.76 2.21 6.13 4.67 2.23 6.00 4.54 2.07<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

4.24 3.90 1.72<br />

4.57 4.01 1.75<br />

4.90 4.10 1.70<br />

5.06 4.16 1.69<br />

5.55 4.31 1.69<br />

5.88 4.43 1.73<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

180 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW186D1 + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD, AQNH18GALA0<br />

[UU18W UED1]+ [UT18 NQD], [UV18 NBD], [UB18 NHD], [CQ18 NAD]<br />

• Heating Capacity<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Indoor Air<br />

Temperature<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.31 2.44 4.60 2.49 5.13 2.36 5.65 2.20 6.15 2.08 6.55 2.03 6.73 1.93<br />

18 4.26 2.48 4.59 2.55 5.14 2.43 5.64 2.27 6.11 2.13 6.47 2.07 6.70 1.95<br />

20 4.24 2.52 4.59 2.61 5.14 2.50 5.63 2.33 6.05 2.17 6.43 2.10 6.72 1.96<br />

21 4.22 2.54 4.59 2.65 5.14 2.53 5.61 2.36 6.01 2.19 6.43 2.11 6.67 1.96<br />

22 4.22 2.57 4.59 2.69 5.14 2.57 5.60 2.39 5.97 2.21 6.42 2.12 6.62 1.96<br />

24 4.18 2.62 4.54 2.72 5.08 2.60 5.57 2.41 5.96 2.23 6.31 2.13 6.58 1.97<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 3.99 2.39 4.26 2.44 4.76 2.31 5.24 2.16 5.70 2.04 6.08 1.99 6.24 1.89<br />

18 3.95 2.43 4.25 2.50 4.77 2.38 5.23 2.22 5.66 2.09 6.00 2.03 6.22 1.91<br />

20 3.93 2.47 4.25 2.56 4.77 2.45 5.22 2.28 5.61 2.13 5.96 2.06 6.23 1.92<br />

21 3.92 2.49 4.25 2.59 4.77 2.48 5.21 2.31 5.57 2.15 5.96 2.07 6.19 1.92<br />

22 3.91 2.52 4.25 2.63 4.77 2.52 5.19 2.34 5.53 2.17 5.95 2.08 6.14 1.92<br />

24 3.87 2.56 4.21 2.67 4.71 2.55 5.16 2.36 5.53 2.18 5.85 2.09 6.10 1.93<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.70 2.67 5.01 2.71 5.60 2.58 6.16 2.41 6.71 2.27 7.15 2.21 7.34 2.10<br />

18 4.65 2.71 5.01 2.78 5.61 2.65 6.16 2.47 6.66 2.33 7.06 2.26 7.31 2.13<br />

20 4.62 2.75 5.01 2.85 5.61 2.73 6.14 2.54 6.60 2.37 7.01 2.29 7.33 2.14<br />

21 4.61 2.78 5.01 2.89 5.61 2.77 6.12 2.57 6.56 2.40 7.01 2.31 7.28 2.14<br />

22 4.60 2.81 5.01 2.93 5.61 2.81 6.11 2.61 6.51 2.41 7.00 2.32 7.22 2.14<br />

24 4.56 2.86 4.96 2.97 5.54 2.84 6.07 2.63 6.50 2.43 6.89 2.32 7.18 2.15<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 181


Capacity tables 5CSL0-06B<br />

Model AQNH18GALA0[CQ18 NAD]<br />

AFR 11.0<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.27 2.42 4.56 2.47 5.09 2.34 5.60 2.19 6.10 2.06 6.50 2.01 6.67 1.91<br />

18 4.23 2.46 4.55 2.53 5.10 2.41 5.60 2.25 6.06 2.12 6.42 2.05 6.65 1.93<br />

20 4.20 2.50 4.55 2.59 5.10 2.48 5.58 2.31 6.00 2.16 6.37 2.08 6.66 1.94<br />

21 4.19 2.53 4.55 2.63 5.10 2.52 5.57 2.34 5.96 2.18 6.37 2.10 6.62 1.95<br />

22 4.18 2.56 4.55 2.67 5.10 2.55 5.55 2.37 5.92 2.20 6.36 2.11 6.56 1.95<br />

24 4.14 2.60 4.51 2.70 5.04 2.59 5.52 2.39 5.91 2.21 6.26 2.11 6.53 1.96<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

182 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW246D +ATNH24GPLED, UVNH246BLAD , ABNH246HLAD<br />

[UU24W UED]+ [UT24 NPD], [UV24 NBD], [UB24 NHD]<br />

• Cooling Capacity<br />

Model ATNH24GPLED[UT24 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 7.66 6.55 1.57 7.32 6.34 1.64 6.88 6.08 2.20 6.67 5.88 2.45 6.38 5.70 2.69 6.20 5.50 2.64<br />

16.0 22.0 8.13 6.64 2.13 7.79 6.44 2.14 7.34 6.20 2.59 7.13 6.00 2.79 6.84 5.83 2.90 6.66 5.64 2.76<br />

18.0 25.0 8.60 6.69 2.30 8.26 6.50 2.31 7.81 6.28 2.72 7.60 6.09 2.84 7.30 5.94 2.94 7.13 5.75 2.76<br />

19.0 27.0 8.84 6.75 2.32 8.50 6.57 2.34 8.04 6.36 2.75 7.81 6.15 2.84 7.54 6.02 2.95 7.36 5.83 2.75<br />

22.0 30.0 9.54 6.89 2.32 9.20 6.72 2.39 8.74 6.52 2.82 8.53 6.34 2.98 8.23 6.21 3.00 8.06 6.03 2.78<br />

24.0 32.0 10.02 7.01 2.31 9.67 6.85 2.41 9.21 6.67 2.87 8.99 6.49 3.03 8.70 6.37 3.06 8.52 6.19 2.84<br />

Model UVNH246BLAD[UV24 NBD]<br />

AFR 15<br />

Indoor Air<br />

Temperature<br />

Model ABNH246HLAD[UB24 NHD]<br />

AFR 18<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 7.55 5.61 1.68 7.22 5.43 1.75 6.78 5.21 2.35 6.57 5.04 2.62 6.29 4.88 2.88 6.11 4.71 2.82<br />

16.0 22.0 8.01 5.69 2.27 7.68 5.51 2.29 7.24 5.31 2.77 7.03 5.14 2.98 6.74 5.00 3.11 6.57 4.83 2.96<br />

18.0 25.0 8.48 5.74 2.46 8.15 5.57 2.47 7.70 5.39 2.91 7.49 5.22 3.04 7.20 5.09 3.15 7.03 4.93 2.95<br />

19.0 27.0 8.71 5.79 2.49 8.38 5.63 2.51 7.93 5.45 2.94 7.70 5.27 3.04 7.43 5.16 3.16 7.26 5.00 2.94<br />

22.0 30.0 9.41 5.90 2.49 9.07 5.75 2.55 8.62 5.59 3.01 8.41 5.43 3.18 8.12 5.32 3.21 7.94 5.16 2.97<br />

24.0 32.0 9.87 6.01 2.47 9.53 5.87 2.57 9.08 5.72 3.07 8.86 5.56 3.25 8.58 5.45 3.28 8.40 5.30 3.04<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

6.02 5.33 2.37<br />

6.49 5.48 2.40<br />

6.95 5.59 2.34<br />

7.19 5.68 2.32<br />

7.88 5.88 2.32<br />

8.35 6.04 2.38<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

5.94 4.56 2.53<br />

6.40 4.69 2.57<br />

6.86 4.79 2.50<br />

7.08 4.86 2.48<br />

7.77 5.04 2.48<br />

8.23 5.18 2.54<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 7.66 5.99 1.91 7.32 5.79 2.00 6.88 5.56 2.68 6.67 5.37 2.99 6.38 5.21 3.28 6.20 5.03 3.22<br />

16.0 22.0 8.13 6.07 2.59 7.79 5.88 2.61 7.34 5.67 3.16 7.13 5.48 3.39 6.84 5.33 3.54 6.66 5.16 3.37<br />

18.0 25.0 8.60 6.12 2.80 8.26 5.95 2.82 7.81 5.75 3.32 7.60 5.57 3.46 7.30 5.43 3.59 7.13 5.26 3.36<br />

19.0 27.0 8.84 6.17 2.83 8.50 6.00 2.86 8.04 5.81 3.35 7.81 5.62 3.46 7.54 5.50 3.60 7.36 5.33 3.35<br />

22.0 30.0 9.54 6.29 2.83 9.20 6.14 2.91 8.74 5.96 3.43 8.53 5.79 3.63 8.23 5.67 3.65 8.06 5.51 3.39<br />

24.0 32.0 10.02 6.41 2.82 9.67 6.26 2.93 9.21 6.10 3.50 8.99 5.93 3.70 8.70 5.82 3.73 8.52 5.66 3.46<br />

TC SHC PI<br />

6.02 4.87 2.89<br />

6.49 5.01 2.92<br />

6.95 5.11 2.85<br />

7.19 5.19 2.83<br />

7.88 5.37 2.83<br />

8.35 5.52 2.90<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 183


Capacity tables 5CSL0-06B<br />

Models : AUUW246D +ATNH24GPLED, UVNH246BLAD , ABNH246HLAD<br />

[UU24W UED]+ [UT24 NPD], [UV24 NBD], [UB24 NHD]<br />

• Heating Capacity<br />

Model ATNH24GPLED[UT24 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.26 3.76 6.68 3.83 7.47 3.63 8.21 3.39 8.95 3.20 9.53 3.12 9.78 2.96<br />

18 6.20 3.81 6.67 3.92 7.48 3.74 8.21 3.49 8.89 3.28 9.41 3.18 9.75 3.00<br />

20 6.16 3.88 6.67 4.02 7.48 3.85 8.18 3.58 8.80 3.35 9.35 3.23 9.77 3.01<br />

21 6.14 3.92 6.67 4.07 7.48 3.90 8.17 3.63 8.74 3.38 9.35 3.25 9.71 3.02<br />

22 6.13 3.96 6.67 4.13 7.48 3.96 8.14 3.67 8.68 3.40 9.34 3.27 9.63 3.02<br />

24 6.07 4.03 6.61 4.19 7.39 4.01 8.10 3.71 8.67 3.43 9.18 3.27 9.57 3.03<br />

Model UVNH246BLAD[UV24 NBD]<br />

AFR 15<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.03 4.06 6.43 4.14 7.19 3.93 7.90 3.67 8.61 3.46 9.17 3.37 9.42 3.20<br />

18 5.97 4.12 6.42 4.24 7.20 4.04 7.90 3.77 8.55 3.55 9.06 3.44 9.39 3.24<br />

20 5.93 4.20 6.42 4.34 7.20 4.16 7.88 3.87 8.47 3.62 9.00 3.49 9.40 3.26<br />

21 5.91 4.23 6.42 4.40 7.20 4.22 7.86 3.92 8.42 3.65 9.00 3.52 9.34 3.26<br />

22 5.90 4.28 6.42 4.47 7.20 4.28 7.84 3.97 8.36 3.68 8.98 3.53 9.27 3.26<br />

24 5.85 4.35 6.36 4.53 7.11 4.33 7.79 4.01 8.34 3.70 8.84 3.54 9.21 3.28<br />

Model ABNH246HLAD[UB24 NHD]<br />

AFR 18<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.26 4.08 6.68 4.15 7.47 3.94 8.21 3.68 8.95 3.47 9.53 3.39 9.78 3.21<br />

18 6.20 4.14 6.67 4.25 7.48 4.06 8.21 3.78 8.89 3.56 9.41 3.45 9.75 3.25<br />

20 6.16 4.21 6.67 4.36 7.48 4.17 8.18 3.88 8.80 3.63 9.35 3.50 9.77 3.27<br />

21 6.14 4.25 6.67 4.42 7.48 4.23 8.17 3.93 8.74 3.67 9.35 3.53 9.71 3.27<br />

22 6.13 4.30 6.67 4.48 7.48 4.29 8.14 3.99 8.68 3.69 9.34 3.54 9.63 3.27<br />

24 6.07 4.37 6.61 4.55 7.39 4.35 8.10 4.02 8.67 3.72 9.18 3.55 9.57 3.29<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

184 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW306D +ATNH30GPLED, UVNH306BLAD , ABNH306GLAD<br />

[UU30W UED]+ [UT30NPD], [UV30 NBD], [UB30 NGD]<br />

• Cooling Capacity<br />

Model ATNH30GPLED[UT30 NPD]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.63 7.22 1.93 8.25 6.98 2.02 7.75 6.70 2.71 7.51 6.48 3.02 7.18 6.28 3.32 6.99 6.06 3.25<br />

16.0 22.0 9.16 7.31 2.62 8.78 7.09 2.64 8.28 6.83 3.20 8.04 6.61 3.43 7.71 6.43 3.58 7.51 6.21 3.41<br />

18.0 25.0 9.69 7.38 2.83 9.31 7.17 2.85 8.80 6.93 3.36 8.56 6.71 3.50 8.23 6.54 3.63 8.03 6.34 3.40<br />

19.0 27.0 9.96 7.44 2.86 9.58 7.24 2.89 9.06 7.00 3.39 8.80 6.78 3.50 8.49 6.63 3.64 8.29 6.43 3.39<br />

22.0 30.0 10.75 7.59 2.86 10.37 7.40 2.94 9.85 7.19 3.47 9.61 6.99 3.67 9.28 6.84 3.70 9.08 6.64 3.43<br />

24.0 32.0 11.28 7.73 2.85 10.90 7.55 2.97 10.38 7.35 3.54 10.13 7.15 3.74 9.80 7.01 3.77 9.60 6.82 3.50<br />

Model UVNH306BLAD[UV30 NBD]<br />

AFR 18<br />

Indoor Air<br />

Temperature<br />

Model ABNH306GLAD[UB30 NGD]<br />

AFR 26.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.20 6.23 1.95 7.84 6.03 2.04 7.36 5.79 2.74 7.14 5.59 3.06 6.82 5.42 3.36 6.64 5.23 3.29<br />

16.0 22.0 8.70 6.32 2.65 8.34 6.12 2.67 7.86 5.90 3.23 7.63 5.71 3.47 7.32 5.55 3.62 7.13 5.37 3.44<br />

18.0 25.0 9.21 6.37 2.86 8.85 6.19 2.88 8.36 5.98 3.39 8.13 5.80 3.54 7.82 5.65 3.67 7.63 5.47 3.44<br />

19.0 27.0 9.46 6.43 2.90 9.10 6.25 2.92 8.61 6.05 3.43 8.36 5.85 3.54 8.07 5.73 3.68 7.88 5.55 3.43<br />

22.0 30.0 10.22 6.55 2.90 9.85 6.39 2.97 9.36 6.21 3.51 9.13 6.03 3.71 8.81 5.91 3.74 8.63 5.74 3.46<br />

24.0 32.0 10.72 6.68 2.88 10.35 6.52 3.00 9.86 6.35 3.58 9.62 6.17 3.78 9.31 6.06 3.82 9.12 5.89 3.54<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

6.79 5.87 2.92<br />

7.31 6.03 2.96<br />

7.84 6.16 2.89<br />

8.10 6.25 2.86<br />

8.88 6.48 2.86<br />

9.41 6.66 2.93<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

6.45 5.07 2.95<br />

6.95 5.21 2.99<br />

7.44 5.32 2.92<br />

7.69 5.40 2.89<br />

8.44 5.60 2.89<br />

8.94 5.75 2.96<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.63 7.69 1.93 8.25 7.44 2.02 7.75 7.14 2.71 7.51 6.90 3.02 7.18 6.69 3.32 6.99 6.45 3.25<br />

16.0 22.0 9.16 7.79 2.62 8.78 7.55 2.64 8.28 7.27 3.20 8.04 7.04 3.43 7.71 6.85 3.58 7.51 6.62 3.41<br />

18.0 25.0 9.69 7.85 2.83 9.31 7.63 2.85 8.80 7.38 3.36 8.56 7.15 3.50 8.23 6.97 3.63 8.03 6.75 3.40<br />

19.0 27.0 9.96 7.92 2.86 9.58 7.71 2.89 9.06 7.46 3.39 8.80 7.22 3.50 8.49 7.06 3.64 8.29 6.84 3.39<br />

22.0 30.0 10.75 8.08 2.86 10.37 7.88 2.94 9.85 7.66 3.47 9.61 7.44 3.67 9.28 7.28 3.70 9.08 7.07 3.43<br />

24.0 32.0 11.28 8.23 2.85 10.90 8.04 2.97 10.38 7.83 3.54 10.13 7.61 3.74 9.80 7.47 3.77 9.60 7.26 3.50<br />

TC SHC PI<br />

6.79 6.25 2.92<br />

7.31 6.43 2.96<br />

7.84 6.56 2.89<br />

8.10 6.66 2.86<br />

8.88 6.90 2.86<br />

9.41 7.09 2.93<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 185


Capacity tables 5CSL0-06B<br />

Models : AUUW306D +ATNH30GPLED, UVNH306BLAD , ABNH306GLAD<br />

[UU30W UED]+ [UT30NPD], [UV30 NBD], [UB30 NGD]<br />

• Heating Capacity<br />

Model ATNH30GPLED[UT30 NPD]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 7.04 4.50 7.52 4.58 8.40 4.35 9.24 4.06 10.07 3.83 10.72 3.73 11.01 3.55<br />

18 6.98 4.56 7.51 4.69 8.42 4.48 9.23 4.17 10.00 3.93 10.59 3.81 10.97 3.59<br />

20 6.93 4.64 7.51 4.80 8.42 4.60 9.21 4.28 9.90 4.00 10.51 3.86 10.99 3.60<br />

21 6.91 4.69 7.51 4.88 8.42 4.67 9.19 4.34 9.84 4.04 10.51 3.89 10.92 3.61<br />

22 6.90 4.74 7.51 4.95 8.42 4.73 9.16 4.40 9.77 4.07 10.50 3.91 10.83 3.61<br />

24 6.83 4.82 7.43 5.01 8.31 4.79 9.11 4.44 9.75 4.10 10.33 3.92 10.77 3.63<br />

Model UVNH306BLAD[UV30 NBD]<br />

AFR 18<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.58 4.80 7.02 4.89 7.84 4.64 8.62 4.34 9.39 4.09 10.01 3.99 10.27 3.79<br />

18 6.51 4.87 7.01 5.01 7.85 4.78 8.62 4.46 9.33 4.19 9.88 4.07 10.24 3.83<br />

20 6.47 4.96 7.01 5.13 7.85 4.92 8.59 4.57 9.24 4.28 9.81 4.13 10.26 3.85<br />

21 6.45 5.00 7.01 5.21 7.85 4.99 8.57 4.63 9.18 4.32 9.81 4.16 10.19 3.86<br />

22 6.44 5.06 7.01 5.28 7.85 5.05 8.55 4.69 9.11 4.35 9.80 4.18 10.11 3.86<br />

24 6.38 5.15 6.94 5.35 7.76 5.12 8.50 4.74 9.10 4.38 9.64 4.18 10.05 3.87<br />

Model ABNH306GLAD[UB30 NGD]<br />

AFR 26.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 7.04 4.00 7.52 4.07 8.40 3.87 9.24 3.61 10.07 3.40 10.72 3.32 11.01 3.15<br />

18 6.98 4.06 7.51 4.17 8.42 3.98 9.23 3.71 10.00 3.49 10.59 3.39 10.97 3.19<br />

20 6.93 4.13 7.51 4.27 8.42 4.09 9.21 3.81 9.90 3.56 10.51 3.44 10.99 3.20<br />

21 6.91 4.17 7.51 4.34 8.42 4.15 9.19 3.86 9.84 3.60 10.51 3.46 10.92 3.21<br />

22 6.90 4.21 7.51 4.40 8.42 4.21 9.16 3.91 9.77 3.62 10.50 3.48 10.83 3.21<br />

24 6.83 4.29 7.43 4.46 8.31 4.26 9.11 3.95 9.75 3.65 10.33 3.48 10.77 3.23<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

186 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW366D +ATNH36GNLED , UVNH366KLAD, ABNH366GLAD<br />

[UU36W UED]+ [UT36 NND] , [UV36 NKD] , [ UB36 NGD]<br />

• Cooling Capacity<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.79 9.49 2.27 10.32 9.18 2.38 9.69 8.81 3.19 9.39 8.52 3.56 8.98 8.26 3.91 8.73 7.97 3.83<br />

16.0 22.0 11.45 9.61 3.08 10.98 9.33 3.11 10.34 8.98 3.76 10.05 8.69 4.04 9.63 8.45 4.21 9.39 8.17 4.01<br />

18.0 25.0 12.11 9.70 3.33 11.64 9.43 3.35 11.00 9.11 3.95 10.70 8.83 4.12 10.29 8.61 4.27 10.04 8.33 4.00<br />

19.0 27.0 12.45 9.78 3.37 11.97 9.52 3.40 11.33 9.21 3.99 11.00 8.91 4.12 10.62 8.72 4.28 10.37 8.45 3.99<br />

22.0 30.0 13.44 9.98 3.37 12.96 9.73 3.46 12.32 9.45 4.09 12.01 9.19 4.32 11.60 8.99 4.35 11.35 8.73 4.03<br />

24.0 32.0 14.11 10.16 3.35 13.62 9.93 3.49 12.97 9.67 4.16 12.66 9.40 4.40 12.25 9.22 4.44 12.00 8.97 4.12<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Indoor Air<br />

Temperature<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.30 8.50 2.42 9.85 8.22 2.53 9.25 7.89 3.40 8.96 7.63 3.79 8.57 7.39 4.16 8.34 7.13 4.08<br />

16.0 22.0 10.93 8.61 3.28 10.48 8.35 3.31 9.87 8.04 4.00 9.59 7.79 4.30 9.20 7.57 4.48 8.96 7.32 4.27<br />

18.0 25.0 11.56 8.69 3.55 11.11 8.44 3.57 10.50 8.16 4.20 10.21 7.91 4.38 9.82 7.71 4.55 9.58 7.46 4.26<br />

19.0 27.0 11.88 8.76 3.59 11.42 8.52 3.62 10.82 8.25 4.25 10.50 7.98 4.38 10.13 7.81 4.56 9.90 7.57 4.25<br />

22.0 30.0 12.83 8.94 3.59 12.37 8.72 3.68 11.76 8.47 4.35 11.46 8.23 4.59 11.07 8.06 4.63 10.83 7.82 4.29<br />

24.0 32.0 13.46 9.10 3.57 13.00 8.89 3.72 12.38 8.66 4.43 12.09 8.42 4.69 11.69 8.26 4.73 11.46 8.03 4.39<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

8.49 7.72 3.44<br />

9.14 7.93 3.48<br />

9.79 8.11 3.40<br />

10.12 8.22 3.37<br />

11.10 8.52 3.37<br />

11.76 8.76 3.45<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

8.10 6.91 3.66<br />

8.72 7.11 3.70<br />

9.35 7.26 3.62<br />

9.66 7.37 3.58<br />

10.60 7.63 3.58<br />

11.22 7.84 3.67<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.79 9.25 2.37 10.32 8.95 2.47 9.69 8.59 3.32 9.39 8.30 3.71 8.98 8.05 4.07 8.73 7.77 3.99<br />

16.0 22.0 11.45 9.38 3.21 10.98 9.09 3.24 10.34 8.76 3.92 10.05 8.48 4.21 9.63 8.24 4.39 9.39 7.97 4.18<br />

18.0 25.0 12.11 9.46 3.47 11.64 9.19 3.49 11.00 8.88 4.12 10.70 8.61 4.29 10.29 8.39 4.45 10.04 8.13 4.17<br />

19.0 27.0 12.45 9.54 3.51 11.97 9.28 3.54 11.33 8.98 4.16 11.00 8.69 4.29 10.62 8.50 4.46 10.37 8.24 4.16<br />

22.0 30.0 13.44 9.73 3.51 12.96 9.49 3.61 12.32 9.22 4.26 12.01 8.96 4.50 11.60 8.77 4.53 11.35 8.52 4.20<br />

24.0 32.0 14.11 9.91 3.49 13.62 9.68 3.64 12.97 9.42 4.34 12.66 9.17 4.59 12.25 8.99 4.63 12.00 8.74 4.30<br />

TC SHC PI<br />

8.49 7.53 3.58<br />

9.14 7.74 3.62<br />

9.79 7.90 3.54<br />

10.12 8.02 3.51<br />

11.10 8.31 3.51<br />

11.76 8.54 3.59<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 187


Capacity tables 5CSL0-06B<br />

Models : AUUW366D +ATNH36GNLED , UVNH366KLAD, ABNH366GLAD<br />

[UU36W UED]+ [UT36 NND] , [UV36 NKD] , [ UB36 NGD]<br />

• Heating Capacity<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.61 5.19 9.19 5.28 10.27 5.02 11.29 4.68 12.30 4.41 13.10 4.31 13.45 4.09<br />

18 8.53 5.26 9.18 5.41 10.29 5.16 11.28 4.81 12.22 4.53 12.94 4.39 13.41 4.14<br />

20 8.47 5.36 9.18 5.54 10.29 5.31 11.25 4.94 12.10 4.62 12.85 4.46 13.43 4.16<br />

21 8.45 5.40 9.18 5.62 10.29 5.39 11.23 5.01 12.02 4.66 12.85 4.49 13.35 4.17<br />

22 8.43 5.47 9.18 5.71 10.29 5.46 11.20 5.07 11.94 4.70 12.84 4.51 13.24 4.17<br />

24 8.35 5.56 9.09 5.78 10.16 5.53 11.13 5.12 11.92 4.73 12.62 4.52 13.16 4.19<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.25 5.25 8.81 5.35 9.85 5.08 10.83 4.74 11.79 4.47 12.56 4.36 12.90 4.14<br />

18 8.18 5.33 8.80 5.48 9.86 5.23 10.82 4.87 11.71 4.58 12.40 4.45 12.85 4.19<br />

20 8.12 5.42 8.80 5.61 9.86 5.38 10.79 5.00 11.60 4.68 12.32 4.51 12.88 4.21<br />

21 8.10 5.47 8.80 5.69 9.86 5.45 10.77 5.07 11.53 4.72 12.32 4.54 12.80 4.22<br />

22 8.08 5.53 8.80 5.78 9.86 5.53 10.73 5.13 11.44 4.76 12.31 4.57 12.69 4.22<br />

24 8.01 5.63 8.71 5.86 9.74 5.60 10.67 5.18 11.43 4.79 12.10 4.58 12.62 4.24<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.75 5.27 9.34 5.36 10.44 5.09 11.48 4.76 12.51 4.48 13.32 4.38 13.68 4.15<br />

18 8.67 5.35 9.33 5.50 10.46 5.24 11.47 4.89 12.42 4.60 13.15 4.46 13.63 4.20<br />

20 8.61 5.44 9.33 5.63 10.46 5.39 11.44 5.02 12.30 4.69 13.06 4.53 13.65 4.22<br />

21 8.59 5.49 9.33 5.71 10.46 5.47 11.41 5.08 12.22 4.74 13.06 4.56 13.57 4.23<br />

22 8.57 5.55 9.33 5.79 10.46 5.54 11.38 5.15 12.13 4.77 13.05 4.58 13.46 4.23<br />

24 8.49 5.65 9.24 5.87 10.33 5.62 11.32 5.20 12.12 4.80 12.83 4.59 13.38 4.25<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

188 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW426D +ATNH42GMLED , UVNH426LLAD, ABNH426RLAD<br />

[UU42W U3D]+ [UT42 NMD], [UV42 NLD] , [UB42 NRD]<br />

• Cooling Capacity<br />

Model ATNH42GMLED[UT42 NMD]<br />

AFR 30<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 11.76 2.84 12.94 11.38 2.96 12.15 10.92 3.98 11.78 10.55 4.44 11.27 10.23 4.87 10.96 9.87 4.78<br />

16.0 22.0 14.36 11.91 3.85 13.77 11.55 3.88 12.98 11.13 4.69 12.60 10.77 5.04 12.09 10.47 5.25 11.78 10.13 5.00<br />

18.0 25.0 15.20 12.02 4.16 14.60 11.68 4.18 13.80 11.28 4.93 13.42 10.94 5.13 12.91 10.66 5.33 12.60 10.33 4.99<br />

19.0 27.0 15.61 12.12 4.21 15.02 11.79 4.24 14.21 11.41 4.98 13.80 11.04 5.13 13.32 10.80 5.34 13.01 10.47 4.98<br />

22.0 30.0 16.86 12.36 4.20 16.26 12.06 4.32 15.45 11.71 5.10 15.07 11.38 5.38 14.55 11.14 5.42 14.24 10.82 5.03<br />

24.0 32.0 17.70 12.59 4.18 17.09 12.30 4.35 16.28 11.98 5.19 15.89 11.65 5.49 15.37 11.43 5.54 15.06 11.11 5.14<br />

Model UVNH426LLAD[UV42 NLD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Model ABNH426RLAD[UB42 NRD]<br />

AFR 36<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 11.03 2.92 12.94 10.67 3.05 12.15 10.24 4.09 11.78 9.90 4.56 11.27 9.60 5.01 10.96 9.26 4.91<br />

16.0 22.0 14.36 11.17 3.95 13.77 10.84 3.99 12.98 10.44 4.82 12.60 10.10 5.18 12.09 9.82 5.40 11.78 9.50 5.14<br />

18.0 25.0 15.20 11.27 4.28 14.60 10.95 4.30 13.80 10.58 5.07 13.42 10.26 5.28 12.91 10.00 5.48 12.60 9.69 5.13<br />

19.0 27.0 15.61 11.37 4.32 15.02 11.06 4.36 14.21 10.70 5.12 13.80 10.36 5.28 13.32 10.13 5.49 13.01 9.82 5.12<br />

22.0 30.0 16.86 11.60 4.32 16.26 11.31 4.44 15.45 10.99 5.24 15.07 10.68 5.53 14.55 10.45 5.58 14.24 10.15 5.17<br />

24.0 32.0 17.70 11.81 4.30 17.09 11.54 4.48 16.28 11.23 5.34 15.89 10.93 5.65 15.37 10.72 5.70 15.06 10.42 5.29<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

10.65 9.56 4.29<br />

11.47 9.83 4.34<br />

12.29 10.04 4.24<br />

12.70 10.19 4.20<br />

13.93 10.56 4.20<br />

14.75 10.85 4.30<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

10.65 8.97 4.41<br />

11.47 9.22 4.46<br />

12.29 9.42 4.36<br />

12.70 9.56 4.31<br />

13.93 9.90 4.32<br />

14.75 10.18 4.42<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 12.46 3.03 12.94 12.06 3.16 12.15 11.57 4.24 11.78 11.18 4.74 11.27 10.84 5.20 10.96 10.46 5.09<br />

16.0 22.0 14.36 12.63 4.10 13.77 12.25 4.14 12.98 11.80 5.01 12.60 11.42 5.38 12.09 11.10 5.60 11.78 10.73 5.33<br />

18.0 25.0 15.20 12.74 4.44 14.60 12.38 4.46 13.80 11.96 5.25 13.42 11.59 5.48 12.91 11.30 5.68 12.60 10.95 5.32<br />

19.0 27.0 15.61 12.85 4.49 15.02 12.50 4.53 14.21 12.09 5.31 13.80 11.70 5.48 13.32 11.45 5.70 13.01 11.10 5.31<br />

22.0 30.0 16.86 13.11 4.49 16.26 12.78 4.60 15.45 12.42 5.44 15.07 12.06 5.74 14.55 11.81 5.79 14.24 11.47 5.37<br />

24.0 32.0 17.70 13.35 4.46 17.09 13.04 4.64 16.28 12.69 5.54 15.89 12.35 5.86 15.37 12.11 5.91 15.06 11.78 5.48<br />

TC SHC PI<br />

10.65 10.14 4.57<br />

11.47 10.42 4.63<br />

12.29 10.65 4.52<br />

12.70 10.80 4.48<br />

13.93 11.19 4.48<br />

14.75 11.50 4.59<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 189


Capacity tables 5CSL0-06B<br />

Models : AUUW426D +ATNH42GMLED , UVNH426LLAD, ABNH426RLAD<br />

[UU42W U3D]+ [UT42 NMD], [UV42 NLD] , [UB42 NRD]<br />

• Heating Capacity<br />

Model ATNH42GMLED[UT42 NMD]<br />

AFR 30<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 6.21 11.70 6.33 13.07 6.01 14.37 5.61 15.66 5.29 16.68 5.16 17.12 4.90<br />

18 10.86 6.31 11.68 6.48 13.09 6.19 14.36 5.77 15.55 5.43 16.47 5.26 17.07 4.96<br />

20 10.78 6.42 11.68 6.64 13.09 6.36 14.32 5.92 15.40 5.53 16.36 5.34 17.09 4.98<br />

21 10.75 6.48 11.68 6.74 13.09 6.45 14.29 6.00 15.30 5.59 16.36 5.38 16.99 4.99<br />

22 10.73 6.55 11.68 6.84 13.09 6.54 14.25 6.08 15.19 5.63 16.34 5.40 16.85 4.99<br />

24 10.63 6.66 11.56 6.93 12.93 6.63 14.17 6.13 15.17 5.67 16.07 5.42 16.75 5.01<br />

Model UVNH426LLAD[UV42 NLD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 6.39 11.70 6.51 13.07 6.18 14.37 5.77 15.66 5.44 16.68 5.31 17.12 5.04<br />

18 10.86 6.49 11.68 6.67 13.09 6.36 14.36 5.93 15.55 5.58 16.47 5.41 17.07 5.10<br />

20 10.78 6.60 11.68 6.83 13.09 6.55 14.32 6.09 15.40 5.69 16.36 5.49 17.09 5.12<br />

21 10.75 6.66 11.68 6.93 13.09 6.64 14.29 6.17 15.30 5.75 16.36 5.53 16.99 5.13<br />

22 10.73 6.74 11.68 7.03 13.09 6.73 14.25 6.25 15.19 5.79 16.34 5.56 16.85 5.13<br />

24 10.63 6.85 11.56 7.13 12.93 6.81 14.17 6.31 15.17 5.83 16.07 5.57 16.75 5.16<br />

Model ABNH426RLAD[UB42 NRD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 5.99 11.70 6.10 13.07 5.79 14.37 5.41 15.66 5.10 16.68 4.98 17.12 4.72<br />

18 10.86 6.08 11.68 6.25 13.09 5.96 14.36 5.56 15.55 5.23 16.47 5.07 17.07 4.78<br />

20 10.78 6.19 11.68 6.40 13.09 6.13 14.32 5.71 15.40 5.33 16.36 5.15 17.09 4.80<br />

21 10.75 6.24 11.68 6.49 13.09 6.22 14.29 5.78 15.30 5.39 16.36 5.18 16.99 4.81<br />

22 10.73 6.31 11.68 6.59 13.09 6.30 14.25 5.86 15.19 5.43 16.34 5.21 16.85 4.81<br />

24 10.63 6.42 11.56 6.68 12.93 6.39 14.17 5.91 15.17 5.46 16.07 5.22 16.75 4.83<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

190 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW486D +ATNH48GMLED , UVNH486LLAD, ABNH486RLAD<br />

[UU48W U3D]+ [UT48 NMD] , [UV48 NLD], [UB48 NRD]<br />

• Cooling Capacity<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.39 12.87 3.36 14.72 12.46 3.51 13.83 11.95 4.71 13.40 11.55 5.26 12.82 11.20 5.78 12.46 10.80 5.66<br />

16.0 22.0 16.34 13.04 4.56 15.67 12.65 4.60 14.76 12.18 5.56 14.34 11.79 5.97 13.75 11.47 6.22 13.40 11.08 5.92<br />

18.0 25.0 17.29 13.15 4.93 16.61 12.78 4.96 15.70 12.35 5.84 15.27 11.97 6.09 14.68 11.67 6.31 14.33 11.30 5.91<br />

19.0 27.0 17.76 13.27 4.98 17.08 12.91 5.03 16.17 12.49 5.90 15.70 12.09 6.09 15.15 11.83 6.33 14.80 11.46 5.90<br />

22.0 30.0 19.19 13.53 4.98 18.50 13.20 5.11 17.58 12.82 6.04 17.14 12.46 6.38 16.55 12.20 6.43 16.20 11.85 5.96<br />

24.0 32.0 20.13 13.79 4.95 19.44 13.47 5.16 18.52 13.11 6.15 18.07 12.75 6.51 17.49 12.51 6.57 17.13 12.16 6.09<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Model ABNH486RLAD[UB48 NRD]<br />

AFR 40<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 14.32 11.51 3.21 13.69 11.13 3.36 12.86 10.68 4.51 12.46 10.32 5.03 11.92 10.01 5.53 11.59 9.66 5.41<br />

16.0 22.0 15.20 11.66 4.36 14.57 11.31 4.40 13.73 10.89 5.32 13.33 10.54 5.71 12.79 10.25 5.95 12.46 9.91 5.67<br />

18.0 25.0 16.08 11.76 4.71 15.45 11.43 4.74 14.60 11.04 5.58 14.20 10.70 5.82 13.66 10.43 6.04 13.33 10.10 5.66<br />

19.0 27.0 16.52 11.86 4.77 15.89 11.54 4.81 15.04 11.16 5.65 14.60 10.80 5.82 14.09 10.57 6.05 13.76 10.24 5.65<br />

22.0 30.0 17.84 12.10 4.77 17.20 11.80 4.89 16.35 11.46 5.78 15.94 11.14 6.10 15.39 10.90 6.15 15.06 10.59 5.70<br />

24.0 32.0 18.72 12.32 4.74 18.08 12.04 4.94 17.22 11.72 5.89 16.81 11.40 6.23 16.26 11.18 6.28 15.93 10.87 5.83<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

12.11 10.47 5.08<br />

13.05 10.76 5.14<br />

13.98 10.99 5.02<br />

14.45 11.16 4.97<br />

15.85 11.56 4.97<br />

16.78 11.88 5.09<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

11.26 9.36 4.86<br />

12.13 9.62 4.92<br />

13.00 9.83 4.80<br />

13.43 9.97 4.76<br />

14.74 10.33 4.76<br />

15.60 10.62 4.87<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.10 13.59 3.39 14.44 13.15 3.54 13.56 12.62 4.76 13.15 12.19 5.31 12.57 11.82 5.83 12.23 11.41 5.71<br />

16.0 22.0 16.03 13.77 4.60 15.37 13.35 4.64 14.48 12.86 5.61 14.06 12.45 6.02 13.49 12.11 6.28 13.14 11.70 5.98<br />

18.0 25.0 16.96 13.89 4.97 16.29 13.50 5.00 15.40 13.04 5.89 14.98 12.64 6.14 14.40 12.32 6.37 14.06 11.93 5.97<br />

19.0 27.0 17.42 14.01 5.03 16.76 13.63 5.07 15.86 13.19 5.95 15.40 12.76 6.14 14.86 12.49 6.38 14.52 12.10 5.95<br />

22.0 30.0 18.82 14.29 5.03 18.14 13.94 5.16 17.24 13.54 6.09 16.81 13.15 6.43 16.24 12.88 6.48 15.89 12.51 6.01<br />

24.0 32.0 19.75 14.56 5.00 19.07 14.22 5.20 18.16 13.84 6.21 17.73 13.46 6.56 17.15 13.21 6.62 16.81 12.84 6.15<br />

TC SHC PI<br />

11.88 11.05 5.12<br />

12.80 11.36 5.19<br />

13.71 11.61 5.06<br />

14.17 11.78 5.02<br />

15.54 12.20 5.02<br />

16.46 12.54 5.14<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 191


Capacity tables 5CSL0-06B<br />

Models : AUUW486D +ATNH48GMLED , UVNH486LLAD, ABNH486RLAD<br />

[UU48W U3D]+ [UT48 NMD] , [UV48 NLD], [UB48 NRD]<br />

• Heating Capacity<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.52 7.29 13.37 7.42 14.94 7.05 16.43 6.58 17.90 6.21 19.06 6.06 19.57 5.75<br />

18 12.41 7.40 13.35 7.61 14.96 7.26 16.41 6.77 17.77 6.36 18.82 6.18 19.50 5.82<br />

20 12.32 7.53 13.35 7.79 14.96 7.47 16.37 6.95 17.60 6.49 18.69 6.26 19.54 5.84<br />

21 12.29 7.60 13.35 7.91 14.96 7.57 16.33 7.04 17.49 6.56 18.69 6.31 19.42 5.86<br />

22 12.27 7.68 13.35 8.02 14.96 7.67 16.29 7.13 17.36 6.60 18.67 6.34 19.25 5.86<br />

24 12.15 7.81 13.22 8.13 14.78 7.77 16.19 7.20 17.34 6.65 18.36 6.35 19.14 5.88<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.52 6.39 13.37 6.51 14.94 6.18 16.43 5.77 17.90 5.44 19.06 5.31 19.57 5.04<br />

18 12.41 6.49 13.35 6.67 14.96 6.36 16.41 5.93 17.77 5.58 18.82 5.41 19.50 5.10<br />

20 12.32 6.60 13.35 6.83 14.96 6.55 16.37 6.09 17.60 5.69 18.69 5.49 19.54 5.12<br />

21 12.29 6.66 13.35 6.93 14.96 6.64 16.33 6.17 17.49 5.75 18.69 5.53 19.42 5.13<br />

22 12.27 6.74 13.35 7.03 14.96 6.73 16.29 6.25 17.36 5.79 18.67 5.56 19.25 5.13<br />

24 12.15 6.85 13.22 7.13 14.78 6.81 16.19 6.31 17.34 5.83 18.36 5.57 19.14 5.16<br />

Model ABNH486RLAD[UB48 NRD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.95 7.29 13.82 7.42 15.45 7.05 16.99 6.58 18.51 6.21 19.71 6.06 20.24 5.75<br />

18 12.83 7.40 13.80 7.61 15.47 7.26 16.97 6.77 18.38 6.36 19.46 6.18 20.17 5.82<br />

20 12.74 7.53 13.80 7.79 15.47 7.47 16.93 6.95 18.20 6.49 19.33 6.26 20.20 5.84<br />

21 12.71 7.60 13.80 7.91 15.47 7.57 16.89 7.04 18.08 6.56 19.33 6.31 20.08 5.86<br />

22 12.68 7.68 13.80 8.02 15.47 7.67 16.84 7.13 17.95 6.60 19.31 6.34 19.91 5.86<br />

24 12.56 7.81 13.67 8.13 15.28 7.77 16.75 7.20 17.93 6.65 18.99 6.35 19.80 5.88<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

192 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW606D +ATNH60GMLED , UVNH606LLAD, ABNH606RLAD<br />

[UU60W U3D]+ [UT60 NMD], [UV60 NLD], [UB60 NRD]<br />

• Cooling Capacity<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.98 12.84 3.94 15.29 12.43 4.11 14.35 11.93 5.52 13.92 11.52 6.16 13.31 11.17 6.77 12.94 10.78 6.63<br />

16.0 22.0 16.97 13.01 5.34 16.27 12.62 5.38 15.33 12.15 6.51 14.89 11.76 7.00 14.28 11.44 7.29 13.91 11.06 6.94<br />

18.0 25.0 17.95 13.12 5.77 17.25 12.76 5.81 16.30 12.32 6.84 15.86 11.95 7.13 15.25 11.65 7.39 14.88 11.28 6.93<br />

19.0 27.0 18.44 13.24 5.84 17.74 12.88 5.89 16.79 12.46 6.91 16.30 12.06 7.13 15.73 11.80 7.41 15.36 11.43 6.91<br />

22.0 30.0 19.92 13.50 5.84 19.20 13.17 5.99 18.25 12.79 7.08 17.79 12.43 7.47 17.18 12.17 7.53 16.82 11.82 6.98<br />

24.0 32.0 20.90 13.75 5.80 20.18 13.43 6.04 19.23 13.08 7.21 18.76 12.72 7.62 18.15 12.48 7.69 17.79 12.13 7.14<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.39 11.96 3.86 14.72 11.57 4.04 13.83 11.11 5.42 13.40 10.73 6.05 12.82 10.41 6.64 12.46 10.04 6.51<br />

16.0 22.0 16.34 12.12 5.24 15.67 11.75 5.29 14.76 11.32 6.39 14.34 10.96 6.87 13.75 10.65 7.16 13.40 10.30 6.81<br />

18.0 25.0 17.29 12.22 5.66 16.61 11.88 5.70 15.70 11.48 6.71 15.27 11.13 7.00 14.68 10.85 7.26 14.33 10.50 6.80<br />

19.0 27.0 17.76 12.33 5.73 17.08 12.00 5.78 16.17 11.61 6.79 15.70 11.23 7.00 15.15 10.99 7.28 14.80 10.65 6.79<br />

22.0 30.0 19.19 12.58 5.73 18.50 12.27 5.88 17.58 11.91 6.95 17.14 11.58 7.33 16.55 11.34 7.39 16.20 11.01 6.85<br />

24.0 32.0 20.13 12.81 5.70 19.44 12.51 5.93 18.52 12.18 7.07 18.07 11.85 7.48 17.49 11.62 7.55 17.13 11.30 7.00<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

12.57 10.44 5.95<br />

13.54 10.74 6.02<br />

14.51 10.97 5.88<br />

15.00 11.13 5.82<br />

16.45 11.53 5.83<br />

17.42 11.85 5.97<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

12.11 9.73 5.84<br />

13.05 10.00 5.91<br />

13.98 10.22 5.77<br />

14.45 10.37 5.72<br />

15.85 10.74 5.72<br />

16.78 11.04 5.86<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.98 14.43 3.83 15.29 13.96 4.01 14.35 13.40 5.38 13.92 12.95 6.00 13.31 12.55 6.59 12.94 12.11 6.46<br />

16.0 22.0 16.97 14.62 5.20 16.27 14.18 5.25 15.33 13.66 6.34 14.89 13.22 6.81 14.28 12.85 7.10 13.91 12.42 6.76<br />

18.0 25.0 17.95 14.74 5.62 17.25 14.33 5.65 16.30 13.85 6.66 15.86 13.42 6.94 15.25 13.08 7.20 14.88 12.67 6.75<br />

19.0 27.0 18.44 14.87 5.69 17.74 14.47 5.74 16.79 14.00 6.73 16.30 13.55 6.94 15.73 13.26 7.22 15.36 12.85 6.73<br />

22.0 30.0 19.92 15.17 5.69 19.20 14.80 5.84 18.25 14.37 6.89 17.79 13.97 7.28 17.18 13.68 7.34 16.82 13.28 6.80<br />

24.0 32.0 20.90 15.45 5.65 20.18 15.09 5.89 19.23 14.70 7.02 18.76 14.29 7.42 18.15 14.02 7.49 17.79 13.63 6.95<br />

TC SHC PI<br />

12.57 11.73 5.79<br />

13.54 12.06 5.87<br />

14.51 12.32 5.73<br />

15.00 12.50 5.67<br />

16.45 12.95 5.68<br />

17.42 13.31 5.81<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 193


Capacity tables 5CSL0-06B<br />

Models : AUUW606D +ATNH60GMLED , UVNH606LLAD, ABNH606RLAD<br />

[UU60W U3D]+ [UT60 NMD], [UV60 NLD], [UB60 NRD]<br />

• Heating Capacity<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 8.83 14.20 8.99 15.87 8.54 17.45 7.98 19.01 7.52 20.25 7.34 20.79 6.97<br />

18 13.18 8.96 14.18 9.22 15.90 8.79 17.44 8.20 18.88 7.71 20.00 7.48 20.72 7.05<br />

20 13.09 9.12 14.18 9.44 15.90 9.04 17.39 8.42 18.70 7.87 19.86 7.59 20.76 7.08<br />

21 13.06 9.20 14.18 9.58 15.90 9.17 17.35 8.53 18.58 7.94 19.86 7.64 20.63 7.09<br />

22 13.03 9.31 14.18 9.72 15.90 9.30 17.30 8.63 18.45 8.00 19.84 7.68 20.46 7.09<br />

24 12.91 9.47 14.04 9.85 15.70 9.42 17.21 8.72 18.42 8.06 19.51 7.70 20.34 7.13<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 8.83 14.20 8.99 15.87 8.54 17.45 7.98 19.01 7.52 20.25 7.34 20.79 6.97<br />

18 13.18 8.96 14.18 9.22 15.90 8.79 17.44 8.20 18.88 7.71 20.00 7.48 20.72 7.05<br />

20 13.09 9.12 14.18 9.44 15.90 9.04 17.39 8.42 18.70 7.87 19.86 7.59 20.76 7.08<br />

21 13.06 9.20 14.18 9.58 15.90 9.17 17.35 8.53 18.58 7.94 19.86 7.64 20.63 7.09<br />

22 13.03 9.31 14.18 9.72 15.90 9.30 17.30 8.63 18.45 8.00 19.84 7.68 20.46 7.09<br />

24 12.91 9.47 14.04 9.85 15.70 9.42 17.21 8.72 18.42 8.06 19.51 7.70 20.34 7.13<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 7.34 14.20 7.47 15.87 7.10 17.45 6.63 19.01 6.25 20.25 6.10 20.79 5.79<br />

18 13.18 7.45 14.18 7.66 15.90 7.31 17.44 6.81 18.88 6.41 20.00 6.22 20.72 5.85<br />

20 13.09 7.58 14.18 7.84 15.90 7.52 17.39 6.99 18.70 6.54 19.86 6.31 20.76 5.88<br />

21 13.06 7.65 14.18 7.96 15.90 7.62 17.35 7.08 18.58 6.60 19.86 6.35 20.63 5.89<br />

22 13.03 7.74 14.18 8.07 15.90 7.72 17.30 7.17 18.45 6.65 19.84 6.38 20.46 5.89<br />

24 12.91 7.87 14.04 8.18 15.70 7.83 17.21 7.24 18.42 6.69 19.51 6.40 20.34 5.92<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

194 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW368D+ATNH36GNLED, UVNH366KLAD, ABNH366GLAD<br />

[UU37W UED]+[UT36 NND], [UV36 NKD], [UB36 NGD]<br />

• Cooling Capacity<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.79 9.49 2.27 10.32 9.18 2.38 9.69 8.81 3.19 9.39 8.52 3.56 8.98 8.26 3.91 8.73 7.97 3.83<br />

16.0 22.0 11.45 9.61 3.08 10.98 9.33 3.11 10.34 8.98 3.76 10.05 8.69 4.04 9.63 8.45 4.21 9.39 8.17 4.01<br />

18.0 25.0 12.11 9.70 3.33 11.64 9.43 3.35 11.00 9.11 3.95 10.70 8.83 4.12 10.29 8.61 4.27 10.04 8.33 4.00<br />

19.0 27.0 12.45 9.78 3.37 11.97 9.52 3.40 11.33 9.21 3.99 11.00 8.91 4.12 10.62 8.72 4.28 10.37 8.45 3.99<br />

22.0 30.0 13.44 9.98 3.37 12.96 9.73 3.46 12.32 9.45 4.09 12.01 9.19 4.32 11.60 8.99 4.35 11.35 8.73 4.03<br />

24.0 32.0 14.11 10.16 3.35 13.62 9.93 3.49 12.97 9.67 4.16 12.66 9.40 4.40 12.25 9.22 4.44 12.00 8.97 4.12<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Indoor Air<br />

Temperature<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.30 8.50 2.42 9.85 8.22 2.53 9.25 7.89 3.40 8.96 7.63 3.79 8.57 7.39 4.16 8.34 7.13 4.08<br />

16.0 22.0 10.93 8.61 3.28 10.48 8.35 3.31 9.87 8.04 4.00 9.59 7.79 4.30 9.20 7.57 4.48 8.96 7.32 4.27<br />

18.0 25.0 11.56 8.69 3.55 11.11 8.44 3.57 10.50 8.16 4.20 10.21 7.91 4.38 9.82 7.71 4.55 9.58 7.46 4.26<br />

19.0 27.0 11.88 8.76 3.59 11.42 8.52 3.62 10.82 8.25 4.25 10.50 7.98 4.38 10.13 7.81 4.56 9.90 7.57 4.25<br />

22.0 30.0 12.83 8.94 3.59 12.37 8.72 3.68 11.76 8.47 4.35 11.46 8.23 4.59 11.07 8.06 4.63 10.83 7.82 4.29<br />

24.0 32.0 13.46 9.10 3.57 13.00 8.89 3.72 12.38 8.66 4.43 12.09 8.42 4.69 11.69 8.26 4.73 11.46 8.03 4.39<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

8.49 7.72 3.44<br />

9.14 7.93 3.48<br />

9.79 8.11 3.40<br />

10.12 8.22 3.37<br />

11.10 8.52 3.37<br />

11.76 8.76 3.45<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.79 9.26 2.56 10.32 8.96 2.67 9.69 8.60 3.59 9.39 8.30 4.01 8.98 8.05 4.40 8.73 7.77 4.31<br />

16.0 22.0 11.45 9.38 3.47 10.98 9.10 3.50 10.34 8.76 4.23 10.05 8.48 4.55 9.63 8.24 4.74 9.39 7.97 4.51<br />

18.0 25.0 12.11 9.46 3.75 11.64 9.19 3.77 11.00 8.88 4.44 10.70 8.61 4.63 10.29 8.39 4.81 10.04 8.13 4.50<br />

19.0 27.0 12.45 9.54 3.79 11.97 9.28 3.83 11.33 8.98 4.49 11.00 8.69 4.63 10.62 8.50 4.82 10.37 8.24 4.49<br />

22.0 30.0 13.44 9.73 3.79 12.96 9.49 3.89 12.32 9.22 4.60 12.01 8.96 4.86 11.60 8.77 4.89 11.35 8.52 4.54<br />

24.0 32.0 14.11 9.91 3.77 13.62 9.68 3.93 12.97 9.43 4.69 12.66 9.17 4.95 12.25 9.00 5.00 12.00 8.74 4.64<br />

TC SHC PI<br />

8.10 6.91 3.66<br />

8.72 7.11 3.70<br />

9.35 7.26 3.62<br />

9.66 7.37 3.58<br />

10.60 7.63 3.58<br />

11.22 7.84 3.67<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

8.49 7.53 3.87<br />

9.14 7.74 3.91<br />

9.79 7.90 3.82<br />

10.12 8.02 3.79<br />

11.10 8.31 3.79<br />

11.76 8.54 3.88<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 195


Capacity tables 5CSL0-06B<br />

Models : AUUW368D+ATNH36GNLED, UVNH366KLAD, ABNH366GLAD<br />

[UU37W UED]+[UT36 NND], [UV36 NKD], [UB36 NGD]<br />

• Heating Capacity<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Indoor Air<br />

Temperature<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.61 5.19 9.19 5.28 10.27 5.02 11.29 4.68 12.30 4.41 13.10 4.31 13.45 4.09<br />

18 8.53 5.26 9.18 5.41 10.29 5.16 11.28 4.81 12.22 4.53 12.94 4.39 13.41 4.14<br />

20 8.47 5.36 9.18 5.54 10.29 5.31 11.25 4.94 12.10 4.62 12.85 4.46 13.43 4.16<br />

21 8.45 5.40 9.18 5.62 10.29 5.39 11.23 5.01 12.02 4.66 12.85 4.49 13.35 4.17<br />

22 8.43 5.47 9.18 5.71 10.29 5.46 11.20 5.07 11.94 4.70 12.84 4.51 13.24 4.17<br />

24 8.35 5.56 9.09 5.78 10.16 5.53 11.13 5.12 11.92 4.73 12.62 4.52 13.16 4.19<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.25 5.25 8.81 5.35 9.85 5.08 10.83 4.74 11.79 4.47 12.56 4.36 12.90 4.14<br />

18 8.18 5.33 8.80 5.48 9.86 5.23 10.82 4.87 11.71 4.58 12.40 4.45 12.85 4.19<br />

20 8.12 5.42 8.80 5.61 9.86 5.38 10.79 5.00 11.60 4.68 12.32 4.51 12.88 4.21<br />

21 8.10 5.47 8.80 5.69 9.86 5.45 10.77 5.07 11.53 4.72 12.32 4.54 12.80 4.22<br />

22 8.08 5.53 8.80 5.78 9.86 5.53 10.73 5.13 11.44 4.76 12.31 4.57 12.69 4.22<br />

24 8.01 5.63 8.71 5.86 9.74 5.60 10.67 5.18 11.43 4.79 12.10 4.58 12.62 4.24<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 8.75 5.60 9.34 5.71 10.44 5.42 11.48 5.06 12.51 4.77 13.32 4.66 13.68 4.42<br />

18 8.67 5.69 9.33 5.85 10.46 5.58 11.47 5.20 12.42 4.89 13.15 4.75 13.63 4.47<br />

20 8.61 5.79 9.33 5.99 10.46 5.74 11.44 5.34 12.30 4.99 13.06 4.82 13.65 4.49<br />

21 8.59 5.84 9.33 6.08 10.46 5.82 11.41 5.41 12.22 5.04 13.06 4.85 13.57 4.50<br />

22 8.57 5.91 9.33 6.16 10.46 5.90 11.38 5.48 12.13 5.08 13.05 4.87 13.46 4.50<br />

24 8.49 6.01 9.24 6.25 10.33 5.98 11.32 5.53 12.12 5.11 12.83 4.88 13.38 4.52<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

196 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW428D +ATNH42GMLED , UVNH426LLAD , ABNH426RLAD<br />

[UU43W U3D]+ [UT42 NMD] , [UV42 NLD] , [UB42 NRD]<br />

• Cooling Capacity<br />

Model ATNH42GMLED[UT42 NMD]<br />

AFR 30<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 11.70 2.84 12.94 11.32 2.96 12.15 10.86 3.98 11.78 10.50 4.44 11.27 10.18 4.87 10.96 9.82 4.78<br />

16.0 22.0 14.36 11.85 3.85 13.77 11.50 3.88 12.98 11.07 4.69 12.60 10.72 5.04 12.09 10.42 5.25 11.78 10.07 5.00<br />

18.0 25.0 15.20 11.96 4.16 14.60 11.62 4.18 13.80 11.23 4.93 13.42 10.88 5.13 12.91 10.61 5.33 12.60 10.27 4.99<br />

19.0 27.0 15.61 12.06 4.21 15.02 11.73 4.24 14.21 11.35 4.98 13.80 10.98 5.13 13.32 10.75 5.34 13.01 10.42 4.98<br />

22.0 30.0 16.86 12.30 4.20 16.26 12.00 4.32 15.45 11.65 5.10 15.07 11.32 5.38 14.55 11.09 5.42 14.24 10.77 5.03<br />

24.0 32.0 17.70 12.53 4.18 17.09 12.24 4.35 16.28 11.92 5.19 15.89 11.59 5.49 15.37 11.37 5.54 15.06 11.05 5.14<br />

Model UVNH426LLAD[UV42 NLD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Model ABNH426RLAD[UB42 NRD]<br />

AFR 36<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 11.03 2.92 12.94 10.67 3.05 12.15 10.24 4.09 11.78 9.90 4.56 11.27 9.60 5.01 10.96 9.26 4.91<br />

16.0 22.0 14.36 11.17 3.95 13.77 10.84 3.99 12.98 10.44 4.82 12.60 10.10 5.18 12.09 9.82 5.40 11.78 9.50 5.14<br />

18.0 25.0 15.20 11.27 4.28 14.60 10.95 4.30 13.80 10.58 5.07 13.42 10.26 5.28 12.91 10.00 5.48 12.60 9.69 5.13<br />

19.0 27.0 15.61 11.37 4.32 15.02 11.06 4.36 14.21 10.70 5.12 13.80 10.36 5.28 13.32 10.13 5.49 13.01 9.82 5.12<br />

22.0 30.0 16.86 11.60 4.32 16.26 11.31 4.44 15.45 10.99 5.24 15.07 10.68 5.53 14.55 10.45 5.58 14.24 10.15 5.17<br />

24.0 32.0 17.70 11.81 4.30 17.09 11.54 4.48 16.28 11.23 5.34 15.89 10.93 5.65 15.37 10.72 5.70 15.06 10.42 5.29<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

10.65 9.52 4.29<br />

11.47 9.78 4.34<br />

12.29 9.99 4.24<br />

12.70 10.14 4.20<br />

13.93 10.50 4.20<br />

14.75 10.80 4.30<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 13.53 12.46 3.03 12.94 12.06 3.16 12.15 11.57 4.24 11.78 11.18 4.74 11.27 10.84 5.20 10.96 10.46 5.09<br />

16.0 22.0 14.36 12.63 4.10 13.77 12.25 4.14 12.98 11.80 5.01 12.60 11.42 5.38 12.09 11.10 5.60 11.78 10.73 5.33<br />

18.0 25.0 15.20 12.74 4.44 14.60 12.38 4.46 13.80 11.96 5.25 13.42 11.59 5.48 12.91 11.30 5.68 12.60 10.95 5.32<br />

19.0 27.0 15.61 12.85 4.49 15.02 12.50 4.53 14.21 12.09 5.31 13.80 11.70 5.48 13.32 11.45 5.70 13.01 11.10 5.31<br />

22.0 30.0 16.86 13.11 4.49 16.26 12.78 4.60 15.45 12.42 5.44 15.07 12.06 5.74 14.55 11.81 5.79 14.24 11.47 5.37<br />

24.0 32.0 17.70 13.35 4.46 17.09 13.04 4.64 16.28 12.69 5.54 15.89 12.35 5.86 15.37 12.11 5.91 15.06 11.78 5.48<br />

TC SHC PI<br />

10.65 8.97 4.41<br />

11.47 9.22 4.46<br />

12.29 9.42 4.36<br />

12.70 9.56 4.31<br />

13.93 9.90 4.32<br />

14.75 10.18 4.42<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

10.65 10.14 4.57<br />

11.47 10.42 4.63<br />

12.29 10.65 4.52<br />

12.70 10.80 4.48<br />

13.93 11.19 4.48<br />

14.75 11.50 4.59<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 197


Capacity tables 5CSL0-06B<br />

Models : AUUW428D +ATNH42GMLED , UVNH426LLAD , ABNH426RLAD<br />

[UU43W U3D]+ [UT42 NMD] , [UV42 NLD] , [UB42 NRD]<br />

• Heating Capacity<br />

Model ATNH42GMLED[UT42 NMD]<br />

AFR 30<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 6.21 11.70 6.33 13.07 6.01 14.37 5.61 15.66 5.29 16.68 5.16 17.12 4.90<br />

18 10.86 6.31 11.68 6.48 13.09 6.19 14.36 5.77 15.55 5.43 16.47 5.26 17.07 4.96<br />

20 10.78 6.42 11.68 6.64 13.09 6.36 14.32 5.92 15.40 5.53 16.36 5.34 17.09 4.98<br />

21 10.75 6.48 11.68 6.74 13.09 6.45 14.29 6.00 15.30 5.59 16.36 5.38 16.99 4.99<br />

22 10.73 6.55 11.68 6.84 13.09 6.54 14.25 6.08 15.19 5.63 16.34 5.40 16.85 4.99<br />

24 10.63 6.66 11.56 6.93 12.93 6.63 14.17 6.13 15.17 5.67 16.07 5.42 16.75 5.01<br />

Model UVNH426LLAD[UV42 NLD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 6.39 11.70 6.51 13.07 6.18 14.37 5.77 15.66 5.44 16.68 5.31 17.12 5.04<br />

18 10.86 6.49 11.68 6.67 13.09 6.36 14.36 5.93 15.55 5.58 16.47 5.41 17.07 5.10<br />

20 10.78 6.60 11.68 6.83 13.09 6.55 14.32 6.09 15.40 5.69 16.36 5.49 17.09 5.12<br />

21 10.75 6.66 11.68 6.93 13.09 6.64 14.29 6.17 15.30 5.75 16.36 5.53 16.99 5.13<br />

22 10.73 6.74 11.68 7.03 13.09 6.73 14.25 6.25 15.19 5.79 16.34 5.56 16.85 5.13<br />

24 10.63 6.85 11.56 7.13 12.93 6.81 14.17 6.31 15.17 5.83 16.07 5.57 16.75 5.16<br />

Model ABNH426RLAD[UB42 NRD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 10.96 6.13 11.70 6.25 13.07 5.93 14.37 5.54 15.66 5.22 16.68 5.10 17.12 4.84<br />

18 10.86 6.23 11.68 6.40 13.09 6.11 14.36 5.69 15.55 5.36 16.47 5.20 17.07 4.89<br />

20 10.78 6.34 11.68 6.56 13.09 6.28 14.32 5.84 15.40 5.46 16.36 5.27 17.09 4.92<br />

21 10.75 6.39 11.68 6.65 13.09 6.37 14.29 5.92 15.30 5.52 16.36 5.31 16.99 4.93<br />

22 10.73 6.47 11.68 6.75 13.09 6.46 14.25 6.00 15.19 5.56 16.34 5.33 16.85 4.93<br />

24 10.63 6.57 11.56 6.84 12.93 6.54 14.17 6.06 15.17 5.60 16.07 5.35 16.75 4.95<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

198 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW488D +ATNH48GMLED , UVNH486LLAD , ABNH486RLAD<br />

[UU49W U3D]+ [UT48 NMD] , [ UV48 NLD] , [UB48 NRD]<br />

• Cooling Capacity<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.39 12.85 3.34 14.72 12.43 3.49 13.83 11.93 4.68 13.40 11.53 5.23 12.82 11.17 5.74 12.46 10.78 5.62<br />

16.0 22.0 16.34 13.01 4.53 15.67 12.62 4.57 14.76 12.16 5.52 14.34 11.77 5.93 13.75 11.44 6.18 13.40 11.06 5.89<br />

18.0 25.0 17.29 13.13 4.90 16.61 12.76 4.92 15.70 12.33 5.80 15.27 11.95 6.05 14.68 11.65 6.27 14.33 11.28 5.88<br />

19.0 27.0 17.76 13.24 4.95 17.08 12.88 5.00 16.17 12.46 5.86 15.70 12.06 6.05 15.15 11.80 6.29 14.80 11.44 5.86<br />

22.0 30.0 19.19 13.51 4.95 18.50 13.17 5.08 17.58 12.79 6.00 17.14 12.43 6.34 16.55 12.17 6.39 16.20 11.82 5.92<br />

24.0 32.0 20.13 13.76 4.92 19.44 13.44 5.13 18.52 13.08 6.11 18.07 12.72 6.46 17.49 12.48 6.52 17.13 12.14 6.05<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 40<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 14.32 11.44 3.21 13.69 11.07 3.36 12.86 10.62 4.51 12.46 10.26 5.03 11.92 9.95 5.53 11.59 9.60 5.41<br />

16.0 22.0 15.20 11.59 4.36 14.57 11.24 4.40 13.73 10.82 5.32 13.33 10.47 5.71 12.79 10.19 5.95 12.46 9.85 5.67<br />

18.0 25.0 16.08 11.69 4.71 15.45 11.36 4.74 14.60 10.97 5.58 14.20 10.64 5.82 13.66 10.37 6.04 13.33 10.04 5.66<br />

19.0 27.0 16.52 11.79 4.77 15.89 11.47 4.81 15.04 11.10 5.65 14.60 10.74 5.82 14.09 10.51 6.05 13.76 10.18 5.65<br />

22.0 30.0 17.84 12.02 4.77 17.20 11.73 4.89 16.35 11.39 5.78 15.94 11.07 6.10 15.39 10.84 6.15 15.06 10.52 5.70<br />

24.0 32.0 18.72 12.25 4.74 18.08 11.96 4.94 17.22 11.65 5.89 16.81 11.33 6.23 16.26 11.11 6.28 15.93 10.80 5.83<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

12.11 10.45 5.05<br />

13.05 10.74 5.11<br />

13.98 10.97 4.99<br />

14.45 11.13 4.94<br />

15.85 11.53 4.94<br />

16.78 11.85 5.06<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.10 13.59 3.39 14.44 13.15 3.54 13.56 12.62 4.76 13.15 12.19 5.31 12.57 11.82 5.83 12.23 11.41 5.71<br />

16.0 22.0 16.03 13.77 4.60 15.37 13.35 4.64 14.48 12.86 5.61 14.06 12.45 6.02 13.49 12.11 6.28 13.14 11.70 5.98<br />

18.0 25.0 16.96 13.89 4.97 16.29 13.50 5.00 15.40 13.04 5.89 14.98 12.64 6.14 14.40 12.32 6.37 14.06 11.93 5.97<br />

19.0 27.0 17.42 14.01 5.03 16.76 13.63 5.07 15.86 13.19 5.95 15.40 12.76 6.14 14.86 12.49 6.38 14.52 12.10 5.95<br />

22.0 30.0 18.82 14.29 5.03 18.14 13.94 5.16 17.24 13.54 6.09 16.81 13.15 6.43 16.24 12.88 6.48 15.89 12.51 6.01<br />

24.0 32.0 19.75 14.56 5.00 19.07 14.22 5.20 18.16 13.84 6.21 17.73 13.46 6.56 17.15 13.21 6.62 16.81 12.84 6.15<br />

TC SHC PI<br />

11.26 9.30 4.86<br />

12.13 9.56 4.92<br />

13.00 9.77 4.80<br />

13.43 9.91 4.76<br />

14.74 10.27 4.76<br />

15.60 10.55 4.87<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

11.88 11.05 5.12<br />

12.80 11.36 5.19<br />

13.71 11.61 5.06<br />

14.17 11.78 5.02<br />

15.54 12.20 5.02<br />

16.46 12.54 5.14<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 199


Capacity tables 5CSL0-06B<br />

Models : AUUW488D +ATNH48GMLED , UVNH486LLAD , ABNH486RLAD<br />

[UU49W U3D]+ [UT48 NMD] , [ UV48 NLD] , [UB48 NRD]<br />

• Heating Capacity<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.52 7.48 13.37 7.62 14.94 7.24 16.43 6.76 17.90 6.37 19.06 6.22 19.57 5.90<br />

18 12.41 7.59 13.35 7.81 14.96 7.45 16.41 6.94 17.77 6.53 18.82 6.34 19.50 5.97<br />

20 12.32 7.73 13.35 8.00 14.96 7.66 16.37 7.13 17.60 6.66 18.69 6.43 19.54 6.00<br />

21 12.29 7.80 13.35 8.11 14.96 7.77 16.33 7.22 17.49 6.73 18.69 6.48 19.42 6.01<br />

22 12.27 7.89 13.35 8.23 14.96 7.88 16.29 7.32 17.36 6.78 18.67 6.51 19.25 6.01<br />

24 12.15 8.02 13.22 8.34 14.78 7.98 16.19 7.39 17.34 6.83 18.36 6.52 19.14 6.04<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.52 7.64 13.37 7.78 14.94 7.39 16.43 6.90 17.90 6.51 19.06 6.35 19.57 6.03<br />

18 12.41 7.76 13.35 7.98 14.96 7.61 16.41 7.09 17.77 6.67 18.82 6.47 19.50 6.10<br />

20 12.32 7.90 13.35 8.17 14.96 7.83 16.37 7.28 17.60 6.81 18.69 6.57 19.54 6.13<br />

21 12.29 7.96 13.35 8.29 14.96 7.94 16.33 7.38 17.49 6.87 18.69 6.62 19.42 6.14<br />

22 12.27 8.06 13.35 8.41 14.96 8.05 16.29 7.47 17.36 6.92 18.67 6.65 19.25 6.14<br />

24 12.15 8.19 13.22 8.52 14.78 8.15 16.19 7.55 17.34 6.97 18.36 6.66 19.14 6.17<br />

Model ABNH486RLAD[UB48 NRD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.95 7.34 13.82 7.47 15.45 7.10 16.99 6.63 18.51 6.25 19.71 6.10 20.24 5.79<br />

18 12.83 7.45 13.80 7.66 15.47 7.31 16.97 6.81 18.38 6.41 19.46 6.22 20.17 5.85<br />

20 12.74 7.58 13.80 7.84 15.47 7.52 16.93 6.99 18.20 6.54 19.33 6.31 20.20 5.88<br />

21 12.71 7.65 13.80 7.96 15.47 7.62 16.89 7.08 18.08 6.60 19.33 6.35 20.08 5.89<br />

22 12.68 7.74 13.80 8.07 15.47 7.72 16.84 7.17 17.95 6.65 19.31 6.38 19.91 5.89<br />

24 12.56 7.87 13.67 8.18 15.28 7.83 16.75 7.24 17.93 6.69 18.99 6.40 19.80 5.92<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

200 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW608D +ATNH60GMLED , UVNH606LLAD , ABNH606RLAD<br />

[UU61W U3D] + [UT60 NMD], [UV60 NLD] , [UB60 NRD]<br />

• Cooling Capacity<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.98 12.76 4.10 15.29 12.34 4.29 14.35 11.84 5.76 13.92 11.44 6.42 13.31 11.10 7.06 12.94 10.71 6.91<br />

16.0 22.0 16.97 12.92 5.57 16.27 12.53 5.61 15.33 12.07 6.79 14.89 11.68 7.29 14.28 11.36 7.60 13.91 10.98 7.23<br />

18.0 25.0 17.95 13.03 6.02 17.25 12.67 6.05 16.30 12.24 7.13 15.86 11.86 7.43 15.25 11.57 7.71 14.88 11.20 7.22<br />

19.0 27.0 18.44 13.15 6.09 17.74 12.79 6.14 16.79 12.38 7.21 16.30 11.98 7.43 15.73 11.72 7.73 15.36 11.36 7.21<br />

22.0 30.0 19.92 13.41 6.09 19.20 13.08 6.25 18.25 12.71 7.38 17.79 12.35 7.79 17.18 12.09 7.85 16.82 11.74 7.28<br />

24.0 32.0 20.90 13.66 6.05 20.18 13.34 6.30 19.23 12.99 7.52 18.76 12.64 7.95 18.15 12.40 8.02 17.79 12.05 7.44<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 38<br />

Indoor Air<br />

Temperature<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.39 11.96 3.86 14.72 11.57 4.04 13.83 11.11 5.42 13.40 10.73 6.05 12.82 10.41 6.64 12.46 10.04 6.51<br />

16.0 22.0 16.34 12.12 5.24 15.67 11.75 5.29 14.76 11.32 6.39 14.34 10.96 6.87 13.75 10.65 7.16 13.40 10.30 6.81<br />

18.0 25.0 17.29 12.22 5.66 16.61 11.88 5.70 15.70 11.48 6.71 15.27 11.13 7.00 14.68 10.85 7.26 14.33 10.50 6.80<br />

19.0 27.0 17.76 12.33 5.73 17.08 12.00 5.78 16.17 11.61 6.79 15.70 11.23 7.00 15.15 10.99 7.28 14.80 10.65 6.79<br />

22.0 30.0 19.19 12.58 5.73 18.50 12.27 5.88 17.58 11.91 6.95 17.14 11.58 7.33 16.55 11.34 7.39 16.20 11.01 6.85<br />

24.0 32.0 20.13 12.81 5.70 19.44 12.51 5.93 18.52 12.18 7.07 18.07 11.85 7.48 17.49 11.62 7.55 17.13 11.30 7.00<br />

Indoor Air<br />

Temperature<br />

TC SHC PI<br />

12.57 10.37 6.20<br />

13.54 10.66 6.28<br />

14.51 10.89 6.13<br />

15.00 11.05 6.07<br />

16.45 11.45 6.08<br />

17.42 11.77 6.22<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 15.98 14.43 3.83 15.29 13.96 4.01 14.35 13.40 5.38 13.92 12.95 6.00 13.31 12.55 6.59 12.94 12.11 6.46<br />

16.0 22.0 16.97 14.62 5.20 16.27 14.18 5.25 15.33 13.66 6.34 14.89 13.22 6.81 14.28 12.85 7.10 13.91 12.42 6.76<br />

18.0 25.0 17.95 14.74 5.62 17.25 14.33 5.65 16.30 13.85 6.66 15.86 13.42 6.94 15.25 13.08 7.20 14.88 12.67 6.75<br />

19.0 27.0 18.44 14.87 5.69 17.74 14.47 5.74 16.79 14.00 6.73 16.30 13.55 6.94 15.73 13.26 7.22 15.36 12.85 6.73<br />

22.0 30.0 19.92 15.17 5.69 19.20 14.80 5.84 18.25 14.37 6.89 17.79 13.97 7.28 17.18 13.68 7.34 16.82 13.28 6.80<br />

24.0 32.0 20.90 15.45 5.65 20.18 15.09 5.89 19.23 14.70 7.02 18.76 14.29 7.42 18.15 14.02 7.49 17.79 13.63 6.95<br />

TC SHC PI<br />

12.11 9.73 5.84<br />

13.05 10.00 5.91<br />

13.98 10.22 5.77<br />

14.45 10.37 5.72<br />

15.85 10.74 5.72<br />

16.78 11.04 5.86<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

TC SHC PI<br />

12.57 11.73 5.79<br />

13.54 12.06 5.87<br />

14.51 12.32 5.73<br />

15.00 12.50 5.67<br />

16.45 12.95 5.68<br />

17.42 13.31 5.81<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 201


Capacity tables 5CSL0-06B<br />

Models : AUUW608D +ATNH60GMLED , UVNH606LLAD , ABNH606RLAD<br />

[UU61W U3D] + [UT60 NMD], [UV60 NLD] , [UB60 NRD]<br />

• Heating Capacity<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 9.06 14.20 9.22 15.87 8.76 17.45 8.18 19.01 7.71 20.25 7.52 20.79 7.14<br />

18 13.18 9.19 14.18 9.45 15.90 9.02 17.44 8.41 18.88 7.91 20.00 7.67 20.72 7.23<br />

20 13.09 9.36 14.18 9.68 15.90 9.27 17.39 8.63 18.70 8.07 19.86 7.78 20.76 7.26<br />

21 13.06 9.44 14.18 9.82 15.90 9.40 17.35 8.74 18.58 8.14 19.86 7.84 20.63 7.28<br />

22 13.03 9.55 14.18 9.96 15.90 9.53 17.30 8.85 18.45 8.20 19.84 7.88 20.46 7.28<br />

24 12.91 9.71 14.04 10.10 15.70 9.66 17.21 8.94 18.42 8.26 19.51 7.89 20.34 7.31<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 38<br />

Indoor Air<br />

Temperature<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 8.83 14.20 8.99 15.87 8.54 17.45 7.98 19.01 7.52 20.25 7.34 20.79 6.97<br />

18 13.18 8.96 14.18 9.22 15.90 8.79 17.44 8.20 18.88 7.71 20.00 7.48 20.72 7.05<br />

20 13.09 9.12 14.18 9.44 15.90 9.04 17.39 8.42 18.70 7.87 19.86 7.59 20.76 7.08<br />

21 13.06 9.20 14.18 9.58 15.90 9.17 17.35 8.53 18.58 7.94 19.86 7.64 20.63 7.09<br />

22 13.03 9.31 14.18 9.72 15.90 9.30 17.30 8.63 18.45 8.00 19.84 7.68 20.46 7.09<br />

24 12.91 9.47 14.04 9.85 15.70 9.42 17.21 8.72 18.42 8.06 19.51 7.70 20.34 7.13<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 13.31 7.55 14.20 7.69 15.87 7.30 17.45 6.82 19.01 6.42 20.25 6.27 20.79 5.95<br />

18 13.18 7.66 14.18 7.88 15.90 7.51 17.44 7.00 18.88 6.59 20.00 6.39 20.72 6.02<br />

20 13.09 7.80 14.18 8.07 15.90 7.73 17.39 7.19 18.70 6.72 19.86 6.49 20.76 6.05<br />

21 13.06 7.86 14.18 8.18 15.90 7.84 17.35 7.29 18.58 6.79 19.86 6.53 20.63 6.06<br />

22 13.03 7.96 14.18 8.30 15.90 7.94 17.30 7.38 18.45 6.84 19.84 6.56 20.46 6.06<br />

24 12.91 8.09 14.04 8.42 15.70 8.05 17.21 7.45 18.42 6.88 19.51 6.58 20.34 6.09<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

202 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW186DH + ATNH18GPLED<br />

[UU18WH UED] + [UT18 NPD]<br />

• Cooling Capacity<br />

Model ATNH18GPLED[UT18 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.39 5.04 0.98 5.16 4.87 1.03 4.84 4.68 1.38 4.70 4.52 1.54 4.49 4.38 1.69 4.37 4.23 1.66<br />

16.0 22.0 5.72 5.10 1.33 5.49 4.95 1.35 5.17 4.77 1.63 5.02 4.61 1.75 4.82 4.49 1.82 4.69 4.34 1.73<br />

18.0 25.0 6.06 5.15 1.44 5.82 5.00 1.45 5.50 4.83 1.71 5.35 4.69 1.78 5.14 4.57 1.85 5.02 4.42 1.73<br />

19.0 27.0 6.22 5.19 1.46 5.98 5.05 1.47 5.67 4.89 1.73 5.50 4.73 1.78 5.31 4.63 1.85 5.18 4.49 1.73<br />

22.0 30.0 6.72 5.30 1.46 6.48 5.17 1.50 6.16 5.02 1.77 6.00 4.88 1.87 5.80 4.77 1.88 5.67 4.64 1.75<br />

24.0 32.0 7.05 5.40 1.45 6.81 5.27 1.51 6.49 5.13 1.80 6.33 4.99 1.91 6.13 4.90 1.92 6.00 4.76 1.78<br />

Capacity tables<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Heating Capacity<br />

Model ATNH18GPLED[UT18 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

4.24 4.10 1.49<br />

4.57 4.21 1.51<br />

4.90 4.30 1.47<br />

5.06 4.37 1.46<br />

5.55 4.52 1.46<br />

5.88 4.65 1.49<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 4.31 2.03 4.60 2.07 5.13 1.96 5.65 1.83 6.15 1.73 6.55 1.69 6.73 1.60<br />

18 4.26 2.06 4.59 2.12 5.14 2.02 5.64 1.89 6.11 1.77 6.47 1.72 6.70 1.62<br />

20 4.24 2.10 4.59 2.17 5.14 2.08 5.63 1.94 6.05 1.81 6.43 1.75 6.72 1.63<br />

21 4.22 2.12 4.59 2.20 5.14 2.11 5.61 1.96 6.01 1.83 6.43 1.76 6.67 1.63<br />

22 4.22 2.14 4.59 2.23 5.14 2.14 5.60 1.99 5.97 1.84 6.42 1.77 6.62 1.63<br />

24 4.18 2.18 4.54 2.27 5.08 2.17 5.57 2.01 5.96 1.85 6.31 1.77 6.58 1.64<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 203


Capacity tables 5CSL0-06B<br />

Models : AUUW216DH + ATNH21GNLED<br />

[UU21WH U4D] + [UT21 NND]<br />

• Cooling Capacity<br />

Model ATNH21GNLED[UT21 NND]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Heating Capacity<br />

Model ATNH21GNLED[UT21 NND]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 7.84 7.10 1.38 7.50 6.87 1.44 7.04 6.59 1.93 6.83 6.37 2.16 6.53 6.18 2.37 6.35 5.96 2.32<br />

16.0 22.0 8.33 7.19 1.87 7.98 6.98 1.89 7.52 6.72 2.28 7.31 6.50 2.45 7.01 6.32 2.55 6.83 6.11 2.43<br />

18.0 25.0 8.81 7.26 2.02 8.46 7.05 2.03 8.00 6.81 2.39 7.78 6.60 2.50 7.48 6.44 2.59 7.30 6.24 2.43<br />

19.0 27.0 9.05 7.32 2.04 8.70 7.12 2.06 8.24 6.89 2.42 8.00 6.67 2.50 7.72 6.52 2.60 7.54 6.32 2.42<br />

22.0 30.0 9.78 7.47 2.04 9.43 7.28 2.10 8.96 7.07 2.48 8.73 6.87 2.62 8.43 6.73 2.64 8.25 6.53 2.44<br />

24.0 32.0 10.26 7.60 2.03 9.91 7.43 2.12 9.44 7.23 2.52 9.21 7.03 2.67 8.91 6.90 2.69 8.73 6.71 2.50<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.40 2.89 6.84 2.94 7.64 2.79 8.40 2.61 9.15 2.46 9.75 2.40 10.01 2.28<br />

18 6.34 2.93 6.83 3.01 7.65 2.88 8.39 2.68 9.09 2.52 9.62 2.45 9.97 2.31<br />

20 6.30 2.98 6.83 3.09 7.65 2.96 8.37 2.75 9.00 2.57 9.56 2.48 9.99 2.32<br />

21 6.28 3.01 6.83 3.13 7.65 3.00 8.35 2.79 8.94 2.60 9.56 2.50 9.93 2.32<br />

22 6.27 3.05 6.83 3.18 7.65 3.04 8.33 2.82 8.88 2.62 9.55 2.51 9.85 2.32<br />

24 6.21 3.10 6.76 3.22 7.56 3.08 8.28 2.85 8.87 2.64 9.39 2.52 9.79 2.33<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

TC SHC PI<br />

6.17 5.77 2.08<br />

6.65 5.94 2.11<br />

7.12 6.06 2.06<br />

7.36 6.15 2.04<br />

8.07 6.37 2.04<br />

8.55 6.55 2.09<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

204 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW246DH + ATNH24GNLED<br />

[UU24WH U4D] + [UT24 NND]<br />

• Cooling Capacity<br />

Model ATNH24GPLED[UT24 NND]<br />

AFR 21<br />

Capacity tables<br />

• Symbol<br />

AFR : Air flow rate [m3 Indoor Air<br />

Outdoor Air Temperature : °CDB<br />

Temperature 20 25 32 35 40 43 46<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.24 7.78 1.43 7.88 7.53 1.50 7.40 7.23 2.01 7.17 6.98 2.24 6.86 6.77 2.46 6.67 6.53 2.41 6.48 6.33 2.16<br />

16.0 22.0 8.74 7.89 1.94 8.38 7.65 1.96 7.90 7.37 2.37 7.67 7.13 2.54 7.36 6.93 2.65 7.17 6.70 2.52 6.98 6.51 2.19<br />

18.0 25.0 9.25 7.95 2.10 8.89 7.73 2.11 8.40 7.47 2.49 8.17 7.24 2.59 7.86 7.06 2.69 7.67 6.84 2.52 7.48 6.65 2.14<br />

19.0 27.0 9.50 8.02 2.12 9.14 7.81 2.14 8.65 7.55 2.51 8.40 7.31 2.59 8.11 7.15 2.70 7.92 6.93 2.51 7.73 6.75 2.12<br />

22.0 30.0 10.26 8.18 2.12 9.90 7.98 2.18 9.41 7.75 2.57 9.17 7.53 2.72 8.86 7.38 2.74 8.67 7.16 2.54 8.48 6.99 2.12<br />

24.0 32.0 10.77 8.34 2.11 10.40 8.14 2.20 9.91 7.93 2.62 9.67 7.71 2.77 9.36 7.56 2.80 9.17 7.35 2.60 8.98 7.18 2.17<br />

• Notes<br />

/min] 1. All capacites are net, evaporator fan motor heat is<br />

DB : Dry bulb temperature [°C]<br />

deducted.<br />

WB : Wet bulb temperature [°C] 2. Indicates rated capacity.<br />

TC : Total capacity [kW] 3. Direct interpolation is permissible. Do not extrapolate<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

• Heating Capacity<br />

Model ATNH24GPLED[UT24 NND]<br />

AFR 21<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CWB<br />

-15 -10 -5 0 6 10 15<br />

˚CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 6.69 3.10 7.14 3.16 7.98 3.00 8.77 2.80 9.56 2.64 10.18 2.57 10.45 2.44<br />

18 6.63 3.15 7.13 3.23 7.99 3.09 8.77 2.88 9.49 2.71 10.05 2.63 10.42 2.47<br />

20 6.58 3.20 7.13 3.31 7.99 3.17 8.74 2.95 9.40 2.76 9.98 2.66 10.43 2.48<br />

21 6.56 3.23 7.13 3.36 7.99 3.22 8.72 2.99 9.34 2.79 9.98 2.68 10.37 2.49<br />

22 6.55 3.27 7.13 3.41 7.99 3.26 8.70 3.03 9.27 2.81 9.97 2.70 10.28 2.49<br />

24 6.49 3.32 7.06 3.46 7.89 3.30 8.65 3.06 9.26 2.83 9.81 2.70 10.22 2.50<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 205


Capacity coefficient factor 5CSL0-06B<br />

2.1.8 Capacity coefficient factor<br />

DC Inverter SINGLE A.(1Ø)<br />

1) Rate <strong>of</strong> change in capacity due to the main piping length<br />

Rate <strong>of</strong> change in cooling capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

Rate <strong>of</strong> change in heating capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

DC Inverter SINGLE A.(3Ø)<br />

5 10 15 20 30 40 50 60 70 75<br />

3.5 kW 100 99.8 99.3 - - - - - - -<br />

5.0 kW 100 99.8 99.3 98.8 97.8 96.9 97.7 - - -<br />

7.1/8.0/10.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 - - -<br />

12.5/14.0/15.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 85.6 82.9 81.5<br />

5 10 15 20 30 40 50 60 70 75<br />

3.5 kW 100 99.8 99.4 - - - - - - -<br />

5.0 kW 100 99.8 99.4 99.0 98.3 97.5 98.3 - - -<br />

7.1/8.0/10.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 - - -<br />

12.5/14.0/15.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 94.6 93.5 93<br />

1) Rate <strong>of</strong> change in capacity due to the main piping length<br />

Rate <strong>of</strong> change in cooling capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

Rate <strong>of</strong> change in heating capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

5 10 15 20 30 40 50 60 70 75<br />

10.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 - - -<br />

12.5/14.0/15.0 kW 100 99.3 97.9 96.6 93.8 91.1 88.4 85.6 82.9 81.5<br />

5 10 15 20 30 40 50 60 70 75<br />

10.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 - - -<br />

12.5/14.0/15.0 kW 100 99.7 99.2 98.7 97.7 96.6 95.6 94.6 93.5 93<br />

206 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

3) Calculation <strong>of</strong> actual system capacity<br />

① Outdoor unit rated capacity<br />

Qodu(rated) [from specification table]<br />

② Outdoor unit capacity at Ti, To temperature.<br />

Qodu(Ti, To) [from capacity table]<br />

③ Outdoor unit capacity coefficient factor<br />

F(Ti, To) = Qodu(Ti, To) / Qodu(rated)<br />

④ Piping correction factor [from capacity coefficient factor table]<br />

Fmain (length, elevation) for main piping length or elevation<br />

Fbranch (length, elevation) for branch piping length or elevation<br />

⑤ Individual indoor unit combinational capacity<br />

Qidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)<br />

⑥ Individual indoor unit actual capacity<br />

Qidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)<br />

Exam<strong>pl</strong>e) • Outdoor unit model : AUUW126D[UU12W ULD]<br />

• Indoor units (ATNH12GRLED[UT12 NRD]) : 3.5 kW<br />

• Outdoor temperature : 40.0°CDB<br />

• Indoor temperature: 19.0°CWB<br />

• Main piping length(O/D to BD):15m<br />

• Indoor unit actual cooling capacity in A room?<br />

- Qodu(rated) : 3.40kW<br />

- Qodu(Ti, To) : 3.28 kW<br />

- F(Ti, To) : 3.28 / 3.40 = 96.47%<br />

- Fmain (length, elevation) = 99.3%<br />

- Qind(actual) =3.4kW x 0.9647 x 0.993 = 3.257kW<br />

Capacity coefficient factor<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 207


Operation range 5CSL0-06B<br />

2.1.9 Operation range<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

46<br />

43<br />

21<br />

-5<br />

-10<br />

Cooling<br />

Operative<br />

Continuous<br />

operation<br />

18 32<br />

Indoor Unit [°C DB]<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

208 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

24<br />

-10<br />

-15<br />

Warming up<br />

Operation<br />

Heating<br />

Continuous<br />

operation<br />

Operative<br />

16 30<br />

Indoor Unit [°C DB]<br />

Operative: Intermittent operation due to the operational<br />

conditions (indoor/outdoor temperature,<br />

humidity, load etc.) can cause the heating<br />

capacity to decrease


5CSL0-06B<br />

2.1.10 Electric characteristics<br />

Unit<br />

Electric characteristics<br />

Power Compressor OFM<br />

Model Type Hz Voltage Voltage range MCA MOP MSC RLA kW FLA<br />

AUUW096D[UU09W ULD]<br />

AUUW126D[UU12W ULD]<br />

AUUW186D[UU18W UED]<br />

AUUW186D1[UU18W UED1]<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]<br />

AUUW366D[UU36W UED]<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW368D[UU37WUED]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

AUUW186DH[UU18WH UED]<br />

AUUW216DH[UU21WH U4D]<br />

AUUW246DH[UU24WH U4D]<br />

1 Phase<br />

inverter<br />

3 phase<br />

inverter<br />

DC Inverter<br />

High<br />

Efficiency<br />

50<br />

50<br />

50<br />

220-240<br />

380-415<br />

220-240<br />

Notes :<br />

1. Voltage range<br />

Voltage sup<strong>pl</strong>ied to the unit terminals should be within the<br />

minimum and maximum range<br />

2. Maximum allowable voltage unbalance between phase is 2 %<br />

3. MCA / MOP<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

- Load1 : Rated running current <strong>of</strong> largest motor<br />

(compressor or other motor)<br />

- Load2 : sum <strong>of</strong> current for all other motors<br />

- Load3 : any other load rated 1.0A or more<br />

4. Select wire spec. based on the MCA<br />

5. Recommended circuit breaker is ELCB (Earth Leakage circuit<br />

breaker)<br />

6. MSC & RLA are measured as the compressor only test<br />

condition.<br />

7. MSC values<br />

Min. : 198<br />

Max. :264<br />

Min. : 352<br />

Max. : 457<br />

Min. : 198<br />

Max. :264<br />

4.25 7.65 3.40 3.40 0.043 0.25<br />

6.25 11.25 5.00 5.00 0.043 0.25<br />

8.75 15.75 7.00 7.00 0.084 0.05<br />

13.00 23.40 - 8.1 0.12 0.60<br />

13.38 24.08 10.70 10.70 0.12 0.60<br />

16.25 29.25 13.00 13.00 0.12 0.60<br />

17.75 31.95 14.20 14.20 0.16 0.70<br />

23.33 41.03 17.70 17.70 0.24 1.20<br />

26.83 47.33 20.50 20.50 0.24 1.20<br />

32.08 56.78 24.70 24.70 0.24 1.20<br />

8.75 15.75 10.00 7.00 0.16 0.70<br />

6.55 10.83 4.28 4.28 0.24 1.20<br />

7.74 12.97 5.23 5.23 0.24 1.20<br />

8.59 14.50 5.91 5.91 0.24 1.20<br />

6.25 11.25 5.0 5.0 0.12 0.6<br />

8.62 15.5 6.9 6.9 0.12 0.6<br />

10.6 19.1 8.5 8.5 0.12 0.6<br />

8. RLA is measured during each individual compressor test<br />

condition.<br />

9. OFM is measured as the outdoor unit test condition<br />

(Exam<strong>pl</strong>e) Selection <strong>of</strong> proper circuit breaker<br />

Model : AUUW186D [UU18W UED]<br />

Rated running current : 7.0A (refer to spec. sheet)<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

= (1.25 x 7.0) + 0 + 0 = 8.75A<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

= (2.25 x 7.0) + 0 + 0 = 15.75A<br />

→ Finally select circuit breaker 15A(Min. circuit breaker is 15A)<br />

MCA : Minimum Circuit Amperes (A)<br />

MOP : Maximum rating over current protective device<br />

MSC : Maximum Starting Current<br />

RLA : Rated Load Amperes (A)<br />

OFM : Outdoor Fan Motor<br />

kW : Fan Motor rated output (kW)<br />

FLA : Full Load Amperes (A)<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 209


Field wiring diagrams 5CSL0-06B<br />

2.1.11 Field wiring diagrams<br />

DC Inverter SINGLE A(1Ø)<br />

1. All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

2. Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the current as required by the air conditioner.<br />

3. Feed the power source to the unit via a distribution switch board designed for this purpose.<br />

4. The terminal screws inside the control box may be loose due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can overload and damage electrical components.)<br />

5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.<br />

L<br />

N<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

Circuit breaker<br />

Fuse<br />

Power cable 3 core x 2.5/5.0mm 2<br />

(Including earth)<br />

L<br />

N<br />

G<br />

Outdoor unit<br />

Terminal Block outdoor<br />

1(L) 2(N) 4(L) 5(N) 3<br />

1(L) 2(N) 3<br />

Terminal block indoor<br />

Notes:<br />

1. All wirings, components and materials to be procured on the site should be according to the standard<br />

2. Use copper conductor only<br />

3. Install circuit breaker for safety<br />

4. Unit should be grounded in com<strong>pl</strong>iance with the ap<strong>pl</strong>icable local and national codes<br />

5. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Transmission<br />

line<br />

210 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)


5CSL0-06B<br />

DC Inverter SINGLE A(3Ø)<br />

R<br />

S<br />

T N<br />

Circuit breaker<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

Fuse<br />

Power cable 5 core x 2.5mm 2<br />

(Including earth)<br />

R<br />

S<br />

T N<br />

Outdoor unit<br />

Terminal Block outdoor<br />

R S T N 1(L) 2(N) 3 4 5<br />

1(L) 2(N) 3<br />

Terminal block indoor<br />

Notes:<br />

1. All wirings, components and materials to be procured on the site should be according to the standard<br />

2. Use copper conductor only<br />

3. Install circuit breaker for safety<br />

4. Unit should be grounded in com<strong>pl</strong>iance with the ap<strong>pl</strong>icable local and national codes<br />

5. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Field wiring diagrams<br />

Transmission<br />

cable<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 211


Sound levels 5CSL0-06B<br />

2.1.12 Sound levels<br />

Sound Pressure Level (dB re 20 Pa)<br />

DC Inverter SINGLE A(1Ø, 3Ø)<br />

Overall<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

D<br />

1m<br />

1m<br />

1m<br />

1m<br />

15m<br />

Sound pressure level<br />

AUUW096D[UU09W ULD]<br />

AUUW126D[UU12W ULD]<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound Pressure Level (dB re 20 Pa )<br />

Center <strong>of</strong><br />

Outdoor Unit<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Notes:<br />

- Sound measured at 1m away from the center <strong>of</strong> the unit.<br />

- Data is valid at free field condition<br />

- Data is valid at nominal operation condition<br />

- Reference accoustic pressure OdB = 20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as the<br />

construction(acoustic absorption coefficient) <strong>of</strong> particular room in<br />

which the equipment is installed.<br />

- The operating conditions are assumed to be standard<br />

AUUW186D[UU18W UED]<br />

AUUW186D1[UU18W UED1]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Octave Band Center Frequency (Hz)<br />

212 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20μPa )<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]


5CSL0-06B<br />

AUUW366D[UU36W UED] AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

Sound Pressure Level (dB re 20μPa )<br />

Octave Band Center Frequency (Hz)<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

Sound levels<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 213<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound Pressure Level (dB re 20 Pa )<br />

AUUW368D[UU37W UED]<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


Sound levels 5CSL0-06B<br />

High Efficiency models(1Ø)<br />

Overall<br />

1m<br />

Sound pressure level<br />

Sound Pressure Level (dB re 20μPa )<br />

Octave Band Center Frequency (Hz)<br />

Microphone<br />

1m<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Notes:<br />

- Sound measured at 1m away from the center <strong>of</strong> the unit.<br />

- Data is valid at free field condition.<br />

- Data is valid at nominal operation condition.<br />

- Reference accoustic pressure 0dB=20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

AUUW186DH[UU18WH UED] AUUW216DH [UU21WH U4D]<br />

AUUW246DH [UU24WH U4D]<br />

Sound Pressure Level (dB re 20μPa )<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

214 Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15


5CSL0-06B<br />

2.1.13 Accessories<br />

Standard accessories<br />

• See the "Installation manual"<br />

Optional accessories (For 3Ø models only)<br />

NOTE<br />

No. Accessory Name Model Name Remarks<br />

1 Air Guide<br />

2<br />

3<br />

Central control<br />

Gateway<br />

PQAGA<br />

PQCSA101S0<br />

PQCSA101S0<br />

PQCSW502A0<br />

PQCSS101S0<br />

PQCSS502A0<br />

PHNFP14A0<br />

PQNFG00A0<br />

* For the detail information, see the "CAC ACCESSORIES Product Data book"<br />

For Air discharge change<br />

Sim<strong>pl</strong>e Type<br />

Deluxe Type<br />

PC Based Type<br />

PI485<br />

CNU<br />

Accessories<br />

Outdoor unit - DC Inverter SINGLE A (1Ø, 3Ø) 215


Power sup<strong>pl</strong>y 5CSL0-06B<br />

2.2 DC Inverter SINGLE A - Synchro (1Ø, 3Ø)<br />

2.2.1 Power sup<strong>pl</strong>y<br />

Type Outdoor unit Capacity (kW) Circuit breaker capacity Power sup<strong>pl</strong>y<br />

1 Phase<br />

Inveter<br />

3 Phase<br />

Inverter<br />

AUUW426D[UU42W U3D] 12.5<br />

AUUW486D[UU48W U3D] 14.0 50A 1Ø, 220-240 V, 50Hz<br />

AUUW606D[UU60W U3D] 15.0<br />

AUUW428D(UU43W U3D) 12.5<br />

AUUW488D[UU49W U3D] 14.0 25A 3Ø, 380-415 V, 50Hz<br />

AUUW608D[UU61W U3D] 15.0<br />

External wiring procedure<br />

- The power sup<strong>pl</strong>y work is needed only to the outdoor unit. The power sup<strong>pl</strong>y to the indoor unit is conducted through the<br />

transmission wiring. Therefore, the power sup<strong>pl</strong>y work can be carried out at just one <strong>pl</strong>ace <strong>of</strong> the outdoor unit. It will<br />

contribute to sim<strong>pl</strong>ify the work procedure and to save cost.<br />

- Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

(Ex. Duo simultaneous operation)<br />

Circuit<br />

breaker<br />

(Ex. Trio simultaneous operation)<br />

Circuit<br />

breaker<br />

AUUW606D<br />

[UU60W U3D]<br />

AUUW606D<br />

[UU60W U3D]<br />

(Ex. Quartet simultaneous operation)<br />

Circuit<br />

breaker<br />

AUUW606D<br />

[UU60W U3D]<br />

Branch kit(PMUB11A)<br />

ATNH30GPLED<br />

[UT30NPD]<br />

Branch kit(PMUB111A)<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

Branch kit(PMUB1111A)<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

ATNH30GPLED<br />

[UT30NPD]<br />

Only one remote controller.<br />

Only one circuit breaker.<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

ATNH18GQLED<br />

[UT18 NQD]<br />

Only one remote controller.<br />

Only one circuit breaker.<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

Only one remote controller.<br />

Only one circuit breaker.<br />

ATNH12GRLED<br />

[UT12 NRD]<br />

216 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.2.2 List <strong>of</strong> functions<br />

DC Inverter Synchro(1Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Auto operation(Artificial intelligence)<br />

Convenience<br />

Auto Restart Operation<br />

Central control(LGAP)<br />

CAC Network<br />

PDI(Power Distribution Indicator)<br />

Function<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

DC Inverter Synchro(3Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Auto operation(Artificial intelligence)<br />

Convenience<br />

Auto Restart Operation<br />

Central control(LGAP)<br />

CAC Network<br />

PDI(Power Distribution Indicator)<br />

Function<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

AUUW426D<br />

[UU42W U3D]<br />

AUUW486D<br />

[UU48W U3D]<br />

List <strong>of</strong> functions<br />

AUUW606D<br />

[UU60W U3D]<br />

O O O<br />

O O O<br />

- - -<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O<br />

(program logic) (program logic) (program logic)<br />

- - -<br />

AUUW428D<br />

[UU43W U3D]<br />

AUUW488D<br />

[UU49W U3D]<br />

AUUW608D<br />

[UU61W U3D]<br />

O O O<br />

O O O<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O O O<br />

(program logic) (program logic) (program logic)<br />

- - -<br />

• Group control is not available which is connected with UU48W & UU60W<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 217


Specifications 5CSL0-06B<br />

2.2.3 Specifications<br />

■ Capacity for sigle combination<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

ATNH42GMLED<br />

[UT42 NMD]<br />

AUUW426D<br />

[UU42W U3D]<br />

ATNH48GMLED<br />

[UT48 NMD]<br />

Notes:<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m(25ft)<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Due to our policy <strong>of</strong> innovation some specifications may be changed without notification.<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

AUUW486D<br />

AUUW606D<br />

[UU48W U3D]<br />

[UU60W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.48 ~ 13.9 ~ 15.7 5.92 ~ 14.6 ~ 16.3<br />

5.6 ~ 14.0 ~ 15.4 6.4 ~ 15.5 ~ 17.6 6.8 ~ 16.9 ~ 18.7<br />

3.89 4.61 5.40<br />

3.87 4.54 5.50<br />

UVNH426LLAD<br />

[UV42 NLD]<br />

AUUW426D<br />

[UU42W U3D]<br />

UVNH486LLAD<br />

[UV48 NLD]<br />

UVNH606LLAD<br />

[UV60 NLD]<br />

AUUW486D<br />

AUUW606D<br />

[UU48W U3D]<br />

[UU60W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.32 ~ 13.3 ~ 14.6 5.72 ~ 14.4 ~ 15.7<br />

5.6 ~ 13.6 ~ 15.4 6.4 ~ 15.3 ~ 17.6 6.8 ~ 16.8 ~ 18.7<br />

4.00 4.41 5.30<br />

3.98 4.76 5.50<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

AUUW426D<br />

[UU42W U3D]<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

AUUW486D<br />

AUUW606D<br />

[UU48W U3D]<br />

[UU60W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.6 ~ 14.0 ~ 15.4 5.92 ~ 14.8 ~ 16.3<br />

5.6 ~ 14.0 ~ 15.4 6.6 ~ 16.4 ~ 18.2 6.8 ~ 16.8 ~ 18.7<br />

4.15 4.65 5.26<br />

3.73 4.54 4.57<br />

218 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

■ Capacity for sigle combination<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

ATNH42GMLED<br />

[UT42 NMD]<br />

AUUW428D<br />

[UU43W U3D]<br />

ATNH48GMLED<br />

[UT48 NMD]<br />

Notes:<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m(25ft)<br />

- Level Difference <strong>of</strong> Zero.<br />

2. Due to our policy <strong>of</strong> innovation some specifications may be changed without notification.<br />

Specifications<br />

ATNH60GMLED<br />

[UT60 NMD]<br />

AUUW488D<br />

AUUW608D<br />

[UU49W U3D]<br />

[UU61W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.48 ~ 13.8 ~ 15.7 5.92 ~ 14.7 ~ 16.3<br />

5.6 ~ 14.0 ~ 15.4 6.4 ~ 15.9 ~ 17.6 6.8 ~ 17.0 ~ 18.7<br />

3.89 4.58 5.63<br />

3.87 4.66 5.64<br />

UVNH426LLAD<br />

[UV42 NLD]<br />

AUUW428D<br />

[UU43W U3D]<br />

UVNH486LLAD<br />

[UV48 NLD]<br />

UVNH606LLAD<br />

[UV60 NLD]<br />

AUUW488D<br />

AUUW608D<br />

[UU49W U3D]<br />

[UU61W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.32 ~ 13.3 ~ 14.6 5.72 ~ 14.4 ~ 15.7<br />

5.6 ~ 13.6 ~ 15.4 6.4 ~ 15.3 ~ 17.6 6.8 ~ 16.8 ~ 18.7<br />

4.00 4.41 5.30<br />

3.98 4.76 5.50<br />

ABNH426RLAD<br />

[UB42 NRD]<br />

AUUW428D<br />

[UU43W U3D]<br />

ABNH486RLAD<br />

[UB48 NRD]<br />

ABNH606RLAD<br />

[UB60 NRD]<br />

AUUW488D<br />

AUUW608D<br />

[UU49W U3D]<br />

[UU61W U3D]<br />

5.0 ~ 12.5 ~ 13.8 5.6 ~ 14.0 ~ 15.4 5.92 ~ 14.8 ~ 16.3<br />

5.6 ~ 14.0 ~ 15.4 6.6 ~ 16.7 ~ 18.2 6.8 ~ 17.0 ~ 18.7<br />

4.15 4.65 5.26<br />

3.82 4.57 4.70<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 219


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, V, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Model<br />

Quantity<br />

Motor Input kW<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge* g<br />

Type<br />

Control<br />

Heat exchnager Tube Size (OD) mm<br />

Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Fan Type<br />

No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level(H/L) Sound Press,1m dB(A)+3<br />

Defrosting<br />

SVC Valve Liquid mm<br />

Gas mm<br />

Max. Interunit Total Piping(Main+Total Branch) m<br />

Piping Length Main Piping m<br />

Total Branch Piping m<br />

Each Branch Piping m<br />

Max. Installation Indoor Unit~Outdoor Unit m<br />

Height Difference Indoor Unit~Indoor Unit m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

AUUW426D<br />

[UU42W U3D]<br />

AUUW486D<br />

[UU48W U3D]<br />

Synchro ap<strong>pl</strong>ication<br />

(simultaneous operation).<br />

Refer to combination table.<br />

AUUW606D<br />

[UU60W U3D]<br />

17.7/16.7 20.5/20.5 24.7/23.5<br />

- - -<br />

1, 220-240, 50 1, 220-240, 50 1, 220-240, 50<br />

3*5.0 3*5.0 3*5.0<br />

4*0.75 4*0.75 4*0.75<br />

950*1,380*330 950*1,380*330 950*1,380*330<br />

103 103 103<br />

Rotary Rotary Rotary<br />

5JD420XAD22 5JD420XAD22 5JD420XAD22<br />

1 1 1<br />

4.18 4.18 4.18<br />

1,300 1,300 1,300<br />

FV50S(PVE) FV50S(PVE) FV50S(PVE)<br />

3,600 3,600 3,600<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

0.276(7.0) 0.276(7.0) 0.276(7.0)<br />

17 17 17<br />

2R,24C X 2 2R,32C x 2 2R,32C x 2<br />

SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3<br />

0.124 X 2 0.124 X 2 0.124 X 2<br />

- - -<br />

Propeller Propeller Propeller<br />

526/1 526/1 526/1<br />

Side Discharge Side Discharge Side Discharge<br />

55(1,942) x 2 55(1,942) x 2 55(1,942) x 2<br />

55/51 55/51 55/51<br />

Reversing cycle Reversing cycle Reversing cycle<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

80 80 80<br />

50 50 50<br />

40 40 40<br />

15 15 15<br />

30 30 30<br />

1 1 1<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

220 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power sup<strong>pl</strong>y Ø, V, Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable(Includes earth) No.* mm 2<br />

Dimensions W*H*D mm<br />

Net Weight Outdoor kg<br />

Compressor Type<br />

(Inverter) Model<br />

Quantity<br />

Motor Input kW<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge* g<br />

Type<br />

Control<br />

Heat exchnager Tube Size (OD) mm<br />

Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Fan Type<br />

No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level(H/L) Sound Press,1m dB(A)+3<br />

Defrosting<br />

SVC Valve Liquid mm<br />

Gas mm<br />

Max. Interunit Total Piping(Main+Total Branch) m<br />

Piping Length Main Piping m<br />

Total Branch Piping m<br />

Each Branch Piping m<br />

Max. Installation Indoor Unit~Outdoor Unit m<br />

Height Difference Indoor Unit~Indoor Unit m<br />

Note :<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

AUUW428D<br />

[UU43W U3D]<br />

AUUW488D<br />

[UU49W U3D]<br />

Synchro ap<strong>pl</strong>ication<br />

(simultaneous operation).<br />

Refer to combination table.<br />

2. Due to our policy <strong>of</strong> innovation some specifications<br />

may be changed without notification.<br />

3. At least two indoor units should be connected.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national<br />

code.<br />

Specifications<br />

AUUW608D<br />

[UU61W U3D]<br />

4.09/4.28 4.98/5.23 5.91/5.79<br />

- - -<br />

3, 380-415, 50 3, 380-415, 50 3, 380-415, 50<br />

5 x 2.5 5 x 2.5 5 x 2.5<br />

4 x 0.75 (Including Earth) 4 x 0.75 (Including Earth) 4 x 0.75 (Including Earth)<br />

950*1,380*330 950*1,380*330 950*1,380*330<br />

103 103 103<br />

Rotary Rotary Rotary<br />

5JD420XBB22 5JD420XBB22 5JD420XBB22<br />

1 1 1<br />

4.18 4.18 4.18<br />

1,300 1,300 1,300<br />

FV50S (PVE) FV50S (PVE) FV50S (PVE)<br />

3,600 3,600 3,600<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

0.276 0.276 0.276<br />

17 17 17<br />

2R, 32C x 2 2R, 32C x 2 2R, 32C x 2<br />

SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3<br />

0.124*2 0.124*2 0.124*2<br />

- - -<br />

Propeller Propeller Propeller<br />

2/526 2/526 2/526<br />

Side Discharge Side Discharge Side Discharge<br />

55 x 2 55 x 2 55 x 2<br />

55/51 55/51 55/51<br />

Reversing cycle Reversing cycle Reversing cycle<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

80 80 80<br />

50 50 50<br />

40 40 40<br />

15 15 15<br />

30 30 30<br />

1 1 1<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 221


Combination table 5CSL0-06B<br />

2.2.4 Combination table<br />

Possible combinations<br />

IDU : INDOOR UNIT<br />

ODU : OUT DOOR INUT<br />

BD : BRANCH DISTRIBUTOR UNIT<br />

REMO : WIRED REMOTE CONTROLLER<br />

OUTDOOR Capacity (kW)<br />

UNITS<br />

AUUW426D<br />

Cooling Heating<br />

[UU42W U3D]<br />

AUUW428D<br />

[UU43W U3D]<br />

AUUW486D<br />

12.5 14.0<br />

[UU48W U3D]<br />

AUUW488D<br />

[UU49W U3D]<br />

AUUW606D<br />

14.0 16.0<br />

[UU60W U3D]<br />

AUUW608D<br />

[UU61W U3D]<br />

15.0 17.0<br />

Wired remote<br />

controller*<br />

Ap<strong>pl</strong>ied<br />

Accessiries<br />

BD unit<br />

Sim<strong>pl</strong>e central<br />

controller**<br />

Function<br />

controller**<br />

Duo<br />

ODU<br />

Cassette Duct Ceiling & Floor<br />

UT24 NPD *2<br />

UT24 NPD *2<br />

UT30 NPD *2<br />

PMUB11A<br />

Possible combination <strong>of</strong> indoor units<br />

Synchro<br />

Quartet<br />

222 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)<br />

Trio<br />

ODU<br />

BD<br />

BD BD<br />

IDU IDU IDU IDU IDU IDU IDU IDU IDU<br />

REMO REMO REMO<br />

UB24 NHD *2<br />

UB24 NHD *2<br />

UB30 NGD *2<br />

UV24 NBD *2<br />

UV24 NHD *2<br />

UV30 NGD *2<br />

Cassette Duct Ceiling & Floor Cassette Duct Ceiling & Floor<br />

UT18 NQD*3<br />

UT18 NQD*3<br />

UT18 NQD*3<br />

UB18 NHD*3<br />

UB18 NHD*3<br />

UB18 NHD*3<br />

PVRCUSZO PVRCUSZO<br />

PMUB111A PMUB1111A<br />

PQCSB101S0<br />

PQCSC101S0<br />

UV18 NBD*3<br />

UV18 NBD*3<br />

UV18 NBD*3<br />

UT12 NRD*4<br />

UT12 NRD*4<br />

UT12 NRD*4<br />

Notes :<br />

1. Possible indoor units: indoor unit series<br />

• Dry contact & Zone control & Auto changeover is not available which is connected with synchro.<br />

• When using synchro operation<br />

- Do not use wireless remote controller<br />

- Use only one wired remote controller in the indoor units.<br />

- Use central and function controller "PQCSB101S0" & "PQCSC101S0" only<br />

2. Between units are the required Branch kits mentioned, that are necessary to install the combination.<br />

(Gas pipe)<br />

(Liquid pipe)<br />

Indoor Classification<br />

2 Units<br />

3 Units<br />

4 Units<br />

C<br />

A<br />

Model Name<br />

PMUB11A<br />

PMUB111A<br />

PMUB1111A<br />

a b c<br />

a b<br />

Type 1 Type 2<br />

B<br />

D<br />

Capacity Ratio(%)<br />

50:50 (1:1)<br />

33:33:33 (1:1:1)<br />

25:25:25:25(1:1:1:1)<br />

(I.D)<br />

ODU<br />

-<br />

-<br />

-<br />

Unit : mm (inch)<br />

ⓐ ⓑ ⓒ Type<br />

Ⓐ Ø15.88(5/8) Ø19.05(3/4) Ø25.4(1) 1<br />

Ⓑ<br />

Ø9.52(3/8)<br />

Ø12.7(1/2)<br />

Ø12.7(1/2)<br />

Ø15.88(5/8)<br />

- 2<br />

Ⓒ Ø6.35(1/4) Ø9.52(3/8) - 2<br />

Ⓓ Ø9.52(3/8) Ø12.7(1/2) - 2<br />

-<br />

-<br />

-


5CSL0-06B<br />

■ 1Ø Synchro Equivalent capacity table<br />

AUUW426D[UU42W U3D] (Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Combination table<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 5.60 14.0 14.0 8.20 20.5 20.5 1.84 4.60 4.60<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 15.0 9.00 22.6 22.6 2.08 5.20 5.20<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 14.0 8.25 21.5 22.0 1.91 4.69 4.82<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 6.40 16.0 16.0 8.20 20.5 20.5 1.84 4.60 4.60<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 17.0 8.70 21.7 21.7 2.08 5.00 5.00<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 16.0 8.50 22.5 22.0 2.10 4.70 4.82<br />

AUUW486D[UU48W U3D] (Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 5.60 14.0 14.7 8.20 20.5 22.6 1.84 4.60 5.06<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 15.7 9.00 22.6 24.9 2.08 5.20 5.72<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 14.7 8.25 21.5 22.0 1.91 4.69 4.82<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 6.40 16.0 16.8 8.20 20.5 22.6 1.84 4.60 5.06<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 17.5 8.70 21.7 23.9 2.08 5.00 5.50<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 16.8 8.50 22.5 22.0 2.20 4.78 4.89<br />

• Notes<br />

1. Individual indoor capacities are not given because the combinations are for simultaneous operation.<br />

2. Rated cooling capacities are based on the following conditions:<br />

Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB.<br />

Rated heating capacities are based on the following conditions:<br />

Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 223


Combination table 5CSL0-06B<br />

AUUW606D[UU60W U3D] (Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Duo 8.0+8.0 16.0 6.00 15.0 16.5 9.32 23.3 24.0 2.24 5.60 5.80<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 16.5 9.00 22.6 22.6 2.08 5.20 5.20<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 15.4 8.25 21.5 22.0 1.91 4.69 4.82<br />

• Heating<br />

Simultaneous<br />

Operation<br />

• Notes<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 8.0+8.0 16.0 6.80 17.0 18.2 9.20 22.0 23.0 2.12 5.30 5.70<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 18.2 8.70 21.7 23.0 2.08 5.00 5.00<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 17.6 8.50 22.5 22.0 2.20 4.78 4.89<br />

1. Individual indoor capacities are not given because the combinations are for simultaneous operation.<br />

2. Rated cooling capacities are based on the following conditions:<br />

Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB.<br />

Rated heating capacities are based on the following conditions:<br />

Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.<br />

224 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

■ 3Ø Synchro Equivalent capacity table<br />

AUUW428D[UU43W U3D](Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Combination table<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 5.60 14.0 14.0 1.99 4.98 5.47 1.84 4.60 4.60<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 15.0 2.36 5.91 6.50 2.08 5.20 5.20<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 14.0 2.02 5.10 5.50 1.91 4.69 4.82<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 6.40 16.0 16.0 2.10 5.23 5.75 1.84 4.60 4.60<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 17.0 2.31 5.79 6.36 2.08 5.00 5.00<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 16.0 2.30 5.40 5.90 1.91 4.69 4.82<br />

AUUW488D[UU49W U3D] (Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 5.60 14.0 14.7 1.99 4.98 5.47 1.84 4.60 5.06<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 15.7 2.36 5.91 6.50 2.08 5.20 5.72<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 14.7 2.02 5.10 5.50 1.91 4.69 5.12<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 7.1+7.1 14.2 6.40 16.0 16.8 2.10 5.23 5.75 1.84 4.60 5.06<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 17.5 2.31 5.79 6.36 2.08 5.00 5.50<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 16.8 2.30 5.40 5.90 1.91 4.69 5.22<br />

• Notes<br />

1. Individual indoor capacities are not given because the combinations are for simultaneous operation.<br />

2. Rated cooling capacities are based on the following conditions:<br />

Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB.<br />

Rated heating capacities are based on the following conditions:<br />

Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 225


Combination table 5CSL0-06B<br />

AUUW608D[UU61W U3D] (Synchro-Duo, Trio, Quartet)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Duo 8.0+8.0 16.0 6.00 15.0 16.5 1.99 4.98 5.47 2.24 5.60 5.80<br />

Trio 5.0+5.0+5.0 15.0 6.00 15.0 16.5 2.36 5.91 6.50 2.08 5.20 5.20<br />

Quartet 3.5+3.5+3.5+3.5 14.2 5.60 14.0 14.0 2.02 5.10 5.50 1.91 4.69 4.82<br />

• Heating<br />

Simultaneous<br />

Operation<br />

• Notes<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Combination <strong>of</strong> indoor units<br />

(kW)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

A<br />

kW<br />

kW kW kW Min Rated Max Min Rated Max<br />

Duo 8.0+8.0 16.0 6.80 17.0 18.2 2.10 5.23 5.75 2.12 5.30 5.70<br />

Trio 5.0+5.0+5.0 15.0 6.80 17.0 18.2 2.31 5.79 6.36 2.08 5.00 5.00<br />

Quartet 3.5+3.5+3.5+3.5 14.2 6.40 16.0 16.0 2.30 5.40 5.90 1.91 4.69 4.82<br />

1. Individual indoor capacities are not given because the combinations are for simultaneous operation.<br />

2. Rated cooling capacities are based on the following conditions:<br />

Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB.<br />

Rated heating capacities are based on the following conditions:<br />

Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.<br />

226 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.2.5 Branch kit<br />

Models : PMUB11A, PMUB111A, PMUB1111A<br />

Picture<br />

Features<br />

Connectable <strong>of</strong><br />

indoor units<br />

Between units are the required Branch kits mentioned, that are necessary to install the combination.<br />

Indoor Classification<br />

2 Units<br />

3 Units<br />

4 Units<br />

Models<br />

2 Units PMUB 11A<br />

3 Units<br />

4 Units<br />

(Gas pipe)<br />

(Liquid pipe)<br />

C<br />

A<br />

PMUB 111A<br />

PMUB 1111A<br />

Model Name<br />

PMUB11A<br />

PMUB111A<br />

PMUB1111A<br />

a b c<br />

a b<br />

Type 1 Type 2<br />

B<br />

Gas pipe Liquid pipe<br />

Gas pipe Liquid pipe<br />

D<br />

(1:1) (1:1)<br />

(1:1:1) (1:1:1)<br />

(1:1:1:1) (1:1:1:1)<br />

Capacity Ratio(%)<br />

50:50 (1:1)<br />

33:33:33 (1:1:1)<br />

25:25:25:25(1:1:1:1)<br />

Branch kit<br />

Unit : mm (inch)<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 227<br />

(I.D)<br />

ⓐ ⓑ ⓒ Type<br />

Ⓐ Ø15.88(5/8) Ø19.05(3/4) Ø25.4(1) 1<br />

Ⓑ<br />

Ø9.52(3/8)<br />

Ø12.7(1/2)<br />

Ø12.7(1/2)<br />

Ø15.88(5/8)<br />

- 2<br />

Ⓒ Ø6.35(1/4) Ø9.52(3/8) - 2<br />

Ⓓ Ø9.52(3/8) Ø12.7(1/2) - 2


Piping diagrams 5CSL0-06B<br />

2.2.6 Piping diagrams<br />

Models : "Synchro" Duo - AUUW426D[UU42W U3D], AUUW486D[UU48W U3D], AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D], AUUW488D[UU49W U3D] , AUUW608D[UU61W U3D]<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Fan<br />

Fan<br />

Fan<br />

Fan<br />

Fan<br />

Gas Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Gas Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Gas Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Gas<br />

Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Gas Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Branch kit<br />

(Accessory)<br />

Service Valve<br />

Gas(Ø15.88)<br />

Service Valve<br />

Liquid(Ø9.52)<br />

Branch kit<br />

(Accessory)<br />

Branch kit<br />

(Accessory)<br />

Service Valve<br />

Gas(Ø15.88)<br />

Service Valve<br />

Liquid(Ø9.52)<br />

Branch kit<br />

(Accessory)<br />

Indoor Unit<br />

(kW)<br />

A B<br />

(mm) (mm)<br />

9.52 15.88<br />

9.52 15.88<br />

Note :<br />

1.The pipes between the indoor units and the branch kits must have<br />

same dimensions as indoor unit connections.<br />

OUTDOOR UNIT<br />

Refrigerant Flow<br />

228 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)<br />

E.E.V.<br />

7.1<br />

8.0<br />

Accumulator<br />

r<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

Note :<br />

1.The pipes between the indoor units and the branch kits must have<br />

same dimensions as indoor unit connections.<br />

Th4<br />

Heat<br />

Exchanger<br />

Models : "Synchro" Trio - AUUW426D[UU42W U3D], AUUW486D[UU48W U3D], AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D], AUUW488D[UU49W U3D] , AUUW608D[UU61W U3D]<br />

Thermistor<br />

Thermistor<br />

Thermistor<br />

E.E.V.<br />

Indoor Unit<br />

(kW)<br />

5.0<br />

Accumulator<br />

r<br />

A<br />

(mm)<br />

6.35<br />

B<br />

(mm)<br />

12.7<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

Th3<br />

Cooling<br />

Heating<br />

OUTDOOR UNIT<br />

Th4<br />

Heat<br />

Exchanger<br />

Th3<br />

Refrigerant Flow<br />

Cooling<br />

Heating


5CSL0-06B<br />

Piping diagrams<br />

Models : "Synchro" Quartet - AUUW426D[UU42W U3D], AUUW486D[UU48W U3D], AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D], AUUW488D[UU49W U3D] , AUUW608D[UU61W U3D]<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

INDOOR UNIT<br />

Heat<br />

Exchanger<br />

Thermistor<br />

Fan<br />

Fan<br />

Fan<br />

Fan<br />

Gas<br />

Piping<br />

ØB<br />

Liquid<br />

Piping<br />

ØA<br />

Gas<br />

Piping<br />

ØB<br />

Liquid<br />

Piping<br />

ØA<br />

Gas<br />

Piping<br />

ØB<br />

Liquid<br />

Piping<br />

ØA<br />

Gas Piping<br />

ØB<br />

Liquid Piping<br />

ØA<br />

Branch kit<br />

(Accessory)<br />

Service Valve<br />

Gas(Ø15.88)<br />

Service Valve<br />

Liquid( Ø9.52)<br />

Branch kit<br />

(Accessory)<br />

Indoor Unit<br />

(kW)<br />

Note :<br />

1.The pipes between the indoor units and the branch kits must have<br />

same dimensions as indoor unit connections.<br />

OUTDOOR UNIT<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 229<br />

3.5<br />

E.E.V.<br />

Accumulator<br />

r<br />

A<br />

(mm)<br />

6.35<br />

B<br />

(mm)<br />

9.52<br />

Th1<br />

Th2<br />

Reversing<br />

Valve<br />

Inverter<br />

Compressor<br />

High Pressure<br />

S/W<br />

Th4<br />

Heat<br />

Exchanger<br />

Th3


Capacity tables 5CSL0-06B<br />

2.2.8 Capacity tables<br />

■ Synchro operation (1Φ)<br />

Models : AUUW426D[UU42W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

• Symbol<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 13.73 2.54 13.13 2.65 12.33 3.56 11.95 3.98 11.43 4.37 11.11 4.28 10.80 3.84<br />

16.0 22.0 14.57 3.45 13.97 3.48 13.17 4.20 12.79 4.51 12.26 4.71 11.95 4.48 11.63 3.89<br />

18.0 25.0 15.42 3.72 14.81 3.75 14.00 4.41 13.62 4.60 13.09 4.77 12.78 4.47 12.47 3.79<br />

19.0 27.0 15.84 3.77 15.23 3.80 14.42 4.46 14.00 4.60 13.51 4.78 13.20 4.46 12.88 3.76<br />

22.0 30.0 17.11 3.77 16.49 3.87 15.68 4.57 15.28 4.82 14.76 4.86 14.45 4.51 14.13 3.76<br />

24.0 32.0 17.95 3.74 17.34 3.90 16.51 4.65 16.12 4.92 15.59 4.96 15.28 4.61 14.96 3.85<br />

14.0 20.0 14.71 2.87 14.07 3.00 13.21 4.03 12.81 4.50 12.25 4.94 11.91 4.84 11.57 4.34<br />

16.0 22.0 15.61 3.89 14.97 3.93 14.11 4.75 13.70 5.10 13.14 5.32 12.80 5.06 12.46 4.39<br />

18.0 25.0 16.52 4.21 15.87 4.24 15.00 4.99 14.59 5.20 14.03 5.39 13.69 5.05 13.36 4.29<br />

19.0 27.0 16.97 4.26 16.32 4.30 15.45 5.04 15.00 5.20 14.48 5.41 14.14 5.04 13.80 4.25<br />

22.0 30.0 18.33 4.26 17.67 4.37 16.80 5.16 16.38 5.45 15.81 5.49 15.48 5.09 15.14 4.25<br />

24.0 32.0 19.24 4.23 18.57 4.41 17.69 5.26 17.27 5.56 16.71 5.61 16.37 5.21 16.03 4.35<br />

14.0 20.0 13.73 2.66 13.13 2.78 12.33 3.73 11.95 4.17 11.43 4.58 11.11 4.48 10.80 4.02<br />

16.0 22.0 14.57 3.61 13.97 3.64 13.17 4.40 12.79 4.73 12.26 4.93 11.95 4.69 11.63 4.07<br />

18.0 25.0 15.42 3.90 14.81 3.93 14.00 4.62 13.62 4.82 13.09 5.00 12.78 4.68 12.47 3.98<br />

19.0 27.0 15.84 3.95 15.23 3.98 14.42 4.68 14.00 4.82 13.51 5.01 13.20 4.67 12.88 3.94<br />

22.0 30.0 17.11 3.95 16.49 4.05 15.68 4.79 15.28 5.05 14.76 5.09 14.45 4.72 14.13 3.94<br />

24.0 32.0 17.95 3.92 17.34 4.09 16.51 4.87 16.12 5.15 15.59 5.20 15.28 4.83 14.96 4.03<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 11.39 5.16 12.15 5.26 13.58 5.00 14.93 4.67 16.27 4.40 17.33 4.29 17.79 4.07<br />

18 11.28 5.24 12.13 5.39 13.60 5.14 14.92 4.79 16.15 4.51 17.11 4.38 17.73 4.12<br />

20 11.20 5.34 12.13 5.52 13.60 5.29 14.88 4.92 16.00 4.60 16.99 4.44 17.76 4.14<br />

21 11.17 5.38 12.13 5.60 13.60 5.36 14.85 4.99 15.90 4.65 16.99 4.47 17.65 4.15<br />

22 11.15 5.44 12.13 5.68 13.60 5.44 14.81 5.05 15.78 4.68 16.97 4.49 17.50 4.15<br />

24 11.04 5.54 12.01 5.76 13.44 5.51 14.72 5.10 15.76 4.71 16.69 4.50 17.40 4.17<br />

16 12.10 5.61 12.91 5.72 14.43 5.43 15.87 5.07 17.29 4.78 18.41 4.66 18.90 4.43<br />

18 11.98 5.70 12.89 5.86 14.45 5.59 15.85 5.21 17.16 4.90 18.18 4.76 18.84 4.48<br />

20 11.90 5.80 12.89 6.00 14.45 5.75 15.81 5.35 17.00 5.00 18.06 4.83 18.87 4.50<br />

21 11.87 5.85 12.89 6.09 14.45 5.83 15.78 5.42 16.89 5.05 18.06 4.86 18.75 4.51<br />

22 11.85 5.92 12.89 6.18 14.45 5.91 15.73 5.49 16.77 5.09 18.03 4.88 18.60 4.51<br />

24 11.73 6.02 12.77 6.26 14.28 5.99 15.64 5.54 16.75 5.12 17.74 4.89 18.49 4.53<br />

16 11.39 5.41 12.15 5.51 13.58 5.23 14.93 4.89 16.27 4.61 17.33 4.50 17.79 4.27<br />

18 11.28 5.49 12.13 5.65 13.60 5.39 14.92 5.02 16.15 4.73 17.11 4.58 17.73 4.32<br />

20 11.20 5.59 12.13 5.78 13.60 5.54 14.88 5.16 16.00 4.82 16.99 4.65 17.76 4.34<br />

21 11.17 5.64 12.13 5.87 13.60 5.62 14.85 5.22 15.90 4.87 16.99 4.68 17.65 4.35<br />

22 11.15 5.71 12.13 5.95 13.60 5.70 14.81 5.29 15.78 4.90 16.97 4.71 17.50 4.35<br />

24 11.04 5.80 12.01 6.04 13.44 5.77 14.72 5.34 15.76 4.94 16.69 4.72 17.40 4.37<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

230 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

Models : AUUW486D[UU48W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 14.41 2.79 13.79 2.92 12.94 3.92 12.55 4.37 12.00 4.80 11.67 4.71 11.34 4.22<br />

16.0 22.0 15.30 3.79 14.67 3.82 13.82 4.62 13.42 4.97 12.87 5.18 12.54 4.93 12.21 4.28<br />

18.0 25.0 16.19 4.10 15.55 4.12 14.70 4.85 14.30 5.06 13.75 5.25 13.42 4.92 13.09 4.17<br />

19.0 27.0 16.63 4.14 15.99 4.18 15.14 4.91 14.70 5.06 14.19 5.26 13.86 4.91 13.53 4.13<br />

22.0 30.0 17.96 4.14 17.32 4.25 16.46 5.02 16.05 5.30 15.50 5.35 15.17 4.96 14.84 4.14<br />

24.0 32.0 18.85 4.12 18.20 4.29 17.34 5.12 16.92 5.41 16.37 5.46 16.04 5.07 15.71 4.24<br />

14.0 20.0 15.39 3.16 14.72 3.30 13.83 4.43 13.40 4.95 12.82 5.43 12.46 5.32 12.11 4.77<br />

16.0 22.0 16.34 4.28 15.67 4.32 14.76 5.23 14.34 5.61 13.75 5.85 13.40 5.57 13.05 4.83<br />

18.0 25.0 17.29 4.63 16.61 4.66 15.70 5.49 15.27 5.72 14.68 5.93 14.33 5.56 13.98 4.72<br />

19.0 27.0 17.76 4.68 17.08 4.73 16.17 5.55 15.70 5.72 15.15 5.95 14.80 5.55 14.45 4.67<br />

22.0 30.0 19.19 4.68 18.50 4.81 17.58 5.68 17.14 6.00 16.55 6.04 16.20 5.60 15.85 4.68<br />

24.0 32.0 20.13 4.66 19.44 4.85 18.52 5.78 18.07 6.12 17.49 6.17 17.13 5.73 16.78 4.79<br />

14.0 20.0 14.41 2.66 13.79 2.78 12.94 3.73 12.55 4.17 12.00 4.58 11.67 4.48 11.34 4.02<br />

16.0 22.0 15.30 3.61 14.67 3.64 13.82 4.40 13.42 4.73 12.87 4.93 12.54 4.69 12.21 4.07<br />

18.0 25.0 16.19 3.90 15.55 3.93 14.70 4.62 14.30 4.82 13.75 5.00 13.42 4.68 13.09 3.98<br />

19.0 27.0 16.63 3.95 15.99 3.98 15.14 4.68 14.70 4.82 14.19 5.01 13.86 4.67 13.53 3.94<br />

22.0 30.0 17.96 3.95 17.32 4.05 16.46 4.79 16.05 5.05 15.50 5.09 15.17 4.72 14.84 3.94<br />

24.0 32.0 18.85 3.92 18.20 4.09 17.34 4.87 16.92 5.15 16.37 5.20 16.04 4.83 15.71 4.03<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 11.95 5.68 12.76 5.79 14.26 5.49 15.68 5.13 17.08 4.84 18.19 4.72 18.68 4.48<br />

18 11.84 5.77 12.74 5.93 14.28 5.66 15.67 5.27 16.96 4.96 17.96 4.81 18.62 4.53<br />

20 11.76 5.87 12.74 6.07 14.28 5.82 15.62 5.41 16.80 5.06 17.84 4.88 18.65 4.55<br />

21 11.73 5.92 12.74 6.16 14.28 5.90 15.59 5.48 16.69 5.11 17.84 4.92 18.53 4.56<br />

22 11.71 5.99 12.74 6.25 14.28 5.98 15.55 5.56 16.57 5.15 17.82 4.94 18.38 4.56<br />

24 11.60 6.09 12.62 6.34 14.11 6.06 15.46 5.61 16.55 5.18 17.53 4.95 18.27 4.59<br />

16 12.45 6.18 13.29 6.29 14.85 5.97 16.33 5.58 17.79 5.26 18.95 5.13 19.46 4.87<br />

18 12.34 6.27 13.27 6.44 14.88 6.15 16.32 5.73 17.67 5.39 18.71 5.23 19.39 4.93<br />

20 12.25 6.38 13.27 6.60 14.88 6.33 16.28 5.89 17.50 5.50 18.59 5.31 19.43 4.95<br />

21 12.22 6.44 13.27 6.70 14.88 6.41 16.24 5.96 17.39 5.55 18.59 5.35 19.31 4.96<br />

22 12.20 6.51 13.27 6.79 14.88 6.50 16.19 6.04 17.26 5.59 18.56 5.37 19.15 4.96<br />

24 12.08 6.62 13.14 6.89 14.70 6.59 16.10 6.10 17.24 5.63 18.26 5.38 19.03 4.98<br />

16 11.95 5.49 12.76 5.59 14.26 5.31 15.68 4.96 17.08 4.67 18.19 4.56 18.68 4.33<br />

18 11.84 5.57 12.74 5.73 14.28 5.47 15.67 5.10 16.96 4.79 17.96 4.65 18.62 4.38<br />

20 11.76 5.67 12.74 5.87 14.28 5.62 15.62 5.23 16.80 4.89 17.84 4.72 18.65 4.40<br />

21 11.73 5.72 12.74 5.95 14.28 5.70 15.59 5.30 16.69 4.94 17.84 4.75 18.53 4.41<br />

22 11.71 5.79 12.74 6.04 14.28 5.78 15.55 5.37 16.57 4.97 17.82 4.78 18.38 4.41<br />

24 11.60 5.89 12.62 6.12 14.11 5.86 15.46 5.42 16.55 5.01 17.53 4.79 18.27 4.43<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 231


Models : AUUW606D[UU60W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Temperature<br />

5CSL0-06B<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 16.18 3.20 15.48 3.35 14.53 4.49 14.09 5.01 13.47 5.51 13.10 5.39 12.73 4.84<br />

16.0 22.0 17.17 4.34 16.47 4.38 15.52 5.30 15.07 5.69 14.45 5.93 14.08 5.65 13.71 4.90<br />

18.0 25.0 18.17 4.70 17.46 4.72 16.50 5.56 16.05 5.80 15.43 6.02 15.06 5.64 14.69 4.78<br />

19.0 27.0 18.67 4.75 17.95 4.79 17.00 5.63 16.50 5.80 15.92 6.03 15.55 5.63 15.18 4.74<br />

22.0 30.0 20.16 4.75 19.44 4.87 18.47 5.76 18.01 6.08 17.40 6.13 17.02 5.68 16.65 4.74<br />

24.0 32.0 21.16 4.72 20.43 4.92 19.46 5.87 18.99 6.20 18.38 6.26 18.01 5.81 17.64 4.86<br />

14.0 20.0 16.18 2.87 15.48 3.00 14.53 4.03 14.09 4.50 13.47 4.94 13.10 4.84 12.73 4.34<br />

16.0 22.0 17.17 3.89 16.47 3.93 15.52 4.75 15.07 5.10 14.45 5.32 14.08 5.06 13.71 4.39<br />

18.0 25.0 18.17 4.21 17.46 4.24 16.50 4.99 16.05 5.20 15.43 5.39 15.06 5.05 14.69 4.29<br />

19.0 27.0 18.67 4.26 17.95 4.30 17.00 5.04 16.50 5.20 15.92 5.41 15.55 5.04 15.18 4.25<br />

22.0 30.0 20.16 4.26 19.44 4.37 18.47 5.16 18.01 5.45 17.40 5.49 17.02 5.09 16.65 4.25<br />

24.0 32.0 21.16 4.23 20.43 4.41 19.46 5.26 18.99 5.56 18.38 5.61 18.01 5.21 17.64 4.35<br />

14.0 20.0 15.10 2.66 14.44 2.78 13.56 3.73 13.15 4.17 12.57 4.58 12.23 4.48 11.88 4.02<br />

16.0 22.0 16.03 3.61 15.37 3.64 14.48 4.40 14.06 4.73 13.49 4.93 13.14 4.69 12.80 4.07<br />

18.0 25.0 16.96 3.90 16.29 3.93 15.40 4.62 14.98 4.82 14.40 5.00 14.06 4.68 13.71 3.98<br />

19.0 27.0 17.42 3.95 16.76 3.98 15.86 4.68 15.40 4.82 14.86 5.01 14.52 4.67 14.17 3.94<br />

22.0 30.0 18.82 3.95 18.14 4.05 17.24 4.79 16.81 5.05 16.24 5.09 15.89 4.72 15.54 3.94<br />

24.0 32.0 19.75 3.92 19.07 4.09 18.16 4.87 17.73 5.15 17.15 5.20 16.81 4.83 16.46 4.03<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.95 6.40 13.82 6.52 15.45 6.19 16.99 5.78 18.51 5.45 19.71 5.32 20.24 5.05<br />

18 12.83 6.50 13.80 6.68 15.47 6.37 16.97 5.94 18.38 5.59 19.46 5.42 20.17 5.11<br />

20 12.74 6.61 13.80 6.84 15.47 6.56 16.93 6.10 18.20 5.70 19.33 5.50 20.20 5.13<br />

21 12.71 6.67 13.80 6.94 15.47 6.65 16.89 6.18 18.08 5.76 19.33 5.54 20.08 5.14<br />

22 12.68 6.75 13.80 7.04 15.47 6.74 16.84 6.26 17.95 5.80 19.31 5.57 19.91 5.14<br />

24 12.56 6.86 13.67 7.14 15.28 6.83 16.75 6.32 17.93 5.84 18.99 5.58 19.80 5.16<br />

16 12.95 5.61 13.82 5.72 15.45 5.43 16.99 5.07 18.51 4.78 19.71 4.66 20.24 4.43<br />

18 12.83 5.70 13.80 5.86 15.47 5.59 16.97 5.21 18.38 4.90 19.46 4.76 20.17 4.48<br />

20 12.74 5.80 13.80 6.00 15.47 5.75 16.93 5.35 18.20 5.00 19.33 4.83 20.20 4.50<br />

21 12.71 5.85 13.80 6.09 15.47 5.83 16.89 5.42 18.08 5.05 19.33 4.86 20.08 4.51<br />

22 12.68 5.92 13.80 6.18 15.47 5.91 16.84 5.49 17.95 5.09 19.31 4.88 19.91 4.51<br />

24 12.56 6.02 13.67 6.26 15.28 5.99 16.75 5.54 17.93 5.12 18.99 4.89 19.80 4.53<br />

16 12.52 5.49 13.37 5.59 14.94 5.31 16.43 4.96 17.90 4.67 19.06 4.56 19.57 4.33<br />

18 12.41 5.57 13.35 5.73 14.96 5.47 16.41 5.10 17.77 4.79 18.82 4.65 19.50 4.38<br />

20 12.32 5.67 13.35 5.87 14.96 5.62 16.37 5.23 17.60 4.89 18.69 4.72 19.54 4.40<br />

21 12.29 5.72 13.35 5.95 14.96 5.70 16.33 5.30 17.49 4.94 18.69 4.75 19.42 4.41<br />

22 12.27 5.79 13.35 6.04 14.96 5.78 16.29 5.37 17.36 4.97 18.67 4.78 19.25 4.41<br />

24 12.15 5.89 13.22 6.12 14.78 5.86 16.19 5.42 17.34 5.01 18.36 4.79 19.14 4.43<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

232 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW428D[UU43W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 13.73 2.54 13.13 2.65 12.33 3.56 11.95 3.98 11.43 4.37 11.11 4.28 10.80 3.84<br />

16.0 22.0 14.57 3.45 13.97 3.48 13.17 4.20 12.79 4.51 12.26 4.71 11.95 4.48 11.63 3.89<br />

18.0 25.0 15.42 3.72 14.81 3.75 14.00 4.41 13.62 4.60 13.09 4.77 12.78 4.47 12.47 3.79<br />

19.0 27.0 15.84 3.77 15.23 3.80 14.42 4.46 14.00 4.60 13.51 4.78 13.20 4.46 12.88 3.76<br />

22.0 30.0 17.11 3.77 16.49 3.87 15.68 4.57 15.28 4.82 14.76 4.86 14.45 4.51 14.13 3.76<br />

24.0 32.0 17.95 3.74 17.34 3.90 16.51 4.65 16.12 4.92 15.59 4.96 15.28 4.61 14.96 3.85<br />

14.0 20.0 14.71 2.87 14.07 3.00 13.21 4.03 12.81 4.50 12.25 4.94 11.91 4.84 11.57 4.34<br />

16.0 22.0 15.61 3.89 14.97 3.93 14.11 4.75 13.70 5.10 13.14 5.32 12.80 5.06 12.46 4.39<br />

18.0 25.0 16.52 4.21 15.87 4.24 15.00 4.99 14.59 5.20 14.03 5.39 13.69 5.05 13.36 4.29<br />

19.0 27.0 16.97 4.26 16.32 4.30 15.45 5.04 15.00 5.20 14.48 5.41 14.14 5.04 13.80 4.25<br />

22.0 30.0 18.33 4.26 17.67 4.37 16.80 5.16 16.38 5.45 15.81 5.49 15.48 5.09 15.14 4.25<br />

24.0 32.0 19.24 4.23 18.57 4.41 17.69 5.26 17.27 5.56 16.71 5.61 16.37 5.21 16.03 4.35<br />

14.0 20.0 13.73 2.66 13.13 2.78 12.33 3.73 11.95 4.17 11.43 4.58 11.11 4.48 10.80 4.02<br />

16.0 22.0 14.57 3.61 13.97 3.64 13.17 4.40 12.79 4.73 12.26 4.93 11.95 4.69 11.63 4.07<br />

18.0 25.0 15.42 3.90 14.81 3.93 14.00 4.62 13.62 4.82 13.09 5.00 12.78 4.68 12.47 3.98<br />

19.0 27.0 15.84 3.95 15.23 3.98 14.42 4.68 14.00 4.82 13.51 5.01 13.20 4.67 12.88 3.94<br />

22.0 30.0 17.11 3.95 16.49 4.05 15.68 4.79 15.28 5.05 14.76 5.09 14.45 4.72 14.13 3.94<br />

24.0 32.0 17.95 3.92 17.34 4.09 16.51 4.87 16.12 5.15 15.59 5.20 15.28 4.83 14.96 4.03<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 11.39 5.16 12.15 5.26 13.58 5.00 14.93 4.67 16.27 4.40 17.33 4.29 17.79 4.07<br />

18 11.28 5.24 12.13 5.39 13.60 5.14 14.92 4.79 16.15 4.51 17.11 4.38 17.73 4.12<br />

20 11.20 5.34 12.13 5.52 13.60 5.29 14.88 4.92 16.00 4.60 16.99 4.44 17.76 4.14<br />

21 11.17 5.38 12.13 5.60 13.60 5.36 14.85 4.99 15.90 4.65 16.99 4.47 17.65 4.15<br />

22 11.15 5.44 12.13 5.68 13.60 5.44 14.81 5.05 15.78 4.68 16.97 4.49 17.50 4.15<br />

24 11.04 5.54 12.01 5.76 13.44 5.51 14.72 5.10 15.76 4.71 16.69 4.50 17.40 4.17<br />

16 12.10 5.61 12.91 5.72 14.43 5.43 15.87 5.07 17.29 4.78 18.41 4.66 18.90 4.43<br />

18 11.98 5.70 12.89 5.86 14.45 5.59 15.85 5.21 17.16 4.90 18.18 4.76 18.84 4.48<br />

20 11.90 5.80 12.89 6.00 14.45 5.75 15.81 5.35 17.00 5.00 18.06 4.83 18.87 4.50<br />

21 11.87 5.85 12.89 6.09 14.45 5.83 15.78 5.42 16.89 5.05 18.06 4.86 18.75 4.51<br />

22 11.85 5.92 12.89 6.18 14.45 5.91 15.73 5.49 16.77 5.09 18.03 4.88 18.60 4.51<br />

24 11.73 6.02 12.77 6.26 14.28 5.99 15.64 5.54 16.75 5.12 17.74 4.89 18.49 4.53<br />

16 11.39 5.41 12.15 5.51 13.58 5.23 14.93 4.89 16.27 4.61 17.33 4.50 17.79 4.27<br />

18 11.28 5.49 12.13 5.65 13.60 5.39 14.92 5.02 16.15 4.73 17.11 4.58 17.73 4.32<br />

20 11.20 5.59 12.13 5.78 13.60 5.54 14.88 5.16 16.00 4.82 16.99 4.65 17.76 4.34<br />

21 11.17 5.64 12.13 5.87 13.60 5.62 14.85 5.22 15.90 4.87 16.99 4.68 17.65 4.35<br />

22 11.15 5.71 12.13 5.95 13.60 5.70 14.81 5.29 15.78 4.90 16.97 4.71 17.50 4.35<br />

24 11.04 5.80 12.01 6.04 13.44 5.77 14.72 5.34 15.76 4.94 16.69 4.72 17.40 4.37<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 233


Models : AUUW488D[UU49W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Temperature<br />

5CSL0-06B<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 14.41 2.79 13.79 2.92 12.94 3.92 12.55 4.37 12.00 4.80 11.67 4.71 11.34 4.22<br />

16.0 22.0 15.30 3.79 14.67 3.82 13.82 4.62 13.42 4.97 12.87 5.18 12.54 4.93 12.21 4.28<br />

18.0 25.0 16.19 4.10 15.55 4.12 14.70 4.85 14.30 5.06 13.75 5.25 13.42 4.92 13.09 4.17<br />

19.0 27.0 16.63 4.14 15.99 4.18 15.14 4.91 14.70 5.06 14.19 5.26 13.86 4.91 13.53 4.13<br />

22.0 30.0 17.96 4.14 17.32 4.25 16.46 5.02 16.05 5.30 15.50 5.35 15.17 4.96 14.84 4.14<br />

24.0 32.0 18.85 4.12 18.20 4.29 17.34 5.12 16.92 5.41 16.37 5.46 16.04 5.07 15.71 4.24<br />

14.0 20.0 15.39 3.16 14.72 3.30 13.83 4.43 13.40 4.95 12.82 5.43 12.46 5.32 12.11 4.77<br />

16.0 22.0 16.34 4.28 15.67 4.32 14.76 5.23 14.34 5.61 13.75 5.85 13.40 5.57 13.05 4.83<br />

18.0 25.0 17.29 4.63 16.61 4.66 15.70 5.49 15.27 5.72 14.68 5.93 14.33 5.56 13.98 4.72<br />

19.0 27.0 17.76 4.68 17.08 4.73 16.17 5.55 15.70 5.72 15.15 5.95 14.80 5.55 14.45 4.67<br />

22.0 30.0 19.19 4.68 18.50 4.81 17.58 5.68 17.14 6.00 16.55 6.04 16.20 5.60 15.85 4.68<br />

24.0 32.0 20.13 4.66 19.44 4.85 18.52 5.78 18.07 6.12 17.49 6.17 17.13 5.73 16.78 4.79<br />

14.0 20.0 14.41 2.83 13.79 2.95 12.94 3.97 12.55 4.43 12.00 4.86 11.67 4.76 11.34 4.27<br />

16.0 22.0 15.30 3.83 14.67 3.87 13.82 4.68 13.42 5.03 12.87 5.24 12.54 4.98 12.21 4.33<br />

18.0 25.0 16.19 4.15 15.55 4.17 14.70 4.91 14.30 5.12 13.75 5.31 13.42 4.98 13.09 4.22<br />

19.0 27.0 16.63 4.19 15.99 4.23 15.14 4.97 14.70 5.12 14.19 5.33 13.86 4.97 13.53 4.18<br />

22.0 30.0 17.96 4.19 17.32 4.30 16.46 5.08 16.05 5.37 15.50 5.41 15.17 5.01 14.84 4.19<br />

24.0 32.0 18.85 4.17 18.20 4.34 17.34 5.18 16.92 5.48 16.37 5.52 16.04 5.13 15.71 4.29<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 11.95 5.68 12.76 5.79 14.26 5.49 15.68 5.13 17.08 4.84 18.19 4.72 18.68 4.48<br />

18 11.84 5.77 12.74 5.93 14.28 5.66 15.67 5.27 16.96 4.96 17.96 4.81 18.62 4.53<br />

20 11.76 5.87 12.74 6.07 14.28 5.82 15.62 5.41 16.80 5.06 17.84 4.88 18.65 4.55<br />

21 11.73 5.92 12.74 6.16 14.28 5.90 15.59 5.48 16.69 5.11 17.84 4.92 18.53 4.56<br />

22 11.71 5.99 12.74 6.25 14.28 5.98 15.55 5.56 16.57 5.15 17.82 4.94 18.38 4.56<br />

24 11.60 6.09 12.62 6.34 14.11 6.06 15.46 5.61 16.55 5.18 17.53 4.95 18.27 4.59<br />

16 12.45 6.18 13.29 6.29 14.85 5.97 16.33 5.58 17.79 5.26 18.95 5.13 19.46 4.87<br />

18 12.34 6.27 13.27 6.44 14.88 6.15 16.32 5.73 17.67 5.39 18.71 5.23 19.39 4.93<br />

20 12.25 6.38 13.27 6.60 14.88 6.33 16.28 5.89 17.50 5.50 18.59 5.31 19.43 4.95<br />

21 12.22 6.44 13.27 6.70 14.88 6.41 16.24 5.96 17.39 5.55 18.59 5.35 19.31 4.96<br />

22 12.20 6.51 13.27 6.79 14.88 6.50 16.19 6.04 17.26 5.59 18.56 5.37 19.15 4.96<br />

24 12.08 6.62 13.14 6.89 14.70 6.59 16.10 6.10 17.24 5.63 18.26 5.38 19.03 4.98<br />

16 11.95 5.86 12.76 5.97 14.26 5.67 15.68 5.29 17.08 4.99 18.19 4.87 18.68 4.62<br />

18 11.84 5.95 12.74 6.12 14.28 5.84 15.67 5.44 16.96 5.12 17.96 4.97 18.62 4.68<br />

20 11.76 6.06 12.74 6.26 14.28 6.00 15.62 5.59 16.80 5.22 17.84 5.04 18.65 4.70<br />

21 11.73 6.11 12.74 6.36 14.28 6.09 15.59 5.66 16.69 5.27 17.84 5.07 18.53 4.71<br />

22 11.71 6.18 12.74 6.45 14.28 6.17 15.55 5.73 16.57 5.31 17.82 5.10 18.38 4.71<br />

24 11.60 6.28 12.62 6.54 14.11 6.25 15.46 5.79 16.55 5.35 17.53 5.11 18.27 4.73<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

234 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

Models : AUUW608D[UU61W U3D]<br />

• Cooling Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43 46<br />

°CWB °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

14.0 20.0 16.18 3.20 15.48 3.35 14.53 4.49 14.09 5.01 13.47 5.51 13.10 5.39 12.73 4.84<br />

16.0 22.0 17.17 4.34 16.47 4.38 15.52 5.30 15.07 5.69 14.45 5.93 14.08 5.65 13.71 4.90<br />

18.0 25.0 18.17 4.70 17.46 4.72 16.50 5.56 16.05 5.80 15.43 6.02 15.06 5.64 14.69 4.78<br />

19.0 27.0 18.67 4.75 17.95 4.79 17.00 5.63 16.50 5.80 15.92 6.03 15.55 5.63 15.18 4.74<br />

22.0 30.0 20.16 4.75 19.44 4.87 18.47 5.76 18.01 6.08 17.40 6.13 17.02 5.68 16.65 4.74<br />

24.0 32.0 21.16 4.72 20.43 4.92 19.46 5.87 18.99 6.20 18.38 6.26 18.01 5.81 17.64 4.86<br />

14.0 20.0 16.18 2.87 15.48 3.00 14.53 4.03 14.09 4.50 13.47 4.94 13.10 4.84 12.73 4.34<br />

16.0 22.0 17.17 3.89 16.47 3.93 15.52 4.75 15.07 5.10 14.45 5.32 14.08 5.06 13.71 4.39<br />

18.0 25.0 18.17 4.21 17.46 4.24 16.50 4.99 16.05 5.20 15.43 5.39 15.06 5.05 14.69 4.29<br />

19.0 27.0 18.67 4.26 17.95 4.30 17.00 5.04 16.50 5.20 15.92 5.41 15.55 5.04 15.18 4.25<br />

22.0 30.0 20.16 4.26 19.44 4.37 18.47 5.16 18.01 5.45 17.40 5.49 17.02 5.09 16.65 4.25<br />

24.0 32.0 21.16 4.23 20.43 4.41 19.46 5.26 18.99 5.56 18.38 5.61 18.01 5.21 17.64 4.35<br />

14.0 20.0 13.73 2.66 13.13 2.78 12.33 3.73 11.95 4.17 11.43 4.58 11.11 4.48 10.80 4.02<br />

16.0 22.0 14.57 3.61 13.97 3.64 13.17 4.40 12.79 4.73 12.26 4.93 11.95 4.69 11.63 4.07<br />

18.0 25.0 15.42 3.90 14.81 3.93 14.00 4.62 13.62 4.82 13.09 5.00 12.78 4.68 12.47 3.98<br />

19.0 27.0 15.84 3.95 15.23 3.98 14.42 4.68 14.00 4.82 13.51 5.01 13.20 4.67 12.88 3.94<br />

22.0 30.0 17.11 3.95 16.49 4.05 15.68 4.79 15.28 5.05 14.76 5.09 14.45 4.72 14.13 3.94<br />

24.0 32.0 17.95 3.92 17.34 4.09 16.51 4.87 16.12 5.15 15.59 5.20 15.28 4.83 14.96 4.03<br />

• Heating Capacity<br />

Simultaneous<br />

Operation<br />

Duo<br />

Trio<br />

Quartet<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature -15 -10 -5 0 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16 12.95 6.40 13.82 6.52 15.45 6.19 16.99 5.78 18.51 5.45 19.71 5.32 20.24 5.05<br />

18 12.83 6.50 13.80 6.68 15.47 6.37 16.97 5.94 18.38 5.59 19.46 5.42 20.17 5.11<br />

20 12.74 6.61 13.80 6.84 15.47 6.56 16.93 6.10 18.20 5.70 19.33 5.50 20.20 5.13<br />

21 12.71 6.67 13.80 6.94 15.47 6.65 16.89 6.18 18.08 5.76 19.33 5.54 20.08 5.14<br />

22 12.68 6.75 13.80 7.04 15.47 6.74 16.84 6.26 17.95 5.80 19.31 5.57 19.91 5.14<br />

24 12.56 6.86 13.67 7.14 15.28 6.83 16.75 6.32 17.93 5.84 18.99 5.58 19.80 5.16<br />

16 12.95 5.61 13.82 5.72 15.45 5.43 16.99 5.07 18.51 4.78 19.71 4.66 20.24 4.43<br />

18 12.83 5.70 13.80 5.86 15.47 5.59 16.97 5.21 18.38 4.90 19.46 4.76 20.17 4.48<br />

20 12.74 5.80 13.80 6.00 15.47 5.75 16.93 5.35 18.20 5.00 19.33 4.83 20.20 4.50<br />

21 12.71 5.85 13.80 6.09 15.47 5.83 16.89 5.42 18.08 5.05 19.33 4.86 20.08 4.51<br />

22 12.68 5.92 13.80 6.18 15.47 5.91 16.84 5.49 17.95 5.09 19.31 4.88 19.91 4.51<br />

24 12.56 6.02 13.67 6.26 15.28 5.99 16.75 5.54 17.93 5.12 18.99 4.89 19.80 4.53<br />

16 11.39 5.41 12.15 5.51 13.58 5.23 14.93 4.89 16.27 4.61 17.33 4.50 17.79 4.27<br />

18 11.28 5.49 12.13 5.65 13.60 5.39 14.92 5.02 16.15 4.73 17.11 4.58 17.73 4.32<br />

20 11.20 5.59 12.13 5.78 13.60 5.54 14.88 5.16 16.00 4.82 16.99 4.65 17.76 4.34<br />

21 11.17 5.64 12.13 5.87 13.60 5.62 14.85 5.22 15.90 4.87 16.99 4.68 17.65 4.35<br />

22 11.15 5.71 12.13 5.95 13.60 5.70 14.81 5.29 15.78 4.90 16.97 4.71 17.50 4.35<br />

24 11.04 5.80 12.01 6.04 13.44 5.77 14.72 5.34 15.76 4.94 16.69 4.72 17.40 4.37<br />

• Symbol<br />

TC : Total capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. Indicates rated capacity.<br />

2. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 235


Capacity coefficient factor (Reference) 5CSL0-06B<br />

2.2.9 Capacity coefficient factor (Reference)<br />

1) Rate <strong>of</strong> Change in Capacity by the Main Piping Length<br />

DC Inverter Synchro.(1Ø, 3Ø)<br />

Rate <strong>of</strong> Change in Cooling Capacity Rate <strong>of</strong> Change in Heating Capacity<br />

HL<br />

(m)<br />

HU<br />

(m)<br />

45<br />

30<br />

15<br />

0<br />

0<br />

15<br />

30<br />

45<br />

0.97<br />

0.93<br />

0.90<br />

0.85 0.81 0.80<br />

0 15 30 45 60 75 80 90<br />

0.97<br />

0.93<br />

0.90<br />

0.85 0.81 0.80<br />

Description <strong>of</strong> symbols:<br />

HL : Level difference(m) between outdoor and indoor units where indoor units are at alower position.<br />

HU : Level difference(m) between outdoor and indoor units where indoor units are in an upper position.<br />

L : Equivalent piping length(m)<br />

δ : Capacity correction factor<br />

• Notes<br />

δ<br />

δ<br />

236 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)<br />

HL<br />

(m)<br />

HU<br />

(m)<br />

45<br />

30<br />

15<br />

0<br />

0<br />

15<br />

30<br />

45<br />

0.99<br />

0.97<br />

0.96<br />

0.94 0.93 0.92<br />

0 15 30 45 60 75 80 90<br />

0.99<br />

0.97<br />

0.96<br />

0.94 0.93 0.92<br />

1. These figures shows the rate change in capacity <strong>of</strong> a standard indoor unit system at max. load (with the thermostat set to<br />

the max.) under the standard conditions.<br />

2. With this outdoor unit during cooling operation, the evaporating temperature is controlled to be constant and during<br />

heating condensing temperature is controlled to be constant.<br />

3. Method <strong>of</strong> calculating the cooling/heating capacity (max. capacity for combination with the standard indoor unit)<br />

Cooling/Heating capacity = Cooling/Heating capacity obtained from the performance characteristics table x each capacity<br />

rate <strong>of</strong> change.<br />

When the piping length is different depending upon the indoor unit, the max. capacity <strong>of</strong> each unit during simultaneous<br />

operation is as follows.<br />

Cooling/Heating Capacity = Cooling/Heating Capacity <strong>of</strong> each unit x capacity rate <strong>of</strong> change for each piping length<br />

4. Even thogh there are over-height, over-length that we guarantee, pipe length and height are followed by each<br />

specification allowed.<br />

δ<br />

δ


5CSL0-06B<br />

2) Rate <strong>of</strong> Change in Capacity by the Branch Piping Length<br />

3.5 kW models 5.0 kW models<br />

Piping Rate <strong>of</strong> Change in Capacity<br />

Length Cooling Heating<br />

5 100.00% 100.00%<br />

10 97.00% 98.30%<br />

15 94.00% 96.50%<br />

7.1 kW models<br />

Piping Rate <strong>of</strong> Change in Capacity<br />

Length Cooling Heating<br />

5 100.00% 100.00%<br />

10 97.80% 99.20%<br />

15 95.50% 98.40%<br />

Capacity coefficient factor (Reference)<br />

Piping Rate <strong>of</strong> Change in Capacity<br />

Length Cooling Heating<br />

5 100.00% 100.00%<br />

10 98.30% 99.50%<br />

15 96.50% 99.00%<br />

8.0 kW models<br />

Piping Rate <strong>of</strong> Change in Capacity<br />

Length Cooling Heating<br />

5 100.00% 100.00%<br />

10 98.40% 99.10%<br />

15 96.80% 98.20%<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 237


Capacity coefficient factor (Reference) 5CSL0-06B<br />

3) Calculation <strong>of</strong> actual system capacity<br />

① Outdoor unit rated capacity<br />

Qodu(rated) [from specification table]<br />

② Outdoor unit capacity at Ti, To temperature.<br />

Qodu(Ti, To) [from capacity table]<br />

③ Outdoor unit capacity coefficient factor<br />

F(Ti, To) = Qodu(Ti, To) / Qodu(rated)<br />

④ Piping correction factor [from capacity coefficient factor table]<br />

Fmain (length, elevation) for main piping length or elevation<br />

Fbranch (length, elevation) for branch piping length or elevation<br />

⑤ Individual indoor unit combinational capacity<br />

Qidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)<br />

⑥ Individual indoor unit actual capacity<br />

Qidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)<br />

Exam<strong>pl</strong>e) • Outdoor unit model : AUUW486D[UU48W U3D]<br />

• Total indoor units combination : UT24 + UT24<br />

• Outdoor temperature : 32.0°CDB<br />

• Indoor temperature: 19.0°WDB<br />

• Main piping length(O/D to BD):40m<br />

• Branch piping length(BD to I/D):10m<br />

• Indoor unit actual cooling capacity<br />

- Qodu(rated) : 14.0 kW<br />

- Qodu(Ti, To) : 14.4 kW<br />

- F(Ti, To) : 14.4 / 14.0 = 1.03%<br />

- Fmain (length, elevation) = 91.1%<br />

- Fbranch (length, elevation) = 97.8%<br />

- Qidu(actual) [UT24 + UT24] = 14.0 kW x 1.03 x 0.911 x 0.978 = 12.85kW<br />

238 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.2.10 Operation range<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

46<br />

43<br />

21<br />

-5<br />

-10<br />

Cooling<br />

Operative<br />

Continuous<br />

operation<br />

18 32<br />

Indoor Unit [°C DB]<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

Operation limit<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 239<br />

24<br />

-10<br />

-15<br />

Warming up<br />

Operation<br />

Heating<br />

Continuous<br />

operation<br />

Operative<br />

16 30<br />

Indoor Unit [°C DB]<br />

Operative: Intermittent operation due to the operational<br />

conditions (indoor/outdoor temperature,<br />

humidity, load etc.) can cause the heating<br />

capacity to decrease


Electric Characteristics 5CSL0-06B<br />

2.2.11 Electric Characteristics<br />

Unit<br />

Power Compressor OFM<br />

Model Type Hz Voltage Voltage range MCA MOP MSC RLA kW FLA<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

1 Phase<br />

inverter<br />

3 Phase<br />

inverter<br />

50<br />

50<br />

220-240<br />

380-415<br />

Notes :<br />

1. Voltage range<br />

Voltage sup<strong>pl</strong>ied to the unit terminals should be within the<br />

minimum and maximum range<br />

2. Maximum allowable voltage unbalance between phase is 2 %<br />

3. MCA / MOP<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

- Load1 : Rated running current <strong>of</strong> largest motor<br />

(compressor or other motor)<br />

- Load2 : sum <strong>of</strong> current for all other motors<br />

- Load3 : any other load rated 1.0A or more<br />

4. Select wire spec. based on the MCA<br />

5. Recommended circuit breaker is ELCB (Earth Leakage circuit<br />

breaker)<br />

6. MSC & RLA are measured as the compressor only test<br />

condition.<br />

7. MSC values<br />

Min.: 198<br />

Max.: 264<br />

Min.: 352<br />

Maxi.: 457<br />

22.45 39.45 14.20 17.00 0.24 1.20<br />

26.20 46.20 14.20 20.00 0.24 1.20<br />

31.83 56.33 14.20 24.50 0.24 1.20<br />

6.55 10.83 4.28 4.28 0.24 1.20<br />

7.74 12.97 5.23 5.23 0.24 1.20<br />

8.59 14.50 5.91 5.91 0.24 1.20<br />

8. RLA is measured during each individual compressor test<br />

condition.<br />

9. OFM is measured as the outdoor unit test condition<br />

(Exam<strong>pl</strong>e) Selection <strong>of</strong> proper circuit breaker<br />

① Model : AUUW486D<br />

- Rated running current : 20.0A (refer to spec. sheet)<br />

② MCA = (1.25 x Load1) + Load2 + Load3<br />

= (1.25 x 20.0) + 0 + 1.20 = 26.2A<br />

③ MOP = (2.25 x Load1) + Load2 + Load3<br />

= (2.25 x 20.0) + 0 + 1.20 = 46.2A<br />

→ Finally select circuit breaker 50A<br />

MCA : Minimum Circuit Amperes (A)<br />

MOP : Maximum rating over current protective device<br />

MSC : Maximum Starting Current<br />

RLA : Rated Load Amperes (A)<br />

OFM : Outdoor Fan Motor<br />

kW : Fan Motor rated output (kW)<br />

FLA : Full Load Amperes (A)<br />

240 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.2.12 Field wiring diagrams<br />

DC Inverter Synchro(1Ø)<br />

1. All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

2. Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the current as required by the air conditioner.<br />

3. Feed the power source to the unit via a distribution switch board designed for this purpose.<br />

4. The terminal screws inside the control box may be loose due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can overload and damage electrical components.)<br />

5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.<br />

L<br />

N<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

Circuit breaker<br />

Power cable 3 core 5.0mm 2<br />

(Including earth)<br />

Fuse<br />

L<br />

N<br />

G<br />

Outdoor unit<br />

Terminal Block outdoor<br />

1(L) 2(N) 1(L) 2(N) 3<br />

Notes:<br />

1. All wirings, components and materials to be procured on the site should be according to the standard<br />

2. Use copper conductor only<br />

3. Install circuit breaker for safety<br />

4. Unit should be grounded in com<strong>pl</strong>iance with the ap<strong>pl</strong>icable local and national codes<br />

5. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Field wiring diagrams<br />

Transmission line<br />

1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3<br />

Terminal block indoor<br />

Terminal block indoor<br />

Terminal block indoor<br />

Terminal block indoor<br />

A unit B unit C unit D unit<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 241


Field wiring diagrams 5CSL0-06B<br />

DC Inverter Synchro(3Ø)<br />

1. All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

2. Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the current as required by the air conditioner.<br />

3. Feed the power source to the unit via a distribution switch board designed for this purpose.<br />

4. The terminal screws inside the control box may be loose due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can overload and damage electrical components.)<br />

5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.<br />

R<br />

S<br />

T N<br />

Circuit breaker<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

Fuse<br />

Power cable 5 core x 2.5mm 2<br />

(Including earth)<br />

R<br />

S<br />

T N<br />

Outdoor unit<br />

Terminal Block outdoor<br />

R S T N 1(L) 2(N) 3 4 5<br />

Notes:<br />

1. All wirings, components and materials to be procured on the site should be according to the standard<br />

2. Use copper conductor only<br />

3. Install circuit breaker for safety<br />

4. Unit should be grounded in com<strong>pl</strong>iance with the ap<strong>pl</strong>icable local and national codes<br />

5. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Transmission<br />

cable<br />

1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3<br />

Terminal block indoor<br />

Terminal block indoor<br />

Terminal block indoor<br />

Terminal block indoor<br />

A unit B unit C unit D unit<br />

242 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.2.13 Sound levels<br />

Sound Pressure Level (dB re 20μPa )<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

D<br />

1m<br />

1m<br />

15m<br />

Sound pressure level<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU48W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Sound levels<br />

Notes:<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as the<br />

construction(acoustic absorption coefficient) <strong>of</strong> particular room in<br />

which the equipment is installed.<br />

- The operating conditions are assumed to be standard<br />

Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø) 243


Accessories 5CSL0-06B<br />

2.2.14 Accessories<br />

Optional accessories<br />

Name Model No. Indoor classification Capacity Ratio(%)<br />

PMUB11A "Synchro" Duo 50:50(1:1)<br />

Branch Kit PMUB111A "Synchro" Trio 33:33:33(1:1:1)<br />

PMUB1111A "Synchro" Quartet 25:25:25:25(1:1:1:1)<br />

244 Outdoor unit - DC Inverter SINGLE A - Synchro (1Ø, 3Ø)


5CSL0-06B<br />

2.3 Non inverter Single A (1Ø, 3Ø)<br />

2.3.1 Power sup<strong>pl</strong>y<br />

External wiring procedure<br />

Power sup<strong>pl</strong>y<br />

Type Outdoor unit Capacity (kW) Circuit breaker capacity Power sup<strong>pl</strong>y<br />

AUUH126D[UU12 ULD]<br />

AUUH186D[UU18 UED]<br />

AUUH246D[UU24 UED]<br />

3.5<br />

5.0<br />

7.1<br />

15A<br />

20A<br />

1Ø, 220-240 V, 50Hz<br />

Heat pump AUUH306D[UU30 UED] 8.0 30A<br />

AUUH368D[UU37 UED] 10.0 25A<br />

AUUH488D[UU48 U3D] 14.0 30A 3Ø, 380V-415V, 50Hz<br />

AUUH608D[UU60 U3D] 15.0 30A<br />

- The power sup<strong>pl</strong>y work is needed only to the outdoor unit. The power sup<strong>pl</strong>y to the indoor unit is conducted through the<br />

transmission wiring.<br />

- Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Circuit breaker<br />

Power sup<strong>pl</strong>y<br />

Earth<br />

Outdoor unit<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 245


List <strong>of</strong> functions 5CSL0-06B<br />

2.3.2 List <strong>of</strong> functions<br />

Non inverter Single A (1Ø, 3Ø)<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Auto operation(Artificial intelligence)<br />

Convenience<br />

Auto Restart Operation<br />

Central control(LGAP)<br />

CAC Network<br />

PDI(Power Distribution Indicator)<br />

Function<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

Category<br />

Function<br />

Defrost / Deicing<br />

High Pressure Switch<br />

Low Pressure Switch<br />

Reliability Phase protection<br />

Restart Delay (3-minutes)<br />

Self Diagnosis<br />

S<strong>of</strong>t Start<br />

Test Function<br />

Auto operation(Artificial intelligence)<br />

Convenience<br />

Auto Restart Operation<br />

Central control(LGAP)<br />

CAC Network<br />

PDI(Power Distribution Indicator)<br />

Function<br />

PI485<br />

Special<br />

Low Ambient Kit<br />

Function Kit<br />

Others Thermistor<br />

AUUH126D<br />

[UU12 ULD]<br />

AUUH186D<br />

[UU18 UED]<br />

AUUH246D<br />

[UU24 UED]<br />

O O O O<br />

- - O O<br />

- - - -<br />

- - - -<br />

O O O O<br />

O O O O<br />

- - - -<br />

O O O O<br />

O O O O<br />

O O O O<br />

O O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O(program logic) AQLA AQLA O(program logic)<br />

- - - -<br />

AUUH368D<br />

[UU37 UED]<br />

AUUH488D<br />

[UU48 U3D]<br />

AUUH306D<br />

[UU30 UED]<br />

O O O<br />

O O O<br />

- O O<br />

O O O<br />

O O O<br />

O O O<br />

- - -<br />

O O O<br />

O O O<br />

O O O<br />

O O O<br />

PQNFG00A0 PQNFG00A0 PQNFG00A0<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

O(program logic) O(program logic) O(program logic)<br />

- - -<br />

AUUH608D<br />

[UU60 U3D]<br />

• O: Ap<strong>pl</strong>ied, • X: Not ap<strong>pl</strong>ied, • - : No relation,<br />

• Option: Model name & price are different according to options, and assembled in factory with main unit.<br />

• Accessory: Installed at field, ordered and purchased separately by the corresponding model name, sup<strong>pl</strong>ied with separate package.<br />

246 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B<br />

2.3.3 Specifications<br />

Specifications<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

ATNH12GRLED ATNH18GQLED ATNH24GPLED ATNH30GPLFD<br />

[UT12 NRD [UT18 NQD] [UT24 NPD] [UT30 NPD]<br />

Outdoor Units<br />

AUUH126D<br />

AUUH186D<br />

AUUH246D<br />

AUUH306D<br />

[UU12 ULD] [UU18 UED] [UU24 UED] [UU30 UED]<br />

Nominal Capacity Cooling kW<br />

3.38 5.25 7.00 8.00<br />

(Min~Rated~Max) Heating kW<br />

3.75 5.67 7.5 9.00<br />

Nominal Input Cooling kW<br />

1.29 1.85 2.49 3.62<br />

(Min~Rated~Max) Heating kW<br />

1.32 1.93 2.60 3.60<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

AVNH12GELAD UVNH186BLAD UVNH246BLAD UVNH306BLAD<br />

[UV12 NED] [UV18 NBD] [UV24 NBD] [UV30 NBD]<br />

Outdoor Units<br />

AUUH126D<br />

AUUH186D<br />

AUUH246D<br />

AUUH306D<br />

[UU12 ULD] [UU18 UED] [UU24 UED] [UU30 UED]<br />

Nominal Capacity Cooling kW<br />

3.27 4.45 6.50 7.80<br />

(Min~Rated~Max) Heating kW<br />

3.75 5.4 7.3 8.80<br />

Nominal Input Cooling kW<br />

1.3 1.84 2.49 3.53<br />

(Min~Rated~Max) Heating kW<br />

1.32 2.00 2.6 3.65<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

ABNH186HLAD<br />

ABNH246HLAD<br />

ABNH306GLAD<br />

[UB18 NHD]<br />

[UB24 NHD]<br />

[UB30 NGD]<br />

AUUH186D<br />

AUUH246D<br />

AUUH306D<br />

[UU18 UED]<br />

[UU24 UED]<br />

[UU30 UED]<br />

4.95 6.5 8.00<br />

5.8 7.40 9.00<br />

1.96 2.49 3.60<br />

2.18 2.6 3.20<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 247


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units AUUH126D[UU12 ULD] AUUH186D[UU18 UED] AUUH246D[UU24 UED] AUUH306D[UU30 UED]<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power Sup<strong>pl</strong>y Ø,V,Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable (Includes earth) No.* mm 2<br />

Compressor Type<br />

Quantity<br />

Model<br />

Motor Input kW<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge* g<br />

Type<br />

Control<br />

Heat exchnager Tube Size (OD) mm<br />

Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Fan Type<br />

No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level(H/L) Sound Press,1m dB(A)+3<br />

Defrosting<br />

SVC Valve Liquid mm<br />

Gas mm<br />

Dimensions W*H*D mm<br />

Net Weight (Outdoor) kg<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge (Over 7.5m) g/m<br />

5.8/5.95 8.26/8.6 11.4/12.6 17.2/16.3<br />

24 36 62 82<br />

1,220-240,50 1,220-240,50 1,220-240,50 1,220-240,50<br />

3*2.5 3*2.5 3*2.5 3*3.5<br />

4*0.75 4*0.75 4*0.75 4*0.75<br />

Rotary Rotary Rotary Rotary<br />

1 1 1 1<br />

GK151PAC 5KS225DAF21 GP290PAC GPT407P<br />

1.24 1.98 2.50 2.17<br />

350 600 1,130 1,200<br />

FVC68D (PVE) FV50S (PVE) FVC68D (PVE) FVC68D (PVE)<br />

1,200 1,300 1,950 1,870<br />

R410A R410A R410A R410A<br />

capillary EEV EEV EEV<br />

7.0 7.0 7.0 7.0<br />

18 18 18 18<br />

2R,24C 2R,28C 2R,36C 2R,36C<br />

OBM-2012P2 IC28640LG28P IC28640LG28P IC28640LG28J<br />

0.25 0.67 0.67 0.67<br />

1.5/370 6/370 6/370 6/370<br />

Propeller Propeller Propeller Propeller<br />

1/400 1/460 1/460 1/460<br />

Side Discharge Side Discharge Side Discharge Side Discharge<br />

26 53 53 53<br />

47 52 52 53<br />

Reversing cycle Reversing cycle Reversing cycle Reversing cycle<br />

6.35 6.35 9.52 9.52<br />

9.52 12.7 15.88 15.88<br />

770*545*245 870*655*320 870*808*320 870*808*320<br />

31 52 60 64<br />

15/10 50/30 40/30 50/30<br />

20 35 45 45<br />

Notes:<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m(25ft)<br />

- Level Difference <strong>of</strong> Zero.<br />

2. * : Full factory charge is shipped in the outdoor unit. The charge is determined based on 7.5m(25ft) <strong>of</strong> line.<br />

3. Due to our policy <strong>of</strong> innovation some specifications may be changed without notification.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

248 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Capacity and Nominal Input<br />

Indoor Units<br />

Outdoor Units<br />

Nominal Capacity Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Nominal Input Cooling kW<br />

(Min~Rated~Max) Heating kW<br />

Specifications<br />

ATNH36GNLED<br />

ATNH48GMLED<br />

ATNH60GMLED<br />

[UT36 NND]<br />

[UT48 NMD]<br />

[UT60 NMD]<br />

AUUH368D<br />

AUUH488D<br />

AUUH608D<br />

[UU37 UED]<br />

[UU48 U3D]<br />

[UU60 U3D]<br />

10.00 13.70 14.30<br />

11.00 15.00 17.00<br />

3.80 5.40 5.90<br />

3.40 5.00 5.80<br />

UVNH366KLAD<br />

UVNH486LLAD<br />

UVNH606LLAD<br />

[UV36 NKD]<br />

[UV48 NLD]<br />

[UV60 NLD]<br />

AUUH368D<br />

AUUH488D<br />

AUUH608D<br />

[UU37 UED]<br />

[UU48 U3D]<br />

[UU60 U3D]<br />

10.00 13.20 14.3<br />

11.00 16.00 17.0<br />

3.72 5.30 5.90<br />

3.78 5.10 5.80<br />

ABNH366GLAD<br />

ABNH486RLAD<br />

ABNH606RLAD<br />

[UB36 NGD]<br />

[UB48 NRD]<br />

[UB60 NRD]<br />

AUUH368D<br />

AUUH488D<br />

AUUH608D<br />

[UU37 UED]<br />

[UU48 U3D]<br />

[UU60 U3D]<br />

10.00 13.70 14.90<br />

11.00 16.00 17.50<br />

4.00 5.84 6.30<br />

3.60 5.10 5.00<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 249


Specifications 5CSL0-06B<br />

Nominal Capacity and Nominal Input<br />

Outdoor Units AUUH368D[UU37 UED] AUUH488D[UU48 U3D] AUUH608D[UU60 U3D]<br />

Running Current Cooling/Heating A<br />

Starting Current Cooling/Heating A<br />

Power Sup<strong>pl</strong>y Ø,V,Hz<br />

Power Sup<strong>pl</strong>y Cable (Includes earth) No.* mm 2<br />

Interunit Cable (Includes earth) No.* mm 2<br />

Compressor Type<br />

Quantity<br />

Model<br />

Motor Input kW<br />

Oil Charge cc<br />

Oil Type<br />

Refrigerant Charge* g<br />

Type<br />

Control<br />

Heat exchnager Tube Size (OD) mm<br />

Fins per inch<br />

No. <strong>of</strong> Rows & Column/No.<br />

Fan motor Model<br />

Output kW<br />

Capacitor μF/Vac<br />

Fan Type<br />

No. Used / Diameter EA/mm<br />

Discharge Side / Top<br />

Air Circulation CMM<br />

Noise Level(H/L) Sound Press,1m dB(A)+3<br />

Defrosting<br />

SVC Valve Liquid mm<br />

Gas mm<br />

Dimensions W*H*D mm<br />

Net Weight (Outdoor) kg<br />

Max. Piping Length/Elevation m<br />

Additional Refrigerant Charge g/m<br />

7.5/7.7 6.5/6.4 6.9/6.7<br />

47 63 67<br />

3,380-415,50 3,380-415,50 3,380-415,50<br />

5*2.5 5*2.5 5*2.5<br />

4*0.75 4*0.75 4*0.75<br />

Scroll Scroll Scroll<br />

1 1 1<br />

AQ042YAA AR061YAB ARA068YAA<br />

3.6 4.4 5.3<br />

1,200 1,800 1,800<br />

FVC68D (PVE) FVC68D (PVE) FVC68D (PVE)<br />

2,450 3,300 3,500<br />

R410A R410A R410A<br />

EEV EEV EEV<br />

7.0 7.0 7.0<br />

18 17 17<br />

2R,48C 2R 64C 2R 64C<br />

5BM-3018P2*2 YDK75-6M YDK75-6M<br />

47*2 63*2 63*2<br />

2.0/400 6/370 6/370<br />

Propeller Propeller Propeller<br />

2 /400 2/520 2/520<br />

Side Discharge Side Discharge Side Discharge<br />

32*2 55*2 55*2<br />

52 55 55<br />

Reversing cycle Reversing cycle Reversing cycle<br />

9.52 9.52 9.52<br />

15.88 15.88 15.88<br />

870*1,060*320 950*1,380*330 950*1,380*330<br />

85(187) 105(231) 105(231)<br />

50/30 50/30 50/30<br />

45 50 40<br />

Notes:<br />

1. Capacities are based on the following conditions:<br />

Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB<br />

- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB<br />

Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB<br />

- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB<br />

Piping Length - Interconnecting Piping Length 7.5m(25ft)<br />

- Level Difference <strong>of</strong> Zero.<br />

2. * : Full factory charge is shipped in the outdoor unit. The charge is determined based on 7.5m(25ft) <strong>of</strong> line.<br />

3. Due to our policy <strong>of</strong> innovation some specifications may be changed without notification.<br />

4. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Conversion Formula<br />

kcal/h = kW × 859.8<br />

CFM = CMM × 35.3<br />

250 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Dimensions<br />

2.3.4 Dimensions<br />

1) Outdoor unit<br />

AUUH126D [UU12 ULD]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

6<br />

Earth screw<br />

SVC valve cover<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

AUUH126D[UU12 ULD]<br />

1/ 220-240 / 50<br />

Simultaneous operation<br />

Refer to combination table<br />

6.35<br />

9.52<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 251<br />

Note


Dimensions<br />

AUUH186D [UU18 UED]<br />

Part Name Remark<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

870<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

160<br />

546<br />

6<br />

Earth screw<br />

SVC valve cover<br />

340<br />

360<br />

10<br />

54.6<br />

AUUH186D[UU18 UED]<br />

Model name<br />

1Ø, 220-240V, 50Hz<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Simultaneous operation<br />

Refer to combination table<br />

Heating Capacity<br />

6.35<br />

12.7<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

301<br />

320<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

252 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

Ø531<br />

Note<br />

4<br />

1<br />

513<br />

630<br />

655<br />

2<br />

319<br />

3<br />

5<br />

50<br />

80<br />

25


5CSL0-06B Dimensions<br />

AUUH246D[UU24 UED]<br />

AUUH306D[UU30 UED]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

6<br />

Earth screw<br />

SVC valve cover<br />

AUUH246D[UU24 UED] AUUH306D[UU30 UED]<br />

1Ø, 220-240V, 50Hz 1Ø, 220-240V, 50Hz<br />

Simultaneous operation<br />

Refer to combination table<br />

9.52<br />

9.52<br />

15.88<br />

15.88<br />

Model name<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Heating Capacity<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 253<br />

1


Dimensions<br />

AUUH368D[UU37 UED]<br />

Part Name Remark<br />

Air discharge grille<br />

Gas pipe connection<br />

Liquid pipe connection<br />

Power & transmission connection<br />

6<br />

Earth screw<br />

SVC valve cover<br />

No.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

AUUH368D[UU37 UED]<br />

Model name<br />

1Ø, 220-240V, 50Hz<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Simultaneous operation<br />

Refer to combination table<br />

Heating Capacity<br />

9.52<br />

15.88<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

5CSL0-06B<br />

254 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

Note


5CSL0-06B Dimensions<br />

AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

4<br />

Supporter<br />

AUUH608D[UU60 U3D]<br />

3Ø, 380-415V, 50Hz<br />

AUUH488D[UU48 U3D]<br />

Model name<br />

3Ø, 380-415V, 50Hz<br />

Power Sup<strong>pl</strong>y<br />

Cooling Capacity<br />

Simultaneous operation<br />

Refer to combination table<br />

Heating Capacity<br />

9.52<br />

15.88<br />

9.52<br />

15.88<br />

Ø/V/Hz<br />

kW<br />

kW<br />

mm<br />

mm<br />

Liquid<br />

Gas<br />

Piping<br />

Connections<br />

1. Unit should be installed in com<strong>pl</strong>iance with the installation manual in<br />

the product box.<br />

2. Unit should be grounded in accordance with the local regulations or<br />

ap<strong>pl</strong>icable national codes.<br />

3. All electrical components and materials to be sup<strong>pl</strong>ied on the site<br />

must com<strong>pl</strong>y with the local regulations or international codes.<br />

4. Electrical characteristics chapter should be considered for electrical<br />

work and design. Especially the capacity <strong>of</strong> power cable and circuit<br />

breaker for outdoor unit should be more than that <strong>of</strong> electrical<br />

characteristics chapter.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 255<br />

Note<br />

490<br />

CHASSIS CODE: U3


Piping diagram<br />

2.3.5 Piping diagram<br />

Models :AUUH126D[UU12 ULD]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 9.52mm)<br />

Liquid<br />

(Ø 6.35mm)<br />

Capillary<br />

Accumulator<br />

Reversing<br />

Valve<br />

Constant<br />

Compressor<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

Th1 Thermistor for condenser pipe temperature CN_TH<br />

Th2 Thermistor for outdoor air temperature CN_TH<br />

5CSL0-06B<br />

256 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

Th2<br />

Th1


5CSL0-06B Piping diagram<br />

Models : AUUH186D[UU18 UED]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 12.7mm)<br />

Liquid<br />

(Ø 6.35mm)<br />

EEV<br />

Accumulator<br />

Reversing<br />

Valve<br />

Constant<br />

Compressor<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_LEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH2<br />

Th2 Thermistor for discharge pipe temperature CN_TH2<br />

Th3 Thermistor for condenser pipe temperature CN_TH1<br />

Th4 Thermistor for outdoor air temperature CN_TH1<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 257<br />

Th1<br />

Th2<br />

Th4<br />

Th3


Piping diagram<br />

Models : AUUH246D[UU24 UED], AUUH306D [UU30 UED]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

EEV<br />

Accumulator<br />

Reversing<br />

Valve<br />

Constant<br />

Compressor<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

5CSL0-06B<br />

258 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

Th.1<br />

Th.2<br />

High<br />

pressure<br />

S/W<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN_LEV1<br />

Th1 Thermistor for suction pipe temperature CN_TH2<br />

Th2 Thermistor for discharge pipe temperature CN_TH2<br />

Th3 Thermistor for condenser pipe temperature CN_TH1<br />

Th4 Thermistor for outdoor air temperature CN_TH1<br />

Th.4<br />

Th.3


5CSL0-06B Piping diagram<br />

Models: AUUH368D [UU37 UED]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

EEV<br />

Accumulator<br />

r<br />

Th1<br />

Reversing<br />

Valve<br />

Constant<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN-EEV1<br />

Th1 Thermistor for suction pipe temperature CN-TH2<br />

Th2 Thermistor for discharge pipe temperature CN-TH2<br />

Th3 Thermistor for condenser pipe temperature CN-TH1<br />

Th4 Thermistor for outdoor air temperature CN-TH1<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 259<br />

Th2<br />

Th3<br />

Th4


Piping diagram<br />

Models: AUUH488D [UU48 U3D], AUUH608D [UU60 U3D]<br />

Field Piping<br />

Refrigerant Flow<br />

Cooling<br />

Heating<br />

Gas<br />

(Ø 15.88mm)<br />

Liquid<br />

(Ø 9.52mm)<br />

EEV<br />

Low Pressure<br />

S/W<br />

Accumulator<br />

r<br />

Th1<br />

Reversing<br />

Valve<br />

Constant<br />

Compressor<br />

High Pressure<br />

S/W<br />

OUTDOOR UNIT<br />

Heat<br />

Exchanger<br />

LOC. Description PCB Connector<br />

EEV Electronic Expansion Valve CN-EEV1<br />

Th1 Thermistor for suction pipe temperature CN-TH2<br />

Th2 Thermistor for discharge pipe temperature CN-TH2<br />

Th3 Thermistor for condenser pipe temperature CN-TH1<br />

Th4 Thermistor for outdoor air temperature CN-TH1<br />

5CSL0-06B<br />

260 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

Th2<br />

Th3<br />

Th4


5CSL0-06B Wiring diagrams<br />

2.3.6 Wiring diagrams<br />

Models : AUUH126D [UU12 ULD]<br />

Communication<br />

CENTRAL CONTROLLER<br />

POWER SUPPLY<br />

CN_POWER<br />

4WAY VALVE<br />

(Main power) COMP FAN<br />

LEV 1<br />

EEPROM<br />

CENTRAL<br />

CONTROLLER<br />

SENSOR<br />

(Air, Cond)<br />

SENSOR<br />

(Dis, Suc)<br />

LGMV<br />

FLASH<br />

(ON bording)<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 261


Wiring diagrams<br />

Model: AUUH186D[UU18 UED]<br />

Central controller<br />

POWER SUPPLY<br />

CN_COM<br />

(Communication)<br />

CN_POWER<br />

(Main power)<br />

COMP 1<br />

CN_FAN 1<br />

SMPS CN_TH 2 CN_CENTRAL<br />

(Suction discharge)<br />

CN_TH 1<br />

(Pipe out)<br />

CN_SV<br />

(4WAY VALVE)<br />

5CSL0-06B<br />

CN_TEST<br />

CN_LEV 1<br />

262 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Wiring diagrams<br />

Models : AUUH246D[UU24 UED]<br />

Central controller<br />

POWER SUPPLY<br />

CN_COM<br />

(Communication)<br />

CN_POWER<br />

(Main power)<br />

COMP 1<br />

CN_FAN 1<br />

SMPS CN_TH 2 CN_CENTRAL<br />

(Suction discharge)<br />

CN_TH 1<br />

(Pipe out)<br />

CN_SV<br />

(4WAY VALVE)<br />

CN_TEST<br />

CN_LEV 1<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 263


Wiring diagrams<br />

Models : AUUH306D [UU30 UED]<br />

CN-PRESS<br />

CN-COM<br />

CENTRAL CONTROLLER<br />

POWER SUPPLY<br />

CN-POWER<br />

(Main Power) RY_COMP2 CN_4WAY<br />

CN_LEV1 EEP ROM<br />

CN_FAN<br />

5CSL0-06B<br />

CENTRAL<br />

CONTROLLER<br />

CN_TH1<br />

CN_TH2<br />

CN_LGMV<br />

CN_FLASH<br />

(ON boarding)<br />

264 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Wiring diagrams<br />

Models : AUUH368D[UU37 UED]<br />

Error Indicator<br />

EEPROM<br />

Central<br />

Controller<br />

Power sup<strong>pl</strong>y<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 265


Wiring diagrams<br />

Models : AUUH488D[UU48 U3D], AUUH608D[UU60 U3D]<br />

CENTRAL<br />

CONTROLLER<br />

POWER<br />

SUPPLY<br />

CN_COM<br />

CN_POWER CN_PRESS1 CN_COMP CN_4WAY<br />

CN_3PHASE<br />

EEPROM<br />

CN_LEV1<br />

CN_<br />

PHASE_FAN<br />

CN_LGMV<br />

5CSL0-06B<br />

Error Indicator<br />

CN_<br />

CENTRAL<br />

CN_<br />

FLASH<br />

CN_TH1<br />

(AIR/PIPE1)<br />

CN_TH2<br />

(PIPE2/DIS1)<br />

266 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

2.3.7 Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH126D + ATNH12GRLED, AVNH12GELAD<br />

[UU12 ULD] + [UT12 NRD], [UV12 NED]<br />

Model ATNH12GRLED[UT12 NRD]<br />

AFR 9.5<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 2.74 2.36 0.85 2.68 2.34 1.00 2.56 2.28 1.17 2.48 2.23 1.23 2.39 2.18 1.31 2.33 2.15 1.35<br />

16.0 22.0 3.20 2.68 0.86 3.13 2.65 1.02 2.98 2.58 1.19 2.89 2.52 1.25 2.79 2.46 1.33 2.72 2.42 1.37<br />

18.0 25.0 3.57 2.92 0.87 3.49 2.88 1.03 3.33 2.79 1.20 3.23 2.73 1.27 3.11 2.66 1.35 3.04 2.62 1.39<br />

19.0 27.0 3.74 3.01 0.89 3.66 2.98 1.05 3.48 2.88 1.22 3.38 2.82 1.29 3.25 2.75 1.37 3.18 2.70 1.42<br />

22.0 30.0 4.10 3.20 0.90 4.01 3.16 1.06 3.82 3.05 1.24 3.71 2.98 1.31 3.57 2.89 1.39 3.49 2.84 1.44<br />

24.0 32.0 4.25 3.25 0.91 4.16 3.20 1.08 3.97 3.09 1.26 3.85 3.02 1.33 3.71 2.93 1.41 3.62 2.88 1.46<br />

Model AVNH12GELAD[UV12 NED]<br />

AFR 9.2<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 2.65 2.29 0.85 2.60 2.27 1.01 2.47 2.20 1.18 2.40 2.16 1.24 2.31 2.11 1.32 2.26 2.08 1.36<br />

16.0 22.0 3.09 2.60 0.86 3.03 2.57 1.03 2.89 2.50 1.20 2.80 2.44 1.26 2.70 2.38 1.34 2.63 2.35 1.38<br />

18.0 25.0 3.45 2.82 0.88 3.38 2.79 1.04 3.22 2.71 1.21 3.12 2.65 1.28 3.01 2.58 1.36 2.94 2.54 1.40<br />

19.0 27.0 3.61 2.92 0.89 3.54 2.89 1.06 3.37 2.79 1.23 3.27 2.73 1.30 3.15 2.66 1.38 3.08 2.62 1.43<br />

22.0 30.0 3.97 3.10 0.90 3.88 3.06 1.07 3.70 2.95 1.25 3.59 2.88 1.32 3.45 2.80 1.40 3.38 2.75 1.45<br />

24.0 32.0 4.12 3.15 0.92 4.03 3.10 1.09 3.84 3.00 1.27 3.72 2.92 1.34 3.59 2.84 1.42 3.50 2.79 1.47<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 267


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH126D + ATNH12GRLED, AVNH12GELAD<br />

[UU12 ULD] + [UT12 NRD], [UV12 NED]<br />

Model ATNH12GRLED[UT12 NRD]<br />

AFR 9.5<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 2.53 0.96 2.98 1.05 3.45 1.15 3.63 1.18 3.80 1.22 4.01 1.24 4.35 1.30 4.80 1.39<br />

18.0 2.45 1.00 2.89 1.09 3.34 1.18 3.51 1.22 3.68 1.26 3.89 1.28 4.21 1.35 4.64 1.44<br />

20.0 2.38 1.03 2.80 1.12 3.24 1.22 3.41 1.26 3.57 1.30 3.75 1.32 4.08 1.39 4.51 1.49<br />

22.0 2.29 1.06 2.70 1.16 3.13 1.26 3.28 1.30 3.44 1.34 3.64 1.36 3.94 1.44 4.34 1.54<br />

24.0 2.21 1.09 2.61 1.19 3.02 1.30 3.17 1.34 3.32 1.38 3.51 1.41 3.80 1.48 4.19 1.58<br />

Model AVNH12GELAD[UV12 NED]<br />

AFR 9.2<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 2.53 0.96 2.98 1.05 3.45 1.15 3.63 1.18 3.80 1.22 4.01 1.24 4.35 1.30 4.80 1.39<br />

18.0 2.45 1.00 2.89 1.09 3.34 1.18 3.51 1.22 3.68 1.26 3.89 1.28 4.21 1.35 4.64 1.44<br />

20.0 2.38 1.03 2.80 1.12 3.24 1.22 3.41 1.26 3.57 1.30 3.75 1.32 4.08 1.39 4.51 1.49<br />

22.0 2.29 1.06 2.70 1.16 3.13 1.26 3.28 1.30 3.44 1.34 3.64 1.36 3.94 1.44 4.34 1.54<br />

24.0 2.21 1.09 2.61 1.19 3.02 1.30 3.17 1.34 3.32 1.38 3.51 1.41 3.80 1.48 4.19 1.58<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

268 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH186D + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD<br />

[UU18 UED] + [UT18 NQD], [UV18 NBD], [UB18 NHD]<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 4.26 3.08 1.21 4.17 3.05 1.44 3.97 2.97 1.68 3.85 2.91 1.76 3.71 2.85 1.88 3.62 2.81 1.94<br />

16.0 22.0 4.97 3.50 1.23 4.86 3.46 1.46 4.63 3.36 1.70 4.50 3.29 1.79 4.33 3.21 1.91 4.23 3.16 1.97<br />

18.0 25.0 5.54 3.81 1.25 5.43 3.76 1.48 5.17 3.65 1.73 5.02 3.57 1.82 4.83 3.48 1.93 4.72 3.42 2.00<br />

19.0 27.0 5.80 3.93 1.27 5.68 3.89 1.51 5.41 3.77 1.76 5.25 3.68 1.85 5.05 3.59 1.97 4.94 3.53 2.03<br />

22.0 30.0 6.37 4.17 1.29 6.23 4.12 1.53 5.94 3.98 1.78 5.76 3.89 1.87 5.55 3.78 1.99 5.42 3.71 2.06<br />

24.0 32.0 6.61 4.24 1.31 6.47 4.18 1.55 6.16 4.04 1.80 5.98 3.94 1.90 5.76 3.83 2.02 5.62 3.76 2.09<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 3.61 2.84 1.21 3.53 2.81 1.43 3.37 2.74 1.67 3.27 2.68 1.76 3.14 2.62 1.87 3.07 2.58 1.93<br />

16.0 22.0 4.21 3.22 1.22 4.12 3.19 1.45 3.93 3.10 1.69 3.81 3.03 1.78 3.67 2.96 1.90 3.58 2.92 1.96<br />

18.0 25.0 4.70 3.51 1.24 4.60 3.47 1.47 4.38 3.36 1.72 4.25 3.29 1.81 4.09 3.20 1.92 4.00 3.15 1.99<br />

19.0 27.0 4.92 3.63 1.26 4.81 3.58 1.50 4.59 3.47 1.75 4.45 3.39 1.84 4.28 3.30 1.96 4.19 3.25 2.02<br />

22.0 30.0 5.40 3.85 1.28 5.28 3.80 1.52 5.03 3.67 1.77 4.88 3.58 1.86 4.70 3.48 1.98 4.59 3.42 2.05<br />

24.0 32.0 5.60 3.91 1.30 5.48 3.86 1.54 5.22 3.72 1.79 5.07 3.63 1.89 4.88 3.53 2.01 4.77 3.46 2.08<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 4.01 3.69 1.28 3.93 3.65 1.52 3.74 3.55 1.77 3.63 3.48 1.87 3.50 3.40 1.99 3.42 3.35 2.05<br />

16.0 22.0 4.68 4.18 1.30 4.59 4.14 1.55 4.37 4.02 1.80 4.24 3.93 1.90 4.08 3.84 2.02 3.99 3.78 2.09<br />

18.0 25.0 5.23 4.55 1.32 5.12 4.50 1.57 4.88 4.36 1.83 4.73 4.26 1.93 4.55 4.16 2.05 4.45 4.09 2.12<br />

19.0 27.0 5.47 4.71 1.35 5.35 4.65 1.60 5.10 4.50 1.86 4.95 4.40 1.96 4.77 4.29 2.08 4.66 4.22 2.15<br />

22.0 30.0 6.00 4.99 1.36 5.88 4.93 1.62 5.60 4.76 1.88 5.43 4.65 1.99 5.23 4.52 2.11 5.11 4.44 2.18<br />

24.0 32.0 6.23 5.07 1.38 6.10 5.00 1.64 5.81 4.83 1.91 5.64 4.71 2.01 5.43 4.58 2.14 5.30 4.49 2.21<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 269


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH186D + ATNH18GQLED, UVNH186BLAD, ABNH186HLAD<br />

[UU18 UED] + [UT18 NQD], [UV18 NBD], [UB18 NHD]<br />

Model ATNH18GQLED[UT18 NQD]<br />

AFR 13<br />

Model UVNH186BLAD[UV18 NBD]<br />

AFR 13.5<br />

Model ABNH186HLAD[UB18 NHD]<br />

AFR 16.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 3.83 1.41 4.51 1.54 5.22 1.68 5.48 1.73 5.74 1.78 6.07 1.81 6.57 1.90 7.25 2.04<br />

18.0 3.71 1.46 4.37 1.59 5.05 1.73 5.31 1.79 5.56 1.84 5.88 1.87 6.36 1.97 7.02 2.11<br />

20.0 3.60 1.50 4.24 1.64 4.90 1.79 5.15 1.84 5.40 1.90 5.67 1.93 6.17 2.03 6.81 2.18<br />

22.0 3.47 1.55 4.08 1.69 4.73 1.85 4.96 1.90 5.20 1.96 5.50 1.99 5.95 2.10 6.57 2.25<br />

24.0 3.35 1.60 3.94 1.75 4.56 1.90 4.79 1.96 5.02 2.02 5.31 2.05 5.74 2.16 6.34 2.32<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 3.65 1.46 4.30 1.59 4.97 1.74 5.22 1.79 5.47 1.84 5.78 1.87 6.26 1.97 6.91 2.11<br />

18.0 3.53 1.51 4.16 1.65 4.81 1.79 5.05 1.85 5.30 1.91 5.60 1.94 6.06 2.04 6.69 2.19<br />

20.0 3.43 1.56 4.04 1.70 4.67 1.85 4.90 1.91 5.14 1.97 5.40 2.00 5.88 2.11 6.49 2.26<br />

22.0 3.30 1.61 3.89 1.76 4.50 1.91 4.73 1.97 4.95 2.03 5.23 2.07 5.67 2.17 6.25 2.33<br />

24.0 3.19 1.66 3.76 1.81 4.35 1.97 4.57 2.03 4.78 2.09 5.05 2.13 5.47 2.24 6.04 2.40<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 3.92 1.59 4.61 1.74 5.34 1.89 5.61 1.95 5.87 2.01 6.21 2.04 6.72 2.15 7.42 2.30<br />

18.0 3.79 1.64 4.47 1.80 5.17 1.96 5.43 2.02 5.69 2.08 6.01 2.11 6.51 2.22 7.18 2.38<br />

20.0 3.68 1.70 4.33 1.85 5.01 2.02 5.27 2.08 5.52 2.14 5.80 2.18 6.31 2.30 6.97 2.46<br />

22.0 3.55 1.75 4.18 1.91 4.83 2.08 5.08 2.15 5.32 2.21 5.62 2.25 6.08 2.37 6.72 2.54<br />

24.0 3.42 1.81 4.03 1.97 4.67 2.15 4.90 2.21 5.14 2.28 5.43 2.32 5.88 2.44 6.48 2.62<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

270 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH246D + ATNH24GPLED , UVNH246BLAD, ABNH246HLAD<br />

[UU24 UED]+ [UT24 NPD], [UV24 NBD], [UB24 NHD]<br />

Model ATNH24GPLED[UT24 NPD]<br />

AFR 17<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.68 4.63 1.63 5.56 4.59 1.93 5.30 4.46 2.25 5.14 4.37 2.38 4.95 4.28 2.53 4.83 4.22 2.61<br />

16.0 22.0 6.62 5.26 1.66 6.48 5.21 1.96 6.18 5.05 2.29 5.99 4.94 2.41 5.77 4.83 2.57 5.64 4.76 2.65<br />

18.0 25.0 7.39 5.72 1.68 7.23 5.66 1.99 6.89 5.48 2.32 6.69 5.36 2.45 6.44 5.22 2.60 6.29 5.14 2.69<br />

19.0 27.0 7.74 5.91 1.71 7.57 5.84 2.03 7.22 5.66 2.36 7.00 5.53 2.49 6.74 5.39 2.65 6.58 5.30 2.74<br />

22.0 30.0 8.49 6.27 1.73 8.31 6.19 2.05 7.92 5.98 2.39 7.68 5.84 2.52 7.40 5.68 2.68 7.22 5.58 2.77<br />

24.0 32.0 8.81 6.38 1.76 8.62 6.29 2.08 8.22 6.07 2.43 7.97 5.92 2.56 7.68 5.75 2.72 7.50 5.64 2.81<br />

Model UVNH246BLAD[UV24 NBD]<br />

AFR 15<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.27 4.03 1.63 5.16 3.99 1.93 4.92 3.88 2.25 4.77 3.80 2.38 4.59 3.72 2.53 4.49 3.67 2.61<br />

16.0 22.0 6.15 4.57 1.66 6.02 4.53 1.96 5.74 4.40 2.29 5.57 4.30 2.41 5.36 4.20 2.57 5.23 4.14 2.65<br />

18.0 25.0 6.86 4.97 1.68 6.72 4.92 1.99 6.40 4.77 2.32 6.21 4.66 2.45 5.98 4.54 2.60 5.84 4.47 2.69<br />

19.0 27.0 7.18 5.14 1.71 7.03 5.08 2.03 6.70 4.92 2.36 6.50 4.81 2.49 6.26 4.69 2.65 6.11 4.61 2.74<br />

22.0 30.0 7.88 5.45 1.73 7.72 5.38 2.05 7.35 5.20 2.39 7.13 5.08 2.52 6.87 4.94 2.68 6.71 4.85 2.77<br />

24.0 32.0 8.18 5.55 1.76 8.01 5.47 2.08 7.63 5.28 2.43 7.40 5.15 2.56 7.13 5.00 2.72 6.96 4.91 2.81<br />

Model ABNH246HLAD[UB24 NHD]<br />

AFR 18<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 5.27 3.87 1.63 5.16 3.84 1.93 4.92 3.73 2.25 4.77 3.65 2.38 4.59 3.57 2.53 4.49 3.52 2.61<br />

16.0 22.0 6.15 4.39 1.66 6.02 4.35 1.96 5.74 4.22 2.29 5.57 4.13 2.41 5.36 4.04 2.57 5.23 3.97 2.65<br />

18.0 25.0 6.86 4.78 1.68 6.72 4.73 1.99 6.40 4.58 2.32 6.21 4.48 2.45 5.98 4.37 2.60 5.84 4.30 2.69<br />

19.0 27.0 7.18 4.94 1.71 7.03 4.88 2.03 6.70 4.73 2.36 6.50 4.62 2.49 6.26 4.50 2.65 6.11 4.43 2.74<br />

22.0 30.0 7.88 5.24 1.73 7.72 5.17 2.05 7.35 5.00 2.39 7.13 4.88 2.52 6.87 4.75 2.68 6.71 4.66 2.77<br />

24.0 32.0 8.18 5.33 1.76 8.01 5.25 2.08 7.63 5.07 2.43 7.40 4.95 2.56 7.13 4.81 2.72 6.96 4.72 2.81<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 271


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH246D + ATNH24GPLED , UVNH246BLAD, ABNH246HLAD<br />

[UU24 UED]+ [UT24 NPD], [UV24 NBD], [UB24 NHD]<br />

Model ATNH24GPLED[UT24 NPD]<br />

AFR 17<br />

Model UVNH246BLAD[UV24 NBD]<br />

AFR 15<br />

Model ABNH246HLAD[UB24 NHD]<br />

AFR 18<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 5.07 1.90 5.97 2.07 6.90 2.26 7.25 2.33 7.60 2.40 8.03 2.44 8.69 2.57 9.59 2.75<br />

18.0 4.91 1.96 5.78 2.14 6.69 2.33 7.02 2.40 7.36 2.48 7.77 2.52 8.42 2.65 9.29 2.84<br />

20.0 4.76 2.02 5.61 2.21 6.49 2.41 6.81 2.48 7.14 2.56 7.50 2.60 8.16 2.74 9.01 2.93<br />

22.0 4.59 2.09 5.40 2.28 6.25 2.49 6.57 2.56 6.88 2.64 7.27 2.68 7.87 2.83 8.69 3.03<br />

24.0 4.43 2.15 5.22 2.35 6.04 2.56 6.34 2.64 6.64 2.72 7.02 2.77 7.60 2.91 8.39 3.12<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 4.93 1.90 5.81 2.07 6.72 2.26 7.06 2.33 7.39 2.40 7.81 2.44 8.46 2.57 9.33 2.75<br />

18.0 4.77 1.96 5.62 2.14 6.51 2.33 6.83 2.40 7.16 2.48 7.56 2.52 8.19 2.65 9.04 2.84<br />

20.0 4.63 2.02 5.46 2.21 6.31 2.41 6.63 2.48 6.95 2.56 7.30 2.60 7.94 2.74 8.77 2.93<br />

22.0 4.46 2.09 5.26 2.28 6.08 2.49 6.39 2.56 6.70 2.64 7.07 2.68 7.66 2.83 8.45 3.03<br />

24.0 4.31 2.15 5.08 2.35 5.87 2.56 6.17 2.64 6.47 2.72 6.83 2.77 7.40 2.91 8.16 3.12<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 5.00 1.90 5.89 2.07 6.81 2.26 7.15 2.33 7.49 2.40 7.92 2.44 8.57 2.57 9.46 2.75<br />

18.0 4.84 1.96 5.70 2.14 6.59 2.33 6.93 2.40 7.26 2.48 7.67 2.52 8.30 2.65 9.16 2.84<br />

20.0 4.69 2.02 5.53 2.21 6.40 2.41 6.72 2.48 7.04 2.56 7.40 2.60 8.05 2.74 8.89 2.93<br />

22.0 4.52 2.09 5.33 2.28 6.17 2.49 6.48 2.56 6.79 2.64 7.17 2.68 7.76 2.83 8.57 3.03<br />

24.0 4.37 2.15 5.15 2.35 5.96 2.56 6.25 2.64 6.55 2.72 6.93 2.77 7.50 2.91 8.27 3.12<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

272 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH306D + ATNH30GPLED , UVNH306BLAD, ABNH306GLAD<br />

[UU30 UED]+ [UT30 NPD], [UV30 NBD], [UB30 NGD]<br />

Model ATNH30GPLED[UT30 NPD]<br />

AFR 19<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 6.49 5.29 2.37 6.35 5.25 2.81 6.05 5.10 3.28 5.87 5.00 3.45 5.65 4.89 3.67 5.52 4.82 3.79<br />

16.0 22.0 7.57 6.01 2.41 7.41 5.95 2.85 7.06 5.78 3.33 6.85 5.65 3.51 6.60 5.52 3.73 6.44 5.43 3.85<br />

18.0 25.0 8.45 6.54 2.45 8.27 6.46 2.90 7.88 6.26 3.38 7.64 6.12 3.56 7.36 5.97 3.79 7.19 5.87 3.91<br />

19.0 27.0 8.84 6.76 2.49 8.65 6.68 2.95 8.25 6.47 3.44 8.00 6.32 3.62 7.70 6.16 3.85 7.52 6.06 3.98<br />

22.0 30.0 9.70 7.17 2.52 9.50 7.07 2.98 9.05 6.84 3.48 8.78 6.67 3.67 8.45 6.49 3.90 8.26 6.38 4.03<br />

24.0 32.0 10.07 7.29 2.56 9.86 7.19 3.03 9.39 6.93 3.53 9.11 6.77 3.72 8.77 6.57 3.96 8.57 6.45 4.09<br />

Model UVNH306BLAD[UV30 NBD]<br />

AFR 18<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 6.33 4.83 2.31 6.19 4.79 2.74 5.90 4.66 3.20 5.72 4.56 3.37 5.51 4.46 3.58 5.38 4.40 3.70<br />

16.0 22.0 7.38 5.49 2.35 7.23 5.43 2.78 6.89 5.28 3.25 6.68 5.16 3.42 6.43 5.04 3.64 6.28 4.96 3.76<br />

18.0 25.0 8.24 5.97 2.38 8.06 5.90 2.83 7.68 5.72 3.30 7.45 5.59 3.47 7.18 5.45 3.69 7.01 5.37 3.81<br />

19.0 27.0 8.62 6.17 2.42 8.44 6.10 2.87 8.04 5.91 3.35 7.80 5.77 3.53 7.51 5.62 3.75 7.34 5.53 3.88<br />

22.0 30.0 9.46 6.55 2.46 9.26 6.46 2.91 8.82 6.24 3.39 8.56 6.09 3.58 8.24 5.93 3.80 8.05 5.82 3.93<br />

24.0 32.0 9.82 6.65 2.49 9.61 6.56 2.95 9.16 6.33 3.44 8.88 6.18 3.63 8.55 6.00 3.86 8.36 5.89 3.99<br />

Model ABNH306GLAD[UB30 NGD]<br />

AFR 26.5<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 6.49 5.36 2.36 6.35 5.31 2.80 6.05 5.17 3.26 5.87 5.06 3.43 5.65 4.95 3.65 5.52 4.88 3.77<br />

16.0 22.0 7.57 6.09 2.40 7.41 6.02 2.84 7.06 5.85 3.31 6.85 5.72 3.49 6.60 5.59 3.71 6.44 5.50 3.83<br />

18.0 25.0 8.45 6.62 2.43 8.27 6.55 2.88 7.88 6.34 3.36 7.64 6.20 3.54 7.36 6.05 3.77 7.19 5.95 3.89<br />

19.0 27.0 8.84 6.84 2.47 8.65 6.76 2.93 8.25 6.55 3.42 8.00 6.40 3.60 7.70 6.24 3.83 7.52 6.13 3.96<br />

22.0 30.0 9.70 7.26 2.50 9.50 7.16 2.97 9.05 6.92 3.46 8.78 6.76 3.65 8.45 6.57 3.88 8.26 6.46 4.01<br />

24.0 32.0 10.07 7.38 2.54 9.86 7.28 3.01 9.39 7.02 3.51 9.11 6.85 3.70 8.77 6.66 3.93 8.57 6.53 4.06<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 273


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH306D + ATNH30GPLED , UVNH306BLAD, ABNH306GLAD<br />

[UU30 UED]+ [UT30 NPD], [UV30 NBD], [UB30 NGD]<br />

Model ATNH30GPLED[UT30 NPD]<br />

AFR 19<br />

Model UVNH306BLAD[UV30 NBD]<br />

AFR 18<br />

Model ABNH306GLAD[UB30 NGD]<br />

AFR 26.5<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 6.08 2.62 7.16 2.87 8.28 3.12 8.70 3.22 9.11 3.32 9.63 3.37 10.4 3.55 11.5 3.80<br />

18.0 5.88 2.71 6.93 2.97 8.02 3.23 8.42 3.33 8.83 3.43 9.33 3.49 10.1 3.67 11.1 3.93<br />

20.0 5.71 2.80 6.73 3.06 7.78 3.34 8.17 3.44 8.56 3.54 9.00 3.60 9.79 3.79 10.81 4.06<br />

22.0 5.50 2.89 6.48 3.16 7.50 3.44 7.88 3.55 8.25 3.65 8.72 3.72 9.44 3.91 10.42 4.19<br />

24.0 5.31 2.98 6.26 3.26 7.24 3.55 7.61 3.66 7.97 3.77 8.42 3.83 9.12 4.03 10.06 4.32<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 5.94 2.45 7.00 2.68 8.10 2.92 8.51 3.01 8.91 3.10 9.42 3.15 10.2 3.32 11.3 3.55<br />

18.0 5.75 2.53 6.78 2.77 7.84 3.02 8.24 3.11 8.63 3.20 9.12 3.26 9.87 3.43 10.9 3.67<br />

20.0 5.58 2.62 6.58 2.86 7.61 3.11 7.99 3.21 8.37 3.31 8.80 3.36 9.58 3.54 10.6 3.79<br />

22.0 5.38 2.70 6.34 2.95 7.33 3.21 7.70 3.31 8.07 3.41 8.53 3.47 9.23 3.65 10.2 3.91<br />

24.0 5.20 2.78 6.12 3.04 7.08 3.31 7.44 3.41 7.79 3.52 8.24 3.58 8.92 3.77 9.84 4.03<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 6.08 2.33 7.16 2.55 8.28 2.78 8.70 2.86 9.11 2.95 9.63 3.00 10.4 3.16 11.5 3.38<br />

18.0 5.88 2.41 6.93 2.64 8.02 2.87 8.42 2.96 8.83 3.05 9.33 3.10 10.1 3.26 11.1 3.50<br />

20.0 5.71 2.49 6.73 2.72 7.78 2.97 8.17 3.06 8.56 3.15 9.00 3.20 9.79 3.37 10.8 3.61<br />

22.0 5.50 2.57 6.48 2.81 7.50 3.06 7.88 3.15 8.25 3.25 8.72 3.30 9.44 3.48 10.4 3.73<br />

24.0 5.31 2.65 6.26 2.90 7.24 3.15 7.61 3.25 7.97 3.35 8.42 3.41 9.12 3.59 10.1 3.84<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

274 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH368D + ATNH36GNLED , UVNH366KLAD, ABNH366GLAD<br />

[UU37 UED]+ [UT36 NND] , [UV36 NKD] , [UB36 NGD]<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.11 6.64 2.49 7.94 6.58 2.95 7.56 6.40 3.44 7.34 6.27 3.62 7.07 6.13 3.86 6.90 6.04 3.98<br />

16.0 22.0 9.46 7.54 2.53 9.26 7.47 3.00 8.83 7.25 3.49 8.56 7.09 3.68 8.24 6.92 3.91 8.05 6.82 4.04<br />

18.0 25.0 10.6 8.20 2.57 10.3 8.11 3.04 9.85 7.86 3.55 9.55 7.68 3.74 9.20 7.49 3.97 8.99 7.37 4.11<br />

19.0 27.0 11.1 8.48 2.61 10.8 8.38 3.09 10.3 8.12 3.61 10.0 7.93 3.80 9.63 7.73 4.04 9.41 7.60 4.18<br />

22.0 30.0 12.1 8.99 2.64 11.9 8.88 3.13 11.3 8.58 3.65 11.0 8.37 3.85 10.6 8.14 4.09 10.3 8.00 4.23<br />

24.0 32.0 12.6 9.14 2.68 12.3 9.02 3.18 11.7 8.70 3.71 11.4 8.49 3.90 11.0 8.25 4.15 10.7 8.10 4.29<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.11 6.11 2.44 7.94 6.06 2.89 7.56 5.89 3.37 7.34 5.77 3.55 7.07 5.64 3.77 6.90 5.56 3.90<br />

16.0 22.0 9.46 6.94 2.48 9.26 6.87 2.93 8.83 6.67 3.42 8.56 6.53 3.60 8.24 6.37 3.83 8.05 6.28 3.96<br />

18.0 25.0 10.6 7.55 2.51 10.3 7.47 2.98 9.85 7.24 3.47 9.55 7.07 3.66 9.20 6.90 3.89 8.99 6.79 4.02<br />

19.0 27.0 11.1 7.81 2.56 10.8 7.71 3.03 10.3 7.47 3.53 10.0 7.30 3.72 9.63 7.11 3.96 9.41 7.00 4.09<br />

22.0 30.0 12.1 8.28 2.59 11.9 8.17 3.07 11.3 7.90 3.58 11.0 7.71 3.77 10.6 7.50 4.01 10.3 7.36 4.14<br />

24.0 32.0 12.6 8.42 2.63 12.3 8.30 3.11 11.7 8.01 3.63 11.4 7.81 3.82 11.0 7.59 4.07 10.7 7.45 4.20<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 8.11 6.53 2.62 7.94 6.47 3.11 7.56 6.30 3.62 7.34 6.17 3.82 7.07 6.03 4.06 6.90 5.95 4.19<br />

16.0 22.0 9.46 7.42 2.66 9.26 7.34 3.15 8.83 7.13 3.68 8.56 6.97 3.87 8.24 6.81 4.12 8.05 6.71 4.26<br />

18.0 25.0 10.6 8.07 2.70 10.3 7.98 3.20 9.85 7.73 3.73 9.55 7.56 3.93 9.20 7.37 4.18 8.99 7.25 4.32<br />

19.0 27.0 11.1 8.34 2.75 10.8 8.24 3.26 10.3 7.98 3.80 10.0 7.80 4.00 9.63 7.60 4.25 9.41 7.48 4.40<br />

22.0 30.0 12.1 8.85 2.78 11.9 8.73 3.30 11.3 8.44 3.85 11.0 8.24 4.05 10.6 8.01 4.31 10.3 7.87 4.45<br />

24.0 32.0 12.6 8.99 2.82 12.3 8.87 3.35 11.7 8.56 3.90 11.4 8.35 4.11 11.0 8.11 4.37 10.7 7.96 4.52<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 275


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH368D + ATNH36GNLED , UVNH366KLAD, ABNH366GLAD<br />

[UU37 UED]+ [UT36 NND] , [UV36 NKD] , [UB36 NGD]<br />

Model ATNH36GNLED[UT36 NND]<br />

AFR 24<br />

Model UVNH366KLAD[UV36 NKD]<br />

AFR 29<br />

Model ABNH366GLAD[UB36 NGD]<br />

AFR 32<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 7.42 2.48 8.74 2.71 10.1 2.95 10.6 3.04 11.1 3.13 11.8 3.19 12.7 3.35 14.1 3.59<br />

18.0 7.19 2.56 8.46 2.80 9.79 3.05 10.3 3.14 10.8 3.24 11.4 3.29 12.3 3.47 13.6 3.71<br />

20.0 6.97 2.65 8.21 2.89 9.50 3.15 10.0 3.25 10.5 3.35 11.0 3.40 12.0 3.58 13.2 3.84<br />

22.0 6.72 2.73 7.92 2.98 9.16 3.25 9.62 3.35 10.1 3.45 10.7 3.51 11.5 3.70 12.7 3.96<br />

24.0 6.49 2.82 7.64 3.08 8.84 3.35 9.29 3.45 9.73 3.56 10.3 3.62 11.1 3.81 12.3 4.08<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 7.42 2.76 8.74 3.01 10.1 3.28 10.6 3.38 11.1 3.48 11.8 3.54 12.7 3.73 14.1 3.99<br />

18.0 7.19 2.85 8.46 3.11 9.79 3.39 10.3 3.50 10.8 3.60 11.4 3.66 12.3 3.86 13.6 4.13<br />

20.0 6.97 2.94 8.21 3.22 9.50 3.50 10.0 3.61 10.5 3.72 11.0 3.78 12.0 3.98 13.2 4.27<br />

22.0 6.72 3.04 7.92 3.32 9.16 3.61 9.62 3.73 10.1 3.84 10.7 3.90 11.5 4.11 12.7 4.40<br />

24.0 6.49 3.13 7.64 3.42 8.84 3.73 9.29 3.84 9.73 3.96 10.3 4.02 11.1 4.24 12.3 4.54<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 7.42 2.62 8.74 2.87 10.1 3.12 10.6 3.22 11.1 3.32 11.8 3.37 12.7 3.55 14.1 3.80<br />

18.0 7.19 2.71 8.46 2.97 9.79 3.23 10.3 3.33 10.8 3.43 11.4 3.49 12.3 3.67 13.6 3.93<br />

20.0 6.97 2.80 8.21 3.06 9.50 3.34 10.0 3.44 10.5 3.54 11.0 3.60 12.0 3.79 13.2 4.06<br />

22.0 6.72 2.89 7.92 3.16 9.16 3.44 9.6 3.55 10.1 3.65 10.7 3.72 11.5 3.91 12.7 4.19<br />

24.0 6.49 2.98 7.64 3.26 8.84 3.55 9.3 3.66 9.7 3.77 10.3 3.83 11.1 4.03 12.3 4.32<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

276 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH488D + ATNH48GMLED , UVNH486LLAD , ABNH486RLAD<br />

[UU48 U3D]+ [UT48 NMD] , [UV48 NLD] , [UB48 NRD]<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 11.1 8.8 3.54 10.9 8.72 4.19 10.4 8.48 4.89 10.1 8.31 5.15 9.68 8.12 5.48 9.46 8.01 5.66<br />

16.0 22.0 13.0 10.0 3.59 12.7 9.89 4.26 12.1 9.60 4.97 11.7 9.40 5.23 11.3 9.17 5.56 11.0 9.04 5.75<br />

18.0 25.0 14.5 10.9 3.65 14.2 10.7 4.32 13.5 10.4 5.04 13.1 10.2 5.31 12.6 9.93 5.65 12.3 9.77 5.83<br />

19.0 27.0 15.1 11.2 3.71 14.8 11.1 4.40 14.1 10.8 5.13 13.7 10.5 5.40 13.2 10.2 5.74 12.9 10.1 5.93<br />

22.0 30.0 16.6 11.9 3.76 16.3 11.8 4.45 15.5 11.4 5.19 15.0 11.1 5.47 14.5 10.8 5.82 14.1 10.6 6.01<br />

24.0 32.0 17.2 12.1 3.81 16.9 11.9 4.52 16.1 11.5 5.27 15.6 11.2 5.55 15.0 10.9 5.90 14.7 10.7 6.10<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 10.7 8.29 3.47 10.5 8.22 4.12 10.0 7.99 4.80 9.69 7.83 5.06 9.33 7.65 5.38 9.11 7.55 5.55<br />

16.0 22.0 12.5 9.41 3.53 12.2 9.32 4.18 11.7 9.05 4.87 11.3 8.85 5.13 10.9 8.64 5.46 10.6 8.51 5.64<br />

18.0 25.0 13.9 10.2 3.58 13.6 10.1 4.24 13.0 9.81 4.95 12.6 9.59 5.21 12.1 9.35 5.54 11.9 9.20 5.73<br />

19.0 27.0 14.6 10.6 3.64 14.3 10.5 4.31 13.6 10.1 5.03 13.2 9.90 5.30 12.7 9.65 5.64 12.4 9.49 5.82<br />

22.0 30.0 16.0 11.2 3.69 15.7 11.1 4.37 14.9 10.7 5.10 14.5 10.5 5.37 13.9 10.2 5.71 13.6 10.0 5.90<br />

24.0 32.0 16.6 11.4 3.74 16.3 11.3 4.43 15.5 10.9 5.17 15.0 10.6 5.45 14.5 10.3 5.79 14.1 10.1 5.98<br />

Model ABNH486RLAD[UB48 NRD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 11.1 9.01 3.83 10.9 8.93 4.54 10.4 8.68 5.29 10.1 8.50 5.57 9.68 8.32 5.93 9.46 8.20 6.12<br />

16.0 22.0 13.0 10.2 3.89 12.7 10.1 4.61 12.1 9.83 5.37 11.7 9.62 5.66 11.3 9.39 6.02 11.03 9.25 6.22<br />

18.0 25.0 14.5 11.1 3.94 14.2 11.0 4.68 13.5 10.7 5.45 13.1 10.4 5.74 12.6 10.2 6.11 12.3 10.0 6.31<br />

19.0 27.0 15.1 11.5 4.01 14.8 11.4 4.75 14.1 11.0 5.54 13.7 10.8 5.84 13.2 10.5 6.21 12.9 10.3 6.42<br />

22.0 30.0 16.6 12.2 4.06 16.3 12.0 4.82 15.5 11.6 5.61 15.0 11.4 5.91 14.5 11.0 6.29 14.1 10.8 6.50<br />

24.0 32.0 17.2 12.4 4.12 16.9 12.2 4.89 16.1 11.8 5.70 15.6 11.5 6.00 15.0 11.2 6.38 14.7 11.0 6.59<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 277


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH488D + ATNH48GMLED , UVNH486LLAD , ABNH486RLAD<br />

[UU48 U3D]+ [UT48 NMD] , [UV48 NLD] , [UB48 NRD]<br />

Model ATNH48GMLED[UT48 NMD]<br />

AFR 34<br />

Model UVNH486LLAD[UV48 NLD]<br />

AFR 36<br />

Model ABNH486RLAD[UB48 NRD]<br />

AFR 40<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 10.1 3.65 11.9 3.98 13.8 4.34 14.5 4.47 15.2 4.61 16.1 4.69 17.4 4.93 19.2 5.28<br />

18.0 9.8 3.77 11.6 4.12 13.4 4.49 14.0 4.62 14.7 4.76 15.5 4.85 16.8 5.10 18.6 5.46<br />

20.0 9.5 3.89 11.2 4.25 13.0 4.63 13.6 4.78 14.3 4.92 15.0 5.00 16.3 5.27 18.0 5.64<br />

22.0 9.2 4.02 10.8 4.39 12.5 4.78 13.1 4.93 13.8 5.08 14.5 5.16 15.7 5.44 17.4 5.82<br />

24.0 8.9 4.14 10.4 4.52 12.1 4.93 12.7 5.08 13.3 5.23 14.0 5.32 15.2 5.60 16.8 6.00<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 10.8 3.72 12.7 4.06 14.7 4.43 15.5 4.56 16.2 4.70 17.1 4.78 18.5 5.03 20.5 5.39<br />

18.0 10.5 3.84 12.3 4.20 14.3 4.58 15.0 4.72 15.7 4.86 16.6 4.94 17.9 5.20 19.8 5.57<br />

20.0 10.2 3.97 12.0 4.34 13.8 4.73 14.5 4.87 15.2 5.02 16.0 5.10 17.4 5.37 19.2 5.75<br />

22.0 9.8 4.10 11.5 4.48 13.3 4.88 14.0 5.03 14.7 5.18 15.5 5.27 16.8 5.54 18.5 5.94<br />

24.0 9.4 4.22 11.1 4.61 12.9 5.03 13.5 5.18 14.2 5.34 15.0 5.43 16.2 5.72 17.9 6.12<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 10.8 3.72 12.7 4.06 14.7 4.43 15.5 4.56 16.2 4.70 17.1 4.78 18.5 5.03 20.5 5.39<br />

18.0 10.5 3.84 12.3 4.20 14.3 4.58 15.0 4.72 15.7 4.86 16.6 4.94 17.9 5.20 19.8 5.57<br />

20.0 10.2 3.97 12.0 4.34 13.8 4.73 14.5 4.87 15.2 5.02 16.0 5.10 17.4 5.37 19.2 5.75<br />

22.0 9.8 4.10 11.5 4.48 13.3 4.88 14.0 5.03 14.7 5.18 15.5 5.27 16.8 5.54 18.5 5.94<br />

24.0 9.4 4.22 11.1 4.61 12.9 5.03 13.5 5.18 14.2 5.34 15.0 5.43 16.2 5.72 17.9 6.12<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

278 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Capacity tables<br />

• Cooling Capacity<br />

Models : AUUH608D + ATNH60GMLED , UVNH606LLAD , ABNH606RLAD<br />

[UU60 U3D]+ [UT60 NMD] , [UV60 NLD] , [UB60 NRD]<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Indoor Air<br />

Temperature<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 11.6 8.97 3.87 11.4 8.89 4.58 10.8 8.65 5.34 10.5 8.47 5.63 10.1 8.28 5.99 9.87 8.16 6.18<br />

16.0 22.0 13.5 10.2 3.93 13.2 10.1 4.65 12.6 9.79 5.42 12.2 9.58 5.71 11.8 9.35 6.08 11.5 9.21 6.28<br />

18.0 25.0 15.1 11.1 3.99 14.8 11.0 4.72 14.1 10.6 5.51 13.7 10.4 5.80 13.2 10.1 6.17 12.9 10.0 6.37<br />

19.0 27.0 15.8 11.5 4.05 15.5 11.3 4.80 14.7 11.0 5.60 14.3 10.7 5.90 13.8 10.4 6.28 13.4 10.3 6.48<br />

22.0 30.0 17.3 12.1 4.10 17.0 12.0 4.86 16.2 11.6 5.67 15.7 11.3 5.98 15.1 11.0 6.36 14.8 10.8 6.57<br />

24.0 32.0 18.0 12.3 4.16 17.6 12.2 4.94 16.8 11.8 5.76 16.3 11.5 6.06 15.7 11.1 6.45 15.3 10.9 6.66<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 40<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 11.6 8.86 3.87 11.4 8.78 4.58 10.8 8.54 5.34 10.5 8.37 5.63 10.1 8.18 5.99 9.87 8.07 6.18<br />

16.0 22.0 13.5 10.1 3.93 13.2 10.0 4.65 12.6 9.67 5.42 12.2 9.46 5.71 11.8 9.24 6.08 11.5 9.10 6.28<br />

18.0 25.0 15.1 10.9 3.99 14.8 10.8 4.72 14.1 10.5 5.51 13.7 10.3 5.80 13.2 10.0 6.17 12.9 9.84 6.37<br />

19.0 27.0 15.8 11.3 4.05 15.5 11.2 4.80 14.7 10.8 5.60 14.3 10.6 5.90 13.8 10.3 6.28 13.4 10.1 6.48<br />

22.0 30.0 17.3 12.0 4.10 17.0 11.8 4.86 16.2 11.4 5.67 15.7 11.2 5.98 15.1 10.9 6.36 14.8 10.7 6.57<br />

24.0 32.0 18.0 12.2 4.16 17.6 12.0 4.94 16.8 11.6 5.76 16.3 11.3 6.06 15.7 11.0 6.45 15.3 10.8 6.66<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

Indoor Air<br />

Temperature<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

Outdoor Air Temperature : °CDB<br />

20 25 32 35 40 43<br />

°CWB °CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI<br />

14.0 20.0 12.1 9.76 4.13 11.8 9.67 4.89 11.3 9.41 5.70 10.9 9.21 6.01 10.5 9.01 6.39 10.3 8.88 6.60<br />

16.0 22.0 14.1 11.1 4.19 13.8 11.0 4.97 13.2 10.6 5.79 12.8 10.4 6.10 12.3 10.2 6.49 12.0 10.0 6.70<br />

18.0 25.0 15.7 12.1 4.26 15.4 11.9 5.04 14.7 11.5 5.88 14.2 11.3 6.20 13.7 11.0 6.59 13.4 10.8 6.81<br />

19.0 27.0 16.5 12.5 4.33 16.1 12.3 5.13 15.4 11.9 5.98 14.9 11.7 6.30 14.3 11.4 6.70 14.0 11.2 6.92<br />

22.0 30.0 18.1 13.2 4.38 17.7 13.0 5.19 16.9 12.6 6.06 16.4 12.3 6.38 15.7 12.0 6.79 15.4 11.8 7.01<br />

24.0 32.0 18.8 13.4 4.45 18.4 13.2 5.27 17.5 12.8 6.15 17.0 12.5 6.47 16.3 12.1 6.89 16.0 11.9 7.11<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 279


Capacity tables<br />

• Heating Capacity<br />

Models : AUUH608D + ATNH60GMLED , UVNH606LLAD , ABNH606RLAD<br />

[UU60 U3D]+ [UT60 NMD] , [UV60 NLD] , [UB60 NRD]<br />

Model ATNH60GMLED[UT60 NMD]<br />

AFR 34<br />

Model UVNH606LLAD[UV60 NLD]<br />

AFR 40<br />

Model ABNH606RLAD[UB60 NRD]<br />

AFR 50<br />

• Symbol<br />

AFR : Air flow rate [m3 /min]<br />

DB : Dry bulb temperature [°C]<br />

WB : Wet bulb temperature [°C]<br />

TC : Total capacity [kW]<br />

SHC : Sensible capacity [kW]<br />

PI : Power Input [kW]<br />

(Comp.+ indoor fan motor+outdoor fan motor)<br />

5CSL0-06B<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 11.5 4.23 13.5 4.62 15.6 5.03 16.4 5.19 17.2 5.34 18.2 5.44 19.7 5.72 21.7 6.13<br />

18.0 11.1 4.37 13.1 4.78 15.1 5.21 15.9 5.36 16.7 5.53 17.6 5.62 19.1 5.92 21.0 6.34<br />

20.0 10.8 4.52 12.7 4.93 14.7 5.38 15.4 5.54 16.2 5.71 17.0 5.80 18.5 6.11 20.4 6.54<br />

22.0 10.4 4.66 12.2 5.09 14.2 5.55 14.9 5.72 15.6 5.89 16.5 5.99 17.8 6.31 19.7 6.75<br />

24.0 10.0 4.80 11.8 5.25 13.7 5.72 14.4 5.89 15.1 6.07 15.9 6.17 17.2 6.50 19.0 6.96<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 11.5 4.23 13.5 4.62 15.6 5.03 16.4 5.19 17.2 5.34 18.2 5.44 19.7 5.72 21.7 6.13<br />

18.0 11.1 4.37 13.1 4.78 15.1 5.21 15.9 5.36 16.7 5.53 17.6 5.62 19.1 5.92 21.0 6.34<br />

20.0 10.8 4.52 12.7 4.93 14.7 5.38 15.4 5.54 16.2 5.71 17.0 5.80 18.5 6.11 20.4 6.54<br />

22.0 10.4 4.66 12.2 5.09 14.2 5.55 14.9 5.72 15.6 5.89 16.5 5.99 17.8 6.31 19.7 6.75<br />

24.0 10.0 4.80 11.8 5.25 13.7 5.72 14.4 5.89 15.1 6.07 15.9 6.17 17.2 6.50 19.0 6.96<br />

Indoor Air<br />

Outdoor Air Temperature : °CWB<br />

Temperature(°C) -10 -5 0 2 4 6 10 15<br />

°CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI<br />

16.0 11.8 3.65 13.9 3.98 16.1 4.34 16.9 4.47 17.7 4.61 18.7 4.69 20.3 4.93 22.4 5.28<br />

18.0 11.4 3.77 13.5 4.12 15.6 4.49 16.4 4.62 17.2 4.76 18.1 4.85 19.6 5.10 21.7 5.46<br />

20.0 11.1 3.89 13.1 4.25 15.1 4.63 15.9 4.78 16.6 4.92 17.5 5.00 19.0 5.27 21.0 5.64<br />

22.0 10.7 4.02 12.6 4.39 14.6 4.78 15.3 4.93 16.0 5.08 17.0 5.16 18.4 5.44 20.3 5.82<br />

24.0 10.3 4.14 12.2 4.52 14.1 4.93 14.8 5.08 15.5 5.23 16.4 5.32 17.7 5.60 19.6 6.00<br />

• Notes<br />

1. All capacites are net, evaporator fan motor heat is<br />

deducted.<br />

2. Indicates rated capacity.<br />

3. Direct interpolation is permissible. Do not extrapolate<br />

4. Capacities are based on the following conditions:<br />

- Interconnecting Piping Length 7.5m<br />

- Level Difference <strong>of</strong> Zero.<br />

280 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B The coefficient <strong>of</strong> capacity change<br />

2.3.8 The coefficient <strong>of</strong> capacity change<br />

1) Rate <strong>of</strong> change in capacity due to the main piping length<br />

Rate <strong>of</strong> change in cooling capacity<br />

Main piping length(m)<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

10 15 20 30 35 40 45 50<br />

3.5kW 99.2 97.6 - - - - - -<br />

5.0/6.0kW 99.5 98.4 97.4 95.2 94.2 93.1 - -<br />

7.1kW 99.7 99.1 98.5 97.4 96.2 95.8 94.3 92.0<br />

8.0kW 99.8 99.5 98.4 97.4 96.3 95.2 94.1 93.1<br />

14.0/15.0kW 99.5 98.4 97.4 95.2 94.2 93.1 92.1 91.0<br />

Rate <strong>of</strong> change in heating capacity<br />

Main piping length(m)<br />

10 15 20 30 35 40 45 50<br />

3.5kW 98.8 96.4 - - - - - -<br />

Rate <strong>of</strong> change<br />

in capacity(%)<br />

5.0/6.0kW<br />

7.1kW<br />

8.0kW<br />

99.5<br />

99.7<br />

99.5<br />

98.4<br />

99.1<br />

98.4<br />

97.4<br />

98.5<br />

97.4<br />

95.2<br />

97.4<br />

95.2<br />

94.2<br />

96.8<br />

94.2<br />

93.1<br />

95.2<br />

93.1<br />

-<br />

94.3<br />

92.1<br />

-<br />

91.8<br />

91.1<br />

14.0/15.0kW 99.5 98.4 97.4 95.2 94.2 93.1 92.1 91.0<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 281


The coefficient <strong>of</strong> capacity change<br />

2) Calculation <strong>of</strong> actual system capacity<br />

① Outdoor unit rated capacity<br />

Qodu(rated) [from specification table]<br />

② Outdoor unit capacity at Ti, To temperature.<br />

Qodu(Ti, To) [from capacity table]<br />

③ Outdoor unit capacity coefficient factor<br />

F(Ti, To) = Qodu(Ti, To) / Qodu(rated)<br />

④ Piping correction factor [from capacity coefficient factor table]<br />

Fmain (length, elevation) for main piping length or elevation<br />

Fbranch (length, elevation) for branch piping length or elevation<br />

⑤ Individual indoor unit combinational capacity<br />

Qidu (combi) = Qodu(rated) x Qidu(rated) / Qidu(rated-total)<br />

⑥ Individual indoor unit actual capacity<br />

Qidu (actual) = Qodu(combi) x F(Ti, To) x Fmain (length, elevation) x Fbranch (length, elevation)<br />

Exam<strong>pl</strong>e) • Outdoor unit model : AUUH368D[UU37 UED]<br />

• Indoor units(ATNH36GNLED) : 10kW<br />

• Outdoor temperature : 32.0°CDB<br />

• Indoor temperature: 19.0°CWB<br />

• Main piping length(O/D to BD) : 30m<br />

• Indoor unit actual cooling capacity<br />

- Qodu(rated) : 10.0 kW<br />

- Qodu(Ti, To) : 10.3 kW<br />

- F(Ti, To) : 103%<br />

- Fmain(length, elevation) = 97.4%(by table)<br />

- Qidu(actual) =10.0kW x 1.03 x 0.974 = 10.03kW<br />

5CSL0-06B<br />

282 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Operation range<br />

2.3.9 Operation range<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

46<br />

43<br />

21<br />

-5<br />

Cooling<br />

Operative<br />

Continuous<br />

operation<br />

18 32<br />

Indoor Unit [°C DB]<br />

❈ Although low ambient kit is installed, in<br />

case outdoor temperature goes below 0°C,<br />

the cooling capacity can be dropped and<br />

operation characteristics can be slightly<br />

different.<br />

Outdoor<br />

Unit<br />

[°C DB]<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 283<br />

24<br />

-5<br />

-10<br />

Warming up<br />

Operation<br />

Heating<br />

Continuous<br />

operation<br />

Operative<br />

16 30<br />

Indoor Unit [°CDB]<br />

Operative:<br />

Intermittent operation due to the operation<br />

conditions (indoor/outdoor temperature humidity,<br />

and load) can cause<br />

the heating capacity to drop.


Electric characteristics<br />

2.3.10 Electric characteristics<br />

Outdoor Unit<br />

Power Compressor OFM<br />

5CSL0-06B<br />

Model Type Hz Voltage Voltage range MCA MOP MSC RLA kW FLA<br />

AUUH126D<br />

[UU12 ULD]<br />

AUUH186D<br />

[UU18 UED]<br />

AUUH246D<br />

[UU24 UED]<br />

AUUH306D<br />

[UU30 UED]<br />

AUUH368D<br />

[UU37 UED]<br />

AUUH488D<br />

[UU48 U3D]<br />

AUUH608D<br />

[UU60 U3D]<br />

Non inverter 50<br />

220-240<br />

380-415<br />

Notes :<br />

1. Voltage range<br />

Voltage sup<strong>pl</strong>ied to the unit terminals should be within the<br />

minimum and maximum range<br />

2. Maximum allowable voltage unbalance between phase is 2 %<br />

3. MCA / MOP<br />

MCA = (1.25 x Load1) + Load2 + Load3<br />

MOP = (2.25 x Load1) + Load2 + Load3<br />

- Load1 : Rated running current <strong>of</strong> largest motor<br />

(compressor or other motor)<br />

- Load2 : sum <strong>of</strong> current for all other motors<br />

- Load3 : any other load rated 1.0A or more<br />

4. Select wire spec. based on the MCA<br />

5. Recommended circuit breaker is ELCB (Earth Leakage circuit<br />

breaker)<br />

6. MSC & RLA are measured as the compressor only test<br />

condition.<br />

7. MSC values<br />

Min.: 198<br />

Max.: 264<br />

Min : 352<br />

Maxi :457<br />

7.50 13.50 24.00 6.00 0.10 0.51<br />

11.25 20.25 35.00 9.00 0.13 0.70<br />

13.75 24.75 62.00 11.00 0.13 0.70<br />

20.88 37.58 82.00 16.70 0.13 0.70<br />

9.13 15.63 47.00 6.50 0.16 1.00<br />

12.77 22.07 63.00 9.30 0.25 1.14<br />

13.14 22.74 74.00 9.60 0.25 1.14<br />

8. RLA is measured during each individual compressor test<br />

condition.<br />

9. OFM is measured as the outdoor unit test condition<br />

(Exam<strong>pl</strong>e) Selection <strong>of</strong> proper circuit breaker<br />

① Model : AUUH126D[UU12 ULD]<br />

- Rated running current : 6.0A (refer to spec. sheet)<br />

② MCA = (1.25 x Load1) + Load2 + Load3<br />

= (1.25 x 6.0) + 0 + 0 = 7.5A<br />

③ MOP = (2.25 x Load1) + Load2 + Load3<br />

= (2.25 x 6.0) + 0 + 0 = 13.5A<br />

→ Finally select circuit breaker 15A (Min. circuit breaker is 15A)<br />

MCA : Minimum Circuit Amperes (A)<br />

MOP : Maximum rating over current protective device<br />

MSC : Maximum Starting Current<br />

RLA : Rated Load Amperes (A)<br />

OFM : Outdoor Fan Motor<br />

kW : Fan Motor rated output (kW)<br />

FLA : Full Load Amperes (A)<br />

284 Outdoor unit - Non inverter Single A (1Ø, 3Ø)


5CSL0-06B Field wiring diagrams<br />

2.3.11 Field wiring diagrams<br />

1. All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

2. Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the current as required by the air conditioner.<br />

3. Feed the power source to the unit via a distribution switch board designed for this purpose.<br />

4. The terminal screws inside the control box may be loose due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can overload and damage electrical components.)<br />

5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.<br />

L N<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

L<br />

Circuit breaker<br />

Fuse<br />

Power cable 3/5 core 2.5/3.5mm 2<br />

(Including earth)<br />

N<br />

G<br />

(1 PHASE)<br />

1(L) 2(N) 3<br />

Terminal block indoor<br />

Outdoor unit<br />

Terminal Block outdoor<br />

1(L) 2(N) 1(L) 2(N) 3<br />

Transmission line<br />

R S T N<br />

Circuit breaker<br />

Fuse<br />

Power sup<strong>pl</strong>y<br />

Main switch<br />

Power cable 5 core x 2.5mm 2<br />

(Including earth)<br />

Notes:<br />

. All wirings, components and materials to be procured on the site should be according to the standard<br />

. Use copper conductor only<br />

. Install circuit breaker for safety<br />

. Unit should be grounded in com<strong>pl</strong>iance with the ap<strong>pl</strong>icable local and national codes<br />

. Wiring cable size must com<strong>pl</strong>y with the ap<strong>pl</strong>icable local and national code.<br />

Outdoor unit<br />

Outdoor unit - Non inverter Single A (1Ø, 3Ø) 285<br />

R S<br />

T N<br />

(3 PHASE)<br />

Terminal Block outdoor<br />

R S T N 1(L) 2(N) 3 4 5<br />

1(L) 2(N) 3<br />

Terminal b lock indoor<br />

Transmission<br />

cable


Sound levels<br />

2.3.12 Sound levels<br />

Overall<br />

Sound Pressure Level (dB re 20μPa)<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

1m<br />

Sound Pressure Level<br />

Sound Pressure Level (dB re 20μPa)<br />

20<br />

NC-25<br />

NC-20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

Microphone<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

1m<br />

Sound Pressure Level (dB re 20μPa)<br />

Sound Pressure Level (dB re 20μPa)<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

Notes:<br />

- Sound measured at 1m away from the center <strong>of</strong> the unit.<br />

- Data is valid at free field condition.<br />

- Data is valid at nominal operation condition.<br />

- Reference accoustic pressure 0dB=20μPa<br />

- Sound level will vary depending on a range <strong>of</strong> factors such as<br />

the construction(acoustic absorption coefficient) <strong>of</strong> particular<br />

room in which the equipment is installed.<br />

- The operating conditions are assumed to be standard.<br />

AUUH126D [UU12 ULD] AUUH186D [UU18 UED] AUUH246D[UU24 UED]<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

5CSL0-06B<br />

286 Outdoor unit - Non inverter Single A (1Ø, 3Ø)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

Sound Pressure Level (dB re 20 Pa)<br />

Sound Pressure Level (dB re 20μPa)<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

NC-15<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

AUUH306D[UU30 UED] AUUH368D[UU37 UED] AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Approximate<br />

Hearing<br />

Threshold<br />

63 125 250 500 1000 2000 4000 8000<br />

Octave Band Center Frequency (Hz)<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20<br />

NC-15<br />

NC-70<br />

NC-65<br />

NC-60<br />

NC-55<br />

NC-50<br />

NC-45<br />

NC-40<br />

NC-35<br />

NC-30<br />

NC-25<br />

NC-20


Part 3 Design and installation<br />

1. General installation guideline ............................................................288<br />

1.1 Installation process & Guideline .......................................................................288<br />

1.2 Checking the drawing ........................................................................................289<br />

2. Guideline for each installation process ............................................290<br />

2.1 Sleeve and inserting work..................................................................................290<br />

2.2 Refrigerant piping work......................................................................................292<br />

2.3 Drain piping work ..............................................................................................298<br />

2.4 Insulation work...................................................................................................304<br />

2.5 Electrical work....................................................................................................307<br />

2.6 Air tight test........................................................................................................310<br />

2.7 Vacuum drying works.........................................................................................312<br />

2.8 Additional charge <strong>of</strong> refrigerant..........................................................................316<br />

2.9 Trail test run operation .......................................................................................317<br />

3. Installation <strong>of</strong> indoor unit ..................................................................318<br />

3.1 Safety precautions .............................................................................................318<br />

3.2 Ceiling cassette 4-way.......................................................................................322<br />

3.3 Ceiling and floor, Ceiling suspended only..........................................................330<br />

3.4 Ceiling concealed duct - High static pressure....................................................341<br />

3.5 Console (Floor stand) ........................................................................................347<br />

4. Installation <strong>of</strong> outdoor Unit ...............................................................355<br />

4.1 Safety precautions .............................................................................................355<br />

4.2 Introduction ........................................................................................................359<br />

4.3 Foundation.........................................................................................................360<br />

4.4 Settlement <strong>of</strong> the outdoor unit............................................................................362<br />

4.5 Selection <strong>of</strong> the best location.............................................................................362<br />

4.6 Clearance space................................................................................................364<br />

4.7 Outdoor unit piping ............................................................................................367<br />

4.8 Outdoor unit installation requirments .................................................................368<br />

4.9 Outdoor unit cabin .............................................................................................372<br />

Design and installation 287


Installation process & Guideline 5CSL0-06B<br />

1. General installation guideline<br />

1.1 Installation process & Guideline<br />

Striking a balance between system installation & general construction work.<br />

Construction work Air conditioning work<br />

Fitting <strong>of</strong> steel sleeves<br />

Moulding box and<br />

reinforcement work<br />

Preparation <strong>of</strong><br />

contract drawing<br />

Sleeve and insert work<br />

Removal moulding boxes Installation <strong>of</strong> indoor unit<br />

Ceiling preparations<br />

Building ro<strong>of</strong>top<br />

Refrigerant piping work<br />

Drain piping work<br />

Duct work<br />

Insulation work<br />

Electrical work<br />

Outdoor unit foundation work<br />

Installation <strong>of</strong> outdoor unit<br />

Air tight test<br />

Vacuum drying<br />

Additional charge <strong>of</strong> refrigerant<br />

Fit decoration panels<br />

Cleaning inside and outside Test run<br />

Energization<br />

Setting sleeve and insert work details<br />

T.A.B and final report<br />

Transfer to customer with<br />

ex<strong>pl</strong>anation<br />

1. The division <strong>of</strong> the work should be thoroughly clarified.<br />

2. keep a constant check on the progress <strong>of</strong> the construction work to avoid deviations from the air conditioning<br />

work schedule.<br />

288 General installation guideline


5CSL0-06B<br />

1.2 Checking the drawing<br />

Installation procedure Remarks<br />

Determination <strong>of</strong> work scope<br />

Preparation <strong>of</strong> contract drawings<br />

Sleeve and insert works<br />

Installation <strong>of</strong> indoor units<br />

Refrigerant piping works<br />

Drain pipe works<br />

Duct works<br />

Insulation works<br />

Electrical work<br />

Outdoor unit foundation works<br />

Installation <strong>of</strong> outdoor units<br />

Air tight test<br />

Vacuum drying<br />

Additional charge <strong>of</strong> refrigerant<br />

Fit decoration panels<br />

Test run<br />

Transfer to customer with ex<strong>pl</strong>anation<br />

Checking the drawing<br />

Check and confirm required loads calculation,<br />

model selection, drawings etc.<br />

Make a relationship between outdoor ,indoor<br />

controller and option connection clear.<br />

(prepare control circuit diagram)<br />

Determine sleeve position, size and<br />

counts as required<br />

Check model name to make sure the fitting is<br />

made correctly<br />

Special attention to dryness , cleanness and<br />

tightness<br />

Make sure that the drain pipe diameter is<br />

big enough and adjust it to downward gradient<br />

Make sure airflow is sufficient<br />

Make sure no gap is left where the<br />

insulating materials are joined<br />

Multi<strong>pl</strong>e core cable must not be used<br />

(suitable cable should be selected)<br />

The foundation must be vibration pro<strong>of</strong> and<br />

in level<br />

Avoid airflow short circuit and ensure<br />

sufficient space is allowed for servicing<br />

For 24 hours at 3.8MPa(R410a) or 2.8MPa(R22)<br />

there must be no drop in pressure<br />

Less than 5 Torr (At least more than 1hr)<br />

Charge the refrigerant accurately by using a<br />

charging cylinder<br />

Make sure there are no gaps left between<br />

facing materials used on the ceiling<br />

Follow the testing operation check sheet<br />

Ex<strong>pl</strong>ain to customer or operator the manual<br />

etc<br />

General installation guideline 289


Sleeve and insert work 5CSL0-06B<br />

2. Guideline for each installation process<br />

2.1 Sleeve and insert work<br />

2.1.1 Positioning <strong>of</strong> the pipe holes<br />

1. The through holes for the drain piping should be positioned<br />

such that pipes have a downward gradient (the<br />

gradient must be at least 1/100.The thickness <strong>of</strong> the insulating<br />

materials must also be taken into consideration.)<br />

2. The diameter <strong>of</strong> the through holes for the refrigerant piping<br />

should include an allowance for the thickness <strong>of</strong> the<br />

heat insulation materials.<br />

3. Attention should be paid to the construction <strong>of</strong> the beam<br />

themselves since there are sometimes parts <strong>of</strong> the beam<br />

which cannot be used to accommodate through holes.<br />

2.1.2 Selection <strong>of</strong> sleeve<br />

1. Sleeve work should be performed to make a space for<br />

passing pipe and wire through the wall or ground under<br />

construction.<br />

For exam<strong>pl</strong>e if gas pipe and liquid pipe is 12.7mm , 6.35mm<br />

the sleeve diameter is minimum 79.05mm .<br />

Gas pipe diameter 12.7mm<br />

Liquid pipe diameter 6.35mm<br />

Insulation thickness(gas pipe) 10mm x 2<br />

Insulation thickness(liquid pipe) 10mm x 2<br />

20mm sur<strong>pl</strong>us 20mm<br />

Total sleeve diameter 79.05mm<br />

* Assumption : Gas pipe insulation thickness and liquid pipe<br />

insulation thickness is 10mm and 10mm respectively<br />

2.1.3 Sleeve type<br />

NOTE<br />

Pipe<br />

Sleeve<br />

Insulation<br />

Sleeve type should be considered as per local regulation &<br />

laws.<br />

NOTE<br />

CAUTION<br />

1. In high voltage generation <strong>pl</strong>aces, water-pro<strong>of</strong> flexible<br />

conduit should be used. (in substation room, in elevator<br />

room)<br />

2. Conduit should be chosen in accordance with electrical<br />

installation regulation.<br />

Cable conduit should be considered under the local regulation<br />

& laws.<br />

2.1.4 Insert work and support work<br />

An insert is a metal tool which is inserted into a floor or<br />

beam before the concrete is set such that fittings such as<br />

duct , pipes or suspension bolts for hanging units can be fitted<br />

into the <strong>pl</strong>ace later. The positioning <strong>of</strong> the inserts must<br />

be decided early.<br />

1. Insert work<br />

Exam<strong>pl</strong>e : Through holes in a reinforced concrete beam<br />

Molding box<br />

290 Guideline for each installation process<br />

Embedding<br />

depth h<br />

Polyblock<br />

Nail securing<br />

molding box<br />

Suspension bolt


5CSL0-06B<br />

2. Support work.<br />

Insulated U-bolt type supporting<br />

Bolt<br />

Saddle supporting<br />

CAUTION<br />

1.5t<br />

<strong>pl</strong>ate<br />

a) Supporting with insulated pipe<br />

Foam<br />

resin<br />

Sleeve and insert work<br />

Guideline for each installation process 291<br />

PVC<br />

PVC<br />

U-bolt supporting 0-ring band supporting<br />

To prevent<br />

Insulation from<br />

pressing, and<br />

lagging, cover<br />

can be used.<br />

Sheathing<br />

pipe<br />

Supporting interval 1.5~2.0m<br />

Insulated O-ring band type supporting<br />

During saddle supporting work, insulation should not be pressed by saddle as this can lead to tearing <strong>of</strong> insulation and<br />

thus falling <strong>of</strong> condensed water during product operation.<br />

B) Down stopper supporting<br />

Hexagonal nut<br />

One point supporter (200kg)<br />

O-ring band<br />

Plate nut<br />

Welding<br />

Down stopper<br />

O-ring<br />

band<br />

lags<br />

Insulated<br />

Supporting band<br />

Sheathing<br />

pipe<br />

Bolt<br />

Welding<br />

Insulated<br />

Supporting band<br />

Refrigerant pipe


Refrigerant piping work 5CSL0-06B<br />

2.2 Refrigerant piping work<br />

2.2.1 Flaring work<br />

NOTE<br />

CAUTION<br />

Flare connection and procedure<br />

1. Stiffened pipe must always be annealed at least once<br />

prior to the flaring work.<br />

A<br />

2. A pipe cutter must be used to cut the pipe.<br />

(A large pipe cutter must be used where<br />

the pipe has a large diameter. When cutting<br />

a pipe which is too big for the pipe cutter a<br />

metal saw may be used but care must be<br />

taken to ensure that the debris from sawing<br />

does not get into the pipe.)<br />

D<br />

CAUTION<br />

Choice <strong>of</strong> material for refrigerant piping<br />

Copper pipe selection<br />

a. The wall thickness <strong>of</strong> the refrigerant piping should com<strong>pl</strong>y with relevant local and national regulation for<br />

R410A the design pressure is 3.8MPa.(38.7kgf/cm2 )<br />

b. If not, we recommend to use with phosphorus deoxidized copper type<br />

c. Generally used copper pipe specifications as follows;<br />

Size(ø)mm<br />

Torque<br />

kg·f.m R22<br />

Thickness<br />

R410A<br />

6.35 1.80~2.50 0.7 0.8<br />

9.52 3.40~4.20 0.8 0.8<br />

12.70 5.50~6.60 0.8 0.8<br />

15.88 6.30~8.20 1.0 1.0<br />

19.05 9.90~12.1 1.0 1.0<br />

* Never use the pipe which is mixed scrap or a pipe used somewhere else<br />

The method how to distinguish the pipe mixed scarp : check the oxidization evidence after leaving the pipe for 24hour.<br />

External diameter <strong>of</strong> pipe D<br />

(in) (mm)<br />

1. Burrs should be carefully removed.<br />

2. 2 spanners should be used to grip the pipe.<br />

3. The flare nut must be inserted before starting the flaring operation.<br />

4. The appropriate amount <strong>of</strong> torque should be used to tighten the flare nut.<br />

5. Check that there is no superficial damage to the surface <strong>of</strong> the flare.<br />

H<br />

3. Set the flaring tool to make sure the flare size remains<br />

within the prescribed limits.<br />

4. Coat the inner and outer surface <strong>of</strong> the<br />

flare with refrigerator oil (Ester or ether<br />

oil).<br />

(this ensures that the flare nut passes<br />

smoothly, preventing the pipe Oil<br />

Oil<br />

from twisting.)<br />

Do not use SUNISO-4GS oil.<br />

Pipe widening dimension A<br />

(mm)<br />

Required flare height H<br />

(mm)<br />

1/4 6.35 8.6~9.0 1.1~1.3<br />

3/8 9.52 12.6~13.0 1.5~1.7<br />

1/2 12.7 15.8~16.2 1.6~1.8<br />

5/8 15.88 19.0~19.4 1.6~1.8<br />

3/4 19.05 22.9~23.3 1.9~2.1<br />

292 Guideline for each installation process


5CSL0-06B Refrigerant piping work<br />

2.2.2 Pipe connection and flaring works<br />

NOTE<br />

1. After installation com<strong>pl</strong>etion make sure to open the<br />

valve. operating the unit with the valve shut <strong>of</strong>f will<br />

destroy the compressor (Refer to the Additional<br />

refrigerant charge detail information)<br />

2. Use R410A to add refrigerant. All field piping must be<br />

installed by a licensed refrigeration technician<br />

3. Must com<strong>pl</strong>y with local and national standard<br />

regulations.<br />

1) Connecting the piping to the indoor unit<br />

and drain hose to drain pipe<br />

① Align the center <strong>of</strong> the piping and sufficiently tighten the<br />

flare nut by hand.<br />

② Tighten the flare nut with a wrench. Wrap the insulation<br />

material around the connecting portion.<br />

Outside diameter(Ø) Torque<br />

mm inch kg.f.m<br />

6.35 1/4 1.80~2.50<br />

9.52 3/8 3.40~4.20<br />

12.7 1/2 5.50~6.60<br />

15.88 5/8 6.30~8.20<br />

19.05 3/4 9.90~12.1<br />

2) Wrap the insulation material around the<br />

connecting portion.<br />

① Overlap the connection pipe insulation material and the<br />

indoor unit pipe insulation material. Bind them together<br />

with vinyl tape so that there is no gap.<br />

② Wrap the area which accommodates the rear piping<br />

housing section with vinyl tape.<br />

③ When the piping is passed through a tray, duct work or a<br />

sleeve the insulation wrapping on the pipe is not required.<br />

3) Close up a socket out <strong>of</strong> use with a brass cap.<br />

① Align the center <strong>of</strong> the piping and sufficiently tighten the<br />

brass cap by hand.<br />

② Tighten the brass cap with a wrench.<br />

③ Wrap the area contacted with insulation.<br />

Indoor unit tubing Flare nut Pipes<br />

2.2.3. SVC valve fitting<br />

Cautions on handling SVC valve<br />

• The figure below shows the name <strong>of</strong> each part required in<br />

handling SVC valve. At the time <strong>of</strong> shipment, SVC valve<br />

is closed.<br />

• If only a torque wrench is used to loosen or tighten the<br />

flare nut, the side <strong>pl</strong>ate may be distorted. Make sure to fix<br />

SVC valve with a spanner, then loosen or tighten the flare<br />

nut with a torque wrench.<br />

• When it is expected that the operating pressure will be<br />

low (for exam<strong>pl</strong>e, when cooling will be performed while<br />

the outside air tem-perature is low), seal sufficiently the<br />

flare nut in SVC valve on the gas line with silicon sealant<br />

to prevent freezing.<br />

[Valve operation method]<br />

Prepare hexagon wrenches (whose size is 4 mm).<br />

How to open the stop valve<br />

1. Insert a hexagon wrench into the valve stem, and turn<br />

the valve stem counterclockwise.<br />

2. When the valve stem cannot be turned any more, stop<br />

turning. Now, the valve is open.<br />

Guideline for each installation process 293<br />

Wrench<br />

Indoor unit tubing<br />

Connection pipe<br />

Open-end wrench (fixed)<br />

Flare nut<br />

Vinyl tape(narrow)<br />

Connection pipe<br />

Vinyl tape (wide) Wrap with vinyl tape<br />

Connecting cable<br />

90°±2°<br />

45°±2°<br />

Flare shape<br />

Indoor unit pipe<br />

Pipe<br />

R0.4~0.8mm


Refrigerant piping work 5CSL0-06B<br />

How to close the stop valve<br />

1. Insert a hexagon wrench into the valve stem, and turn the<br />

valve stem clockwise.<br />

2. When the valve stem cannot be turned any more, stop<br />

turning. Now, the valve is closed.<br />

Service port<br />

Valve stem<br />

Valve cap<br />

Field piping<br />

connection part<br />

Silicon sealant<br />

(Take care not to generate cavity.)<br />

Opening direction Opening direction<br />

<br />

Cautions on handling the valve cap<br />

• The valve is sealed in the arrow area. Take care not to<br />

damage the arrow area.<br />

Valve cap<br />

SVC valve<br />

(valve cap attachment area)<br />

• After handling the valve, make sure to tighten the valve<br />

cap securely.<br />

Liquid line Gas line<br />

3.4~4.2 m-kgf 6.3~8.2 m-kgf<br />

Cautions on handling the service port<br />

• Use charge hose equipped with push in the work.<br />

• After the work, make sure to tighten the valve cap securely.<br />

Tightening torque.....8.5~10.3 ft·lbf<br />

Do not ap<strong>pl</strong>y any force to the valve cap<br />

Using a spanner on the valve cap and the valve body could<br />

cause a refrigerant leak.<br />

Oil Trap<br />

• Necessity <strong>of</strong> trap<br />

Since there is fear <strong>of</strong> the oil held inside the riser piping<br />

flowing back into the compressor when stopped and causing<br />

liquid compression phenomenon, or cases <strong>of</strong> deterioration<br />

<strong>of</strong> oil return, it will be necessary to provide a trap at an<br />

appropriate <strong>pl</strong>ace in the riser gas piping.<br />

• Trap installation spacing<br />

NOTE<br />

Spanner<br />

prohibition to<br />

valve cap and<br />

body part<br />

SVC valve <strong>of</strong> two<br />

hands method<br />

SVC valve <strong>of</strong> one<br />

hands method<br />

294 Guideline for each installation process<br />

Spanner<br />

Torque<br />

wrench<br />

Torque<br />

wrench<br />

A trap is not necessary when the outdoor unit is installed<br />

in a higher position than the indoor unit.


5CSL0-06B<br />

2.2.4 Brazing work<br />

CAUTION<br />

Brazing <strong>of</strong> refrigerant piping :<br />

The following precaution should be taken.<br />

1. Do not use flux when brazing copper to copper<br />

refrigerant piping.<br />

(Particularly for the HFC refrigerant piping)<br />

Therefore, use the phosphor copper brazing filler metal<br />

(BCuP) which does not require flux.<br />

(Flux has extremely harmful influence on refrigerant piping<br />

systems. For instance, if the chlorine based flux is<br />

used, it will cause pipe corrosion or, in particular, if the<br />

flux contains fluorine, it will damage the refrigerant oil.)<br />

1. Niorogen flushing method (During brazing)<br />

CAUTION<br />

Taping<br />

Brazing section<br />

Copper pipe 1/4<br />

Packless<br />

valve<br />

Outdoor unit<br />

High<br />

pressure hose<br />

Pipe<br />

Packless<br />

valve<br />

Pressure regulator<br />

Nitrogen cylinder<br />

Hose<br />

Pressure<br />

regulator<br />

Nitrogen cylinder<br />

Nitrogen Brazing<br />

a. This procedure is designed to prevent formation <strong>of</strong><br />

oxidation film by filling piping with inert gas. Note that<br />

excessive gas pressure will generate pinholes at<br />

brazed points. (Nitrogen gas: Sup<strong>pl</strong>y pressure<br />

0.05~0.1kg/cm 2 G)<br />

b. When sup<strong>pl</strong>ying inert gas, be sure to open one end <strong>of</strong><br />

piping.<br />

CAUTION<br />

Refrigerant piping work<br />

If brazing work is carried out without passing nitrogen gas<br />

through the pipes then it allows the formation <strong>of</strong><br />

oxidation bubbles on the inside surface <strong>of</strong> the pipes.<br />

These oxidation bubbles are then carried along inside the<br />

pipes to cause damage to various members <strong>of</strong> the system<br />

such as valve or compressors and the system ceases to<br />

function properly.<br />

In order to avoid this problem nitrogen is passed through<br />

the pipe while the soldering work is being carried out.<br />

This operation work is known as nitrogen<br />

re<strong>pl</strong>acement.(Air is re<strong>pl</strong>aced by nitrogen)<br />

This is standard work during all brazing works.<br />

CAUTION<br />

Water enters Plaster enters<br />

Make sure to keep the connecting piping dry (away<br />

from water) , clean (away from dust) , and air tight<br />

(avoid refrigerant leakage)<br />

Pipe bending<br />

Annealed copper pipe with small diameter (Ø6.35 or<br />

Ø9.52) can be easily bent manually. In this case, secure<br />

large R (radius) for the bend section and gradually bend<br />

pipe. If annealed copper pipe is large in diameter<br />

(Ø15.88 or over), bend pipe with bender. Use bender<br />

appropriate for the pipe diameter.<br />

(Direction <strong>of</strong> Nitrogen gas.)<br />

Nitrogen Brazing<br />

Guideline for each installation process 295<br />

N2


Refrigerant piping work 5CSL0-06B<br />

Brazing work should be carried out either downwards or sideways.<br />

An upward direction should be avoided wherever possible(to prevent leakage).<br />

Piping size<br />

6.35<br />

9.52<br />

12.7<br />

15.9<br />

19.1<br />

22.2<br />

25.4<br />

31.8<br />

38.1<br />

44.5<br />

CAUTION<br />

Table 1: Correlation <strong>of</strong> nozzle tip and size <strong>of</strong> refrigeration piping<br />

# 200<br />

over 10mm<br />

(Expending pipe brazing)<br />

(Flare part brazing)<br />

N2<br />

N2<br />

over 10mm<br />

(Pipe brazing with socket)<br />

(Butt-brazing)<br />

Nozzle tip No. Brazing filler diameter Ø<br />

# 225 # 250 # 315 # 400 # 450 # 500 1.6 2.4 3.2<br />

1. Generally expending pipe brazing is performed with pan-coil type copper pipe, and socket blazing is<br />

performed with straight copper pipe.<br />

2. Do not perform flare part brazing or butt-brazing.<br />

3. Brazing should be performed on welding table.<br />

4. Any dust should enter in the pipe while brazing.<br />

5. Distance <strong>of</strong> copper pipe support spacing is within 1~2m<br />

6. The copper pipe should not be secured directly by metal brackets.<br />

296 Guideline for each installation process<br />

N2<br />

N2


5CSL0-06B<br />

2.2.5 Refrigerant pipe flushing<br />

Flushing is a method <strong>of</strong> cleaning extraneous matter out <strong>of</strong> pipes using pressurized gas.<br />

NOTE<br />

Refrigerant pipe flushing <strong>of</strong> 3 major effects<br />

1. Removal <strong>of</strong> oxidation bubbles formed inside copper pipes when “nitrogen re<strong>pl</strong>acement is insufficient”<br />

during soldering work<br />

2. Removal <strong>of</strong> extraneous material and moisture from pipes when covering has been insufficient<br />

3. Checks connections in pipes linking outdoor and indoor units (Both liquid and gas pipes)<br />

① Set pressure regulator on nitrogen cylinder.<br />

② Connect the charge hose from pressure regulator to<br />

service port on the liquid pipe side <strong>of</strong> the outdoor unit<br />

before its connection to BD unit or indoor unit.<br />

③ Open the main valve on the nitrogen cylinder and set<br />

the pressure regulator to 0.5MPa.<br />

④ Ensure that nitrogen is flowing through the pipe properly.<br />

⑤ For flushing block the end <strong>of</strong> the pipe with wood insulation<br />

block.<br />

⑥ When the pressure becomes great remove the block<br />

quickly.<br />

⑦ Do step 6 & 7 repeatedly till cleanness is ensured.<br />

⑧ Connect the charge hose from pressure regulator to<br />

service port on the gas pipe side <strong>of</strong> outdoor unit before<br />

its connection to BD unit or indoor unit.<br />

⑨ Flow the steps 3, 4, 5, 6, 7.<br />

⑩ In case <strong>of</strong> BD unit system, before connecting to indoor<br />

units, each pipe should be flushed individually.<br />

⑪ Flow the steps 3, 4, 5, 6, 7.<br />

CAUTION<br />

After welding the pipe, nitrogen flushing is strongly<br />

recommended.<br />

Nitrogen<br />

Nitrogen<br />

Primary<br />

side<br />

Nitrogen<br />

Pressure regulator<br />

Gas pressure <strong>of</strong> 0.5 MPa<br />

Refrigerant piping work<br />

Guideline for each installation process 297<br />

Lo Hi<br />

Lo Hi<br />

Wood Insulation<br />

Lo Hi<br />

Secondary<br />

side 0.5 MPa<br />

Taping


Drain piping work 5CSL0-06B<br />

2.3 Drain piping work<br />

The purpose <strong>of</strong> drain piping is to prevent damage <strong>of</strong> products and ceiling materials by proper draining <strong>of</strong> dew condensation<br />

which is generated from the evaporator <strong>of</strong> indoor unit when the hot vapors come in contact with the evaporator.<br />

1. Ap<strong>pl</strong>ication<br />

Pipes for draining water generated from indoor unit on cooling operation<br />

Specification for drain piping<br />

Single A<br />

Type<br />

Cassette 4 way<br />

Duct<br />

Ceiling and floor<br />

Suspended only<br />

[Reference Table] Drain amount per capacity<br />

kW<br />

2.04<br />

2.33<br />

2.91<br />

4.36<br />

5.82<br />

7.28<br />

8.73<br />

10.2<br />

11.6<br />

14.6<br />

Air flow rate<br />

(CMH)<br />

8<br />

8.5<br />

10.5<br />

11.5<br />

17<br />

19<br />

21<br />

23<br />

25<br />

34<br />

Drain pipe<br />

diameter<br />

(External/<br />

Internal)<br />

Ø32/25mm<br />

Ø32/25mm<br />

-<br />

Drain<br />

pump<br />

Standard<br />

Accessory<br />

Remark<br />

400 (0.4)<br />

Indoor temp. : 26C DB<br />

Indoor humidity RH : 85%<br />

Outlet temp. :14C DB<br />

Outlet temp. RH: 50%<br />

298 Guideline for each installation process<br />

-<br />

Drain pump<br />

discharge<br />

head (mm)<br />

700<br />

700<br />

- -<br />

-<br />

-<br />

Drain amount<br />

(lpm)<br />

0.128<br />

0.137<br />

0.169<br />

0.185<br />

0.273<br />

0.305<br />

0.337<br />

0.369<br />

0.402<br />

0.546<br />

-<br />

Drain amount<br />

(at 10mm height)<br />

cm 3/min (lpm)<br />

400 (0.4)<br />

-


5CSL0-06B<br />

2.3.1 Drain pipe slope and support<br />

Drain piping work<br />

• Slope gradient for drain should be (1/50~1/100mm) and PVC pipes should be used.<br />

• Support hanger should be at 1~1.5m interval to prevent from loosing and dropping.<br />

• Drain pipe insulation<br />

: The inside temperature <strong>of</strong> drain pipe is about 10°C. When high temperature and humidity air touches the surface <strong>of</strong><br />

pipe, dew condensation occurs. To prevent that, drain pipe keeps warm using insulation with polyethylene 10mm<br />

thickness.<br />

Indoor unit<br />

Or<br />

Drain pan<br />

1. Ap<strong>pl</strong>ication<br />

Refrigerant pipe length contracts and expands on heating and cooling repeatedly. So supporting work is needed not to<br />

hinder each copper pipe connection part.<br />

2. Supporting distance for common drain pipe<br />

[Table]The interval <strong>of</strong> the supporting hanger for drainage pipe<br />

Gradient <strong>of</strong> at least 1 / 50 ~ 1 / 100<br />

Pipe diameter<br />

(mm) Ø20~40 Ø40~50 Ø65~125<br />

Max. interval(m) Below 1.0 Below 1.2 Below 1.5<br />

3. Anchor bolt supporting work<br />

Anchor bolt supporting work should be used for supporting a heavy indoor unit to ceiling.<br />

Clamp hanger supporting work is for hanging refrigerant pipe, drain pipe and cables.<br />

It can prevent vibrating noise from passing through pipe.<br />

We recommend set anchor bolt for supporting indoor unit and strong anchor bolt for supporting pipes and cables<br />

Guideline for each installation process 299


Drain piping work 5CSL0-06B<br />

2.3.2 Drain pipe trap (only for high static duct)<br />

A ≥ 50mm<br />

SP = External Pressure<br />

(mmAq)<br />

Ex) External Pressure<br />

= 10mmAq<br />

A<br />

A ≥ 50mm<br />

B ≥ 50mm<br />

<br />

Indoor unit<br />

Plug<br />

U-Trap<br />

- In case <strong>of</strong> duct high static pressure, the U trap maintains a positive pressure on the indoor side <strong>of</strong> the unit.<br />

Models with drain pump:<br />

Models without drain pump<br />

Max. 700<br />

Polyethylene insulation 10t<br />

PVC drain pipe<br />

300mm or less<br />

PVC elbow<br />

Drain pump<br />

PVC<br />

Flexible hose<br />

[Unit : mm]<br />

Metal clamp<br />

Flexible drain hose<br />

Drain pan Thermal insulation(bend area)<br />

300 Guideline for each installation process<br />

B<br />

Common drain pipe<br />

Thermal insulation (drain pipe area)


5CSL0-06B<br />

2.3.3 Grouped drain pipes<br />

NOTE<br />

It is standard work practice to make connections to the main pipe from above.<br />

The pipe down from the combination should be as large as possible.<br />

The diameter <strong>of</strong> ventilation pipe should be same or larger than drain pipe diameter.<br />

45~60°<br />

45~60°<br />

45~60°<br />

Grouped drain piping standard<br />

slope 1/50 ~ 1/100<br />

45~60° angle connection against overflow<br />

Sharing horizontal pipe<br />

700mm<br />

maxinmum<br />

Common drain pipe<br />

Trap in the end<br />

Drain piping work<br />

Face the vent pipe mouth<br />

downward to keep foreign matter<br />

from penentrating the system<br />

1. Trap is required if the pie is open towards sewage to prevent bad smell from coming to indoor.<br />

2. Do not connect drain pipe with building common drain pipe in heavy snow area. It might block the pipe with ice and<br />

remaining collected water can get back to indoor unit.<br />

Provide seperate air conditioner drain pipe.<br />

- For drain pipe diameter selection, refer to the following table.<br />

- The drainpipe should be used for only air conditioners. If you share it for rainwater drain, you should be careful <strong>of</strong> a<br />

back flow, leakage, bad odor and so on.<br />

- Use separate drain pipe for polluted water or wasted water<br />

NOTE<br />

Sum <strong>of</strong> the capacity<br />

<strong>of</strong> indoor units (Btu/h)<br />

[Table] Drain pipe diameter selection standard<br />

~80,000 ~200,000 ~400,000 ~600,000 ~1000,000<br />

Internal diameter (External) 25(32) 32(40) 40(50) 50(60) 65(75)<br />

Select the diameter <strong>of</strong> the horizontal pipe bigger than vertical.<br />

Guideline for each installation process 301


Drain piping work 5CSL0-06B<br />

2.3.4 Caution for drain piping work<br />

Notice on drain working<br />

1. Drain pipe should be insulated all connected joints and ends.<br />

CAUTION<br />

Flexible tube should be connected with clamp concentrically.<br />

If not, water will leak from the connection.<br />

<br />

2. No reverse slope for drain connection<br />

Water flow<br />

<br />

Sh Sharp crook<br />

Sharp crook<br />

302 Guideline for each installation process


5CSL0-06B<br />

Drain pipe insulation<br />

- Drain pipe should be insulated all connected joints and ends.<br />

Insulation<br />

not required<br />

- Do not use the loose fitting insulation.<br />

Drain water leakage test<br />

- Water leakage test should be performed 24 hours later after drain work finishing.<br />

- In the test, only water should be used. Other liquids are unacceptable.<br />

2.3.5. Outdoor unit drain (recommendation)<br />

• Mild heating region : 2) South EU<br />

use drain hose recommended (drain hole diameter 20mm)<br />

• Intermediate heating : 1) central,3) central-east,5) east EU<br />

outdoor unit Drain pan(local) recommended.<br />

• Hard heating region : 4) North EU<br />

super extreme heat pump model<br />

Heating<br />

Index<br />

115<br />

100<br />

85<br />

Insulation<br />

required<br />

1) Central<br />

Loose fitting<br />

wrong insulation<br />

4) North<br />

3) Central-East<br />

2) South<br />

5) East<br />

Fitting insulation<br />

Drain piping work<br />

Region devided<br />

Heating index<br />

Guideline for each installation process 303


Insulation work 5CSL0-06B<br />

2.4 Insulation work<br />

2.4.1 Insulation<br />

1) Operational steps<br />

1 EPDM length should be more<br />

longer than pipe length.<br />

Do not extend EPDM by force.<br />

2) Bending vertical side <strong>of</strong> insulation<br />

1 Use the original uncut insulation<br />

material.<br />

2 Put the pipe in EPDM insulation 3 Bond on both side <strong>of</strong> cut surfaces 4 Dry it until it becomes thick, sticky<br />

carefully so that the pipe will not <strong>of</strong> move sure to use the correct type and does not get detached.<br />

get damaged with EPDM.<br />

<strong>of</strong> bond for EPDM cut surface<br />

attaching.<br />

2 Only in specialcase is the vertical 3 Bond both sides <strong>of</strong> the surface <strong>of</strong> 4 Dry it until it becomes thick and<br />

cutting <strong>of</strong> the insulation allowed. EPDM and press them together for<br />

long lasting bonding.<br />

sticky.<br />

3) ' L'<br />

Fitting connection part insulation<br />

1 All <strong>of</strong> the fitting connecting parts 2 Make fitting cover to fit the EPDM 3 Bond the both cutting sides <strong>of</strong><br />

should be insulated.<br />

insulation fitting cover should be fitting cover.<br />

Bring face to face the each end <strong>of</strong> overlapped with insulation min 1<br />

EPDM on fitting connection part. inch (2.5cm).<br />

304 Guideline for each installation process


5CSL0-06B<br />

2.4.2 Forming the piping<br />

Insulation work<br />

1) Form the piping by wrapping the connecting portion <strong>of</strong> the indoor unit with insulation material and secure<br />

it with two kinds <strong>of</strong> vinyl tape.<br />

• If you want to connect an additional drain hose, the end <strong>of</strong> the drain outlet should be routed above the ground. Secure the<br />

drain hose appropriately.<br />

2) In cases where the outdoor unit is installed below the indoor unit perform the following.<br />

① Tape the piping, drain hose and transmission cable from down to up.<br />

② Secure the tapped piping along the exterior wall using saddle or equivalent.<br />

The cable is required to prevent rain water<br />

from entering into electrical parts <strong>of</strong> outdoor unit.<br />

4 way pipe direction : select what you want<br />

to form pipe.<br />

Guideline for each installation process 305


Insulation work 5CSL0-06B<br />

2.4.3 Essential points <strong>of</strong> thermal insulation<br />

1) Thermal insulation <strong>of</strong> refrigerant piping<br />

Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness<br />

heat-resistant insulation materials, so that no gap is observed in the joint between indoor unit and insulating material, and<br />

insulating materials themselves. When insulation work is insufficient, there is a possibility <strong>of</strong> condensation drip, etc. pay special<br />

attention to insulation work to ceiling <strong>pl</strong>enum.<br />

Wrong<br />

method<br />

Correct<br />

method<br />

3) Insulation tube thickness<br />

① Thickness decision <strong>of</strong> insulation tube<br />

• Insulation material: EPDM or polyethylene foam<br />

• Thermal conductivity 0.035 kcal~0.040kcal/mh°C<br />

• Heat resistance=85°C(Cooling only) or more<br />

100°C(Heat pump) or over<br />

② The thickness <strong>of</strong> the thermal insulation material must be determined in the light <strong>of</strong> the pipe sizes.<br />

Pipe size Thickness <strong>of</strong> insulation material<br />

6.35 ~ 25.4 mm 10mm or more<br />

25.4 ~ 15mm<br />

③ It will be necessary to increase the thickness <strong>of</strong> insulation in the above table when conditions are hot and humid.<br />

④ Where a customer sup<strong>pl</strong>ies his own specifications then these must be adhered to.<br />

CAUTION<br />

• Do not insulate gas or low pressure pipe and liquid or high<br />

pressure pipe together .<br />

A<br />

B<br />

C<br />

C<br />

B<br />

C<br />

A<br />

A Liquid pipe<br />

B Gas pipe<br />

C Insulation<br />

A Liquid pipe<br />

B Gas pipe<br />

C Insulation<br />

• Be sure to fully insulate connecting portion.<br />

A These parts are not insulated.<br />

2) Caution during insulation work<br />

• In case the cables are installed in the conduit, a finishing tape is not required.<br />

• Defect and insufficient insulation can cause condensation drops.<br />

• Binding the insulation too tight may result in dew drops.<br />

• Be sure not to tie rap the insulation but put special taping or the clamp at the connecting portion.<br />

• The insulation overlapping part at the piping connection must be a distance from the flaring part at the pipe connection.<br />

Outdoor temperature and hummidity around the cooling piping might exceed 30°C and RH80%, reinforce the insulation<br />

on the cooling piping (at least 20mm thick)<br />

306 Guideline for each installation process<br />

A


5CSL0-06B Electrical work<br />

2.5 Electrical work<br />

2.5.1 Precautions<br />

CAUTION<br />

When knocking out knock holes<br />

• To punch a knock hole, hit on it with a hammer.<br />

• After knocking out the holes, we recommend you paint<br />

the edges and areas around the edges using paint to<br />

prevent rusting.<br />

• When passing electrical wiring through the knock holes,<br />

remove any burrs from the knock holes and wrap the<br />

wiring with protective tape to prevent damage.<br />

Use a conduit for the cable<br />

• Outside the unit, make sure the thin signal cable (i.e. for the<br />

remote control, between units, etc.) and the thick electric<br />

wiring do not pass near each other and use <strong>of</strong> the shield signal<br />

cable is recommended.<br />

Otherwise, the outdoor unit may be affected by electrical<br />

noise (external noise), and malfunction or fail.<br />

• Secure the wiring with the accessory clamps so that it does<br />

not touch the piping.<br />

• Make sure the wiring and the electric parts box cover do not<br />

stick up above the structure, and close the cover firmly.<br />

CAUTION<br />

Burr<br />

If there are any possibilities that<br />

small animals or insects enter the<br />

system through the knock holes,<br />

<strong>pl</strong>ug the holes with packing<br />

materials (to be prepared onsite).<br />

Do not operate the air conditioner until the refrigerant piping<br />

work is com<strong>pl</strong>eted.<br />

(Operating the air conditioner before the refrigerant piping<br />

work is com<strong>pl</strong>eted may damage the compressor.)<br />

• Install an earth leakage circuit breaker.<br />

Since this is a inverter air conditioner. In order to prevent<br />

malfunction <strong>of</strong> the earth leakage breaker itself, use a<br />

breaker resistant to higher harmonics.<br />

• After finishing the electric work, confirm that each electric<br />

part and terminal inside the electric parts box is connected<br />

securely.<br />

NOTE<br />

• Only pr<strong>of</strong>essional electricians having sufficient knowledge<br />

should perform the electrical wiring work.<br />

Perform the electrical wiring work in accordance with the<br />

electrical wiring diagram.<br />

Make sure to set OFF the branch switch and over current<br />

breaker before starting the work.<br />

• Install an earth leakage breaker.<br />

• Perform grounding to the indoor units and outdoor units.<br />

• Do not connect the ground wire to gas pipes, sewage<br />

pipes, lightning rods telephone ground wires.<br />

• Gas pipes ···· Can ex<strong>pl</strong>ode or catch fire if gas leaks.<br />

• Sewage pipes···· Provides no grounding effect if hard<br />

<strong>pl</strong>astic pipes are used.<br />

• Telephone ground wires and lightening rods ···· dangerous<br />

when struck by lightening due to abnormal rise in the<br />

ele trical potential in the ground.<br />

• Use only copper wires.<br />

• Make sure to shut down the power before starting the electric<br />

wiring work.<br />

Do not set ON any switch until the work is com<strong>pl</strong>eted.<br />

• The outdoor unit has an inverter compresser which generates<br />

noise and charges the outer casing with the leakag<br />

current. The outdoor unit should be grounded so that the<br />

effect <strong>of</strong> the generated noise on othe equipment can be<br />

reduced, and that the outer casing can be discharged.<br />

• Never install a phase advancing capacitor for power factor<br />

improvement.<br />

(Even if it is installed, the power factor is not improved. And<br />

if it is installed, the outdoor unit is abnormally overheated.)<br />

• Use specified electric wires in the wiring, and connect them<br />

securely.<br />

Fix them in such a way that external force is not ap<strong>pl</strong>ied at<br />

the terminals<br />

(transmission wiring in the local field and ground terminal).<br />

• Never push excessive electric wires into the units.<br />

• Protect electric wires with conduit tubes or other proper<br />

tubes so that they will not be damaged by edges <strong>of</strong> knock<br />

holes.<br />

• Do not use multi conductor cable which have more than 5<br />

wires in one core.<br />

Guideline for each installation process 307


Electrical work 5CSL0-06B<br />

2.5.2 Control wiring / power sup<strong>pl</strong>y<br />

1) All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

2) Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the<br />

current as required by the air conditioner.<br />

3) Feed the power source to the unit via a distribution<br />

switch board designed for this purpose.<br />

4) The terminal screws inside the control box may be loose<br />

due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can<br />

overload and damage electrical components.)<br />

5) Always ground the air conditioner with a grounding wire<br />

and connector to meet the LOCAL REGULATION.<br />

DC inverter Single A<br />

1Phase model<br />

Terminals on the indoor unit<br />

Terminals on the outdoor unit 1(L) 2(N) 1(L) 2(N) 3<br />

DC inverter Single A synchro<br />

Non inverter Single A<br />

1Phase heat pump model<br />

Terminals on the indoor unit<br />

Terminals on the outdoor unit 1(L) 2(N) 1(L) 2(N) 3<br />

POWER<br />

INPUT<br />

3Phase heat pump model.<br />

R S T N<br />

Power<br />

Input<br />

POWER<br />

INPUT<br />

Circuit breaker<br />

Circuit Break<br />

Power<br />

Input<br />

Terminal Block<br />

(Outdoor Unit)<br />

1(L) 2(N) 3<br />

1(L) 2(N) 3<br />

Terminal Block<br />

(Outdoor Unit)<br />

4 5<br />

1(L) 2(N) 3 4 5<br />

Terminal Block<br />

(Indoor Unit)<br />

1(L) 2(N) 3 4 5<br />

4 5<br />

308 Guideline for each installation process


5CSL0-06B<br />

Connecting the cable to Outdoor Unit<br />

Electrical work<br />

• Remove the side panel for wiring connection.<br />

• Use the cord clamp to fix the cord.<br />

• Earthing work<br />

- Case 1 :Terminal block <strong>of</strong> Outdoor Unit have mark.<br />

• Connect the cable <strong>of</strong> diameter 1.6mm2 or more to the earthing terminal provided in the control box and do earthing.<br />

- Case 2 :Terminal block <strong>of</strong> Outdoor Unit don't have mark.<br />

• Connect the cable <strong>of</strong> diameter 1.6mm2 or more, to the panel <strong>of</strong> control box, marked as and fasten with earth screw.<br />

❈ Please check !!<br />

CAUTION<br />

Connecting cable terminal<br />

Power cord terminal<br />

Cord clamp<br />

Cord clamp<br />

* Make sure the rubber bushes are<br />

Properly used in knock-out holes after<br />

connecting main Power cable<br />

• The circuit diagram is not subject to change without notice.<br />

• Be sure to connect wires according to the wiring diagram.<br />

• Connect the wires firmly, so that not to be pulled out easily.<br />

• Connect the wires according to color codes by referring the wiring diagram.<br />

Guideline for each installation process 309


Air tight test 5CSL0-06B<br />

2.6 Air tight test<br />

2.6.1 Air purging<br />

Air and moisture remaining in the refrigerant system have<br />

undesirable effects as indicated below.<br />

① Pressure in the system rises.<br />

② Operating current rises.<br />

③ Cooling (or heating) efficiency drops.<br />

④ Moisture in the refrigerant circuit may freeze and block<br />

capillary tubing.<br />

⑤ Water may lead to corrosion <strong>of</strong> parts in the refrigeration<br />

system. Therefore, the indoor/outdoor unit and connecting<br />

tube must be checked for leak tight, and vacuumed<br />

to remove incondensable gas and moisture in the system.<br />

Checking method<br />

1) Preparation<br />

• Check that each pipe (both liquid and gas side pipes)<br />

between the indoor and outdoor units have been properly<br />

connected and all wiring for the test run has been com<strong>pl</strong>eted.<br />

Remove the service valve caps from both the gas<br />

and the liquid side on the outdoor unit. Check that both the<br />

liquid and the gas side service valves on the outdoor unit<br />

are kept closed at this stage.<br />

2) Leakage test<br />

• Connect the manifold valve (with pressure gauges) and<br />

dry nitrogen gas cylinder to this service port with charge<br />

hoses.<br />

CAUTION<br />

Be sure to use a manifold valve for leakage test. If it is<br />

not available, use a stop valve for this purpose. The "Hi"<br />

knob <strong>of</strong> the manifold valve must always be kept close.<br />

Outdoor unit<br />

Gas Pipe pipe Pipe<br />

Liquid Pipe<br />

pipe<br />

Manifold gauge hose<br />

Manifold valve<br />

Pressure<br />

gauge<br />

Charge hose<br />

Nitrogen gas<br />

cylinder(in vertical<br />

standing position)<br />

Lo Hi<br />

CAUTION<br />

To avoid nitrogen entering the refrigerant system<br />

in a liquid state, the top <strong>of</strong> the cylinder must be higher<br />

than its bottom when you pressurize the system. Usually,<br />

the cylinder is used in a vertical standing position.<br />

1. Do a leakage test <strong>of</strong> all joints <strong>of</strong> the Tubing (both<br />

indoor and outdoor) and both gas and liquid side service<br />

valves. Bubbles indicate a leak. Be sure to wipe<br />

<strong>of</strong>f the soap with a clean cloth.<br />

2. After the system is found to be free <strong>of</strong> leaks, relieve the<br />

nitrogen pressure by loosening the charge hose connector<br />

at the nitrogen cylinder. When the system pressure<br />

is reduced to normal, disconnect the hose from<br />

the cylinder.<br />

2.6.2 Essential points <strong>of</strong> testing<br />

The key to successful testing is strict adherence to<br />

the following procedure:<br />

a) The liquid and gas piping in each refrigerant system<br />

should be pressurized in turn in accordance with the<br />

following steps. (Nitrogen gas must be Manifold used.) gauge<br />

Step 1: increase pressure to 0.3MPa<br />

for 3 minutes or more<br />

Step 1: increase pressure to 1.5MPa<br />

for 3 minutes or more<br />

Step 3: increase pressure to 3.8MPa<br />

for approxmate 24 hours<br />

Liquid Pipe<br />

Indicates existence<br />

<strong>of</strong> major leaks<br />

Indicates existence<br />

<strong>of</strong> major leaks<br />

310 Guideline for each installation process<br />

Gas Pipe<br />

Increasing the system pressure to 3.8MPa does not guarantee<br />

the identification <strong>of</strong> minor leaks if pressure is maintained<br />

for only a short time. It is therefore recommended<br />

that the system remain pressurized in accordance with<br />

Step 3 above for at least 24 hours.<br />

NOTE<br />

Piping should not be pressured more than 3.8MPa.<br />

b) Check for pressure drop<br />

If there is no drop in pressure then the test is deemed a<br />

success.<br />

If the pressure drops then the leak must be located. See<br />

following <strong>page</strong>.<br />

However, if there is a change in the ambient temperature<br />

between the pressurizing stage and the time when<br />

you check for a drop in pressure then you will have to<br />

adjust your calculations accordingly since a change <strong>of</strong><br />

1°C can account for a pressure change <strong>of</strong> approximately<br />

0.01MPa.<br />

Compensating adjustment value:<br />

(temperature at time <strong>of</strong> pressurizing – temperature at<br />

time <strong>of</strong> checking) × 0.01


5CSL0-06B<br />

Exam<strong>pl</strong>e:<br />

During <strong>of</strong> pressurizing: 3.8MPa 25˚C<br />

24 hours later: 3.75MPa 20˚C<br />

Although the gauge pressure is dropped from 3.8MPa to<br />

3.75MPa, it can be safely assumed that there is no leakage<br />

because the gauge pressure can also drop due to<br />

the change in outdoor temperature.<br />

(MPa)<br />

3.8<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

0.5<br />

0<br />

3 minutes<br />

5 minutes<br />

Step 3 3.8MPa x 24min<br />

Step 1 1.5MPa x 5min<br />

Step 1 0.3MPa x 3min<br />

Gas Pipe<br />

Outdoor Outdoor Outdoor temperature(℃)<br />

temperature(<br />

temperature(°C)<br />

24 hours<br />

Liquid Pipe<br />

2.6.3 Checking for leakage<br />

[Check 1] (Where pressure falls while carrying out Steps 1<br />

to 3 described on previous <strong>page</strong>)<br />

▶ Check by measure gage......gas detector.<br />

▶ Check by ear......Listen for the sound <strong>of</strong> a major leakage.<br />

▶ Check by hand......Check for leak by feeling around jointed<br />

sections with hand.<br />

▶ Bubble check ......Bubbles will reveal the presence <strong>of</strong> a<br />

leakage.<br />

[Check 2] (When searching for a minor leak or when there<br />

has been a fall in pressure while the system has<br />

been fully pressurized but the source <strong>of</strong> the leak<br />

cannot be traced.)<br />

1. Release the nitrogen until the pressure reaches 0.3MPa.<br />

2. Increase pressure to 1.5MPa using gaseous<br />

refrigerant(R410).<br />

3. Search for the source <strong>of</strong> the leakage using a leackage<br />

detector such as a halide torch or a propane or electrronic<br />

detector.<br />

4. If the source <strong>of</strong> the leakage still cannot be traced then<br />

repressurize with nitrogen up to 3.8MPa and check again.<br />

(The pressure must not be increased to more than<br />

3.8MPa.)<br />

3.75<br />

25°C<br />

20°C<br />

15°C<br />

(Time)<br />

(System sam<strong>pl</strong>e)<br />

(R410A gas)<br />

Nitrogen gas Gauge Vacuum pump<br />

Do not open the<br />

service valve during<br />

the airtight test.<br />

Air tight test<br />

Important points<br />

1. Where the lengths <strong>of</strong> piping involved are particularly long<br />

then the air tight test should be carried out block by block.<br />

1) Indoor side<br />

2) Indoor side + vertical pipes<br />

3) Indoor side + vertical pipes + outdoor side<br />

CAUTION<br />

2-way valve<br />

(Open)<br />

3-way valve<br />

(Close)<br />

Liquid side<br />

Hexagonal wrench<br />

Liquid Pipe<br />

Manifold gauge<br />

Gas side<br />

Guideline for each installation process 311<br />

Gas Pipe<br />

Soap water method<br />

1. Remove the caps from the 2-way and 3-way valves.<br />

2. Remove the service-port cap from the 3-way valve.<br />

3. To open the 2-way valve turn the valve stem counterclockwise<br />

approximately 90°, wait for about 2~3 sec,<br />

and close it.<br />

4. Ap<strong>pl</strong>y a soap water or a liquid neutral detergent on the<br />

indoor unit connection or outdoor unit connections by a<br />

s<strong>of</strong>t brush to check for leakage <strong>of</strong> the connecting points<br />

<strong>of</strong> the piping.<br />

5. If bubbles appear then those points have leakage.<br />

Cap


Vacuum drying works<br />

2.7 Vacuum drying works<br />

2.7.1 What is Vacuum drying?<br />

Vacuum drying is : The use <strong>of</strong> a vacuum pump to<br />

vaporize(gasify) the moisture (liquid) inside the pipe and<br />

expel it leaving the pipes com<strong>pl</strong>etely dry inside.<br />

At 1 atm(760mmHg) the boiling point (evaporating temperature)<br />

<strong>of</strong> water is 100°C but if a vacuum is created inside the<br />

pipes using a vacuum pump then the boiling point is rapidly<br />

reduced as the degree <strong>of</strong> the vacuum is increased.<br />

If the boiling point is reduced to a level below that <strong>of</strong> the<br />

ambient temperature then the moisture in the pipes will<br />

evaporate.<br />

Exam<strong>pl</strong>e<br />

When outside temperature is 11.7°C as shown in the table<br />

on the right , the degree <strong>of</strong> vacuum must be lowered below -<br />

750mmHg<br />

Boilng point <strong>of</strong><br />

water(°C)<br />

The degree<br />

<strong>of</strong> a vacuum<br />

mmHg<br />

Pressure<br />

Pa Torr<br />

40 -705 7333 55<br />

30 -724 4800 36<br />

26.7 -735 3333 25<br />

24.4 -738 3066 22<br />

22.2 -740 2666 20<br />

20.6 -742 2400 18<br />

17.8 -745 2000 15<br />

15.0 -747 1733 13<br />

11.7 -750 1333 10<br />

7.2 -752 1066 8<br />

0 -755 667 5<br />

The evacuation <strong>of</strong> air conditioner piping provides the following<br />

effects.<br />

1. Vaccum drying<br />

2. Removes air and nitrogen(used in air-tightness test)<br />

from the inside <strong>of</strong> pipes.<br />

Therefore , it is necessary to ensure that both purposes<br />

have been achieved in the vacuum drying operation.<br />

NOTE<br />

Key point: Maintain a vacuum level <strong>of</strong> -755mmHg<br />

mmHg<br />

760<br />

-20 -10 0 10 20 30 40<br />

(C)<br />

50 60 70<br />

2.7.2 Evacuation<br />

Temperature<br />

5CSL0-06B<br />

1. Connect the manifold hose end described in the preceding<br />

steps to the vacuum pump to evacuate the tubing and<br />

indoor unit. Confirm the "Lo" knob <strong>of</strong> the manifold valve is<br />

open. Then, run the vacuum pump. The operation time<br />

for evacuation varies with tubing length and capacity <strong>of</strong><br />

the pump. The following table shows the time required for<br />

evacuation.<br />

2. When the desired vacuum is reached, close the "Lo"<br />

knob <strong>of</strong> the manifold valve and stop the vacuum pump.<br />

312 Guideline for each installation process<br />

3.8MPa<br />

Required degree<br />

<strong>of</strong> vaccum<br />

Evaporation<br />

point<br />

The degree <strong>of</strong> a vacuum (mmHg)<br />

60<br />

160<br />

260<br />

0<br />

360<br />

460<br />

560<br />

660<br />

670<br />

680<br />

690<br />

700<br />

710<br />

720<br />

730<br />

740<br />

755<br />

760mmHg<br />

700<br />

600<br />

500<br />

400<br />

300<br />

200<br />

100<br />

90<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

5<br />

Absolute pressure (mmHg)<br />

0 mmHg<br />

x<br />

Outside<br />

temperature<br />

range


5CSL0-06B Vacuum drying works<br />

CAUTION<br />

Outdoor unit<br />

Pressure<br />

gauge<br />

Gas Pipe<br />

Manifold valve<br />

Lo Hi<br />

Open Close<br />

Vacuum pump<br />

(0.5 ~ 1HP)<br />

Liquid Pipe Pipe<br />

Manifold gauge<br />

Finishing the job<br />

1. With a service valve wrench, turn the valve stem <strong>of</strong> liquid<br />

side valve counter-clockwise to fully open the valve.<br />

2. Turn the valve stem <strong>of</strong> gas side valve counter-clockwise<br />

to fully open the valve.<br />

3. Loose the charge hose connected to the gas side service<br />

port slightly to release the pressure, then remove<br />

the hose.<br />

4. Re<strong>pl</strong>ace the flare nut and fasten the flare nut securely<br />

with an adjustable wrench. This process is very important<br />

to prevent leakage from the system.<br />

5. Re<strong>pl</strong>ace the valve caps at both gas and liquid side service<br />

valves and fasten them tight. This com<strong>pl</strong>etes air<br />

purging with a vacuum pump. The air conditioner is now<br />

ready for test run.<br />

2.7.3 Choosing a vacuum pump<br />

The necessity for counter flow prevention<br />

After the vacuum process <strong>of</strong> the refrigerant cycle, the inside<br />

<strong>of</strong> the hose will be vacuumed after stopping the vacuum<br />

pump, the oil <strong>of</strong> vacuumpump may flow back. Moreover, if<br />

the vacuum pump stops during the operation for some rea-<br />

Guideline for each installation process 313<br />

son.<br />

Gas Pipe<br />

Manifold gauge<br />

Therefore, in order to prevent the counter flow from the vacuum<br />

pump, a check valve is reguired.<br />

1) Vacuum pump performanceLiquid<br />

Pipe<br />

The 2 most important things for determining vacuum<br />

pump performance are as follows:<br />

(1) Exhaust velocity<br />

(2) Degree <strong>of</strong> vacuum<br />

(1) Exhaust velocity<br />

Exhaust volume is usually expressed as l/min or m3 /hr. The<br />

larger the number, the faster the vacuum is achieved.<br />

Generally speaking, the faster the exhaust velocity, the larger<br />

and heavier the vacuum pump itself is.<br />

Commercially available vacuum pumps (exhaust velocity <strong>of</strong><br />

20 - 30 l/min) usually take an extremely long time to achieve<br />

vacuum. (We recommend a vacuum pump <strong>of</strong> approx. 60 -<br />

100 l/min.)<br />

(2) Degree <strong>of</strong> vacuum<br />

Ultimate vacuum varies largely according to use <strong>of</strong> the vacuum<br />

pump. Vacuum pumps used for vacuum forming cannot<br />

be used for vacuum drying. (A vacuum pump with a high<br />

degree <strong>of</strong> vacuum is required.)<br />

When selecting a vacuum, you should select one which is<br />

capable <strong>of</strong> achieving 0.2 Torr <strong>of</strong> ultimate vacuum.<br />

Degree <strong>of</strong> vacuum is expressed in Torr, micron, mmHg, and<br />

Pascal (Pa). The units correlate as follows:<br />

Unit<br />

Standard<br />

atmospheric<br />

pressure<br />

Perfect vacuum<br />

Gauge Pressure kg/cm 2 0 -1.033<br />

Absolute Pressure kg/cm 2 abs 1.033 0<br />

Torr Torr 760 0<br />

Micron Micron 760000 0<br />

mmHg mmHg 0 760<br />

Pa Pa 1013.33 0


Vacuum drying works<br />

Degree <strong>of</strong> vacuum must be within the range expressed by<br />

0 Torr<br />

0 Pa<br />

760 mmHg<br />

Perfect vacuum<br />

5 Torr<br />

667 Pa<br />

755 cmHg<br />

Vacuum target value<br />

2) Vacuum pump maintenance<br />

Because <strong>of</strong> their nature, most vacuum pumps contain large<br />

amounts <strong>of</strong> oil which lubricates bearings, etc., and functions<br />

to enhance airtightness <strong>of</strong> pistons. When using a vacuum<br />

pump to discharge air from refrigerant piping, moisture in<br />

the air tends to get mixed in with the oil. You must therefore<br />

change oil periodically and make sure the proper oil level is<br />

maintained. (Perform periodic inspections in accordance<br />

with the operating instructions.)<br />

3) Degree <strong>of</strong> vacuum measurement<br />

An extremely accurate vacuum gauge is required to test<br />

degree <strong>of</strong> vacuum. You cannot accurately measure degree<br />

<strong>of</strong> vacuum with the compound gauge on the gauge manifold.<br />

A Pirani vacuum gauge is required to measure degree<br />

<strong>of</strong> vacuum accurately. Because Pirani gauges are very sensitive<br />

and require extreme care when using, they are not<br />

very suitable for use in the field. You should therefore use<br />

the Pirani gauge to calibrate the attached vacuum gauge on<br />

the gauge manifold and the degree <strong>of</strong> vacuum <strong>of</strong> the vacuum<br />

pump.<br />

4) Calibration method<br />

1. Connect a Pirani vacuum gauge and the gauge manifold<br />

vacuum gauge (760 mmHg) to the vacuum pump at the<br />

same time, and run the pump for about 3 minutes.<br />

2. Make sure the reading <strong>of</strong> the Pirani vacuum gauge is 5<br />

Torr (667 Pa ) or less. The reading <strong>of</strong> conventional vacuum<br />

pumps lowers to about 0.2 Torr.<br />

If the reading is not 5 Torr or less, check the vacuum<br />

pump oil. (Oil is low in many cases.)<br />

3. Check the attached gauge on the gauge manifold. Adjust<br />

the gauge if the reading is not exactly correct.<br />

4. Adjust the gauge manifold valve so that the Pirani vacuum<br />

gauge reads 5 Torr.<br />

5. Mark the position indicated by the gauge manifold gauge<br />

with an oil based ink pen.<br />

6. Use the mark <strong>of</strong> the gauge manifold as a target when<br />

vacuuming in the field.<br />

Pressure detection section<br />

Indicator<br />

5CSL0-06B<br />

760 Torr<br />

1013.33 hPa<br />

0 mmHg<br />

Standard atmospheric pressure<br />

Gauge manifold<br />

(Reference) Types <strong>of</strong> vacuum pump with respect to maximum<br />

degree <strong>of</strong> vacuum<br />

Vacuum pump<br />

Many handy<br />

pumps fall into this<br />

category<br />

314 Guideline for each installation process<br />

Type<br />

Oil rotary<br />

(Oil using)<br />

Oilless rotary<br />

(No need <strong>of</strong> oil)<br />

Maximum degree <strong>of</strong> vacuum Use<br />

Expulsion capacity Vacuum drying Air expulsion<br />

0.02 mmHg<br />

100 l/min Suitable Suitable<br />

10 mmHg<br />

0.02 mmHg<br />

50 l/min<br />

40 l/min<br />

Unsuitable<br />

Suitable<br />

Suitable<br />

Suitable


5CSL0-06B<br />

2.7.4 Vacuum drying procedure<br />

There are two vacuum drying methods and the appropriate one<br />

should always be chosen to confirm with individual local conditions.<br />

[Normal vacuum drying]........The standard method<br />

[Operational steps]<br />

1. Vacuum drying (1st time): Connect a manifold gauge to the service<br />

port <strong>of</strong> the liquid or gas pipe and operate the vacuum pump<br />

for at least 2 hours.<br />

(The degree <strong>of</strong> vacuum produced should be in excess <strong>of</strong> 5 Torr)<br />

If after 2 hours the vacuum produced has not exceeded 5 Torr<br />

then either there is moisture in the pipe or there is a leak.<br />

Operate the vacuum pump for further one more hour.<br />

If, even after 3 hours, the vacuum has not reached 5 Torr then<br />

check the system for a leak.<br />

2. Carry out vacuum test.<br />

Produce a vacuum in excess <strong>of</strong> 5 Torr and do not release it for<br />

an hour or more. Check the vacuum gauge to make sure that it<br />

has not risen. (If the gauge rise then there is still moisture in the<br />

pipe or there is a leak somewhere.)<br />

3. Additional charge <strong>of</strong> refrigerant.<br />

Connect the charging cylinder to the liquid pipe service port and<br />

charge with the required amount <strong>of</strong> refrigerant.<br />

4. Open stop valve to the full.<br />

Open the stop valve on the liquid and the gas pipes to the full.<br />

NOTE<br />

Vacuums should be produced in both the liquid and the gas pipes.<br />

(Because there are a large number <strong>of</strong> functional components in the<br />

indoor unit which cut <strong>of</strong>f the vacuum mid-way through)<br />

Rising pressure<br />

Falling<br />

pressure<br />

(vacuum)<br />

+0.05MPa<br />

(Atmospheric<br />

pressure)<br />

0 MPa<br />

Vacuum<br />

drying<br />

Vacuum drying works<br />

Maintaining<br />

vacuum test<br />

(2 hours) (1 hours)<br />

Time required: approximately 3 hours.<br />

Guideline for each installation process 315<br />

0 MPa<br />

-200 mmHg<br />

-400 mmHg<br />

-600 mmHg<br />

-700 mmHg<br />

-760 mmHg<br />

-755 mmHg<br />

(5 Torr)<br />

Time.<br />

Additional refrigerant<br />

charge


Additional charge <strong>of</strong> refrigerant 5CSL0-06B<br />

2.8 Additional charge <strong>of</strong><br />

refrigerant<br />

2.8.1 Refrigerant charging instructions<br />

Refrigerant charging<br />

1. The results <strong>of</strong> all calculations must be recorded. (make a<br />

list)<br />

2. The refrigerant will need to be additionally charged when<br />

the distance between the outdoor Unit and the most distant<br />

indoor unit is more than length (refer to section 8 outdoor<br />

unit installation condition)<br />

3. The additional charging operation should be carried out<br />

by input <strong>of</strong> liquid into the liquid pipes from a charging<br />

cylinder following com<strong>pl</strong>etion <strong>of</strong> the Vacuum drying operation.<br />

4. When the additional charging operation cannot be satisfactorily<br />

com<strong>pl</strong>eted , use the action <strong>of</strong> the compressor to<br />

com<strong>pl</strong>ete the additional charging during the test run.<br />

R-410A is a non-azeotrope refrigerants. Therefore , these<br />

refrigerants must be charged in the Liquid state.<br />

When charging the refrigerant into equipment from the cylinder<br />

, turn the refrigerant cylinder upside down.<br />

NOTE<br />

Make sure that the refrigerant (liquid) is taken out from the<br />

bottom part <strong>of</strong> the refrigerant cylinder.<br />

Do not take out the refrigerant (gas) at the upper <strong>of</strong> the<br />

refrigerant cylinder for charging.<br />

Refrigerant<br />

cylinder<br />

Outdoor unit A<br />

CAUTION<br />

Outdoor unit B<br />

• Since some refrigerant cylinders differ in the internal<br />

mechanism, it is necessary to examine the cylinder<br />

carefully.<br />

(Some cylinders have a siphon tube to eliminate the<br />

need for turning it upside down)<br />

316 Guideline for each installation process<br />

Refrigerant<br />

cylinder<br />

siphon tube


5CSL0-06B<br />

2.9 Trial test run operation<br />

2.9.1 Test run procedure<br />

Check the following before turning power on<br />

Wrong power wiring , loosed screws<br />

Wrong control transmission wiring , loose screws<br />

Piping size , presence <strong>of</strong> thermal insulation<br />

Measurement <strong>of</strong> main power circuit insulation<br />

Addition or refrigerant if required<br />

Fully open respective stop valves on liquid, gas<br />

Turn on outdoor unit power<br />

Use a mega-tester<br />

Be sure to record the additional<br />

quantity <strong>of</strong> refrigerant<br />

2.9.2 Evaluation performance<br />

Evaluation <strong>of</strong> the performance<br />

Operate unit for 15~20 minutes, then check the system<br />

refrigerant charge:<br />

1. Measure the pressure <strong>of</strong> the gas side service valve.<br />

2. Measure the temperature <strong>of</strong> the intake and discharge <strong>of</strong> air.<br />

3. Ensure the difference between the intake temperature<br />

and the discharge is more than 8°C<br />

4. For reference, the gas side pressure <strong>of</strong> optimum condition<br />

is as below. (Cooling)<br />

Refrigerant<br />

Discharge air<br />

Outside ambient<br />

Temp.<br />

Intake temperature<br />

Discharge<br />

temperature<br />

The pressure <strong>of</strong> the gas side<br />

service valve.<br />

R410A 35°C (95°F) 8.0~10.0kg/cm 2 G<br />

NOTE<br />

Trial test run operation<br />

: If the actual pressure is higher than shown, the system is<br />

most likely overcharged so extra refrigerant should be<br />

removed.<br />

If the actual pressure is lower than shown, the system is<br />

most likely undercharged so extra refrigerant should be<br />

added.<br />

The air conditioner is now ready for use.<br />

2.9.3 Transfer to customer with ex<strong>pl</strong>anation<br />

1. Operational step<br />

Com<strong>pl</strong>ete test run<br />

Ex<strong>pl</strong>ain how to<br />

operate and<br />

maintain equipment<br />

Make final report<br />

(test run<br />

inspection sheet)<br />

Hand over<br />

relevant printed<br />

materials<br />

a) The measurements taken during the test run should be<br />

recorded and kept on a test run inspection sheet.<br />

b) Do not forget to record the length <strong>of</strong> the refrigerant piping<br />

and the refrigerant additional charging volume on the<br />

<strong>pl</strong>ate on the back <strong>of</strong> the outdoor unit external notice<br />

board, as this information will be required for servicing<br />

the system.<br />

c) Ex<strong>pl</strong>ain to the customer how to operate and maintain the<br />

equipment and let him try it.<br />

d) Assemble all the relevant diagrams and other printed<br />

matter which is required to operate the system and hand<br />

over to the customer (on the spot) and request him to<br />

keep it handy.<br />

e) Service contact address.<br />

List <strong>of</strong> equipment which has been delivered<br />

Installation drawing<br />

It is essential to prepare a control wiring diagram<br />

which clarifies the refrigerant system and the<br />

control system.<br />

1 set <strong>of</strong> operation manuals<br />

Names <strong>of</strong> those responsible for the<br />

work (emergency contact address)<br />

Equipment guarantees.<br />

Guideline for each installation process 317


Safety precautions<br />

3. Installation <strong>of</strong> indoor unit<br />

3.1 Safety precautions<br />

Please strictly follow the instructions given in the Installation<br />

manual .Improper installation by ignoring the instructions<br />

can lead to damage to life and property.<br />

Make sure to read the following safety instructions very<br />

carefully and throughly .<br />

WARNING<br />

: This symbol indicates the possibility <strong>of</strong><br />

death or serious injury.<br />

CAUTION : This symbol indicates the possibility <strong>of</strong><br />

injury or damage to properties.<br />

■ The meanings <strong>of</strong> the symbols used in this manual are as<br />

shown below.<br />

: Be sure not to do.<br />

: Be sure to follow the instruction.<br />

WARNING<br />

Do not use a defective or underrated circuit breaker.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Always use this ap<strong>pl</strong>iance on a dedicated circuit breaker.<br />

• Otherwise it can cause electric shock or fire.<br />

For electrical work, contact the dealer, seller, a qualified<br />

electrician, or an authorized service center. Do not disassemble<br />

or repair the product by yourself.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Always ground the product as per the field wiring diagram.<br />

Do not connect the ground wire to gas or water pipes lightening<br />

rod or telephone ground wire.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Install the panel and the cover <strong>of</strong> control box securely.<br />

• There is risk <strong>of</strong> fire or electric shock due to dust , water etc.<br />

Use the correctly rated breaker or fuse.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Do not modify or extend the power cable. If the power<br />

cable or cord has scratches or skin peeled <strong>of</strong>f or deterioted<br />

then immediately re<strong>pl</strong>ace it.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

For installation, removal or reinstall, always contact the<br />

dealer or an Authorized Service Center.<br />

• There is risk <strong>of</strong> fire, electric shock, ex<strong>pl</strong>osion, or injury.<br />

Do not install the product on a defective installation foundation.<br />

Be sure that the installation area does not deteriorate<br />

with age.<br />

• If the base collapses, the air conditioner could fall with it,<br />

causing property damage, product failure, and personal<br />

injury.<br />

When the product is soaked (flooded or submerged) in<br />

water, contact an Authorized Service Center for repair<br />

before using it again.<br />

5CSL0-06B<br />

• There is risk <strong>of</strong> fire or eletric shock.<br />

In outdoor unit the step-up capacitor sup<strong>pl</strong>ies high voltage<br />

electlicity to the electrical components.<br />

Be sure to discharge the capacitor com<strong>pl</strong>etely before conducting<br />

the repair work.<br />

• An charged capacitor can cause electrical shock.<br />

Be sure to use only those parts which are listed in the service<br />

parts list. Never attempt to modify the equipment.<br />

• The use <strong>of</strong> inappropriate parts can cause an electrical shock,<br />

excessive heat generation or fire.<br />

Indoor/outdoor wiring connections must be secured tightly<br />

and the cable should be routed properly so that there is<br />

no force pulling the cable at the connection terminals.<br />

• Improper or loose connections can cause excessive heat<br />

generation or fire.<br />

Safely dispose <strong>of</strong>f the packing materials.<br />

• Things like screws, nails, batteries, broken things etc. after<br />

installation or svc can cause injury to small kids. Tear away<br />

and throw away the <strong>pl</strong>astic packaging bags so that children<br />

will not <strong>pl</strong>ay with them.<br />

During svc be sure to check the refrigerant to the used.<br />

• Incorrect refrigerant used can prevent the normal operation <strong>of</strong><br />

the unit.<br />

When installing the unit, use the installation kit provided<br />

with the product.<br />

• Otherwise the unit may fall and cause severe injury .<br />

Do not touch, operate, or repair the product with wet<br />

hands.<br />

• There is risk <strong>of</strong> electric shock or fire.<br />

Do not <strong>pl</strong>ace a heater or other ap<strong>pl</strong>iances near the power<br />

cable.<br />

• There is risk <strong>of</strong> fire and electric shock.<br />

Do not allow water to run into electric parts. Install the unit<br />

away from water sources<br />

• There is risk <strong>of</strong> fire, failure <strong>of</strong> the product, or electric shock.<br />

Do not store or use or even allow flammable gas or combustibles<br />

near the product.<br />

• There is risk <strong>of</strong> fire or failure <strong>of</strong> product.<br />

Do not use the product in a tightly closed space for a long<br />

time. Perform ventilation regularly.<br />

• Oxygen deficiency could occur and hence harm your health.<br />

If strange sounds, smell or smoke comes from product,<br />

immediately turn the breaker <strong>of</strong>f or disconnect the power<br />

sup<strong>pl</strong>y cable.<br />

• There is risk <strong>of</strong> electric shock or fire.<br />

When installing the unit, use the installation kit provided<br />

with the product.<br />

• Otherwise the unit may fall and cause severe injury.<br />

Do not open the front grill <strong>of</strong> the product during operation.<br />

(Do not touch the electrostatic filter, if the unit is so<br />

equipped.)<br />

• There is risk <strong>of</strong> physical injury, electric shock or product failure.<br />

318 Installation <strong>of</strong> indoor unit


5CSL0-06B Safety precautions<br />

Ventilate the product room from time to time when operating<br />

it together with a stove, or heating element etc.<br />

• Oxygen deficiency can occur and hence harm your health.<br />

Turn the main power when cleaning or repairing the product.<br />

• There is risk <strong>of</strong> electric shock.<br />

When the product is not to be used for a long time, shut<br />

<strong>of</strong>f the circuit breaker.<br />

• There is risk <strong>of</strong> product damage or failure or unintended operation.<br />

CAUTION<br />

Use two or more peo<strong>pl</strong>e to lift and transport the product.<br />

• Avoid personal injury.<br />

Do not install the product where it will be exposed to<br />

sea wind (salt spray) directly.<br />

• It may cause corrosion on the product. Corrosion, particularly<br />

on the condenser and evaporator fins, could cause<br />

product malfunction or inefficient operation.<br />

Install the drain hose to ensure that water is drained<br />

away properly.<br />

• A bad connection may cause water leakage.<br />

Keep level even when installing the product.<br />

• To avoid vibration or noise.<br />

Always check for gas (refrigerant) leakage after installation<br />

or repair <strong>of</strong> product.<br />

• Low pressure levels may cause failure <strong>of</strong> product.<br />

Do not block the inlet or outlet <strong>of</strong> air flow.<br />

• It may cause product failure.<br />

Use a s<strong>of</strong>t cloth to clean. Do not use harsh detergents,<br />

solvents or s<strong>pl</strong>ashing water etc .<br />

• There is risk <strong>of</strong> fire, electric shock, or damage to the <strong>pl</strong>astic<br />

parts <strong>of</strong> the product.<br />

Do not step on or put anyting on the product. (outdoor<br />

units)<br />

• There is risk <strong>of</strong> personal injury and failure <strong>of</strong> product.<br />

Do not insert hands or other objects through the air<br />

inlet or outlet while the product is operating.<br />

• There are sharp and moving parts that could cause personal<br />

injury.<br />

Be cautious when unpacking and installing the product.<br />

• Sharp edges could cause injury. Be especially careful <strong>of</strong><br />

the case edges and the fins on the condenser and evaporator.<br />

If the refrigerant gas leaks during the repair, do not<br />

touch the leaking refrigerant gas.<br />

• The refrigerant gas can cause frostbite (cold burn).<br />

Do not tilt the unit when removing or uninstalling it.<br />

• The condensed water inside can cause spill and wet the<br />

furniture and the floor.<br />

Do not mix air or gas other than the specified refrigerant<br />

used in the system.<br />

• If air enters the refrigerant system, an excessively high<br />

pressure results, causing equipment damage or injury.<br />

Re<strong>pl</strong>ace the all batteries in the remote control with new<br />

ones <strong>of</strong> the same type. Do not mix old and new batteries<br />

or different types <strong>of</strong> batteries.<br />

• There is risk <strong>of</strong> fire or ex<strong>pl</strong>osion.<br />

If the liquid from the batteries gets onto your skin or<br />

clothes, wash it well with clean water. Do not use the<br />

remote if the batteries have leaked.<br />

• The chemicals in batteries could cause burns or other<br />

health hazards.<br />

Do not use the product for special purposes, such as<br />

preserving foods, works <strong>of</strong> art, etc. It is a consumer air<br />

conditioner, not a precision refrigeration system.<br />

• There is risk <strong>of</strong> damage or loss <strong>of</strong> property.<br />

Do not touch the metal parts <strong>of</strong> the product when<br />

removing the air filter.<br />

• There is risk <strong>of</strong> personal injury.<br />

If the refrigerant gas leaks during the installation or<br />

operation ventilate the area immediately.<br />

• Otherwise it can be harmfull for your health.<br />

Do not turn <strong>of</strong>f the power immediately after stopping<br />

the operation.<br />

• Always wait for 5 minutes before turning <strong>of</strong>f the power otherwise<br />

water leakage and troubles can occur.<br />

Do not let the air conditioner run for a long time when<br />

the humidity is very high and a door or a window is left<br />

open.<br />

• Moisture may condense and wet or damage furniture.<br />

Do not expose your skin or kids or <strong>pl</strong>ants to the cool or<br />

hot air draft.<br />

• This could harm to your health.<br />

Do not drink the water drained from the product.<br />

• It is not sanitary and could cause serious health issues.<br />

Use a firm stool or ladder when cleaning, maintaining<br />

or repairing the product at an height.<br />

• Be careful and avoid personal injury.<br />

Dismantling <strong>of</strong> the unit , treatment <strong>of</strong> the refrigerant oil<br />

and eventual parts should be done in accordance with<br />

local and national standards.<br />

Do not recharge or disassemble the batteries. Do not<br />

dispose <strong>of</strong>f batteries in fire.<br />

• They may burn or ex<strong>pl</strong>ode.<br />

Installation <strong>of</strong> indoor unit 319


Safety precautions<br />

3.1.1 Points for ex<strong>pl</strong>anation about<br />

operations<br />

The items with WARNING and CAUTION marks in the operation<br />

manual are the items pertaining to possibillties for<br />

bodily injury and material damage in addition to the general<br />

usage <strong>of</strong> the product. Accordingly, it is necessary that you<br />

make a full ex<strong>pl</strong>anation about the described contents and<br />

also ask your customers to read the owner's manual.<br />

1. Note to the installer<br />

Be sure to instruct customers how to properly operate the<br />

unit (especially cleaning filters, operating different functions,<br />

and adjusting the temperature) by having them carry out<br />

operations themselves while looking at the manual.<br />

3.1.2 Selecting installation site for<br />

indoor units<br />

1. Select an installation site where the following conditions<br />

are fulfilled and that meets with your customer's<br />

approval.<br />

1) Location strong enough to bear the weight <strong>of</strong> the unit.<br />

2) Location accessible and having enough clearance for<br />

inspection and service in the future.<br />

3) Location allowing easy condensate drainage and suitable<br />

gradient <strong>of</strong> the unit and the drain pipe.<br />

4) Piping between the indoor and outdoor unit is possible<br />

within the allowable limits.<br />

5) Location free from electrical noise.<br />

6) Location allowing optimum air distribution without any<br />

blocking to air flow.<br />

7) Location having no risk <strong>of</strong> flammable gas leakage.<br />

8) Location free from mineral oil mist or an oil spray or<br />

vapor exam<strong>pl</strong>e in kitchen .It could result in leakage .<br />

9) Location free from corrosive gases such as sulphurous<br />

acid gas because it corrodes the copper pipes or soldered<br />

parts resulting in leakage .<br />

10) Location free from any machinery emitting electromagnetic<br />

waves which may disturb the control system<br />

thus causing malfunction <strong>of</strong> the unit .<br />

11) Location free from flammable gases , carbon fibre , or<br />

ignitable dust suspensions in the air or where volatile<br />

flames are handled like gasoline or thinner. Operating<br />

in such conditions may result in fire .<br />

12) Install the indoor and outdoor units, power sup<strong>pl</strong>y<br />

wiring and connecting wires at least 1m away from<br />

televisions or radios in order to prevent image interference<br />

or noise. (Depending on the radio waves, a<br />

distance <strong>of</strong> 1m. may not be sufficient enough to eliminate<br />

the noise.)<br />

5CSL0-06B<br />

13) Consider whether the <strong>pl</strong>ace where the unit will be<br />

installed can support the full weight <strong>of</strong> the unit, and<br />

reinforce it with boards and beams, etc. If needed<br />

before proceeding with the installation. Also, reinforce<br />

the <strong>pl</strong>ace to prevent vibration and noise before<br />

installing.<br />

14) The indoor artcool, artcool mirror, wallmount unit may<br />

not be directly installed on the wall. Use the attached<br />

installation <strong>pl</strong>ate before installing the unit.<br />

15) Obey the local and national regulations and limits<br />

regarding airconditioner installation.<br />

320 Installation <strong>of</strong> indoor unit


5CSL0-06B Safety precautions<br />

2. For the following items, take special care during construction and check after installation is finished<br />

1. Items to be checked after com<strong>pl</strong>etion <strong>of</strong> installtion work<br />

Items to be checked If not properly done, what is likely to occur Check<br />

Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.<br />

Is the gas leak test finished? It may result in insufficient cooling or heating.<br />

Is the unit fully insulated? Condensate water may drip.<br />

Does drainage flow smoothly? Condensate water may drip.<br />

Does the power sup<strong>pl</strong>y voltage correspond to that<br />

shown on the name <strong>pl</strong>ate?<br />

The unit may malfunction or the components burn out.<br />

Are wiring and piping correct? The unit may malfunction or the components burn out.<br />

Is the unit safely grounded? It may be dangerous during electric leakage.<br />

Is wiring size correct according to specifications? The unit may malfunction or the components burn out.<br />

Is there something blocking the air outlet or inlet <strong>of</strong><br />

either the indoor or outdoor units?<br />

It may result in insufficient cooling or heating.<br />

Are refrigerant piping length and additional<br />

refrigerant charge noted down?<br />

The refrigerant charge in the system is not clear.<br />

3.1.3 Before installation<br />

1. During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure on<br />

other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts.<br />

• The accessories needed for installation must be retained in your custody until the installation work is com<strong>pl</strong>eted. Do not discard<br />

them!<br />

• Decide upon a line <strong>of</strong> transport.<br />

• Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is unavoidable, use a sling <strong>of</strong><br />

s<strong>of</strong>t material or protective <strong>pl</strong>ates together with a rope when lifting, to avoid damage or scratches to the unit.<br />

• When using the wireless remote controller, refer to the installation manual attached to the wireless remote controller.<br />

NOTE<br />

• Be sure to read this manual before installing the indoor unit.<br />

• Entrust installation to the <strong>pl</strong>ace <strong>of</strong> purchase or an authorized serviceman. Improper installation could lead to leaks and in<br />

worst cases, electric shock <strong>of</strong> fire.<br />

• Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to<br />

fall out <strong>of</strong> <strong>pl</strong>ace, or could lead to leaks and in the worst cases, electric shock or fire.<br />

Installation <strong>of</strong> indoor unit 321


Ceiling cassette 4-way<br />

3.2 Ceiling cassette 4-way<br />

• Please read the instruction sheets com<strong>pl</strong>etely before installing the product.<br />

• When the power cord is damaged, re<strong>pl</strong>acement work shall be performed by authorized personnel only.<br />

• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.<br />

Name<br />

Quantity<br />

Air sup<strong>pl</strong>y<br />

3.2.1 Accessories<br />

Check whether the following accessories are included with your unit.<br />

1) Standard accessories<br />

Drain hose<br />

1 EA<br />

Air<br />

return<br />

Clamp metal<br />

1 EA<br />

Washer for<br />

hanging backet<br />

8 EA<br />

Clamp<br />

Insulation for<br />

fitting<br />

1 SET<br />

Shape for gas pipe<br />

for liquid pipe<br />

5CSL0-06B<br />

322 Installation <strong>of</strong> indoor unit<br />

8 EA<br />

Long life filter<br />

(Other)<br />

• Paper pattern for<br />

installation<br />

• Owner's manual<br />

• Installation manual


5CSL0-06B Ceiling cassette 4-way<br />

3.2.2 Selection <strong>of</strong> the best location<br />

• There should not be any heat source or steam near the<br />

unit.<br />

• There should not be any obstacles to the air circulation.<br />

• There should be provision <strong>of</strong> easy condensate drain.<br />

• Taking into accounting the noise prevention criteria, spot<br />

the installation location.<br />

• Do not install the unit near the door way.<br />

• Keep proper distances, <strong>of</strong> the unit, from ceiling, fence,<br />

floor, walls and other obstacles as shown in figure.<br />

• The indoor unit must have the maintenance space.<br />

NOTE<br />

Ceiling<br />

False ceiling<br />

1500 or<br />

more<br />

Above figure means minimum value. Please keep these<br />

value at least.<br />

If H is 2700~3200: High ceiling operation control requied<br />

If H is ~2700: Normal operation<br />

1500 or more<br />

1500<br />

or more<br />

20 or more<br />

1500 or more<br />

H<br />

Floor<br />

1500 or<br />

more<br />

1500 or more<br />

False ceiling<br />

1500 or more<br />

Unit:mm<br />

3.2.3 Precautions regarding cassette<br />

indoor unit installation<br />

1) Main points about the indoor installation<br />

• In case <strong>of</strong> high height ceiling<br />

In general commercial <strong>pl</strong>aces and <strong>of</strong>fices though the<br />

height <strong>of</strong> the ceiling is 2.7 m, the ceiling height can be 3<br />

m. In such cases because <strong>of</strong> the temperature difference<br />

with the floor the heating effect can fall down.<br />

High elevation<br />

<strong>of</strong> the ceiling<br />

Discharge<br />

• Countermeasure method<br />

① Air conditioner must be able to operate in high ceiling<br />

conditioner.<br />

② Plan to install the circulator.<br />

③ The air discharge port is made to give more airflow to the<br />

down wood directions.<br />

④ The gate or exit <strong>of</strong> the building is protected by dual door<br />

system.<br />

2) In case the floor or surfaces <strong>of</strong> the <strong>pl</strong>ace<br />

to be air conditioned is in direct contact<br />

with the outdoor air<br />

• The floor <strong>of</strong> the heating room indirect contact with<br />

the storeroom, garage or the outside air receives<br />

the cold air at the floor and the floor temperature<br />

decrease will feel cold at the feet.<br />

Outdoor side<br />

In such <strong>pl</strong>aces where the feet comes in direct contact<br />

with floors will give a cold feeling to the floor.<br />

Installation <strong>of</strong> indoor unit 323<br />

Suction<br />

Hot air<br />

Cold air<br />

Indoor<br />

Outdoor side<br />

Garage<br />

Outdoor<br />

side (Entering <strong>of</strong> air by<br />

frequent opening<br />

and closing <strong>of</strong> door)<br />

Low temperature<br />

<strong>of</strong> the floor<br />

(50~100mm<br />

Insulation required)<br />

Outdoor side


Ceiling cassette 4-way<br />

• Countermeasure:<br />

- Use the carpet on the floor (compared to the tiles the carpet<br />

over it will have a 3 degree rise in temperature)<br />

- Insulating the floor.<br />

- Floor heating<br />

CAUTION<br />

• Case <strong>of</strong> cold air intake:<br />

The duct surface will have the dew drops so a insulation<br />

on the duct is a must.(Insulation material: a glass wool <strong>of</strong><br />

thickness 25 mm will be appropriate.)<br />

3) In case <strong>of</strong> high temperature or high<br />

humidity between the false ceiling and<br />

ceiling slab(near by the sea, river, lake,<br />

spa)<br />

• In case <strong>of</strong> temperature <strong>of</strong> 30 degree and humidity<br />

above 80%, the units body as well as the piping<br />

insulation should be strengthened.<br />

Refer to the picture given below.<br />

Psychrometric chart Enhance additional<br />

insulation required area<br />

Relative humidity<br />

30˚C<br />

• Places having the temperature and humidity <strong>of</strong> the<br />

surrounding and the<br />

The surrounding water sources(sea, river etc.)<br />

In case the steam is generated between the false ceiling<br />

and the ceiling slab<br />

Due to some nearby by steam source.<br />

- Indoor unit: Insulate the unit body with some insulation<br />

like glass wool atleast 10 mm in thickness.<br />

Additional insulation required<br />

5CSL0-06B<br />

• In case <strong>of</strong> the multi flow type, use the high humidity kit.<br />

Otherwise the dew drops can be seen in the unit body.<br />

• Refrigerant piping: Increase the piping insulation<br />

thickness with thickness above 20 mm.<br />

• Others: Inside the ceiling near th air tight seal <strong>pl</strong>aces<br />

(no escape <strong>of</strong> the humidity)<br />

Grill for ventilation<br />

Refrigerant piping<br />

• In case <strong>of</strong> multi<strong>pl</strong>e indoor cassette units<br />

(recommended)<br />

Indoor unit<br />

Above 1500mm<br />

324 Installation <strong>of</strong> indoor unit<br />

Lighting<br />

Ventilator<br />

Above 2000mm<br />

Above 3000mm<br />

Indoor unit


5CSL0-06B Ceiling cassette 4-way<br />

3.2.4 Ceiling opening dimensions and<br />

hanging bolt location<br />

① The dimensions <strong>of</strong> the paper pattern for installation are<br />

the same as those <strong>of</strong> the ceiling opening dimensions.<br />

② Select and mark the position for fixing bolts and piping<br />

hole.<br />

③ Decide the position for fixing bolts slightly tilted to the<br />

drain direction after considering the direction <strong>of</strong> drain<br />

hose.<br />

④ Drill the hole for anchor bolt on the wall.<br />

39.5<br />

671<br />

TQ,TR MODEL<br />

600 (Ceiling opening)<br />

521(Hanging bolt) 39.5<br />

570 Unit siz size<br />

570 Unit siz size<br />

TP/TN/TM Model<br />

875(Ceiling opening)<br />

787(Hanging bolt)<br />

840 Unit size<br />

840 Unit size<br />

684(Hanging bolt)<br />

450 (Hanging bolt) 75<br />

75<br />

600 (Ceiling opening)<br />

Unit:mm<br />

875(Ceiling opening)<br />

Unit:mm<br />

1) Install the suspension bolts.<br />

(Use either a W3/8” or M10 size bolt) Use a hole-in anchor<br />

for existing ceilings, and a sunken insert, sunken anchor or<br />

other field sup<strong>pl</strong>ied parts for new ceilings to reinforce the<br />

ceiling to bear the weight <strong>of</strong> the unit. Adjust clearance from<br />

the ceiling before proceeding further.<br />

All the above parts are field suppiled.<br />

Installation <strong>of</strong> indoor unit 325<br />

NOTE<br />

Ceiling<br />

Anchor<br />

Long nut or turn-buckle<br />

Suspension bolt<br />

False ceiling


Ceiling cassette 4-way<br />

3.2.5 Indoor unit installation<br />

• Installing <strong>of</strong> the accessories (except for the decoration<br />

panel) before installing the indoor unit is easier.<br />

1) Install the indoor unit temporarily.<br />

• Attach the hanger bracket to the suspension bolt. Be sure<br />

to fix it securely by using a nut and washer from the upper<br />

and lower sides <strong>of</strong> the hanger bracket.<br />

Hanging bolt<br />

(W3/8 or M10)<br />

Nut<br />

(W3/8 or M10)<br />

Spring washer<br />

(M10)<br />

Keep the length<br />

<strong>of</strong> the bolt<br />

from the bracket<br />

to 40mm or more<br />

Adjust the same height<br />

Ceiling<br />

Air conditioner body<br />

• The following parts are local purchasing.<br />

- Hanging Bolt - W 3/8 or M10<br />

- Nut - W 3/8 or M10<br />

- Spring Washer - M10<br />

- Plate Washer - M10<br />

Flat washer for M10<br />

(accessory)<br />

Flat washer for M10<br />

(accessory)<br />

Nut<br />

(W3/8 or M10)<br />

False ceiling<br />

2) For new ceilings<br />

(1) Refer to the paper pattern for ceiling opening<br />

dimension.<br />

• The center <strong>of</strong> the ceiling opening is indicated on the<br />

paper pattern for installation.<br />

The center <strong>of</strong> the unit is indicated on the label attached<br />

to the unit and on the paper pattern for installation.<br />

• First remove paper packaging material from the<br />

4 corners <strong>of</strong> the paper pattern for installation , fix the<br />

paper pattern to the unit with screws.<br />

• Ceiling height is shown on the side <strong>of</strong> the paper pattern<br />

for installation. Adjust the height <strong>of</strong> the unit according to<br />

this indication.<br />

5CSL0-06B<br />

<br />

(2) Adjust the unit to the right position for installation.<br />

(3) Assure that the unit is horizontal.<br />

• The indoor unit is equipped with a built-in drain pump<br />

and float switch. At each <strong>of</strong> the unit's 3 corners, verify<br />

that it is level by using awater-level or a water-filled<br />

vinyl tube. (Otherwise it will result in the malfunctioning<br />

<strong>of</strong> unit and cause water to drip.)<br />

(4) Remove the washer fixing <strong>pl</strong>ate used for<br />

preventing the washer from falling and tighten<br />

the upper nut.<br />

(5) Remove the paper pattern for installation<br />

3) For existing ceilings<br />

(1) Adjust the height and position <strong>of</strong> the unit.<br />

(2) Perform steps 3 and 4 in "5.1 For new ceilings".<br />

3.2.6 Connecting pipes to the indoor<br />

unit<br />

1) Refrigerant piping work<br />

<strong>pl</strong>ease refer “REFRIGERANT PIPING WORK”.<br />

2) Piping insulation<br />

① Perform heat insulation work com<strong>pl</strong>etely on both gas and<br />

the liquid pipe. Because improper insulation will result<br />

condensate formation over pipe.<br />

② Use the heat insulation material for the refrigerant piping<br />

which has an excellent heat resistance (over 120°C).<br />

③ Precautions in high humidity circumstance:<br />

④ Refer to insulation work<br />

CAUTION<br />

• Make sure to insulate any field piping all the way to the<br />

piping connection inside the unit. Any exposed piping<br />

may cause condensation or burns if touched.<br />

326 Installation <strong>of</strong> indoor unit


5CSL0-06B Ceiling cassette 4-way<br />

3) Indoor unit drain piping<br />

• Drain piping must have downward (1/50 to 1/100): be sure<br />

not to provide up-and-down slope to prevent reverse flow.<br />

• During drain piping connection, be careful not to exert<br />

extra force on the drain port on the indoor unit.<br />

• The outside diameter <strong>of</strong> the drain connection on the inddor<br />

unit is 32mm.<br />

Piping material: Polyvinyl chloride pipe 25mm and pipe<br />

fittings<br />

p<br />

• Be sure to install heat insulation on the drain piping.<br />

Heat insulation material: Polyethylene foam with thickness<br />

more than 10 mm.<br />

4) Drain test<br />

Sqeezing<br />

Water feeder<br />

Drain pump<br />

Drain pan<br />

1/50~<br />

1/100<br />

MAX<br />

700mm<br />

Upward<br />

routing<br />

not allowed<br />

Flexible drain hose<br />

(Accessory)<br />

Main<br />

drain pipe<br />

Drain<br />

port Glue the joint<br />

Drain hose connection<br />

use the clip (Accessory)<br />

Flexible drain hose<br />

3.2.7 Decoration panel<br />

The decoration panel has its installation<br />

direction.<br />

Before installing the decoration panel, always<br />

remove the paper tem<strong>pl</strong>ate.<br />

1. Temporarily fix two decoration panel fixing screws<br />

(hexagon M5 screw) on the unit body. (Tighten by<br />

amount 10mm in length.)<br />

The fixing screws (hexagon M5 screw) are included<br />

the indoor unit box.<br />

2. Remove the air inlet grille from the decoration panel.<br />

(Remove the hook for the air inlet grille cord.)<br />

3. Hook the decoration panel key hole ( ) on the<br />

screws fixed in step above, and slide the panel so that<br />

the screws reach the key hole edge.<br />

4. Retighten com<strong>pl</strong>etely two temporarily fixed screws and<br />

other two screws. (Total 4 screws)<br />

5. Connect the louver motor connector and dis<strong>pl</strong>ay connector.<br />

6. After tightening these screws, install the air inlet grille<br />

(including the air filter).<br />

Decoration panel fixing screws<br />

(hexagon M5 screws)<br />

Temporally fitting at 2 <strong>pl</strong>aces<br />

(Tightening about 10mm)<br />

Inlet Grille<br />

Air conditioner unit<br />

Piping side<br />

Decoration panel<br />

Decoration panel fixing screws<br />

(Hexagon M5 M5 screw) screw)<br />

Control box cover<br />

Flexible drain hose<br />

Louver motor<br />

Installation <strong>of</strong> indoor unit 327<br />

Dis<strong>pl</strong>ay<br />

Lead wire for<br />

louver motor and<br />

dis<strong>pl</strong>ay


Ceiling cassette 4-way<br />

CAUTION<br />

Install certainly the decoration panel.<br />

Cool air leakage causes sweating.<br />

➔ Water drops fall.<br />

3.2.8 Electric wiring work<br />

1) General instructions<br />

Air conditioner<br />

unit<br />

Decoration panel<br />

Fit the insulation (this part) and<br />

be careful for cool air leakage<br />

Air<br />

False<br />

ceiling<br />

Air conditioner unit<br />

Cool air leakage(no good)<br />

False<br />

ceiling<br />

Decoration panel<br />

① All field sup<strong>pl</strong>ied parts and materials, electric works must<br />

conform to local codes.<br />

Use copper wire only.<br />

② Follow the "WIRING DIAGRAM” attached to the unit<br />

body to wire the outdoor unit, indoor units and the remote<br />

controller.<br />

③ All wiring must be performed by an authorized electrician.<br />

④ This system consists <strong>of</strong> multi<strong>pl</strong>e indoor units. Mark each<br />

indoor unit as unit A, unit B..., and be sure the terminal<br />

board wiring to the outdoor unit and indoor units are<br />

properly matched. If wiring and piping between the outdoor<br />

unit and an indoor units are mismatched, the system<br />

may cause a malfunction.<br />

⑤ A circuit breaker capable <strong>of</strong> shutting down the power<br />

sup<strong>pl</strong>y to the entire system must be installed.<br />

5CSL0-06B<br />

2) Wiring Connection<br />

① Open the control box cover and connect the Remote<br />

controller cord and Indoor power wires.<br />

Indoor<br />

power cable<br />

Remote<br />

controller<br />

cable<br />

Control Box Cover Control box<br />

cover screw<br />

Indoor<br />

power<br />

cord<br />

Terminal block in indoor<br />

[Air inlet side view]<br />

1(L) 2(N) 3 4<br />

Connected to outdoor Unit<br />

Remote<br />

control<br />

cord<br />

② Make sure to attach the sealing material (field sup<strong>pl</strong>ied)<br />

to hole <strong>of</strong> wiring to prevent the infiltration <strong>of</strong> foreign particle<br />

from outside. Otherwise a short-circuit may occur<br />

inside the electric parts box<br />

328 Installation <strong>of</strong> indoor unit


5CSL0-06B Ceiling cassette 4-way<br />

③ When clamping the wires, be sure no pressure is ap<strong>pl</strong>ied<br />

to the wire connections by using the included clamping<br />

material to make appropriate clamps. Also, when wiring,<br />

make sure the cover on the electric parts box fits snugly<br />

by arranging the wires neatly and attaching the electric<br />

parts box cover firmly. When attaching the electric parts<br />

box cover, make sure no wires get caught in the edges.<br />

Pass wiring through the holes to prevent damage to<br />

them.<br />

④ Make sure the remote controller wiring, the wiring<br />

between the units, and other electrical wiring do not pass<br />

through the same locations outside <strong>of</strong> the unit, separating<br />

them properly, otherwise electrical noise (external<br />

static) could cause product malfunction.<br />

NOTE<br />

WARNING<br />

• Make sure that the screws <strong>of</strong> the terminal are not loose.<br />

1. Use round crimp-style terminals for connecting<br />

wires to the power sup<strong>pl</strong>y terminal block. If<br />

unavailable, observe the following points when<br />

wiring.<br />

• Do not connect wires <strong>of</strong> different gauge to the same<br />

power sup<strong>pl</strong>y terminal. (Looseness connection may<br />

cause overheating.)<br />

• Use the specified electric wire. Connect the wire<br />

securely to the terminal. Lock the wire down without<br />

ap<strong>pl</strong>ying excessive force to the terminal.<br />

Round crimp-style terminal<br />

Attach insulation sleeve<br />

Electricwire<br />

Connect wires <strong>of</strong> the same gauge to both sides<br />

2. Tightening torque for the terminal screws.<br />

• Use the correct screwdriver for tightening the terminal<br />

screws. If the blade <strong>of</strong> screwdriver is too small, the<br />

head <strong>of</strong> the screw might be damaged, and the screw<br />

will not be properly tightened.<br />

• If the terminal screws are tightened too hard, screws<br />

might be damaged.<br />

3. Do not connect wires <strong>of</strong> different gauge to the<br />

same grounding terminal. Loose connection may<br />

deteriorate protection.<br />

4. At the unit, keep proper separation between transmissio<br />

and power sup<strong>pl</strong>y wiring.<br />

The equipment may malfunction if subjected to<br />

electrical (external) noise.<br />

5. Never connect power sup<strong>pl</strong>y wiring to the terminal<br />

block for remote controller wiring. A mistake <strong>of</strong><br />

the sort could damage the entire system.<br />

6. Use only specified wire and tightly connect wires<br />

to terminals. Be careful that wires should not<br />

<strong>pl</strong>ace external stress on terminals. Keep wiring in<br />

neat order and so as not to obstruct other equipment<br />

such as popping open the electric parts box<br />

cover. Make sure the cover closes tight.<br />

Incom<strong>pl</strong>ete connections could result in overheating,<br />

and in worst case, electric shock or fire.<br />

CAUTION<br />

After the confirmation <strong>of</strong> the above conditions, prepare the<br />

wiring as follows:<br />

1) Never fail to have an individual power circuit specifically<br />

for the air conditioner. As for the method <strong>of</strong> wiring, be<br />

guided by the circuit diagram posted on the inside <strong>of</strong><br />

control cover.<br />

2) The screw which fasten the wiring in the casing <strong>of</strong> electrical<br />

fittings are liable to become loose from vibrations<br />

to which the unit is subjected during the course <strong>of</strong> transportation.<br />

Check them and make sure that they are all<br />

tightly fastened. (If they are loose, it could cause burnout<br />

<strong>of</strong> the wires.)<br />

3) Confirm the specification <strong>of</strong> power source.<br />

4) Confirm that electrical capacity is sufficient.<br />

5) See to that the starting voltage is maintained at more<br />

than 90 percent <strong>of</strong> the rated voltage marked on the<br />

name <strong>pl</strong>ate.<br />

6) Confirm that the cable thickness is as specified in the<br />

power source specification.<br />

(Particularly note the relation between cable length and<br />

thickness.)<br />

7) Always install an earth leakage circuit breaker in a wet<br />

or moist area.<br />

8) The following would be caused by voltage drop.<br />

• Vibration <strong>of</strong> a magnetic switch, which will damage the<br />

contact point, fuse breaking, disturbance <strong>of</strong> the normal<br />

function <strong>of</strong> the overload.<br />

9) The means for disconnection from a power sup<strong>pl</strong>y shall<br />

be incorporated in the fixed wiring and have an air gap<br />

contact separation <strong>of</strong> at least 3mm in each<br />

active(phase) conductors.<br />

Installation <strong>of</strong> indoor unit 329


Ceiling and floor, Ceiling suspended only<br />

3.3. Ceiling and floor, Ceiling suspended only<br />

• Please read the instruction sheets com<strong>pl</strong>etely before installing the product.<br />

• When the power cord is damaged, re<strong>pl</strong>acement work shall be performed by authorized personnel only.<br />

• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.<br />

1) Installation parts provided<br />

① Installation Plate (VB, 2pcs)<br />

② Installation Plate (VE, 1pcs)<br />

③ Washer Bolt (M8×L25, 4pcs, type "A")<br />

④ Floor Mount Bracket (1pcs)<br />

⑤ Drain Hose, Insulated<br />

⑥ Drain Hose Hanger and screw<br />

2) The other installation parts needed<br />

⑦ Suspension Bolt<br />

⑧ Bolts for Mount Bracket<br />

- Connecting Tube(mm)<br />

• Gas side : Ø12.7, Ø15.88, Ø9.52<br />

• Liquid side : Ø6.35, Ø9.52<br />

- Connecting Cable<br />

- Drain Hose for extention<br />

2<br />

(Floor mounting)<br />

5CSL0-06B<br />

330 Installation <strong>of</strong> indoor unit<br />

7<br />

6<br />

8<br />

4<br />

1<br />

(Ceiling/wall mounting)<br />

3.3.1 How to set Floor/Ceiling selection button (UV09 NED,UV12 NED)<br />

CN_ CENTRAL<br />

CONTROL<br />

CN_ WRITE<br />

CN_ DISPLAY<br />

CN_ OPTION<br />

CN_ REMO<br />

CN_ PIPE/OUT<br />

SW01<br />

CVT 5:Install<br />

Off (Factory Set) Ceiling<br />

On Bottom<br />

CN_ PIPE/IN CN_ ROOM<br />

CN_ vain 1<br />

CN_ vain 2<br />

CN_ DOOR CN_ MOTOR1<br />

CN_ MOTOR2<br />

BOTTOM INSTALLATION : SET No.5 SW "ON"<br />

CEILING INSTALLATION : NO NEED TO SET SW01 MAIN PCB.<br />

CN_ POWER<br />

5<br />

3


5CSL0-06B Ceiling and floor, Ceiling suspended only<br />

3.3.2 Selection <strong>of</strong> the best location<br />

• There should not be any heat source or steam near the<br />

unit.<br />

• There should not be any obstacles to the air circulation.<br />

• There should be provision <strong>of</strong> easy condensate drain.<br />

• Taking into accounting the noise prevention criteria, spot<br />

the installation location.<br />

• Do not install the unit near the door way.<br />

• Keep proper distances, <strong>of</strong> the unit, from ceiling, fence,<br />

floor, walls and other obstacles as shown in figure.<br />

• The indoor unit must have the maintenance space.<br />

• The mounting ceiling or wall should be strong and solid<br />

enough to protect it from the vibration.<br />

More than<br />

20cm<br />

More than eye-level<br />

More than<br />

20cm<br />

3.3.3 Installation<br />

(Ceiling installation)<br />

(Floor/wall installation)<br />

Models : UV18, UV24, UV30<br />

More than<br />

20cm<br />

1. Before Installing, prepare Installation<br />

Plates<br />

• 'Installation Plates' are attached at the bottom <strong>of</strong> indoor<br />

unit.<br />

Detach them by removing each 3 screws at both sides.<br />

• Pull the upper right and left side <strong>of</strong> 'Inlet Grille' to the front,<br />

and it will stop at slightly tilted position.<br />

• Unhook the 'Inlet hanger' from the 'Hanger screw' on the<br />

both left and right side.<br />

• Detach the 'Inlet Grille' from the Indoor Unit.<br />

• Detach 'Side Plate (R,L)' by removing each 3 screws on<br />

both sides.<br />

R<br />

R<br />

More than<br />

20cm<br />

Install Plate<br />

Inlet Grille<br />

Side Plate<br />

Inlet hanger<br />

1) Installation on the ceiling<br />

① Measure and mark the position for the Suspension bolts<br />

and the piping hole.<br />

② Drill the hole for anchor nut on the ceiling.<br />

Drill the piping hole on the wall slightly tilted to the outdoor<br />

side using a ø70 hole-core drill.<br />

❈ Before secure the Installation Plates, select the bent<br />

direction <strong>of</strong> the Installion Plate to the inside or the outside<br />

according to the installation circumstances.<br />

Installation <strong>of</strong> indoor unit 331<br />

1)<br />

2)<br />

1076<br />

Suspension<br />

bolt<br />

R<br />

265<br />

Hanger<br />

screw<br />

Center-line for the<br />

piping hole<br />

1236 265<br />

Indoor WALL<br />

Outdoor<br />

5~7mm


Ceiling and floor, Ceiling suspended only<br />

③ Insert the nuts and washer onto the suspension bolts for<br />

locking the suspension bolts on the ceiling.<br />

④ Mount the suspension bolts to the anchor-nuts firmly.<br />

⑤ Secure the installation <strong>pl</strong>ates onto the suspension bolts<br />

(adjust level roughly) using nuts, washers and spring<br />

washers.<br />

1<br />

2<br />

Suspension<br />

bolts<br />

Spring<br />

washer<br />

Nut<br />

max.<br />

12mm Washer<br />

Ceiling<br />

Nut<br />

Suspension<br />

bolts<br />

Anchor nut<br />

Washer<br />

⑥ Engage 2 hooks on the both left and right side <strong>of</strong> the unit<br />

to the lower slot <strong>of</strong> Installation <strong>pl</strong>ates.<br />

⑦ Adjust a level with a level gauge on the direction <strong>of</strong> leftright,<br />

back-forth by adjusting suspension bolts.<br />

⑧ Move the hooks on the unit to the upper slot <strong>of</strong> installation<br />

<strong>pl</strong>ates. Then the unit will be declined to the bottomside<br />

so as to drain well.<br />

Suspension<br />

bolt<br />

Lower slot<br />

Level gauge<br />

R<br />

Installation <strong>pl</strong>ate<br />

Adjust a level<br />

5CSL0-06B<br />

⑨ Secure the unit to the installation <strong>pl</strong>ates with four M8<br />

bolts and washers.<br />

⑩ Before working, refer to 'Connecting pipe and cable to<br />

indoor unit.<br />

⑪ Fit the projection hooks <strong>of</strong> the side <strong>pl</strong>ates to the 'Side<br />

Panel'<br />

⑫ Fasten the screws.<br />

332 Installation <strong>of</strong> indoor unit<br />

R<br />

R<br />

R<br />

R<br />

R<br />

Upper slot


5CSL0-06B Ceiling and floor, Ceiling suspended only<br />

⑬ Hook up the Inlet Grille Hook to the cabinet. • Fit the projection hooks <strong>of</strong> the side <strong>pl</strong>ates to the 'Side<br />

Panel' and the 'Front Panel' by lifting it.<br />

Inlet hanger<br />

• Fasten the screws.<br />

CAUTION : Installation Information For Declination<br />

1. Install declination <strong>of</strong> the indoor unit is very important for the drain <strong>of</strong> the convertible type air conditioner.<br />

2. Minimum thickness <strong>of</strong> the insulation for the connecting pipe shall be 10mm.<br />

3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.<br />

Drain hose<br />

R<br />

Hook<br />

Cabinet Bottom<br />

5~10mm<br />

10~20mm<br />

Front <strong>of</strong> view<br />

• The unit must be horizontal or inclined at angle.<br />

• The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain<br />

direction as shown in fig.<br />

Ceiling<br />

Ceiling<br />

Side <strong>of</strong> view<br />

Ceiling<br />

10~20mm<br />

• The unit must be declined to the bottomside <strong>of</strong> the unit when finished installation.<br />

Installation <strong>of</strong> indoor unit 333<br />

1<br />

R<br />

R<br />

2


Ceiling and floor, Ceiling suspended only<br />

2) Installation on the Wall<br />

① Select and mark the position for fixing bolts and piping<br />

hole.<br />

Decide the position for fixing bolts slightly tilted to the<br />

drain direction after considering the direction <strong>of</strong> drain<br />

hose.<br />

② Drill the hole for anchor nut on the wall.<br />

③ Secure the 'Install <strong>pl</strong>ate' onto the wall with four anchor<br />

bolts, washers and spring washers.<br />

Nut<br />

Spring<br />

washer<br />

more than<br />

260<br />

Washer<br />

Anchor nut<br />

Less than<br />

12mm<br />

Wall<br />

1076<br />

※ Before securing the installation <strong>pl</strong>ates, select the bent<br />

direction <strong>of</strong> the 'Installation <strong>pl</strong>ates' to the inside or outside<br />

according to the installation circumstances.<br />

1236<br />

265<br />

Unit: mm<br />

Unit: mm<br />

5CSL0-06B<br />

3) Install the indoor unit on the installation <strong>pl</strong>ate.<br />

① Insert 2 hooks on the both left and right side <strong>of</strong> the unit to<br />

the inner slot (wall side) <strong>of</strong> the Installation Plate.<br />

② Secure the unit to the Installation Plate with four M8 bolts<br />

and washers.<br />

• Before working, refer to "Connecting pipe<br />

and cable to Indoor Unit".<br />

③ Fit the projection hooks <strong>of</strong> the side <strong>pl</strong>ates to the 'Side<br />

Panel' and the 'Front Panel' by lifting it.<br />

④ Fasten the screws.<br />

⑤ Hook up the Inlet Grille Hook to the cabinet.<br />

⑥ Hang the Inlet Hanger to the screw.<br />

334 Installation <strong>of</strong> indoor unit<br />

R<br />

Inner slot


5CSL0-06B Ceiling and floor, Ceiling suspended only<br />

4) Installation on the floor<br />

Installation <strong>of</strong> mount bracket.<br />

① Select and mark the position for Mount Brackets and the<br />

piping hole.<br />

② Drill the hole for the anchor nut on the wall.<br />

③ Drill the piping hole using a ø70 hole-core drill.<br />

④ Secure the mount brackets on the wall with four M4<br />

screws.<br />

5) Install the indoor unit on the mount brackets.<br />

① Engage the slot at the back <strong>of</strong> the unit with mount bracket.<br />

Slot<br />

Floor mount<br />

bracket<br />

From the left wall<br />

more than 760mm<br />

From the<br />

right wall<br />

more than 840mm<br />

448mm<br />

6) After installing, reassemble detached parts.<br />

① Hang the 'Inlet grille' and hook the 'Inlet hanger' to the<br />

hanger screw.<br />

② Assemble the 'Side <strong>pl</strong>ates(R,L)' with 2 screws on both<br />

left and right side.<br />

Slot<br />

Wall<br />

Floor mount<br />

bracket<br />

Install <strong>pl</strong>ate<br />

Piping hole<br />

Models : UV38, UV42, UV48, UV60<br />

1) Installation on the ceiling<br />

① Prepare 4 suspension bolts (Each bolts length should be<br />

same.)<br />

② Measure and mark the position for the suspension bolts<br />

and the piping hole.<br />

③ Insert the nuts and washer onto the suspension bolts for<br />

locking the suspension bolts on the ceiling.<br />

④ Mount the suspension bolts to the anchor-nuts firmly.<br />

⑤ Secure the hangers onto the suspension bolts (adjust<br />

level roughly) using nuts, washers and spring washers.<br />

⑥ Adjust a level with a level gauge on the direction <strong>of</strong> leftright,<br />

back-forth by adjusting suspension bolts.<br />

⑦ Adjust a level on the direction <strong>of</strong> top-bottom by adjusting<br />

supension bolts. Then the unit will be declined to the bottomside<br />

so as to drain well.<br />

Nut<br />

Suspension<br />

bolts<br />

piping hole<br />

(Ø45)<br />

Suspension bolt<br />

Installation <strong>of</strong> indoor unit 335<br />

Ceiling<br />

Anchor nut<br />

CAUTION<br />

Washer<br />

40<br />

820<br />

Suspension<br />

bolts<br />

Spring<br />

washer<br />

Hangen<br />

Max.<br />

12mm<br />

235<br />

Nut<br />

Washer<br />

50<br />

100<br />

Reference<br />

<strong>of</strong> piping<br />

hole (Ø25)<br />

• Tighten the nut and bolt to prevent unit from falling.


Ceiling and floor, Ceiling suspended only<br />

Hanging bolt<br />

(W3/8 or M10)<br />

Nut<br />

(W3/8 or M10)<br />

Spring washer<br />

(M10)<br />

2) Installation on the wall<br />

Flat washer for M10<br />

(accessory)<br />

Flat washer for M10<br />

(accessory)<br />

Nut<br />

(W3/8 or M10)<br />

The wall you select should be strong enough to prevent<br />

vibration<br />

① Mount the installation <strong>pl</strong>ate on the wall with<br />

type "A" screws. If mounting the unit on a concrete wall,<br />

use anchor bolts.<br />

② Mount the installation <strong>pl</strong>ate horizontally by aligning the<br />

centerline using a level.<br />

Type "A" screw<br />

Installation Plate<br />

③ Measure the wall and mark the centerline. It is also<br />

important to use caution concerning the location <strong>of</strong> the<br />

installation <strong>pl</strong>ate-routing <strong>of</strong> the wiring to power outlets is<br />

through the walls typically. Drilling the hole through the<br />

wall for piping connections must be done safely.<br />

70<br />

Ø70mm<br />

Installation <strong>pl</strong>ate<br />

120<br />

Left rear piping more than 200<br />

Right rear piping<br />

Foor<br />

Ø70mm<br />

70<br />

Models : UV36, UV42, UV48, UV60<br />

1) Open side cover<br />

5CSL0-06B<br />

1. Remove two screws from side-cover as shown in fig.<br />

2. Unlock side-cover from side panel by slightly pulling<br />

the edge <strong>of</strong> side cover.<br />

3. Tap the side-cover with your palm on the<br />

backside.(Inlet grill side.)<br />

4. Hold the side-cover with other hand while tapping to<br />

prevent it to fall down.<br />

Recommendation: it is recommended to select the left<br />

side for drain to have common hole in the side-cover<br />

along with pipe and wiring.<br />

5. Remove the rubber stop<strong>pl</strong>e in the desired drain<br />

direction.<br />

6. Knock out the pipe hole from the left side-cover with<br />

the help or nipper/<strong>pl</strong>ier.<br />

7. Knock hole on right side-cover only if right side is<br />

selected for water drain.<br />

336 Installation <strong>of</strong> indoor unit<br />

2<br />

Edge part<br />

1


5CSL0-06B Ceiling and floor, Ceiling suspended only<br />

2) Mounting the anchor nut and bold<br />

• Prepare 4 suspension bolts. (Each bolts length<br />

should be same.)<br />

• Measure and mark the position for the Suspension<br />

bolts and the piping hole.<br />

• Drill the hole for anchor nut on the ceiling.<br />

• Insert the nuts and washer onto the suspension<br />

bolts for locking the suspension bolts on the ceiling.<br />

• Mount the suspension bolts to the anchor-nuts<br />

firmly.<br />

• Secure the hangers onto the Suspension bolts<br />

(adjust level roughly.) using nuts, washers and<br />

spring washers.<br />

• Adjust a level with a level gauge on the direction<br />

<strong>of</strong> left-right, back-forth by adjusting suspension<br />

bolts.<br />

• Adjust a level on the direction <strong>of</strong> top-bottom by<br />

adjusting supension bolts. Then the unit will be<br />

declined to the bottomside so as to drain well.<br />

MODEL<br />

DIM.<br />

A B<br />

VL 1655 320<br />

VK 1255 320<br />

VJ 855 320<br />

Ceiling<br />

Nut<br />

Suspension<br />

bolts<br />

Anchor nut<br />

Washer<br />

A<br />

Suspension bolt<br />

Suspension<br />

bolts<br />

Spring<br />

washer<br />

Hangen<br />

Max.<br />

12mm<br />

B<br />

Nut<br />

Washer<br />

3.3.4 Piping and drainage<br />

1) Installation on the ceiling<br />

• Connecting the pipes to the indoor unit<br />

The pipe can be connected to right side, bottom or back <strong>of</strong><br />

the unit.<br />

• For the right side piping<br />

① After bending an end <strong>of</strong> the connecting tube, align the<br />

center <strong>of</strong> the pipings and sufficiently tighten the flare nut<br />

with fingers.<br />

② Finally, tighten the flare nut with torque wrench until the<br />

wrench clicks.<br />

③ Connect the drain hose insulated to the drain outlet. Drain<br />

hose should go under the hose bracket as shown in figure ❹.<br />

④ Hang the drain hose on the hose hanger and fix it to the<br />

hole <strong>of</strong> the hose bracket with a screw.<br />

Installation <strong>of</strong> indoor unit 337<br />

R<br />

4<br />

R<br />

Piping<br />

2<br />

Drain hose<br />

Hose hanger<br />

5<br />

1<br />

Hose<br />

Bracket<br />

3


Ceiling and floor, Ceiling suspended only<br />

• For the bottom side piping<br />

① Remove the knock-out from the bottomside <strong>of</strong> inlet grille<br />

② Align the center <strong>of</strong> the pipings and sufficiently tighten the<br />

flare nut with fingers.<br />

③ Finally, tighten the flare nut with torque wrench until the<br />

wrench clicks.<br />

④ Connect the drain hose insulated to the drain outlet.<br />

⑤ Hang the drain hose on the hose hanger and fix it to the<br />

hole <strong>of</strong> cabinet bottom with a screw.<br />

R<br />

Hose<br />

hanger<br />

• Connecting the drain hose<br />

① The drain hose can be connected to not only the right<br />

side but also left side <strong>of</strong> the unit.<br />

② If the drain hose is connected to the left side, it should go<br />

through the cabinet bottom.<br />

③ Hang the drain hose on the hose hanger and fix it to the<br />

hole <strong>of</strong> cabinet bottom with a screw.<br />

Hose hanger<br />

Drain hose<br />

Bottom<br />

5CSL0-06B<br />

2) Installation on the wall or floor<br />

• Connecting the pipes to the indoor unit<br />

• For the right rear piping<br />

① Remove the knock-out from the back side <strong>of</strong> the cabinet.<br />

② After bending an end <strong>of</strong> the connecting tube, align the<br />

center <strong>of</strong> the pipings and sufficiently tighten the flare nut<br />

with fingers.<br />

③ Finally, tighten the flare nut with torque wrench until the<br />

wrench clicks.<br />

④ Connect the drain hose to the drain outlet.<br />

⑤ Tape the drain hose to the pipings to avoid coming <strong>of</strong>f <strong>of</strong><br />

the drain-outlet.<br />

338 Installation <strong>of</strong> indoor unit<br />

Taping<br />

Taping<br />

Drain hose<br />

Wired remote<br />

control<br />

Drain hose<br />

Piping<br />

• For the right side piping<br />

① After bending an end <strong>of</strong> the connecting tube, align the<br />

center <strong>of</strong> the pipings and sufficiently tighten the flare nut<br />

with fingers.<br />

② Finally, tighten the flare nut with torque wrench until the<br />

wrench clicks.<br />

③ Connect the drain hose to the drain outlet.<br />

④ Tape the drain hose to the pipings to avoid coming <strong>of</strong>f<br />

the drain-outlet.<br />

Taping<br />

Drain hose<br />

Piping<br />

• For the right bottom piping<br />

① Align the center <strong>of</strong> the pipings and sufficiently tighten the<br />

flare nut with fingers.<br />

② Finally, tighten the flare nut with torque wrench until the<br />

wrench clicks.<br />

③ Connect the drain hose to the drain outlet.<br />

Piping<br />

Connecting<br />

Cable


5CSL0-06B Ceiling and floor, Ceiling suspended only<br />

• Connecting the drain hose<br />

① The drain hose can be connected to not only right side<br />

but also left side <strong>of</strong> the unit.<br />

Drain hose<br />

3) Checking the drainage<br />

• Remove the air filter.<br />

• Check the drainage.<br />

① Spray one or two glasses <strong>of</strong> water upon the evaporator.<br />

② Ensure that water flows through drain hose <strong>of</strong> indoor unit<br />

without any leakage.<br />

R<br />

R<br />

Rear<br />

Bottom<br />

① To remove air filter, take hold <strong>of</strong> tab and pull slightly<br />

upwards.<br />

3.3.5 Electric wiring work<br />

1) General instructions<br />

① All field sup<strong>pl</strong>ied parts and materials, electric works must<br />

conform to local codes.<br />

Use copper wire only.<br />

② Follow the "WIRING DIAGRAM” attached to the unit body to<br />

wire the outdoor unit, indoor units and the remote controller.<br />

③ All wiring must be performed by an authorized electrician.<br />

③ This system consists <strong>of</strong> multi<strong>pl</strong>e indoor units. Mark each<br />

indoor unit as unit A, unit B...., and be sure the terminal<br />

board wiring to the outdoor unit and indoor unit are properly<br />

matched. If wiring and piping between the outdoor unit and<br />

an indoor unit are mismatched, the system may cause a<br />

malfunction.<br />

④ A circuit breaker capable <strong>of</strong> shutting down the power sup<strong>pl</strong>y<br />

to the entire system must be installed.<br />

2) Wiring connection<br />

• Connecting cables to the indoor unit<br />

① Remove the air guide - L by loosening 2 screws after removing<br />

the inlet grille from the Indoor unit.<br />

② Connect the wires to the terminals on the control board individually<br />

according to the outdoor unit connection.<br />

• Ensure that the color <strong>of</strong> the wires <strong>of</strong> outdoor unit and the<br />

terminal No. are the same as those <strong>of</strong> indoor unit respectively<br />

Terminal block in indoor<br />

1(L) 2(N) 3 4<br />

Connected to outdoor Unit<br />

2) Clamping <strong>of</strong> cables<br />

① Arrange 2 power cables on the control panel.<br />

② First, fasten the steel clamp with a screw to the inner<br />

boss <strong>of</strong> control panel.<br />

③ For the cooling model, fix the other side <strong>of</strong> the clamp with<br />

a screw strongly.<br />

For the heat pump model, put the 0.75mm2 cable(thinner<br />

cable) on the clamp and tighten it with a <strong>pl</strong>astic clamp to<br />

the other boss <strong>of</strong> the control panel.<br />

④ In Australia, the length <strong>of</strong> power sup<strong>pl</strong>y cord measured<br />

from the entry <strong>of</strong> the power sup<strong>pl</strong>y cord to the middle <strong>of</strong><br />

live pin on the power <strong>pl</strong>ug should be over 1.8m.<br />

Installation <strong>of</strong> indoor unit 339


Ceiling and floor, Ceiling suspended only<br />

Air guide-l<br />

Indoor unit<br />

Clamp<br />

CAUTION<br />

CAUTION<br />

1<br />

Control<br />

panel<br />

• Make sure that the screws <strong>of</strong> the terminal are fixed<br />

tightly.<br />

• Make sure to attach the sealing material (field sup<strong>pl</strong>ied) to<br />

hole <strong>of</strong> wiring to prevent the infiltration <strong>of</strong> foreign particle<br />

from outside. Otherwise a short-circuit may occur inside the<br />

electric parts box<br />

• When clamping the wires, be sure no pressure is ap<strong>pl</strong>ied to<br />

the wire connections by using the included clamping material<br />

to make appropriate clamps. Also, when wiring, make<br />

sure the cover on the electric parts box fits snugly by<br />

arranging the wires neatly and attaching the electric parts<br />

box cover firmly. When attaching the electric parts box<br />

cover, make sure no wires get caught in the edges. Pass<br />

wiring through the holes to prevent damage to them.<br />

• Make sure the remote controller wiring, the wiring between<br />

the units, and other electrical wiring do not pass through the<br />

same locations outside <strong>of</strong> the unit, separating them properly,<br />

otherwise electrical noise (external static) could cause<br />

mistaken operation or breakage.<br />

R<br />

2<br />

5CSL0-06B<br />

1. Use round crimp-style terminals for connecting wires to<br />

the power sup<strong>pl</strong>y terminal block.<br />

If unavailable, observe the following points when wiring.<br />

① Do not connect wires <strong>of</strong> different gauge to the same power sup<strong>pl</strong>y<br />

terminal.<br />

② Use the specified electric wire. connect the wire securely to the<br />

terminal. Lock the wire down without ap<strong>pl</strong>ying excessive force<br />

to the terminal.<br />

2. Tightening torque for the terminal screws.<br />

① Use the correct screw driver for tightening the terminal screws.<br />

If the blade <strong>of</strong> screwdriver is too small, the head <strong>of</strong> the screw<br />

might be damaged, and the screw will not be properly tightened.<br />

② If the terminal screws are tightened too hard, screws might be<br />

damaged.<br />

3. Do not connect wires <strong>of</strong> different gauge to the same<br />

grounding terminal. Loose connection may deteriorate<br />

protection.<br />

4. Outside <strong>of</strong> the unit, keep proper separation between<br />

transmission and power sup<strong>pl</strong>y wiring. The equipment<br />

may malfunction if subjected to electrical (external)<br />

noise.<br />

5. Never connect power sup<strong>pl</strong>y wiring to the terminal<br />

block for remote controller wiring. A mistake <strong>of</strong> the sort<br />

could damage the entire system.<br />

6. Use only specified wire and tightly connect wires to terminals.<br />

Be careful wires do not <strong>pl</strong>ace external stress on<br />

terminals. Keep wiring in neat order and so as not to<br />

obstruct other equipment such as popping open the<br />

electric parts box cover. Make sure the cover closes<br />

tight. Incom<strong>pl</strong>ete connections could result in overheating,<br />

and in worse case, electric shock or fire.<br />

340 Installation <strong>of</strong> indoor unit<br />

NOTE<br />

Round crimp-style terminal<br />

Attach insulation sleeve<br />

Electric wire<br />

Connect wires <strong>of</strong> the same gauge to both sides


5CSL0-06B Ceiling concealed duct (High static)<br />

3.4 Ceiling concealed duct (High static)<br />

• Please read the instruction sheets com<strong>pl</strong>etely before installing the product.<br />

• When the power cord is damaged, re<strong>pl</strong>acement work shall be performed by authorized personnel only.<br />

• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.<br />

3.4.1 Accessories<br />

Check whether the following accessories are included with your unit.<br />

1) Standard accessories<br />

Name<br />

Quantity<br />

Clamp metal<br />

1 EA<br />

Air Sup<strong>pl</strong>y<br />

Drain hose<br />

1 EA<br />

Air sup<strong>pl</strong>y vents<br />

Air return vents<br />

Insulation for<br />

fitting<br />

Shape for gas pipe<br />

Remote controller<br />

1 set 6 EA 1 set<br />

for liquid pipe<br />

Air return<br />

Clamp<br />

Air filters<br />

(Optional)<br />

Remote controller<br />

Screws for<br />

duct flanges<br />

Air filter<br />

Can be installed<br />

inside return grill.<br />

(Other)<br />

• Owner's manual<br />

• Installation manual<br />

• Washers(8 pcs.)<br />

Installation <strong>of</strong> indoor unit 341


Ceiling concealed duct (High static)<br />

3.4.2 Selection <strong>of</strong> the best location<br />

Install the air conditioner in the location that satisfies the following<br />

conditions.<br />

1. The <strong>pl</strong>ace shall easily bear a load <strong>of</strong> the indoor unit.<br />

2. The <strong>pl</strong>ace should have enough area for inspection as shown<br />

in figure.<br />

3. The <strong>pl</strong>ace where the unit shall be leveled.<br />

4. The <strong>pl</strong>ace shall allow easy water drainage.(Suitable dimension<br />

“H” is necessary to get a slope to drain as figure.)<br />

5. The <strong>pl</strong>ace shall easily connect with the outdoor unit.<br />

6. The <strong>pl</strong>ace where the unit is not affected by an electrical<br />

noise.<br />

7. The <strong>pl</strong>ace where air circulation in the room will be good .<br />

8. There should not be any heat source or steam near the unit.<br />

3.4.3 Ceiling dimension, also hanging<br />

bolt location and service space<br />

1) Select an installation site where the following conditions<br />

are fulfilled and also that meets with your<br />

customer's approval.<br />

• If supporting structural members are not strong enough<br />

to take the units weight, the unit could fall out <strong>of</strong> <strong>pl</strong>ace<br />

and cause serious injury.<br />

• Where sufficient clearance <strong>of</strong> maintenance and service<br />

can be ensured.<br />

• Where optimum air distribution can be ensured.<br />

• Where nothing blocks the air passage.<br />

• Where condensate can be properly drained.<br />

• Where piping between indoor and outdoor units is possible<br />

within the allowable limit (Refer to the installation<br />

manual <strong>of</strong> the outdoor unit.)<br />

• Keep the indoor and outdoor units, power cable and<br />

transmission wiring, at least 1 m from TVs and radios,<br />

to prevent distorted pictures and static.(Depending on<br />

the type and source <strong>of</strong> the electrical waves, static may<br />

be heard even when more than 1 m away.)<br />

B<br />

A C<br />

Model A B C<br />

ABNH186HLAD [UB18 NHD]<br />

ABNH246HLAD [UB24 NHD]<br />

880 260 450<br />

ABNH306GLAD [UB30 NGD]<br />

ABNH366GLAD [UB36 NGD]<br />

ABNH426RLAD [UB42 NRD]<br />

1,180 298 450<br />

ABNH486RLAD [UB48 NRD]<br />

ABNH606RLAD [UB60 NRD]<br />

1,229 589 379<br />

Min. 460<br />

(Service space)<br />

30mm or more<br />

30mm or more<br />

5CSL0-06B<br />

2) Relative positions <strong>of</strong> indoor unit, suspension bolt<br />

and inspection hatch size<br />

3) Install a canvass duct to the air discharge outlet<br />

and air inlet so that vibration from the machine<br />

body is not transmitted to the duct or ceiling. You<br />

should also ap<strong>pl</strong>y acoustic (insulation material) to<br />

the inside <strong>of</strong> the duct, and vibration insulation<br />

rubber to the suspension bolts.<br />

4) Install suspension bolts.<br />

(Use bolts <strong>of</strong> 10 mm diameter.)<br />

• Install the equipment where supporting structures are<br />

strong enough to bear the equipment's weight. Use<br />

embedded inserts or anchor bolts with new buildings<br />

and hole-in-anchors with old buildings.<br />

342 Installation <strong>of</strong> indoor unit<br />

NOTE<br />

a<br />

If the service panel is at the top <strong>of</strong> the unit, then provide<br />

sufficient service clearance as per convenience.<br />

932<br />

882<br />

1232<br />

1182<br />

Model A<br />

ABNH186HLAD [UB18 NHD]<br />

ABNH246HLAD [UB24 NHD]<br />

900<br />

ABNH306GLAD [UB30 NGD]<br />

ABNH366GLAD [UB36 NGD]<br />

ABNH426RLAD [UB42 NRD]<br />

1200<br />

ABNH486RLAD [UB48 NRD]<br />

ABNH606RLAD [UB60 NRD]<br />

1320<br />

120<br />

Inspection<br />

hatch 600 x 600<br />

150<br />

740<br />

740<br />

Inspection<br />

hatch 600 x 600


5CSL0-06B Ceiling concealed duct (High static)<br />

3.4.4 Position <strong>of</strong> suspension bolt<br />

① Install the unit leaning to a drainage hole side as given in<br />

the figure above for easy water drainage.<br />

② A <strong>pl</strong>ace where the unit will be leveled and that can support<br />

the weight <strong>of</strong> the unit.<br />

③ A <strong>pl</strong>ace where the unit can withstand its vibration.<br />

④ A <strong>pl</strong>ace where service can be easily performed.<br />

⑤ Select and mark the position for fixing bolts.<br />

⑥ Drill the hole for set anchor on the face <strong>of</strong> ceiling.<br />

CAUTION<br />

M10 Nut x 4<br />

M10 SP. washer x 4<br />

M10 washer<br />

(Local<br />

sup<strong>pl</strong>y)<br />

x 4<br />

M10 washer x 4<br />

M10 SP. washer x 4<br />

M10 Nut<br />

(Local<br />

sup<strong>pl</strong>y)<br />

x 4<br />

• Tighten the nut and bolt to prevent unit from<br />

falling.<br />

⑦ Insert the set anchor and washer on the suspension bolts<br />

for locking the suspension bolts on the ceiling.<br />

⑧ Mount the suspension bolts to the set anchor firmly.<br />

⑨ Secure the installation <strong>pl</strong>ates on the suspension bolts<br />

(adjust level roughly) using nuts, washers and spring<br />

washers.<br />

Old building New building<br />

1 Set anchor<br />

2 Plate washer<br />

3 Spring washer<br />

4 Nut<br />

5 Suspension<br />

bolts<br />

Installation <strong>of</strong> indoor unit 343


Ceiling concealed duct (High static)<br />

3.4.5 Connection pipes to the indoor<br />

unit<br />

1) Refrigerant piping work<br />

<strong>pl</strong>ease refer “REFRIGERANT PIPING WORK”.<br />

2) Piping insulation<br />

① Perform heat insulation work com<strong>pl</strong>etely on both gas and<br />

the liquid pipe. Because improper insulation will result<br />

due condensate formation over pipe.<br />

② Use the heat insulation material for the refrigerant piping<br />

which has an excellent heat resistance (over 120°C).<br />

③ Precautions in high humidity circumstance.<br />

④ Refer to the insulation works.<br />

CAUTION<br />

Liquid pipe<br />

Union for gas pipe<br />

Clamp for insulation<br />

(Local sup<strong>pl</strong>y)<br />

Insulation<br />

(Local sup<strong>pl</strong>y)<br />

Refrigerant pipe and thermal<br />

insulation(Local sup<strong>pl</strong>y)<br />

Thermal insulation for refrigerant pipe<br />

(Local sup<strong>pl</strong>y) Thermal insulation for<br />

piping(Local sup<strong>pl</strong>y)<br />

Overlap with<br />

insulation<br />

Make sure that there is no clearance here.<br />

• Make sure to insulate any field piping all the way to the<br />

piping connection inside the unit. Any exposed piping<br />

may cause condensation or burns if touched.<br />

3) Indoor unit drain piping<br />

5CSL0-06B<br />

① During drain piping connection, be careful not to exert<br />

extra force on the drain port on the indoor unit.<br />

② The outside diameter <strong>of</strong> the drain connection on the<br />

indoor unit is 32mm.<br />

Piping material: Polyvinyl chloride pipe inner diameter<br />

Ø 25mm and pipe fitting<br />

CAUTION<br />

1. Decline Installation <strong>of</strong> indoor unit is very important for<br />

the drain <strong>of</strong> the duct type air conditioner.<br />

2. Minimum thickness <strong>of</strong> the insulation for the connecting<br />

pipe should be 5mm.<br />

4) Caution for gradient <strong>of</strong> unit and drain piping<br />

- Without drain pump<br />

① Always lay the drain with downward inclination (1/50 to<br />

1/100).<br />

Prevent any upward flow or reverse flow in any part.<br />

② 10mm or thicker formed thermal insulation shall always<br />

be provided for the drain pipe.<br />

Approx 2~3mm<br />

Attached drain hose<br />

Downward 1/50~1/100 or more<br />

Bottom <strong>of</strong> unit<br />

※ U-trap is not required for low static model in which the<br />

external static pressure is below 50 pa(5mm Aq)<br />

344 Installation <strong>of</strong> indoor unit<br />

50mm<br />

or more<br />

50mm<br />

or more


5CSL0-06B Ceiling concealed duct (High static)<br />

- With drain pump<br />

① Possible drain head is upto 700mm.<br />

② Keep the drain pipe downward stope upto 1/50~1/100.<br />

Prevent any upward flow or reverse flow in any part.<br />

③ 10mm or thicker insulation should be provided for the<br />

drain pipe.<br />

Unit<br />

Drain Pipe<br />

Drain Pump<br />

3) Checking the drain<br />

1) Checking the drain<br />

① Remove the air filter.<br />

MAX 700mm<br />

Elbow<br />

Drain pump<br />

1/50~1/100<br />

Thermal insulattion<br />

(Local sup<strong>pl</strong>y)<br />

Drain pipe<br />

(Local sup<strong>pl</strong>y)<br />

2. Check the drain.<br />

① Poor eough water on the drain pan.<br />

② Ensure that water flows through the drain pipe from<br />

indoor unit without any leakage.<br />

3.4.6 Electric wiring work<br />

1) General instructions<br />

① All field sup<strong>pl</strong>ied parts and materials, electric works must<br />

conform to local codes.<br />

Use copper wire only.<br />

② Follow the "WIRING DIAGRAM” attached to the unit<br />

body to wire the outdoor unit, indoor units and the remote<br />

controller.<br />

③ All wiring must be performed by an authorized electrician.<br />

④ This system consists <strong>of</strong> multi<strong>pl</strong>e indoor units. Mark each<br />

indoor unit as unit A, unit B..., and be sure the terminal<br />

board wiring to the outdoor unit and indoor unit are properly<br />

matched. If wiring and piping between the outdoor<br />

unit and an indoor unit are mismatched, the system may<br />

cause a malfunction.<br />

⑤ A circuit breaker capable <strong>of</strong> shutting down the power<br />

sup<strong>pl</strong>y to the entire system must be installed.<br />

Installation <strong>of</strong> indoor unit 345


Ceiling concealed duct (High static)<br />

2) Wiring connection<br />

Connect the wires to the terminals on the control board individually<br />

according to the outdoor unit connection.<br />

① Ensure that the color <strong>of</strong> the wires <strong>of</strong> outdoor unit and the<br />

terminal No. are the same as those <strong>of</strong> indoor unit respectively<br />

30k/36k/42k/48k/60kBtu/h.<br />

② If the sup<strong>pl</strong>y cord is damaged, it must be re<strong>pl</strong>aced by a<br />

special cord or assembly availible from the manufacturer<br />

<strong>of</strong> its service agent.<br />

WARNING<br />

Terminal block in indoor<br />

1(L) 2(N) 3 4<br />

Connected to outdoor unit<br />

1(L) 2(N)<br />

POWER INPUT<br />

• Make sure that the screws <strong>of</strong> the terminal are fixed tightly.<br />

CAUTION<br />

• Make sure to attach the sealing material or (field sup<strong>pl</strong>ied)<br />

to hole <strong>of</strong> wiring to prevent the infiltration <strong>of</strong> foreign<br />

particle from outside. Otherwise a short-circuit may<br />

occur inside the electric parts box<br />

• When clamping the wires, be sure no pressure is ap<strong>pl</strong>ied<br />

to the wire connections by using the included clamping<br />

material to make appropriate clamps. Also, when wiring,<br />

make sure the cover on the electric parts box fits snugly<br />

by arranging the wires neatly and attaching the electric<br />

parts box cover firmly. When attaching the electric parts<br />

box cover, make sure no wires get caught in the edges.<br />

Pass wiring through the holes to prevent damage to<br />

them.<br />

• Make sure the remote controller wiring, the wiring<br />

between the units, and other electrical wiring do not pass<br />

through the same locations outside <strong>of</strong> the unit, separating<br />

them properly, otherwise electrical noise (external<br />

static) could cause product malfunction.<br />

5CSL0-06B<br />

1. Use round crimp-style terminals for connecting<br />

wires to the power sup<strong>pl</strong>y terminal block. If<br />

unavailable, observe the following points when<br />

wiring.<br />

① Do not connect wires <strong>of</strong> different gauge to the same<br />

power sup<strong>pl</strong>y terminal.<br />

② Use the specified electric wire. Connect the wire securely<br />

to the terminal. Lock the wire down without ap<strong>pl</strong>ying<br />

excessive force to the terminal.<br />

2 Tightening torque for the terminal screws.<br />

① Use the correct screwdriver for tightening the terminal<br />

screws. If the blade <strong>of</strong> screwdriver is too small, the head<br />

<strong>of</strong> the screw might be damaged, and the screw will not<br />

be properly tightened.<br />

② If the terminal screws are tightened too hard, screws<br />

might be damaged.<br />

3. Do not connect wires <strong>of</strong> different gauge to the<br />

same grounding terminal. Loose connection may<br />

deteriorate protection.<br />

4. Outside <strong>of</strong> the unit, keep proper separation<br />

between transmission and power sup<strong>pl</strong>y wiring.<br />

The equipment may malfunction if subjected to<br />

electrical (external) noise.<br />

5. Never connect power sup<strong>pl</strong>y wiring to the terminal<br />

block for remote controller wiring. A mistake <strong>of</strong><br />

the sort could damage the entire system.<br />

6. Use only specified wire and tightly connect wires<br />

to terminals. Be careful wires do not <strong>pl</strong>ace external<br />

stress on terminals. Keep wiring in neat order<br />

and so as not to obstruct other equipment such as<br />

popping open the electric parts box cover. Make<br />

sure the cover closes tight. Incom<strong>pl</strong>ete connections<br />

could result in overheating, and in worse<br />

case, electric shock or fire.<br />

346 Installation <strong>of</strong> indoor unit<br />

NOTE<br />

Round crimp-style terminal<br />

Attach insulation sleeve<br />

Electric wire<br />

Connect wires <strong>of</strong> the same gauge to both sides


5CSL0-06B Console (Floor stand)<br />

3.5 Console (Floor stand)<br />

3.5.1 Accessories<br />

Check whether the following accessories are included with your unit.<br />

1) Standard accessories<br />

Name<br />

Quantity<br />

Shape<br />

❈ You should purchase the installation parts.<br />

Install <strong>pl</strong>ate<br />

1 EA<br />

Drain hose<br />

1 EA<br />

Remote controller<br />

& holder<br />

Battery<br />

Sleeve<br />

Bushing-Sleeve<br />

Putty(Gum Type Sealant)<br />

Bend the pipe as closely<br />

on the wall as possible,<br />

but be careful that it<br />

doesn't break.<br />

Allergy filter<br />

Screw<br />

1 set 1 EA 1 set<br />

• Fixing Screw for<br />

R. Controller<br />

Holder<br />

• Fixing Screw for<br />

Install Plate 4 x<br />

25mm<br />

• Wood Screw for<br />

Indoor fixation<br />

(Other)<br />

• Owner's<br />

manual<br />

• Installation<br />

manual<br />

• Washers<br />

(8 pcs.)<br />

Installation <strong>of</strong> indoor unit 347


Console (Floor stand)<br />

3.5.2 Selection <strong>of</strong> the best location<br />

Install the air conditioner in the location that satisfies the following<br />

conditions.<br />

1.There should not be any heat or steam near the unit.<br />

2. Select a <strong>pl</strong>ace where there are no obstacles around <strong>of</strong> the<br />

unit.<br />

3. Make sure that condensation drainage can be conveniently<br />

routed away.<br />

4. Do not install near a doorway.<br />

5. Ensure that the interval between a wall and the left (or right)<br />

<strong>of</strong> the unit is more than 300mm.<br />

6. Use a metal detector to locate studs to prevent unnecessary<br />

damage to the wall.<br />

7. It is away from electronic ignition type fluorescent lamps as<br />

they may shorten the remote controller range.<br />

8. Please check at least 1m away from television or radio.(It<br />

cause interference with the picture or sount)<br />

NOTE<br />

• Before choosing the installation site, <strong>pl</strong>ease obtain user<br />

approval<br />

• If the unit is installed below a window,check the interference<br />

<strong>of</strong> window curtain.(more than 300mm)<br />

• Because <strong>of</strong> dust problem, If the bottm height "H" is less<br />

than 100mm, Keep the bottom vane close not to make<br />

dust from the bottom.<br />

More than<br />

300<br />

250 or less<br />

from the Floor<br />

More than 300<br />

More than<br />

300<br />

(Unit : mm)<br />

3.5.3 Installation<br />

1) Preparation / Removing front panel<br />

5CSL0-06B<br />

① Open the front grille by pulling forward<br />

② Then pull out the link <strong>of</strong> grille from groove in front panel.<br />

③ Then pull out 2 hinges <strong>of</strong> grille from grooves in front<br />

panel.<br />

④ Then remove 4 screws, dismount the front panel while<br />

pulling it forward.<br />

2) Preparation / For Moldings , Side Piping,<br />

and Concealed Installation<br />

① For Moldings<br />

• Remove the slit portions on the Rear Panel.<br />

Remove<br />

348 Installation <strong>of</strong> indoor unit


5CSL0-06B Console (Floor stand)<br />

② For Concealed Installation<br />

• Remove the 6 screws.<br />

• Remove the Upper Deco cover.<br />

• Remove the Side Deco covers.<br />

Side Deco cover<br />

③ For Side Piping (Reference ②)<br />

• Remove the Deco Covers.<br />

• Remove the slit portions<br />

• Assemble the Deco Covers.<br />

3) Refrigerant Piping<br />

① The location <strong>of</strong> hole is different depending on which side<br />

<strong>of</strong> the pipe is taken out.<br />

② Drill a hole (Ø70mm)in the point indicated by symbol<br />

in the illustration as below<br />

45<br />

Upper Deco cover<br />

Left bottom piping 90 75 Right bottom piping<br />

Right back piping<br />

50<br />

Left/right piping<br />

40<br />

Wall<br />

60<br />

90 75<br />

Left back piping Right back piping<br />

45<br />

45<br />

(Unit : mm)<br />

The suggested shortage pipe length is 5m,in order to avoid<br />

noise from the outdoor unit and vibration.<br />

4) Drill a Hole in the wall<br />

• Drill the piping hole with a ø70mm hole core drill. Drill<br />

the piping hole at either the right or the left with the<br />

hole slightly slanted to the outdoor side.<br />

5) Drain piping<br />

① The Outer diameter <strong>of</strong> Drain Hose (which is sup<strong>pl</strong>ied with<br />

indoor unit) is 17mm at connecting end,600mm long.<br />

② Use commercial rigid PVC pipe for extension.<br />

③ Insulate the indoor drain pipe with 10mm or more <strong>of</strong> insulation<br />

material to prevent condensation.<br />

Installation <strong>of</strong> indoor unit 349<br />

NOTE<br />

NOTE<br />

Indoor<br />

[Unit : mm]<br />

103<br />

Water<br />

leakage<br />

Water<br />

leakage<br />

600<br />

Do not raise<br />

WALL<br />

87<br />

Tip <strong>of</strong> drain hose<br />

dipped in water<br />

Ditch<br />

Water<br />

leakage<br />

5-7mm<br />

Outdoor<br />

(3/16"~5/16")<br />

Accumulated<br />

drain water<br />

Air<br />

Waving<br />

Ø17<br />

Less than<br />

50mm gap<br />

The drain pipe should be inclined downward so that water<br />

will flow smoothly without any accumulation.


Console (Floor stand)<br />

6) Installing Indoor unit<br />

① Installation on the Floor.<br />

• Fix up using 6 screws for floor installation.<br />

② Installation on the Wall<br />

• Fix up the installation <strong>pl</strong>ate using 5 screws and the<br />

indoor unit using 4 screws.<br />

• The installation <strong>pl</strong>ate should be fixed on a wall which<br />

4 screw (M*25L)<br />

6 screw (M*25L)<br />

30.5<br />

210<br />

180<br />

140<br />

170<br />

Installation Plate<br />

Molding<br />

can support the weight <strong>of</strong> the indoor unit.<br />

64<br />

(700)<br />

647<br />

159<br />

30.5<br />

26<br />

140<br />

170<br />

160<br />

(600)<br />

574<br />

(Unit : mm)<br />

③ Half concealed installation.<br />

• Make a wall hole <strong>of</strong> the size shown Fig-1.<br />

5CSL0-06B<br />

• Installation <strong>of</strong> sup<strong>pl</strong>emental <strong>pl</strong>ate for attaching main unit<br />

The rear <strong>of</strong> the unit can be fixed with screws at the points<br />

shown in the Fig-2. Be sure to install the sup<strong>pl</strong>emental<br />

<strong>pl</strong>ate in accordance with the depth <strong>of</strong> the inner wall.<br />

• Pipeing Hole<br />

350 Installation <strong>of</strong> indoor unit<br />

45<br />

Wall<br />

Sup<strong>pl</strong>emental <strong>pl</strong>ate<br />

(Field sup<strong>pl</strong>y)<br />

200<br />

150<br />

Hole<br />

670<br />

200<br />

150<br />

585<br />

<br />

95 Sup<strong>pl</strong>emental <strong>pl</strong>ate<br />

(Field sup<strong>pl</strong>y)<br />

1) Normal concealed 2) Deep concealed<br />

50<br />

140<br />

170<br />

75<br />

647<br />

<br />

(Unit : mm)<br />

140<br />

170<br />

Left bottom pipng Right bottom pipng<br />

75<br />

35<br />

(Unit : mm)<br />

Wall


5CSL0-06B Console (Floor stand)<br />

• Remove the Deco Covers and Fixing Indoor Unit<br />

Remove the Deco Covers.(Reference ② <strong>of</strong> 2))<br />

Insert the Indoor Unit to the Wall hole.<br />

Secure using 6 screws. (shown the illustration)<br />

NOTE<br />

Left pipng<br />

Wall<br />

50<br />

Check the horizon <strong>of</strong> Indoor unit with the wall. Please use<br />

the Leveler on the drain pan guide.<br />

45<br />

(Unit : mm)<br />

Leveler Drain pan<br />

Less than 5mm<br />

Less than 5mm<br />

Less than 5mm<br />

Installation <strong>of</strong> indoor unit 351


Console (Floor stand)<br />

3.5.4 Connection pipes to the indoor<br />

unit<br />

1) Refrigerant piping work<br />

<strong>pl</strong>ease refer “REFRIGERANT PIPING WORK”.<br />

2) Piping connection<br />

① When you connect the refrigerant pipe, it is easier that<br />

connect the gas pipe first.<br />

② The direction <strong>of</strong> piping is available for six way as below<br />

illustration.<br />

③ Remove the pillars <strong>of</strong> side covers and rear panel what<br />

you need to cut.<br />

3<br />

2<br />

CAUTION<br />

1<br />

4<br />

5<br />

More than<br />

5mm<br />

• If the drain hose is routed inside the room insulate<br />

the hose with an insulation material* so that dripping<br />

from sweating (condensation) will not damage<br />

furniture or floors.<br />

* Foamed polyethylene or equivalent is recommended.<br />

6<br />

Drain hose<br />

Connecting pipe<br />

5CSL0-06B<br />

3.5.5 Wiring connection<br />

1) Loosen No 1,2 screws <strong>of</strong> control box<br />

cover.<br />

2) Connect the cable followed by circuit diagram.<br />

3) If it is needed for indoor units setting,<br />

loosen No.3 screw and lift up the PCB.<br />

(option: usage <strong>of</strong> bottom vanes, limit<br />

angle <strong>of</strong> top vane)<br />

352 Installation <strong>of</strong> indoor unit<br />

1<br />

2<br />

3<br />

Tape<br />

Connecting<br />

cable<br />

Terminal Block <strong>of</strong> Indoor Unit<br />

1(L) 2(N) 3<br />

Dip S/W Description S/W OFF S/W ON<br />

S/W 5 Install scene Exposed Half<br />

Concealed<br />

S/W 7 Vane Top+Bottom Top vane<br />

vane only


5CSL0-06B Console (Floor stand)<br />

CAUTION<br />

The connecting cable connected to the indoor and<br />

outdoor unit should be com<strong>pl</strong>ied with the following<br />

specifications (Rubber insulation, type H05RN-F<br />

approved by HAR or SAA).<br />

If the sup<strong>pl</strong>y cord is damaged, it must be re<strong>pl</strong>aced<br />

by a special cord or assembly available from the<br />

manufacturer <strong>of</strong> its service agent.<br />

WARNING<br />

GN/YL<br />

4) Electrical wiring<br />

20mm<br />

NORMAL<br />

CROSS-SECTIONAL<br />

AREA 0.75mm 2 (9k12k/18k Btu/h)<br />

Make sure that the screws <strong>of</strong> the terminal are free<br />

from looseness.<br />

① All wiring must com<strong>pl</strong>y with LOCAL REGULATIONS.<br />

② Select a power source that is capable <strong>of</strong> sup<strong>pl</strong>ying the<br />

current required by the air conditioner.<br />

③ Feed the power source to the unit via a distribution<br />

switch board designed for this purpose.<br />

④ The terminal screws inside the control box may be loose<br />

due to vibration during transport.<br />

Check the screws for loose connection.<br />

(Running the air conditioner with loose connection can<br />

overload and damage electrical components.)<br />

⑤ Always ground the air conditioner with a grounding wire<br />

and connector to meet the LOCAL REGULATION.<br />

CAUTION<br />

• The circuit diagram is not subject to change without notice.<br />

• Be sure to connect wires according to the wiring diagram.<br />

• Connect the wires firmly, so that not to be pulled out easily.<br />

• Connect the wires according to color codes by referring the<br />

wiring diagram.<br />

Main power source<br />

Air<br />

Conditioner<br />

3.5.6 Installation front panel<br />

Circuit Breaker<br />

① Fit the Front Panel onto the indoor unit and push the<br />

upper area that are marked with arrows<br />

② Check the air sensor and install the 4 screws<br />

③ Then assemble the front grille and put the hinges<br />

④ Close the grille.<br />

Installation <strong>of</strong> indoor unit 353


Console (Floor stand)<br />

5CSL0-06B<br />

354 Installation <strong>of</strong> indoor unit


5CSL0-06B<br />

4. Installation <strong>of</strong> outdoor unit<br />

4.1 Safety Precautions<br />

Please strictly follow the instructions given in the Installation<br />

manual .Improper installation by ignoring the instructions<br />

can lead to damage to life and property.<br />

Make sure to read the following safety instructions very<br />

carefully and throughly .<br />

WARNING : This symbol indicates the possibility <strong>of</strong><br />

death or serious injury.<br />

CAUTION : This symbol indicates the possibility <strong>of</strong><br />

injury or damage to properties.<br />

■ The meanings <strong>of</strong> the symbols used in this manual are as<br />

shown below.<br />

: Be sure not to do.<br />

: Be sure to follow the instruction.<br />

WARNING<br />

Do not use a defective or underrated circuit breaker.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Do not use a multi consent. Always use this ap<strong>pl</strong>iance<br />

on a dedicated circuit and breaker.<br />

• Otherwise it can cause electric shock or fire.<br />

For electrical work, contact the dealer, seller, a qualified<br />

electrician, or an authorized service center. Do not disassemble<br />

or repair the product by yourself.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Always ground the product as per the wiring diagram.<br />

Do not connect the ground wire to gas or water pipes<br />

lightening rod or telephone ground wire.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

Install the panel and the cover <strong>of</strong> control box securely.<br />

• There is risk <strong>of</strong> fire or electric shock due to dust , water<br />

etc.<br />

Use the correctly rated breaker or fuse.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

If the power cable or cord has scratches or skin peeled<br />

<strong>of</strong>f or deterioted then immediately re<strong>pl</strong>ace it.<br />

• There is risk <strong>of</strong> fire or electric shock.<br />

For installation, removal or reinstall, always contact the<br />

dealer or an authorized service center.<br />

• There is risk <strong>of</strong> fire, electric shock, ex<strong>pl</strong>osion, or injury.<br />

Do not install the product on a defective foundation. Be<br />

sure that the installation area does not deteriorate with<br />

age.<br />

• If the foundation collapses, the air conditioner could fall<br />

with it, causing property damage, product failure, and personal<br />

injury.<br />

Safety Precautions<br />

Never install the outdoor unit at a <strong>pl</strong>ace from where it<br />

can fall down.<br />

• The falling outdoor unit can cause damage or injury or<br />

even death <strong>of</strong> a person and also damage or malfunctioning<br />

<strong>of</strong> the product itself.<br />

When the product is soaked (flooded or submerged) in<br />

water, contact an authorized service center for repair<br />

before using it again.<br />

• There is risk <strong>of</strong> fire or eletric shock.<br />

In outdoor units the the step up capacitor sup<strong>pl</strong>ies high<br />

voltage electricity to the electrical components. Be sure<br />

to discharge the capacitor com<strong>pl</strong>etely before conducting<br />

the repair work.<br />

• An charged capacitor can cause electrical shock.<br />

Be sure to use only those parts which are listed in the<br />

svc parts list. Never attempt to modify the equipment.<br />

• The use <strong>of</strong> inappropriate parts can cause an electrical<br />

shock, excessive heat generation or fire.<br />

Indoor/outdoor wiring connections must be secured<br />

tightly and the cable should be routed properly so that<br />

there is no force pulling the cable at the connection<br />

terminals.<br />

• Improper or loose connections can cause excessive heat<br />

heat generation or fire.<br />

Safely dispose <strong>of</strong>f the packing materials.<br />

• Things like screws, nails, batteries, broken things etc after<br />

installation or svc can cause injury to small kids. Tear<br />

away and throw away the <strong>pl</strong>astic packaging bags so that<br />

children will not <strong>pl</strong>ay with them.<br />

Make sure to check that the power cable <strong>pl</strong>ug is not<br />

dirty, loose or broken, then only insert the <strong>pl</strong>ug com<strong>pl</strong>etely.<br />

• Dirty,loose or broken power <strong>pl</strong>ug can cause electric shock<br />

or fire.<br />

During svc be sure to check the refrigerant to the used.<br />

• Incorrect refrigerant used can prevent the normal operation<br />

<strong>of</strong> the unit.<br />

When installing the unit, use the installation kit provided<br />

with the product.<br />

• Otherwise the unit may fall and cause severe injury .<br />

Do not touch, operate, or repair the product with wet<br />

hands.<br />

• There is risk <strong>of</strong> electric shock or fire.<br />

Do not <strong>pl</strong>ace a heater or other ap<strong>pl</strong>iances near the<br />

power cable.<br />

• There is risk <strong>of</strong> fire and electric shock.<br />

Do not allow water to run into electric parts. Install the<br />

unit away from water sources<br />

• There is risk <strong>of</strong> fire, failure <strong>of</strong> the product, or electric shock.<br />

Do not store or use or even allow flammable gas or<br />

combustibles near the product.<br />

• There is risk <strong>of</strong> fire or failure <strong>of</strong> product.<br />

Installation <strong>of</strong> outdoor unit 355


Safety Precautions 5CSL0-06B<br />

If strange sounds, smell or smoke comes from the<br />

product, immediately turn the breaker <strong>of</strong>f or disconnect<br />

the power sup<strong>pl</strong>y cable.<br />

• There is risk <strong>of</strong> electric shock or fire.<br />

Do not open the front grill <strong>of</strong> the product during operation.<br />

(Do not touch the electrostatic filter, if the unit is<br />

so equipped.)<br />

• There is risk <strong>of</strong> physical injury, electric shock, or product<br />

failure.<br />

Turn the main power <strong>of</strong>f when cleaning or repairing the<br />

product.<br />

• There is risk <strong>of</strong> electric shock.<br />

When the product is not to be used for a long time, turn<br />

<strong>of</strong>f the circuit breaker.<br />

• There is risk <strong>of</strong> product damage or failure, or unintended<br />

operation.<br />

Take care to ensure that nobody especially kids could<br />

step on or fall onto the outdoor unit.<br />

• This could result in personal injury and product damage.<br />

CAUTION<br />

Use two or more peo<strong>pl</strong>e to lift and transport the product.<br />

• Avoid personal injury.<br />

Do not install the product where it will be exposed to<br />

sea wind (salt spray) directly.<br />

• It may cause corrosion on the product. Corrosion, particularly<br />

on the condenser and evaporator fins, could cause<br />

product malfunction or inefficient operation.<br />

Keep level even when installing the product.<br />

• To avoid vibration or noise.<br />

Do not install the product where the noise or hot air<br />

from the outdoor unit could damage or disturb the<br />

neighborhoods.<br />

• It may cause a problem for your neighbors and hence dispute.<br />

Always check for gas (refrigerant) leakage after installation<br />

or repair <strong>of</strong> product.<br />

• Low refrigerant levels may cause failure <strong>of</strong> product.<br />

Do not block the inlet or outlet <strong>of</strong> air flow.<br />

• It may cause product failure.<br />

Do not step on or put anyting on the product.<br />

• There is risk <strong>of</strong> personal injury and failure <strong>of</strong> product.<br />

Do not insert hands or other objects through the air<br />

inlet or outlet while the product is operating.<br />

• There are sharp and moving parts that could cause personal<br />

injury.<br />

Be cautious when unpacking and installing the product.<br />

• Sharp edges could cause injury. Be especially careful <strong>of</strong><br />

the case edges and the fins on the condenser and evaporator.<br />

If the refrigerant gas leaks during the repair, do not<br />

touch the leaking refrigerant gas.<br />

• The refrigernat gas can cause frostbite (cold burn).<br />

Do not tilt the unit when removing or uninstalling it.<br />

• The condensed water inside can cause spill and wet the<br />

furniture and the floor.<br />

Do not mix air or gas other than the specified refrigerant<br />

used in the system.<br />

• If air enters the refrigerant system, an excessively high<br />

pressure results, causing equipment damage or injury.<br />

If the refrigerant gas leaks during the installation or<br />

operation ventilate the area immediately.<br />

• Otherwise it can be harmfull for your health.<br />

Do not expose your skin or kids or <strong>pl</strong>ants to the cool or<br />

hot air draft.<br />

• This could harm to your health.<br />

Use a firm stool or ladder when cleaning, maintaining<br />

or repairing the product at an height.<br />

• Be careful and avoid personal injury.<br />

Dismantling the unit , treatment <strong>of</strong> the refrigerant oil, oil<br />

and eventual parts should be done in accordance with<br />

local and national standards.<br />

4.1.1 Points for ex<strong>pl</strong>anation about<br />

operations<br />

The items with WARNING and CAUTION marks in the operation<br />

manual are the items pertaining to possibillties for<br />

bodily injury and material damage in addition to the general<br />

usage <strong>of</strong> the product. Accordingly, it is necessary that you<br />

make a full ex<strong>pl</strong>anation about the described contents and<br />

also ask your customers to read the operation manual.<br />

4.1.2 Note to the installer<br />

Be sure to instruct customers how to properly operate the<br />

unit (especially cleaning filters, operating different functions,<br />

and adjusting the temperature) by having them carry out<br />

operations themselves while looking at the manual.<br />

4.1.3 Selecting installation site for<br />

outdoor units<br />

Select an installation site where the following conditions are<br />

fulfilled and that meets with your customer's approval.<br />

1. Location strong enough to bear the weight <strong>of</strong> the unit.<br />

2. Location accessible and having enough clearance for<br />

inspection and service in the future.<br />

3. Location allowing easy condensate drainage suitable gradient<br />

<strong>of</strong> the unit and the drain pipe.<br />

4. Piping between the indoor and outdoor unit is possible<br />

within the allowable limits.<br />

356 Installation <strong>of</strong> outdoor unit


5CSL0-06B<br />

5. Location free from electrical noise.<br />

6. Location allowing optimum air distribution without any<br />

blocking to air flow.<br />

7. Location having no risk <strong>of</strong> flammable gas leakage.<br />

8. Location free from mineral oil mist or an oil spray or vapor<br />

eg in kitchen .It could result in leakage .<br />

9. Location free from corrosive gases such as sulphurous<br />

acid gas because it corrodes the copper pipes or soldered<br />

parts resulting in leakage .<br />

10. Location free from any machinery emitting electromagnetic<br />

waves which may disturb the control system thus<br />

causing malfunction <strong>of</strong> the unit .<br />

11. Location free from flammable gases , carbon fibre , or<br />

ignitable dust suspensions in the air or where volatile<br />

flames are handled like gasoline or thinner. Operating in<br />

such conditions may result in fire.<br />

Safety Precautions<br />

12. Install the indoor and outdoor units, power sup<strong>pl</strong>y wiring<br />

and connecting wires at least 1m. away from televisions<br />

or radios in order to prevent image interference or noise.<br />

(Depending on the radio waves, a distance <strong>of</strong> 1m. may<br />

not be sufficient enough to eliminate the noise.)<br />

13. Consider whether the <strong>pl</strong>ace where the unit will be<br />

installed can support the full weight <strong>of</strong> the unit, and reinforce<br />

it with boards and beams, etc. if needed before<br />

proceeding with the installation. Also, reinforce the <strong>pl</strong>ace<br />

to prevent vibration and noise before installing. (The<br />

installation pitch can be found on the paper pattern for<br />

installation (3), so refer to it when considering the<br />

necessity for reinforcing the location.)<br />

14. Obey the local and national regulations and limits<br />

regarding airconditioner installation.<br />

15. Location free from lavatory (NH3.etc.). NH3 gas will<br />

cause corrosion <strong>of</strong> outdoor unit metallic parts.<br />

4.1.4 For the following items, take special care during construction and check<br />

after installation is finished<br />

1. Items to be checked after com<strong>pl</strong>etion <strong>of</strong> work<br />

Unit<br />

Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.<br />

Is the gas leak test finished? It may result in insufficient cooling.<br />

Is the unit fully insulated? Condensate water may drip.<br />

Does drainage flow smoothly? Condensate water may drip.<br />

Does the power sup<strong>pl</strong>y voltage correspond to that<br />

shown on the name <strong>pl</strong>ate?<br />

The unit may malfunction or the components burn out.<br />

Are wiring and piping correct? The unit may malfunction or the components burn out.<br />

Is the unit safely grounded? It may be dangerous at electric leakage.<br />

Is wiring size according to specifications? The unit may malfunction or the components burn out.<br />

Is something blocking the air outlet or inlet <strong>of</strong><br />

either the indoor or outdoor units?<br />

It may result in insufficient cooling.<br />

Are refrigerant piping length and additional<br />

refrigerant charge noted down?<br />

The refrigerant charge in the system is not clear.<br />

CAUTION<br />

NOTE<br />

Items to be checked If not properly done, what is likely to occur Check<br />

• Be very careful about product transportation.<br />

Some products use PP bands for packaging. Do not use any PP bands for a means <strong>of</strong> transportation. It is dangerous.<br />

• Safely dispose <strong>of</strong> the packing materials.<br />

Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.<br />

Tear apart and throw away <strong>pl</strong>astic packaging bags so that children will not <strong>pl</strong>ay with them. If children <strong>pl</strong>ay with a <strong>pl</strong>astic<br />

bag which was not torn apart, they face the risk <strong>of</strong> suffocation.<br />

• Install the indoor and outdoor units, power sup<strong>pl</strong>y wiring and connecting wires at least 1m. away from televisions<br />

or radios in order to prevent image interference or noise.<br />

(Depending on the radio waves, a distance <strong>of</strong> 1m. may not be sufficient enough to eliminate the noise.)<br />

Installation <strong>of</strong> outdoor unit 357


Safety Precautions<br />

4.1.5 Before installation<br />

5CSL0-06B<br />

• During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure<br />

on other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts.<br />

• Be sure to remove a cushion (corrugated paper) located between the heat exchanger and the right air filter.<br />

• Be sure to check the type <strong>of</strong> R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent<br />

normal operation <strong>of</strong> the unit.)<br />

• The accessories needed for installation must be retained in your custody until the installation work is com<strong>pl</strong>eted. Do not<br />

discard them!<br />

• Decide upon a line <strong>of</strong> transport.<br />

• Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is unavoidable, use<br />

a sling <strong>of</strong> s<strong>of</strong>t material or protective <strong>pl</strong>ates together with a rope when lifting, to avoid damage or scratches to the unit.<br />

• For the installation <strong>of</strong> an outdoor unit, refer to the installation manual attached to the outdoor unit.<br />

• When using the wireless remote controller, refer to the installation manual attached to the wireless remote controller.<br />

• Entrust installation to the <strong>pl</strong>ace <strong>of</strong> purchase or an authorized serviceman. Improper installation could lead to leaks and in<br />

worst cases, electric shock <strong>of</strong> fire.<br />

• Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to<br />

fall out <strong>of</strong> <strong>pl</strong>ace, or could lead to leaks and, in the worst cases, electric shock or fire.<br />

358 Installation <strong>of</strong> outdoor unit


5CSL0-06B Introduction<br />

4.2 Introduction<br />

This installation guidance describes the procedures for outdoor unit installation, piping, wiring, and control between outdoor<br />

units, indoor units and controller.<br />

Installation <strong>of</strong> the indoor units is not described in this part. Please refer to the installation guidance manual which sup<strong>pl</strong>ied<br />

with indoor units for their respective installation.<br />

4.2.1 Lifting method<br />

1. When carrying the unit suspended, pass the ropes under<br />

the unit and use the two fork lift slots each at the front<br />

and rear.<br />

2. Always lift the unit with ropes attached at four points so<br />

that impact is not ap<strong>pl</strong>ied to the unit.<br />

3. Attach the ropes to the unit at an angle <strong>of</strong> 40° or less.<br />

4. Use two ropes at least 7 m long.<br />

CAUTION<br />

Be very careful when carrying the product.<br />

• PP bands are used to pack some products. Do not use<br />

them as a mean for transportation because they are<br />

dangerous.<br />

• Do not touch heat exchanger fins with your bare hands.<br />

Otherwise you may get a cut.<br />

• Tear <strong>pl</strong>astic packaging bag and scrap it so that children<br />

cannot <strong>pl</strong>ay with it. Otherwise <strong>pl</strong>astic packaging bag<br />

may suffocate children to death.<br />

• When carrying in outdoor unit, be sure to support it at<br />

four points. Carrying in and lifting with 3-point support<br />

may make outdoor unit unstable, resulting in a fall <strong>of</strong> it.<br />

4.2.2 Inspecting and handling the<br />

unit<br />

At the time <strong>of</strong> delivery, the package should be checked for<br />

any damage from out side and inside, If damaged then it<br />

should be reported to the carrier claims agent immediately .<br />

When handling the unit refer to following cautions:<br />

1. Handle the unit with care. Keep the unit upright in order<br />

to avoid inside components damage.<br />

2. If a forklift is to be used it should pass the forklift arms<br />

through the openings at the bottom <strong>of</strong> the unit.<br />

3. If a crane is used, lift the unit preferably with 2 ropes <strong>of</strong><br />

at least 7m length.<br />

4. When lifting the unit with a crane, always use protectors<br />

to prevent belt damage and pay attention to the position<br />

<strong>of</strong> the unit's center <strong>of</strong> gravity.<br />

5. Bring the unit in original package to prevent damage<br />

during local transport.<br />

Installation <strong>of</strong> outdoor unit 359


Foundation<br />

4.3. Foundation<br />

For good drain <strong>of</strong> outdoor unit, keep the bottom height from icing upward.<br />

AUUW096D [ULD]<br />

AUUW126D [ULD]<br />

AUUH126D [ULD]<br />

<br />

Bolt Factor M10-J type<br />

Concrete height 100mm or more<br />

Bolt inserted depth 70mm or more<br />

AUUW186D [UED],*AUUW186DH [UED]<br />

AUUW186D1[UED1]<br />

AUUW246D[UU24W UED], AUUW306D[UU30W UED]<br />

AUUH186D [UED]<br />

AUUH246D[UU24 UED], AUUH306D[UU30 UED]<br />

<br />

Bolt Factor M10-J type<br />

Concrete height 100mm or more<br />

Bolt inserted depth 70mm or more<br />

* AUUW186DH : DISCHARGE GRILLE SHPE IS<br />

DOFFERENT<br />

AUUW366D[UU36W UED]<br />

AUUW368D[UU37W UED]<br />

AUUH368D[UU37 UED]<br />

<br />

Bolt Factor M10-J type<br />

Concrete height 200mm or more<br />

Bolt inserted depth 70mm or more<br />

100mm<br />

or more<br />

100mm<br />

or more<br />

100mm<br />

or more<br />

546mm 370mm or more<br />

518mm 287mm or more<br />

550mm 360mm or more<br />

5CSL0-06B<br />

360 Installation <strong>of</strong> outdoor unit


5CSL0-06B Foundation<br />

AUUW426D[UU42W U3D], AUUW486D[UU42W U3D]<br />

AUUW606D[UU60W U3D], AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D], AUUW608D[UU61W U3D]<br />

AUUH488D[UU48 U3D], AUUH608D[UU60 U3D]<br />

<br />

Bolt Factor M10-J type<br />

Concrete height 200mm or more<br />

Bolt inserted depth 70mm or more<br />

Diagram <strong>of</strong> lower<br />

surface<br />

AUUW216DH[UU21WH U4D]<br />

AUUW246DH[UU24WH U4D]<br />

<br />

Bolt Factor M10-J type<br />

Concrete height 200mm or more<br />

Bolt inserted depth 70mm or more<br />

Diagram <strong>of</strong> lower<br />

surface<br />

20<br />

20<br />

200mm<br />

or more<br />

200mm<br />

or more<br />

Installation <strong>of</strong> outdoor unit 361<br />

200mm<br />

200mm<br />

400mm 620mm or more<br />

400mm 620mm or more


Settlement <strong>of</strong> the outdoor unit<br />

5CSL0-06B<br />

4.4 Settlement <strong>of</strong> the outdoor unit 4.5 Selection <strong>of</strong> the best location<br />

• Anchor the outdoor unit with a bolt and nut tightly and<br />

horizontally on a concrete or rigid mount.<br />

• When installing on the wall, ro<strong>of</strong> or ro<strong>of</strong>top, anchor the<br />

mounting base securely with a nail or wire assuming the<br />

influence <strong>of</strong> wind and earthquake.<br />

• In the case when the vibration <strong>of</strong> the unit is conveyed to<br />

the house, secure the unit with an anti-vibration rubber.<br />

Bolt construction work<br />

Settlement draw <strong>of</strong> outdoor units<br />

Bolt<br />

CAUTION<br />

Mechanical anchor bolt<br />

M10<br />

Diagram <strong>of</strong> lower surface<br />

60~120<br />

20<br />

Tubing connection<br />

• The ingredients <strong>of</strong> foundation : Cement : Sand : Gravel<br />

for the concrete should 1 : 2 : 4 ratio<br />

• The foundation surface should be finished with mortar.<br />

• The edges <strong>of</strong> foundation should be rounded.<br />

• A drain passage should be made around the foundation<br />

to thoroughly drain water away from the equipment<br />

installation area.<br />

• If installing the outdoor units on the ro<strong>of</strong>, the ro<strong>of</strong>'s<br />

strength have to be checked.<br />

• Care should be taken for weather - pro<strong>of</strong>ing<br />

• Blocking all gaps <strong>of</strong> outdoor unit, for passing piping and<br />

wiring, using sealing material (Field sup<strong>pl</strong>y)<br />

(Animals and bugs might enter in the machine.)<br />

This Single A unit is suitable for installation in a residential<br />

and commercial environmental situation.<br />

If installed near a household ap<strong>pl</strong>iance it can cause electromagnetic<br />

interference.<br />

The units should be installed in a location that meets the following<br />

requirements:<br />

1. A robust and strong base which can support the weight <strong>of</strong><br />

the unit and will not degrade easily<br />

2. If an awning is built over the unit to prevent direct sunlight<br />

or rain exposure, make sure that the discharge air <strong>of</strong> the<br />

condenser is not restricted.<br />

3. It is recommended that the outdoor unit should be fenced<br />

to avoid animals or <strong>pl</strong>ants being exposed in the direct<br />

path <strong>of</strong> the discharged air .<br />

4. Ensure proper spaces between the unit and its surrounding<br />

as given in the figure.<br />

5. Ensure that the water shall not cause any damage by<br />

overflowing in case <strong>of</strong> water condensation<br />

6. The noise, vibration and hot discharged air <strong>of</strong> the outdoor<br />

unit should not annoy the surrounding environment.<br />

7. Ensure that there is no damage to the pipes in long run<br />

as it may cause the refrigerant leakage.<br />

8. In case the outdoor may have heavy snow :<br />

a. Make foundation at a suitable height not for ice to grow<br />

upward.<br />

b. Fit a suitable hood or a awning over the unit not to<br />

attach outdoor unit heat exchanger directly.<br />

c. In very cold snowing area, <strong>pl</strong>ease consult with your<br />

consultant.<br />

9. Ro<strong>of</strong>top Installations : If the outdoor unit is installed on a<br />

ro<strong>of</strong> structure, be sure to level the unit. Ensure the ro<strong>of</strong><br />

structure and anchoring method are adequate for the unit<br />

location. Consult local codes regarding ro<strong>of</strong>top mounting.<br />

CAUTION<br />

An inverter air conditioner can cause electronic noise<br />

generated from broadcasting frequency. Make sure to<br />

maintain proper distances between the products and<br />

electric wires keeping away from stereo, TV set or other<br />

ap<strong>pl</strong>iances<br />

1. Branch switch, over current breaker<br />

2. Remote controller<br />

3. Cool/heat selector<br />

4. Radio or TV set<br />

5. Wireless microphone<br />

If frequency signal <strong>of</strong> AM broadcasting or TV Set is non<br />

stable, keep distances <strong>of</strong> 3m or more from product and<br />

use electric wire along with conduit tubes for power and<br />

transmission cable.<br />

362 Installation <strong>of</strong> outdoor unit


5CSL0-06B Selection <strong>of</strong> the best location<br />

CAUTION<br />

1. Actually the R410A refrigerant is not toxic, nonflammable and odor free. Any how if the refrigerant is leaked then its<br />

concentration may exceed the allowable limit depending on the related space volume.<br />

Due to this, it is necessary to take measures for the volume size against leakage.<br />

2. Do not install unit in following locations.<br />

• Locations where sulfurous acids or this kind <strong>of</strong> other corrosive gases might be help to corrode <strong>of</strong> copper piping and<br />

soldered joints, and can cause refrigerant leakage.<br />

• Locations such as kitchens or cuisine which contain a lot <strong>of</strong> hot oil or steam or where oil may s<strong>pl</strong>atter to the product.<br />

Can cause the unit to make leak or other serious problem.<br />

• Locations where electromagnetic waves is prevalent. The electromagnetic waves may cause the control system to<br />

malfunction or causing an abnormal operation.<br />

• Locations where inflammable gas might leak, where combined gasoline, methane or other volatile substances, carbon<br />

dust and other incendiary substances are found in the atmosphere. Leaked gas may accumulate around the unit, can<br />

cause an serious ex<strong>pl</strong>osion.<br />

Installation <strong>of</strong> outdoor unit 363


Clearance space 5CSL0-06B<br />

4.6 Clearance space<br />

4.6.1 Clearance around outdoor unit<br />

AUUW096D [UU09W ULD]<br />

AUUW126D [UU12W ULD]<br />

AUUW186D [UU18W UED]<br />

AUUW186D1[UU18W UED1]<br />

AUUW246D[UU24W UED]<br />

AUUW306D[UU30W UED]<br />

AUUH126D [UU12 ULD]<br />

AUUH186D [UU18 UED]<br />

AUUH246D[UU24 UED]<br />

AUUH306D[UU30 UED]<br />

200 mm or more<br />

300 mm<br />

or more 300 mm<br />

or more<br />

300 mm<br />

or more<br />

200 mm or more<br />

300 mm<br />

or more<br />

200 mm<br />

or more<br />

Fence or<br />

obstacles<br />

Air inlet grille<br />

Sunro<strong>of</strong><br />

100 100 mm<br />

mm<br />

or or more<br />

600 mm or m<br />

(Service spac<br />

More than 50cm<br />

(Service space)<br />

• Ensure that the space around the back is more than 200 mm on the opposite to the PCB side and secure 600 mm<br />

space near the compressor and PCB side <strong>of</strong> the aircondition for service.<br />

AUUW366D[UU36W UED]<br />

AUUW368D[UU37W UED]<br />

AUUH368D[UU37 UED]<br />

AUUW216DH [UU21WH U4D]<br />

AUUW246DH [UU24WH U4D]<br />

• Ensure that the space around the back is<br />

more than 300 mm on the opposite side<br />

to the PCB side and secure 600 mm<br />

space near the compressor and PCB<br />

side <strong>of</strong> the air conditioner for service.<br />

AUUW426D[UU42W U3D]<br />

AUUW486D[UU42W U3D]<br />

AUUW606D[UU60W U3D]<br />

AUUW428D[UU43W U3D]<br />

AUUW488D[UU49W U3D]<br />

AUUW608D[UU61W U3D]<br />

AUUH488D[UU48 U3D]<br />

AUUH608D[UU60 U3D]<br />

• Install the unit so that its discharge port faces to the<br />

wall <strong>of</strong> the building.<br />

Keep a distance 500mm or more between the unit<br />

and the wall surface.<br />

• Supposing the wind direction during the operation<br />

season <strong>of</strong> the air conditioner, install the unit so that<br />

the discharge port is set at right angle to the wind<br />

direction.<br />

300 mm<br />

or more<br />

Fence or<br />

obstacles<br />

Sunro<strong>of</strong><br />

Turn the air outlet side toward the<br />

building's wall, fence or windbreak<br />

screen.<br />

300 mm<br />

or more<br />

600 mm or more<br />

(Service space)<br />

More than 50cm<br />

(Service space)<br />

364 Installation <strong>of</strong> outdoor unit<br />

500<br />

Strong<br />

wind<br />

Blown<br />

air<br />

Sunro<strong>of</strong><br />

Strong<br />

wind<br />

Set the otlet side at a rignt angle<br />

to the direction <strong>of</strong> the wind.


5CSL0-06B<br />

Clearance <strong>of</strong> side discharge unit (unit : mm).<br />

1. Where there is an obstacle on the air intake side:<br />

■ No obstacle above<br />

• Obstacle on the suction side only • Obstacle on the both sides<br />

100 or more<br />

■ Obstacle above, too<br />

• Obstacle on the air intake side, too • Obstacle on the air intake side, and both sides<br />

500 or less<br />

100 or more<br />

1000 or more<br />

500 or more<br />

Clearance space<br />

Installation <strong>of</strong> outdoor unit 365<br />

300 or more<br />

2. Where there is an obstacle on the discharge side:<br />

300 or more<br />

600 or more<br />

500 or less<br />

600 or more<br />

■ No obstacle above ■ Obstacle above, too<br />

3. Where there are obstacles on both suction and discharge sides:<br />

■ Where the obstacles on the discharge side is higher than the unit:<br />

• No obstacle above<br />

• Obstacle above, too<br />

The relations between H, A and L are as follows:<br />

L A<br />

L ≤ H<br />

0 < L ≤ 1/2H<br />

1/2H < L<br />

750<br />

1000<br />

H < L Set the stand as: L ≤ H<br />

Close the bottom <strong>of</strong> the installation frame to prevent<br />

the discharged air from being bypassed.<br />

100 or more<br />

1000 or more<br />

150 or more<br />

H<br />

500 or less<br />

500 or more<br />

500 or more<br />

A<br />

500 or less<br />

1000 or more<br />

100 or more<br />

L<br />

1000 or more<br />

200 or more


Clearance space 5CSL0-06B<br />

■ Where the obstacles on the discharge side is lower than the unit:<br />

• No obstacle above<br />

• Obstacle above, too<br />

The relations between H, A and L are as follows:<br />

L A<br />

L ≤ H<br />

0 < L ≤ 1/2H<br />

1/2H < L<br />

100<br />

200<br />

H < L Set the stand as: L ≤ H<br />

Close the bottom <strong>of</strong> the installation frame to prevent<br />

the discharged air from being bypassed.<br />

4. Series installation<br />

4.6.2 Air guide work<br />

In case <strong>of</strong> out door unit is located outdoor cabin <strong>of</strong> apartment<br />

or flats, then the efficiency can drop and system<br />

pressure increases thus finally damaging the compressor<br />

or other components in the system by heat short circuit.<br />

4.6.3 Lightning safety zone<br />

1) To protect outdoor unit from lightning, it should be <strong>pl</strong>aced<br />

within lightning safety zone.<br />

Safety zone<br />

Building Height [m] 20 30 45 60<br />

Protection Angle [˚] 55 45 35 25<br />

2) Power cable and communication cable should be 1.5m<br />

away from lightning rod.<br />

3) High resistance grounded system should be performed<br />

against induced lightning or indirect stroke.<br />

4) If the building has no lightning protection, outdoor may be<br />

damage from lightning. This should be informed to customer<br />

or building owner in advance.<br />

500 or more<br />

[Exam<strong>pl</strong>e]<br />

1000 or more<br />

<br />

Safety dorice activation<br />

Lightning rod<br />

Protection Angle (25˚~55˚)<br />

<br />

Normal operation<br />

366 Installation <strong>of</strong> outdoor unit<br />

Lightning rod<br />

100 or more<br />

1.5m<br />

Ground<br />

500 or more<br />

L<br />

500 or less<br />

Safe zone<br />

100 or more<br />

500 or more<br />

A<br />

H<br />

1000 or more<br />

※ Regarding the safety<br />

from atmosphere<br />

electricity, follow the<br />

local or national<br />

regulations


5CSL0-06B<br />

4.7 Outdoor unit piping<br />

4.7.1 Outdoor unit piping<br />

Required tools<br />

4.7.2 Connecting piping<br />

1) Connecting socket must be used when connecing the piping to the indoor and outdoor units<br />

■ Branching kit<br />

C<br />

Outdoor unit piping<br />

Screw Driver Drill M/C f 3.5/F14.5 Measuring Tape, Blade Core drill Spanner Torque Wrench<br />

Soap Foam Thermometer Hexagonal wrench(4mm, 5mm) Hook Meter Multi Tester Flare Set<br />

A<br />

Indoor Classification Model Name Capacity Ratio(%)<br />

2 Units PMUB11A 50:50 (1:1)<br />

3 Units PMUB111A 33:33:33 (1:1:1)<br />

4 Units PMUB1111A 25:25:25:25(1:1:1:1)<br />

B<br />

2) Finally, tighten the flare nut with torque wrench until the wrench clicks.<br />

• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.<br />

Suction Line piping<br />

(Bigger diameter)<br />

Torque wrench<br />

D<br />

Evaporator Line<br />

piping<br />

(Smaller<br />

diameter)<br />

a b c<br />

a b<br />

Type 1 Type 2<br />

Unit : mm (inch)<br />

(I.D) ⓐ ⓑ ⓒ Type<br />

Ⓐ Ø15.88(5/8) Ø19.05(3/4) Ø25.4(1) 1<br />

Ⓑ<br />

Ø9.52(3/8)<br />

Ø12.7(1/2) Ø12.7(1/2)<br />

Ø15.88(5/8)<br />

- 2<br />

Ⓒ Ø6.35(1/4) Ø9.52(3/8) - 2<br />

Ⓓ Ø9.52(3/8) Ø12.7(1/2) - 2<br />

Continuous<br />

Torque<br />

wrench<br />

(250mm )<br />

Installation <strong>of</strong> outdoor unit 367<br />

➝<br />

❈ When tighten the pipe, hold the haxagonal body.


Outdoor unit installation requirments 5CSL0-06B<br />

4.8 Outdoor unit installation requirments<br />

4.8.1 Piping elevation and length<br />

• For 1 Phase Inverter Model<br />

Model<br />

UU09W/UU12W<br />

UU18W<br />

UU24W<br />

UU30W<br />

UU36W<br />

UU42W<br />

UU48W<br />

UU60W<br />

Model<br />

UU37W<br />

UU43W<br />

UU49W<br />

UU61W<br />

Pipe Size (Diameter:Ø) Length(m) Elevation(m) *Additional<br />

Gas Liquid Standard Max. Max. refrigerant(g/m)<br />

9.52 (3/8)<br />

12.7 (1/2)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

• For 3 Phase Inverter Model<br />

6.35 (1/4)<br />

6.35 (1/4)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

5.0<br />

5.0<br />

5.0<br />

5.0<br />

5.0<br />

7.5<br />

7.5<br />

7.5<br />

368 Installation <strong>of</strong> outdoor unit<br />

15<br />

40<br />

50<br />

50<br />

50<br />

75<br />

75<br />

75<br />

10<br />

30<br />

30<br />

30<br />

30<br />

30<br />

30<br />

30<br />

Pipe Size (Diameter:Ø) Length(m) Elevation(m)<br />

Gas Liquid Standard Max. Max.<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

• For Non-inverter Model<br />

Model<br />

UU12<br />

UU18<br />

UU24<br />

UU30<br />

UU36<br />

UU48<br />

UU60<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

Pipe Size (Diameter:Ø)<br />

5.0<br />

7.5<br />

7.5<br />

7.5<br />

50<br />

75<br />

75<br />

75<br />

30<br />

30<br />

30<br />

30<br />

Length(m) Elevation(m)<br />

Gas Liquid Standard Max. Max.<br />

9.52 (3/8)<br />

12.7 (1/2)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

15.88 (5/8)<br />

6.35 (1/4)<br />

6.35 (1/4)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

9.52 (3/8)<br />

5.0<br />

5.0<br />

5.0<br />

5.0<br />

5.0<br />

7.5<br />

7.5<br />

15<br />

50<br />

40<br />

50<br />

50<br />

50<br />

40<br />

10<br />

30<br />

30<br />

30<br />

30<br />

30<br />

30<br />

20<br />

20<br />

35<br />

35<br />

50<br />

40<br />

40<br />

40<br />

*Additional<br />

refrigerant(g/m)<br />

45<br />

40<br />

40<br />

40<br />

*Additional<br />

refrigerant(g/m)<br />

20<br />

35<br />

45<br />

45<br />

45<br />

50<br />

50


5CSL0-06B<br />

❈ Extra refrigerant = (Extended length - Rated length) x Additional refrigerant.<br />

CAUTION<br />

2) DC inverter Single A - synchro<br />

Outdoor unit installation requirments<br />

Install the branch pipe so that pipe length and difference between high and low will not exceed below SPEC.<br />

h1<br />

Indoor unit<br />

L2<br />

L3<br />

L4<br />

L5<br />

B<br />

Main (L1)<br />

A<br />

Outdoor unit<br />

Branch<br />

Indoor unit<br />

• When installing the branch pipe, direction and angle <strong>of</strong> installation is not limited.<br />

• Take care so that burrs and foreign material may not enter into the cutting surface when connecting.<br />

• Donʼt use the liquid pipe by too bending or twisting.<br />

h2<br />

Outdoor unit<br />

• Capacity is based on standard length and maximum allowance length is on the basis <strong>of</strong> reliability.<br />

• Improper refrigerant charge may result in abnormal cycle.<br />

A<br />

Pipe Length(m)<br />

Total(Main+Branch)<br />

L1+L2+L3+L4+L5<br />

Main Pipe(L1)<br />

Total Branch Pipe<br />

Each Barnch(L2, L3, L4, L5)<br />

In out (h1)<br />

In-In (h2)<br />

L1+L2, L1+L3, L1+L4, L1+L5<br />

Indoor-Indoor_(b)<br />

L2-L3, L4-L5<br />

AUUW42~606(8)D<br />

Installation <strong>of</strong> outdoor unit 369<br />

B<br />

80<br />

50<br />

40<br />

15<br />

30<br />

1<br />

70<br />

10


Outdoor unit installation requirments 5CSL0-06B<br />

Refrigerant Additional Charging Method<br />

For additional charging method, see below table.<br />

NOTE<br />

Synchro Refrigerant Additional charging (kg)<br />

Duo<br />

Trio<br />

Quartet<br />

(L1=Main Pipe, L2~L5 : Branch Pipe)<br />

Model<br />

AUUW42-606(8)D 7.5 m<br />

NOTE<br />

CAUTION<br />

If the total additional charge value after calculation comes out to be negative, then do not consider additional charge.<br />

Long pipe setting (Inverter Single A)<br />

1. Open the side panel <strong>of</strong> outdoor unit.<br />

2. Set the DIP SW2 as below Fig.<br />

DIP SW2<br />

ON<br />

1 2 3 4 5<br />

0 0 0 1 0<br />

3. Close the side panel and check whether the<br />

product works normally.<br />

CAUTION<br />

Refrigerant = (L1-a) x B + (L2 + L3) x A<br />

Refrigerant = (L1-a) x B + (L2 + L3 + L4) x A<br />

Refrigerant = (L1-a) x B + (L2 + L3 + L4 + L5) x A<br />

a<br />

✽ 1 means S/W up.<br />

0 means S/W down.<br />

Do not open the top cover or set the pipe<br />

length when operating the product.<br />

B<br />

0.04 kg/m<br />

Refrigerant Branch<br />

Pipe (mm)<br />

370 Installation <strong>of</strong> outdoor unit<br />

Ø 6.35<br />

Ø 9.52<br />

DIP SW2<br />

ON<br />

1 2 3 4 5<br />

A<br />

0.03 kg/m<br />

0.04 kg/m<br />

If total additional charge value after calculation comes out to be negative, then do not consider additional charge.<br />

a Standard piping length<br />

A Refrigerant Additional charging (For Branch Pipe)<br />

B Refrigerant Additional charging (For Main Pipe)<br />

• Rated performance for refrigerant line length <strong>of</strong> 7.5m.<br />

• Capacity is based on standard length and maximum allowance length is on the basis <strong>of</strong><br />

reliability.<br />

• Improper refrigerant charge may result in abnormal cycle.


5CSL0-06B<br />

1. DIP SW2 Setting<br />

Set the DIP SW2 as below Table.a (Ⓐ)<br />

❈ 1 means S/W up.<br />

0 means S/W down.<br />

2. Auto Addressing Method<br />

Addressing work assigns address to each indoor<br />

unit. When firstly installing product or re<strong>pl</strong>acing the<br />

indoor unit PCB.Auto Addressing work should be<br />

done for simultaneous operation.<br />

❈ Work procedure<br />

1) DIP SW2 correctly.<br />

2) Turn on main power.<br />

3) Press the SW01B for about 3 seconds within 3minutes<br />

After main power on.(Ⓑ)<br />

4) After step 3), the LED01H(green LED) rapidly flickers.When<br />

Addressing work is done, green LED is<br />

<strong>of</strong>f, else LED stops flickering and lights continuously.<br />

5) If you fail to perform the Addressing work, repeat<br />

step 2),3).<br />

CAUTION<br />

1. Regulation for refrigerant leakage<br />

: the amount <strong>of</strong> refrigerant leakage should satisfy the following equation for human safety.<br />

Total amount <strong>of</strong> refrigerant in the system<br />

Volume <strong>of</strong> the room at which indoor unit <strong>of</strong> the least capacity is installed<br />

Outdoor unit installation requirments<br />

Table.a DIP SW2 Setting<br />

DIP SW2 Indoor Unit No.<br />

≤ 0.3 ( kg / m 3 )<br />

2. If the above equation can not be satisfied, then follow the following steps.<br />

① Selection <strong>of</strong> air conditioning system: select one <strong>of</strong> the followings.<br />

• Effective opening part Installation<br />

• Reconfirmation <strong>of</strong> outdoor unit capacity and piping length<br />

• Reduction <strong>of</strong> the amount or refrigerant<br />

• 2 or more security device installation <strong>of</strong> alarm for gas leakage<br />

② Change indoor unit type<br />

: installation position should be over 2m from the floor (Wall mounted type Cassette type)<br />

③ Adoption <strong>of</strong> ventilation system<br />

: choose ordinary ventilation system or building ventilation system<br />

④ Limitation in piping work<br />

: design for earthquake-pro<strong>of</strong> and prevention against thermal stress<br />

1(Single)<br />

2(Duo)<br />

3(Trio)<br />

4(Quartet)<br />

Installation <strong>of</strong> outdoor unit 371<br />

DIP SW2<br />

ON<br />

A<br />

LED01H<br />

B<br />

ON<br />

1 2 3 4 5<br />

0 0 0 0 0<br />

ON<br />

1 2 3 4 5<br />

1 0 0 0 0<br />

ON<br />

1 2 3 4 5<br />

1 1 0 0 0<br />

ON<br />

1 2 3 4 5<br />

SW01B<br />

1 2 3 4 5<br />

1 1 1 0 0<br />

MAIN PCB


Outdoor unit cabin 5CSL0-06B<br />

4.9 Outdoor unit cabin<br />

4.9.1 Outdoor Cabin louver requirement<br />

1. Outdoor cabin type : Manual door open type<br />

2. Louver angle : less than 15° on the horizontal base<br />

3. Louver interval: over 100mm (recommend)<br />

4. Louver shape : wing type or <strong>pl</strong>ane type<br />

CAUTION<br />

• Opening rate and suction should be considered for<br />

louvered outdoor room.<br />

• Do not use 'S' type louver.<br />

NOTE<br />

Noise can occur due to the<br />

backward flow <strong>of</strong> the air<br />

passing through the louver<br />

blade<br />

Louver<br />

Outside<br />

Max15°<br />

(Recommended)<br />

Over 100mm<br />

(Recommended)<br />

Section<br />

Inside<br />

The problem in case the louver opening rate is small.<br />

1. Noise can occur due to the increased velocity <strong>of</strong> the air passing through louver blade.<br />

2. Noise can occur due to the louver blade vibrations.<br />

3. Drop in outdoor fan performance (Excess static pressure damage can cause drop in the performance as well as outdoor<br />

heat exchange efficiency).<br />

4. In case the louver opening rate is small or there is insufficient air flow exchange, it might stop the air conditioner.<br />

Opening rate by louver radian<br />

≤ 15°<br />

ho = h * COS<br />

Total face area(A) = H * W<br />

Number <strong>of</strong> open space (N) = (number <strong>of</strong> louver - 1)<br />

Effective face area(Af) = ho * W * N<br />

Louver opening rate (n) = Af/A<br />

Af = A * n<br />

ho<br />

Effective face area <strong>of</strong> cross section<br />

h<br />

[Side view]<br />

372 Installation <strong>of</strong> outdoor unit<br />

W<br />

[Front view]<br />

H


5CSL0-06B<br />

4.9.2 Air flow rate confirmation<br />

Exam<strong>pl</strong>e. 1<br />

■ Ap<strong>pl</strong>ication Model : AUUW366D [UU36W UED] Airflow rate 106CMM<br />

[Total opening rate]<br />

1400mm<br />

1200mm<br />

1900mm<br />

Air guide duct<br />

1380 mm<br />

■ Louver total dimension (excluding frame) (A) = 1.2 m x 1.9 m = 2.28 m 2<br />

■ Louver shielding dimension by product (B) = 0.9 m x 1.13 m = 1.02 m 2<br />

■ Suction able louver dimension (A-B) = 1.26m 2<br />

■ Equivalent suction dimension (Opening rate 80%) = 1.26 m 2 x 0.8 = 1.01 m 2<br />

■ Equivalent suction air volume = 1.2816 m 2 x 2.5 m/s x 60s/m = 152 CMM<br />

■ Required air volume / equivalent voloume = 152 CMM / 106 CMM(product airflow rate) = 142 %<br />

➡ OK<br />

950mm<br />

■ Case : velocity <strong>of</strong> discharging air: 5m/s,<br />

velocity <strong>of</strong> suction air: 2.5m/s<br />

■ Openness rate = 80% or more<br />

✻ Openness rate =<br />

Effective face area(Af)<br />

Total face area(A)<br />

Outdoor unit cabin<br />

■ Air guide <strong>of</strong> discharging air part should be equipped.<br />

Installation <strong>of</strong> outdoor unit 373


5CSL0-06B<br />

374 Installation <strong>of</strong> outdoor unit


Part 4 Accessories<br />

List <strong>of</strong> ap<strong>pl</strong>icable models<br />

1. Controller accessories .......................................................................377<br />

1.1 Wireless remote controller .........................................................................................377<br />

1.2 Sim<strong>pl</strong>e remote controller ............................................................................................382<br />

1.3 Deluxe remote controller............................................................................................384<br />

1.4 Hotel use remote controller........................................................................................386<br />

1.5 Zone controller ...........................................................................................................388<br />

1.6 Dry contact module ....................................................................................................391<br />

2. Mechanical accessories............................................................................393<br />

2.1 Branch kit ...................................................................................................................393<br />

2.2 Drain pump ................................................................................................................395<br />

2.3 Air guide.....................................................................................................................400<br />

2.4 Cassette cover ...........................................................................................................401<br />

Accessories 375


List <strong>of</strong> ap<strong>pl</strong>icable models 5CSL0-06B<br />

List <strong>of</strong> ap<strong>pl</strong>icable models<br />

Individual<br />

control<br />

CAC Network<br />

function<br />

Special<br />

function kit<br />

Wired Remote Controller(Deluxed)<br />

Wired Remote Controller(Sim<strong>pl</strong>e)<br />

Wired Remote Controller(for hotel use)<br />

Picto wired remote controlxer<br />

Wireless Remote Controller<br />

General Central Controller(Non LGAP)<br />

Network Function(LGAP)<br />

PI485<br />

Function<br />

Dry_Contact<br />

PDI(Power Distribution Indicator)<br />

Low Ambient Kit<br />

Zone Controller (for Duct)<br />

Model name<br />

Wall mounted Artcool CST Ceiling & Floor Duct<br />

X X PQRCUDS0 X PQRCUDS0<br />

X X PQRCUCA0 PVRCUSZ0 PQRCUCA0<br />

X X PQRCFCS0 X PQRCFCS0<br />

X X PQRCUSA0 X X<br />

X X "PQWRHSF0 X "PQWRHSF0<br />

X X AHWRHD X AHWRHD<br />

X X AHWRHS X AHWRHS<br />

X X X X X<br />

O O O O O<br />

PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0<br />

PQDSB PQDSB PQDSB PQDSB PQDSB<br />

PQNUD1S00 PQNUD1S00 PQNUD1S00 PQNUD1S00 PQNUD1S00<br />

AQLA AQLA AQLA AQLA AQLA<br />

X X X X ABZCA<br />

376 Accessories


5CSL0-06B Wireless remote controller<br />

1. Controller accessories<br />

1.1 Wireless remote controller<br />

Picture:<br />

Functions:<br />

A Wireless remote controller allows the operation <strong>of</strong> air conditioner from any corner <strong>of</strong> the room<br />

Ap<strong>pl</strong>icable Models:<br />

Ceiling cassete<br />

Ceiling concealed duct<br />

PQWRHSF0<br />

AHWRHD<br />

AHWRHS<br />

Functions PQWRHSF0 AHWRHD AHWRHS<br />

Air circulation / Fan operation<br />

Room temperature checking<br />

Sleep mode operation<br />

Temperature settings<br />

Operation mode selection<br />

Air-swing & Jet cool (Cassette Only)<br />

On/Off Timer settings<br />

Accessory: Wireless remote control ............................................................................................................................1EA<br />

Owner's manual ........................................................................................................................................1EA<br />

Controller accessories 377


Wireless remote controller<br />

Installation procedure:<br />

Mounting on the wall<br />

1) Mount the remote control stand on the wall with the help <strong>of</strong> screw driver and screw purchased<br />

locally.<br />

2) Insert the remote control in the stand.<br />

How to insert batteries:<br />

1) Remove the battery cover from the remote control. Slide the cover in the direction <strong>of</strong> arrow.<br />

2) Insert two batteries. Take care about the polarity(+/-) and batteries should be new.<br />

3) Re-<strong>pl</strong>ace the cover by sliding it back into position.<br />

How to use<br />

For ceiling cassette :<br />

Point the signal transmitter towards the front panel <strong>of</strong> the cassette indoor unit (for C, D, E, F<br />

Chassis models) and press any function key. For B chassis point the signal transmitter towards<br />

the wired remote control and press any function key.<br />

For ceiling concealed duct, ducted s<strong>pl</strong>it & Single package :<br />

Point the signal transmitter towards the wired remote control and press any function key.<br />

Remarks<br />

1. Do not use rechargeable batteries for wireless remote control .<br />

2. Remove the batteries from the remote control if the air conditioner is not going to be used for<br />

long time.<br />

5CSL0-06B<br />

378 Controller accessories


5CSL0-06B Wireless remote controller<br />

Function's detail<br />

Models : PQWRHSF0<br />

The remote control transmits the signals to the system.<br />

5<br />

6<br />

4<br />

2<br />

7<br />

11<br />

8<br />

13<br />

15<br />

ON OFF<br />

Operation Mode<br />

CANCEL<br />

SET<br />

AUTO CLEAN<br />

Cooling Operation<br />

Auto Operation or Auto Changeover<br />

Healthy Dehumidification Operation<br />

Heating Operation<br />

Signal transmitter<br />

1<br />

3<br />

10<br />

9<br />

12<br />

14<br />

16<br />

Flip-up door<br />

(opened)<br />

• Cooling Model( ), Heat Pump Model( )<br />

17<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

9<br />

10.<br />

11.<br />

12.<br />

13.<br />

14.<br />

15.<br />

16.<br />

17.<br />

START/STOP BUTTON<br />

Operation starts when this button is pressed and stops<br />

when the button is pressed again.<br />

Operation mode selection button<br />

Used to select the operation mode.<br />

ROOM TEMPERATURE SETTING BUTTONS<br />

Used to select the room temperature.<br />

INDOOR FAN SPEED SELECTOR<br />

Used to select fan speed in four steps<br />

low, medium, high and CHAOS.<br />

JET COOL<br />

Used to start or stop the speed<br />

cooling. (Speed cooling operates<br />

super high fan speed in cooling mode.)<br />

CHAOS SWING BUTTON<br />

Used to stop or start louver movement and set the desired<br />

up/down airflow direction.<br />

ON/OFF TIMER BUTTONS<br />

Used to set the time <strong>of</strong> starting and stopping operation.<br />

TIME SETTING BUTTONS<br />

Used to adjust the time.<br />

TIMER SET/CANCEL BUTTON<br />

Used to set the timer when the desired time is obtained and<br />

to cancel the Timer operation.<br />

SLEEP MODE AUTO BUTTON<br />

Used to set Sleep Mode Auto operation.<br />

AIR CIRCULATION BUTTON<br />

Used to circulate the room air without cooling or heating.<br />

ROOM TEMPERATURE CHECKING BUTTON<br />

Used to check the room temperature.<br />

PLASMA(OPTIONAL)<br />

Used to start or stop the <strong>pl</strong>asma-purification function.<br />

HORIZONTAL AIRFLOW DIRECTION CONTROL<br />

BUTTON (NOT ON ALL MODELS)<br />

Used to set the desired horizontal airflow direction.<br />

RESET BUTTON<br />

Used prior to resetting time or after re<strong>pl</strong>acing batteries.<br />

2nd F Button<br />

Used prior to using modes printed in blue at the bottom <strong>of</strong><br />

buttons.<br />

AUTO CLEAN(OPTIONAL)<br />

Used to set Auto Clean mode.<br />

Controller accessories 379


Wireless remote controller<br />

Models : AHWRHD<br />

3<br />

4<br />

5<br />

6<br />

Flip-up door(opened)<br />

ON OFF<br />

SET CANCEL<br />

Signal transmitter<br />

1<br />

7<br />

2<br />

8<br />

9<br />

10<br />

11<br />

5CSL0-06B<br />

1. Operation dis<strong>pl</strong>ay<br />

Dis<strong>pl</strong>ays the operation conditions.<br />

2. Start/Stop button<br />

Operation starts when this button is pressed and stops<br />

when the button is pressed again.<br />

3. Operation mode selection button<br />

Used to select the operation mode.<br />

4. on/<strong>of</strong>f timer buttons<br />

Used to set the time <strong>of</strong> starting and stopping operation.<br />

5. Time setting buttons<br />

Used to adjust the time.<br />

6. timer set/cancel buttons<br />

Used to set the timer when the desired time is obtained<br />

and to cancel the Timer operation.<br />

7. Air flow direction start/stop button<br />

Used to stop or start louver movement and set the<br />

desired up/down airflow direction.<br />

8. Sleep mode auto button<br />

Used to set Sleep Mode Auto operation.<br />

9. Air circulation button<br />

Used to circulate the room air without cooling or heating<br />

(turns indoor fan on/<strong>of</strong>f).<br />

10. room temperature checking button<br />

Used to check the room temperature.<br />

11. Reset button<br />

Used prior to resetting time or after re<strong>pl</strong>acing batteries.<br />

380 Controller accessories


5CSL0-06B Wireless remote controller<br />

Models : AHWRHS<br />

Signal transmitter<br />

Transmits the signals to the signal receptor.<br />

1<br />

4<br />

3<br />

5<br />

6<br />

A/CL<br />

9<br />

2<br />

7<br />

8<br />

1. FAN operation button<br />

Used to circulate room air without cooling or heating.<br />

2. Cooling operation button<br />

3. S<strong>of</strong>t dry operation button<br />

Used to dehumidify without overcooling.<br />

4. Heating operation button<br />

(Heat pump model only)<br />

5. Timer set button<br />

Used to set the timer when the desired time is obtained.<br />

Then the wired remote controller is set up to 24 hours by<br />

an hour but the wireless remote controller is set up to 7<br />

hours by an hour. Therefore, if you want to set over 7<br />

hours, use the wired remote controller.<br />

6. Fan speed button<br />

Used to set the desired fan speed.<br />

7. On/Off button<br />

Operation starts when this button is pressed, and stops<br />

when the button is pressed again.<br />

8. Set temperature button<br />

Used to set the temperature when the desired temperature<br />

is obtained<br />

9. Auto operation button<br />

Controller accessories 381


Sim<strong>pl</strong>e wired remote control<br />

1.2 Sim<strong>pl</strong>e wired remote controller<br />

Models : PQRCUCA0<br />

Picture:<br />

Ap<strong>pl</strong>icable models<br />

Cassette, duct and ceiling and floor<br />

Functional control<br />

Dimension<br />

PQRCHCS0<br />

Defrost Preheat Out door<br />

Slo<br />

Lo<br />

Med<br />

Hi<br />

Po<br />

Cooling Heating Auto Dry Fan<br />

MODE<br />

FAN<br />

SPEED<br />

Room Temp<br />

Total on<br />

Central Run<br />

120mm<br />

1<br />

2<br />

3<br />

4<br />

5<br />

PQRCHCS0<br />

Defrost Preheat Out door<br />

Slo<br />

Room Temp<br />

Lo<br />

Total on<br />

Med<br />

Hi<br />

Po<br />

Central Run<br />

Cooling Heating Auto Dry Fan<br />

MODE<br />

70mm<br />

FAN<br />

SPEED<br />

Functional description:<br />

13.5mm<br />

5CSL0-06B<br />

1. Sim<strong>pl</strong>e design.<br />

2. Sim<strong>pl</strong>e & easy use.<br />

3. Memorize data(operation data) in case <strong>of</strong> power failure.<br />

4. ON/OFF , Temperature setting, room temperature dis<strong>pl</strong>ay,<br />

Air flow control, lock setting, Fault diagnosis function,<br />

operation mode setting, basic functions.<br />

5. Easy address setting with central control.<br />

6. Operation LED is on during operation.<br />

1. Operation Dis<strong>pl</strong>ay Panel<br />

2. On/<strong>of</strong>f Function<br />

3. Fan Speed Button<br />

4. Temperature Control Button<br />

5. Mode Selection Check Button<br />

382 Controller accessories


5CSL0-06B Sim<strong>pl</strong>e wired remote control<br />

Installation method:<br />

1 Put the installation paper on the <strong>pl</strong>ace and determine the position and height <strong>of</strong> the fixing screws <strong>of</strong> the wired remote controller.<br />

• Refer to the printed side <strong>of</strong> the installation paper.<br />

2 Plug the connecting cable into the indoor unit.<br />

• The product is being shipped with the cable connected only to the remote controller.<br />

Fix the connecting cable with the cable rack.<br />

Side <strong>of</strong><br />

remote Controller<br />

The position <strong>of</strong> the fixing screws<br />

Side <strong>of</strong><br />

Indoor Unit<br />

3 Remove the installation paper before installing the remote controller so that it can fit at the right <strong>pl</strong>ace.<br />

Fixing the<br />

remote controller<br />

Main frame<br />

* Do not embed the remote controller into the wall. (It may cause the breakdown <strong>of</strong> the temperature sensor.)<br />

* If you want to install a number <strong>of</strong> remote controller at the same <strong>pl</strong>ace in a vertical line, install them at regular intervals <strong>of</strong><br />

2cm. (It may cause the breakdown <strong>of</strong> the temperature sensor.)<br />

* Do not install the cable with a distance <strong>of</strong> 30 m or longer. (This can cause communication error.)<br />

* When installing the cable, check whether the connector between the remote controller and the product is installed properly.<br />

The connector will not be connected when installed in opposite sides.<br />

o Sup<strong>pl</strong>y the power after connecting wired remote controller.<br />

When you need to change wired remote controller, switch <strong>of</strong>f the main power and change it.<br />

If the wired remote controller is changed before switching <strong>of</strong>f the main power, the option function <strong>of</strong> the indoor unit can't<br />

be used. (option function like "slow" fan speed selection)<br />

Controller accessories 383<br />

2CM<br />

Main<br />

indoor unit<br />

CN-M C CN-ZONE<br />

J15<br />

C01K<br />

J14<br />

CN-REMO<br />

IC01A<br />

CN-DISP<br />

LO1K<br />

LO1D C07D<br />

LO2K<br />

Red Yellow Brown


Deluxe wired remote controller<br />

1.3 Deluxe wired remote controller<br />

Models : PQRCUDS0<br />

Picture:<br />

Ap<strong>pl</strong>icable models<br />

Cassette, duct and ceiling and floor<br />

Functional control<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

5CSL0-06B<br />

Functional Description:<br />

1. Big LCD panel which can dis<strong>pl</strong>ay various information.<br />

2. Deluxe touch panel.<br />

3. Memorize data(operation data) in case <strong>of</strong> power failure.<br />

4. ON/OFF,Temperature setting, room temperature dis<strong>pl</strong>ay,<br />

5. Air flow control, lock setting,reservation function,<br />

6. Fault diagnosis function, operation mode setting, basic<br />

functions.<br />

7. Easy address setting with central control.<br />

8. Deluxe with LCD back light ap<strong>pl</strong>ied<br />

9. Vane control & child lock, optimum air control as deluxe<br />

function<br />

10. Back light LED is on during operation.<br />

1. Operation Dis<strong>pl</strong>ay Panel<br />

2. Room Temperature Button<br />

3. Fan Speed Button<br />

4. Fan/Plasma/Swirl Swing Button<br />

5. Automatic / Power Saving Vane Control Button<br />

6. Timer Mode Button<br />

7. Date Selection Button<br />

8. Hour/Minute Button<br />

9. Mode Selection Button<br />

10. On/Off Button for reservation<br />

11. Temperature Control Button<br />

12. On/Off Button<br />

13. Special Function Button<br />

14. Dehumidification/ Heater/ Go-out Button<br />

15. Sub Function Button<br />

16. Easy Reservation Button<br />

17. Cancel Button<br />

18. Heating/Ventilation/Elevation Grill Button<br />

19. Setting Button<br />

20. Cooling / Auto Swing / Child Lock Button<br />

384 Controller accessories


5CSL0-06B Deluxe wired remote controller<br />

Installation method:<br />

1 Put the installation paper on the <strong>pl</strong>ace and determine the position and height <strong>of</strong> the fixing screws <strong>of</strong> the wired remote controller.<br />

• Refer to the printed side <strong>of</strong> the installation paper.<br />

The position <strong>of</strong> the fixing screws<br />

2 Plug the connecting cable into the indoor unit.<br />

• The product is being shipped with the cable connected only to the remote controller. Put each cable to the remote controller<br />

according to the color match<br />

Yellow<br />

Yellow<br />

Side <strong>of</strong><br />

remote Controller<br />

Side <strong>of</strong><br />

Indoor Unit<br />

Main frame<br />

3 Remove the installation paper before installing the remote controller so that it can fit into the right <strong>pl</strong>ace.<br />

CN-M C CN-ZONE<br />

J15<br />

Fixing the<br />

remote controller<br />

Be careful not to alter the colors<br />

<strong>of</strong> the remote controller<br />

connection cables.<br />

C01K<br />

J14<br />

CN-REMO<br />

IC01A<br />

CN-DISP<br />

LO1K<br />

LO1D C07D<br />

Red Yellow Brown<br />

LO2K<br />

Fixing the<br />

connecting cable<br />

* When installing the wired remote controller, do not install it so that it is buried to the wall. (This can cause error in the<br />

temperature sensor)<br />

* When installing multi<strong>pl</strong>e wired remote controllers horizontally in one location, leave a minimum distance apart (2cm).<br />

(This can cause error in the temperature sensor)<br />

* Do not install the cable with a distance <strong>of</strong> 50 m or longer. (This can cause communication error.)<br />

* When installing the cable, check whether the connector between the remote controller and the product is installed properly.<br />

The connector will not be connected when installed in opposite sides.<br />

❏ Sup<strong>pl</strong>y the power after connecting wired remote controller.<br />

When you need to change wired remote controller, switch <strong>of</strong>f the main power and change it Before switch <strong>of</strong>f the main<br />

power if changed the wired remote controller , you can't use the option function <strong>of</strong> the indoor unit.<br />

Controller accessories 385


Hotel use remote controller<br />

1.4 Hotel use remote controller<br />

Models : PQRCFCS0<br />

Picture:<br />

Ap<strong>pl</strong>icable models<br />

Cassette, duct and ceiling and floor<br />

Functional control<br />

PQRCHCS0<br />

Defrost Preheat Out door<br />

Slo<br />

Lo<br />

Med<br />

Hi<br />

Po<br />

Cooling Heating Auto Dry Fan<br />

MODE<br />

FAN<br />

SPEED<br />

Room Temp<br />

Total on<br />

Central Run<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Functional description:<br />

5CSL0-06B<br />

Can control one or multi indoor units which have been<br />

installed at remote areas with same function by same controller<br />

at same time<br />

1. Sim<strong>pl</strong>e design.<br />

2. Sim<strong>pl</strong>e & easy use.<br />

3. Memorize data(operation data) in case <strong>of</strong> power failure.<br />

4. ON/OFF , Temperature setting, room temperature dis<strong>pl</strong>ay,<br />

Air flow control, lock setting, Fault diagnosis function,<br />

operation mode setting, basic functions.<br />

5. Easy address setting with central control.<br />

6. Operation LED is on during operation.<br />

7. Operation mode setting can be done by central control<br />

1. Operation Dis<strong>pl</strong>ay Panel<br />

2. On/<strong>of</strong>f Function<br />

3. Fan Speed Button<br />

4. Temperature Control Button<br />

5. Room temperature button<br />

386 Controller accessories


5CSL0-06B Hotel use remote controller<br />

Dimension<br />

Operation<br />

1. LCD Panel to show various information.<br />

2. Can check indoor operation status by Key.<br />

3. Memorize data(operation data) in case <strong>of</strong> power failure.<br />

4. ON/OFF , Temperature setting, room temperature dis<strong>pl</strong>ay, Air flow control, lock setting, Fault diagnosis function, operation<br />

mode setting, basic functions, reservation function, Clock function.<br />

5. Easy address setting with central control.<br />

NOTE<br />

120mm<br />

PQRCHCS0<br />

Defrost Preheat Out door<br />

Slo<br />

Room Temp<br />

Lo<br />

Total on<br />

Med<br />

Hi<br />

Po<br />

Central Run<br />

Cooling Heating Auto Dry Fan<br />

MODE<br />

70mm<br />

FAN<br />

SPEED<br />

13.5mm<br />

1. Two types <strong>of</strong> controller CST/DUCT.<br />

2. Can control one or multi indoor units which have been installed at remote areas with same function by same controller at<br />

same time.<br />

Controller accessories 387


Zone Control<br />

1.5 Zone Control<br />

Models : ABZCA<br />

Picture<br />

Zone Control<br />

sub PCB<br />

Ap<strong>pl</strong>icable models<br />

Ceiling concealed duct<br />

Accessory<br />

• Factory Sup<strong>pl</strong>ied :<br />

5CSL0-06B<br />

- Zone Control PCB............................................................................................................................................................1EA<br />

- Trans................................................................................................................................................................................1EA<br />

- Case ................................................................................................................................................................................1EA<br />

- Cover ...............................................................................................................................................................................1EA<br />

- Main lead wires................................................................................................................................................................1EA<br />

- Screws .............................................................................................................................................................................4EA<br />

- Holder ..............................................................................................................................................................................4EA<br />

- Installation Manual................................................................................................................................................................1<br />

• Purchased Locally :<br />

- Damper Motor<br />

- Thermostat<br />

- Damper<br />

ROOM1 Thermostat<br />

Damper Motor<br />

Damper Motor<br />

ROOM3 Thermostat<br />

ROOM2 Thermostat<br />

Damper Motor<br />

Damper Motor<br />

ROOM4 Thermostat<br />

Functional Description:<br />

1) Operation Summary<br />

A device which senses temperature <strong>of</strong> each zone controls<br />

operation <strong>of</strong> each diffuser,so temperature <strong>of</strong> each zone<br />

can be controlled.<br />

2) Specific Operation<br />

- If every zone (diffuser) is closed, Comp and outer fan<br />

become turned <strong>of</strong>f to protect compressor.<br />

* Zone controller requires diffuser temperatures and controllers<br />

available locally.<br />

3) Operating Scene<br />

• The temperature <strong>of</strong> all zones are controlled individually<br />

(makes energy savings) controlled by the signal <strong>of</strong> every<br />

zones in duct system (By connecting the thermostat<br />

and VAV Diffuser to Main PCB,comp. & fan)<br />

• Diffuser and Thermostat are locally sourced Connected<br />

to Another Apparatus, Control it Freely.<br />

388 Controller accessories


5CSL0-06B Zone Control<br />

Installation method:<br />

• Connect main lead wires between main PCB and Zone Control.<br />

• Connect thermostat to Zone Control according to thermostat maker's manuals.<br />

• Connect Damper Motor to Zone Control according to Damper Motor maker's manuals.<br />

• Wiring also depends upon the type <strong>of</strong> the damper actuators.<br />

• Spring Return Damper Actuators<br />

Trans : 12VA<br />

(24V/130mA*4)<br />

Trans<br />

Main<br />

PCB<br />

Indoor Unit<br />

Zone<br />

Controller<br />

PCB<br />

CH1<br />

CH2<br />

CH3<br />

CH4<br />

COM<br />

COM<br />

COM<br />

COM<br />

AC 24V<br />

24V<br />

24V<br />

Power Input<br />

24V<br />

AC220~240V 50/60Hz<br />

Thermostat #1<br />

Thermostat #2<br />

Thermostat #3<br />

Thermostat #4<br />

• Non Spring Return Damper Actuators<br />

Trans : 12VA<br />

(24V/130mA*4)<br />

Trans<br />

Main<br />

PCB<br />

Indoor Unit<br />

Zone<br />

Controller<br />

PCB<br />

AC(L) AC(N)<br />

CH1<br />

CH2<br />

CH3<br />

CH4<br />

COM<br />

COM<br />

COM<br />

COM<br />

AC 24V<br />

24V<br />

24V<br />

Power Input<br />

24V<br />

AC(L) AC(N)<br />

AC220~240V 50/60Hz<br />

By Pass Damper System :-<br />

24 VCA<br />

power sup<strong>pl</strong>y<br />

HVAC<br />

Thermostat #1<br />

Thermostat #2<br />

Thermostat #3<br />

Thermostat #4<br />

By-pass damper<br />

Damper<br />

Motor<br />

#1<br />

Damper<br />

Motor<br />

#2<br />

Damper<br />

Motor<br />

#3<br />

Damper<br />

Motor<br />

#4<br />

Controller accessories 389<br />

N<br />

Damper<br />

Motor<br />

#1<br />

N<br />

L L L L<br />

N N N<br />

S S S S<br />

Damper<br />

Motor<br />

#2<br />

Damper<br />

Motor<br />

#3<br />

N N N<br />

L : Live<br />

N : Neutral<br />

S : Signal<br />

Return Sup<strong>pl</strong>y<br />

40 VA<br />

transformer<br />

NC NO<br />

Pressure controller<br />

Closed<br />

Open<br />

Common<br />

2 3<br />

1<br />

Static<br />

pressure<br />

control<br />

3-channel damper motor<br />

Damper<br />

Motor<br />

#4<br />

To maintain an adequate flow <strong>of</strong> air and static pressure through the HVAC system, a by-pass system can be used that is<br />

equipped with a motorized damper and a static pressure control.


Zone Control<br />

Installation Procedure:<br />

5CSL0-06B<br />

• The control should be mounted to control panel using 4 screws sup<strong>pl</strong>ied.<br />

• Fasten it to any holes on control panel as long as there is enough space to install. If necessary drill holes to install on proper<br />

position.<br />

• When drilling, ensure that metal f does not foul any electronic components.<br />

* Central<br />

Contr oller<br />

Wiring Diagram:<br />

* Central<br />

Sub PCB<br />

** Wir ed<br />

Remote<br />

Contr oller<br />

**Main Pcb<br />

** Dis<strong>pl</strong>ay PCB<br />

*RF<br />

Remote<br />

Contr oller<br />

Indoor Unit<br />

When the area dampers open or close, the static pressure control will open or close the by-pass damper so as to maintain<br />

the adequate static pressure. Dimensions <strong>of</strong> the by-pass damper depends on the cooling capacity <strong>of</strong> the unit.<br />

Btu/h Size <strong>of</strong> the by-pass (ø)<br />

36K 250 mm<br />

42K 250 mm<br />

48K 300 mm<br />

60K 300 mm<br />

91K 350 mm<br />

120K 350 mm<br />

Remarks:<br />

• Turn <strong>of</strong>f the Power before installation or maintenance.<br />

Array <strong>of</strong> PCB & Controllers Local sourcing components<br />

* Zone<br />

Contr oller<br />

Sub Pcb<br />

AC 24V<br />

Transformer<br />

Outdoor Unit<br />

ZONE CONTROLLER WIRING DIAGRAM<br />

Thermostat #1<br />

Thermostat #2<br />

Thermostat #3<br />

Thermostat #4<br />

In case <strong>of</strong> 220V Damper,<br />

attach AC 24V Relay<br />

390 Controller accessories<br />

Relay<br />

Relay<br />

Relay<br />

Relay<br />

Damper<br />

#1<br />

Damper<br />

#2<br />

Damper<br />

#3<br />

Damper<br />

#4


5CSL0-06B Dry contact module<br />

1.6 Dry contact module<br />

Models : PQDSA [Without case], PQDSB [With case]<br />

Picture:<br />

PQDSA<br />

Accessory:<br />

PQDSA<br />

• Dry Contact PCB ..........................................................1EA<br />

• Installation Manual .......................................................1EA<br />

• Lead Wire Assembly ....................................................4EA<br />

Ap<strong>pl</strong>icable Models<br />

• LGAP ap<strong>pl</strong>ication models<br />

Installation Procedure:<br />

Installation steps for single product<br />

PQDSB<br />

• Dry Contact PCB 1EA<br />

• Case 1EA<br />

• Installation Manual 1EA<br />

• Lead Wire Assembly 4EA<br />

1 . Connect CN-CC with Main PCB by the cable(provided)<br />

- Connection <strong>of</strong> Dry contact only - Connection <strong>of</strong> Dry contact & LG Central Controller<br />

MAIN<br />

PCB<br />

CN-CC CN-CC<br />

PQDSB<br />

DRY CONTACT<br />

SUB PCB<br />

2 1 1<br />

4 4<br />

3 3<br />

2 2<br />

1 1<br />

AC 220V<br />

1<br />

3 4 5 6<br />

Controller accessories 391<br />

MAIN<br />

PCB<br />

2<br />

1 CN-POWER : AC 220V Connector<br />

2 CN-CC : MAIN PCB Connector<br />

3 CN_DRY (L) : DRY CONTROLLER Connector<br />

4 CN_DRY ( SIG ) : DRY CONTROLLER Connector<br />

5 CN_DRY (ERROR CHECK) : ERROR Check<br />

Dis<strong>pl</strong>ay Connector<br />

6 CN_DRY( OPER STATE): Operation Dis<strong>pl</strong>ay<br />

Connector<br />

Connection PCB<br />

(6871A30056A)<br />

CN-CC CN-CC<br />

S1<br />

BR1<br />

ON<br />

L1 2 3 4<br />

TANS01Y<br />

C03Y<br />

SWITCH<br />

U03Y<br />

OSC01B<br />

L02D<br />

L01D<br />

U04Y<br />

C04Y<br />

U02Y<br />

C01A<br />

LED1<br />

LED01G<br />

LED02G<br />

LED03G<br />

IC01A<br />

CN_COMM<br />

ZNR01Y<br />

DRY CONTACT<br />

SUB PCB<br />

2 1 1<br />

4 4<br />

3 3<br />

2 2<br />

1 1<br />

AC 220V<br />

PI485 PCB : Special purchase for<br />

Central Control<br />

(Ex : PHNFP14A0 or PSNFP14A0...)


Dry contact module<br />

Installation steps for muiti product<br />

1 . Connect CN_DRY with Control Unit .<br />

(Fix SUB PCB into the proper location.)<br />

- To ap<strong>pl</strong>y power source through PCB - To ap<strong>pl</strong>y power source from the outside<br />

DRY CONTACT<br />

SUB PCB<br />

CN-CC<br />

User guide<br />

Function<br />

RY1<br />

RY2<br />

4 4<br />

3 3<br />

2 2<br />

1 1<br />

2<br />

2 1 N L<br />

1<br />

INPUT<br />

AC 220V<br />

Operation Dis<strong>pl</strong>ay<br />

Error Check Dis<strong>pl</strong>ay<br />

Dry contact<br />

Controller<br />

DRY CONTACT<br />

SUB PCB<br />

Dry contact<br />

Controller<br />

5CSL0-06B<br />

392 Controller accessories<br />

CN-CC<br />

RY1<br />

RY2<br />

2<br />

2 1 N L<br />

1<br />

4 4<br />

3 3<br />

2 2<br />

1 1<br />

AC 220V<br />

Operation Dis<strong>pl</strong>ay<br />

Error Check Dis<strong>pl</strong>ay<br />

It gives a selection whether to turn ON the unit directly or not from the external source (such as key holder in hotel rooms).<br />

The selection can be made by pressing Cancel button <strong>of</strong> the wireless remote controller 3 times within 3 minutes <strong>of</strong> starting<br />

the unit facing it towards the unit (This function availability depends on indoor unit model type.)<br />

1. Normal mode (Factory set)<br />

• Not to turn ON the unit directly from the external source.<br />

On inserting the key inside the key holder, it activates the system.<br />

Later on , the unit can be turned ON by the remote controller.<br />

2.Automatic mode<br />

• To turn ON the unit directly from the external source<br />

On inserting the key inside the key holder, it automatically turns<br />

ON the air conditioner. So no need to use remote controller.<br />

❈ However the unit can be turned <strong>of</strong>f directly if the key is taken out <strong>of</strong> the key holder for both cases.<br />

CAUTION<br />

• In case <strong>of</strong> power failure the air conditioner will resume its similar operation before the power failure.<br />

• In case power comes again after a power failure. Auto restart the unit auto magically operates to the previous operation<br />

conditions.


5CSL0-06B Branch kit<br />

2. Mechanical accessories<br />

2.1 Branch kit<br />

Models : PMUB11A, PMUB111A, PMUB1111A<br />

Picture<br />

Features<br />

Connectable <strong>of</strong><br />

indoor units<br />

Models<br />

2 Units PMUB 11A<br />

3 Units<br />

4 Units<br />

PMUB 111A<br />

PMUB 1111A<br />

Gas pipe Liquid pipe<br />

Gas pipe Liquid pipe<br />

(1:1) (1:1)<br />

(1:1:1) (1:1:1)<br />

(1:1:1:1) (1:1:1:1)<br />

Mechanical accessories 393


Branch kit<br />

Branch kit<br />

Between units are the required Branch kits mentioned, that are necessary to install the combination.<br />

C<br />

Indoor Classification<br />

2 Units<br />

3 Units<br />

4 Units<br />

A<br />

Model Name<br />

PMUB11A<br />

PMUB111A<br />

PMUB1111A<br />

a b c<br />

a b<br />

Type 1 Type 2<br />

B<br />

D<br />

Capacity Ratio(%)<br />

50:50 (1:1)<br />

33:33:33 (1:1:1)<br />

25:25:25:25(1:1:1:1)<br />

5CSL0-06B<br />

Unit : mm (inch)<br />

394 Mechanical accessories<br />

(I.D)<br />

ⓐ ⓑ ⓒ Type<br />

Ⓐ Ø15.88(5/8) Ø19.05(3/4) Ø25.4(1) 1<br />

Ⓑ<br />

Ø9.52(3/8)<br />

Ø12.7(1/2)<br />

Ø12.7(1/2)<br />

Ø15.88(5/8)<br />

- 2<br />

Ⓒ Ø6.35(1/4) Ø9.52(3/8) - 2<br />

Ⓓ Ø9.52(3/8) Ø12.7(1/2) - 2


5CSL0-06B<br />

2.2 Drain pump<br />

Ceiling Concealed Duct<br />

Accessory Model Name D, F Chassis G, H & R Chassis E Chassis<br />

ABDPD ABDPG ABDPE<br />

Functional Description:<br />

• To remove the condensed water from the indoor unit.<br />

• In some <strong>of</strong> the <strong>pl</strong>aces where natural drainage is not possible Drain Pump is very useful to remove condensed water.<br />

Picture:<br />

Accessory:<br />

Factory Sup<strong>pl</strong>ied Parts<br />

For D, E & F Chassis Models<br />

- Drain Pump Assembly<br />

(AC220-240,50/60Hz,400CMM).........................1EA<br />

- Elbow (ø32)........................................................1EA<br />

- Hose...................................................................1EA<br />

- Tie Wrap ...........................................................2EA<br />

- Screw ...............................................................10EA<br />

- Rubber ...............................................................1EA<br />

- Installation Manual .............................................1EA<br />

For G, H & R Chassis Models :<br />

- Drain Pump Assembly<br />

(AC220-240,50/60Hz,400CMM).........................1EA<br />

- Screw .................................................................4EA<br />

- Cap ....................................................................1EA<br />

- Installation Manual .............................................1EA<br />

ABDPD/ABDPE ABDPG<br />

Parts needed for servicing<br />

(Factory Sup<strong>pl</strong>ied)<br />

For D, E & F Chassis Models :<br />

Part Name Part No.<br />

Water Pump 5858A10001L<br />

Switch Assy, Float 6601A20001E<br />

For G, H & R Chassis Models :<br />

Part Name Part No.<br />

Water Pump 5858A10001L<br />

Switch Assy, Float 6601A20001E<br />

Drain pump<br />

Mechanical accessories 395


Drain pump 5CSL0-06B<br />

Installation procedure<br />

For D,E&F Chassis Models:<br />

Step 1. Separate the filter and Open the top cover.<br />

Step 2. Assemble the drain pump assembly and Attach the elbow to the side panel. Tighten 4 screws to the channel.<br />

Tighten 2 screws to the Side panel.<br />

Step 3. Connect the hose and tie wrap and Connect two lead wires to control box. Connect two lead wires to control box,<br />

One wire is for float switch and other Wire is for power sup<strong>pl</strong>y to drain pump.<br />

.<br />

Step 4. Assemble the top cover.<br />

396 Mechanical accessories


5CSL0-06B<br />

Installation procedure<br />

For G, H & R Chassis Models:<br />

Step 1. Separate the filter and Open the top cover.<br />

Drain pump<br />

Step 2. Remove the knock-out from the side panel and Assemble the drain pump assembly. Tighten 4 screws to the Side<br />

Panel.<br />

Step 3. Connect two lead wires to control box and Close the drainage hole with the provided cap. Connect two lead wires<br />

to control box (One wire is for float switch and other Wire is for power sup<strong>pl</strong>y to drain pump.)<br />

Step 4. Assemble the top cover and insert the filter.<br />

Mechanical accessories 397


Drain pump 5CSL0-06B<br />

Wiring diagram:<br />

For D, E & F chassis models<br />

For G & H Chassis Models :<br />

TO OUTDOOR UNIT<br />

TO OUTDOOR UNIT<br />

1(L) 2(N) 4<br />

3 5<br />

TERMINAL<br />

BLOCK<br />

1(L) 2(N) 4<br />

3 5<br />

TERMINAL<br />

BLOCK<br />

T/B<br />

BR<br />

BL<br />

RD<br />

BK<br />

GN/YL<br />

BR<br />

BL<br />

RD<br />

BK<br />

BL<br />

GN/YL<br />

VENTILATOR<br />

INDOOR ELECTRIC CIRCUIT<br />

INDOOR<br />

MOTOR<br />

398 Mechanical accessories<br />

COMP<br />

BR<br />

YL<br />

FUSE<br />

250V10A<br />

OR<br />

RD<br />

BL<br />

BK<br />

4 WAY<br />

GN/YL<br />

DRAIN<br />

PUMP<br />

BL<br />

BL<br />

Drain Pump Assy<br />

ZONE<br />

CONTROL<br />

INDOOR ELECTRIC CIRCUIT<br />

FUSE<br />

250V 8A<br />

COMP<br />

YL<br />

BR<br />

OR<br />

A/CL<br />

UNIT<br />

INDOOR<br />

MOTOR<br />

BR<br />

BK<br />

4 WAY<br />

GN/YL<br />

TRIAC<br />

VENT<br />

TELECONTROL/<br />

CENTRAL CONTROL<br />

DRAIN<br />

PUMP<br />

BL<br />

BL<br />

Drain Pump Assy<br />

ZONE<br />

CONTROL<br />

TEMP.<br />

THERMISTOR<br />

TEMP.<br />

THERMISTOR<br />

PIPE<br />

THERMISTOR<br />

FLOAT S/W<br />

REMOTE<br />

CONTROL<br />

PIPE<br />

THERMISTOR<br />

FLOAT S/W<br />

REMOTE<br />

CONTROL<br />

OPTION


5CSL0-06B<br />

Remarks<br />

For D, E, F, G, H & R Chassis Models<br />

• Possible drain-head height is up to 700mm. so, installation must be<br />

below 700mm.<br />

• Keep the drain hose inclined downward with a slope <strong>of</strong> 1/50~1/100.<br />

• Prevent upward or reverse flow.<br />

- To prevent condensate forming over the drain pipe minimum 5mm thick insulation should be ap<strong>pl</strong>ied.<br />

- Upward rounding is not allowed.<br />

- Be sure that there should not be any leakage<br />

- after closing the drainage hole with the cap.<br />

Unit<br />

1/50~1/100<br />

Drainage Hole<br />

• Disconnect the power sup<strong>pl</strong>y before installation & maintenance.<br />

• Check the drain pump for normal operation and abnormal noise after electrical wiring.<br />

Drain Pipe<br />

Drain Pump<br />

MAX 700mm<br />

Drain pump<br />

1/50~1/100<br />

Mechanical accessories 399<br />

Elbow<br />

Drain pump<br />

Thermal insulator<br />

(Local sup<strong>pl</strong>y)<br />

Drainage pipe<br />

(Local sup<strong>pl</strong>y)<br />

Cap


Air guide 5CSL0-06B<br />

2.3 Air guide<br />

Models : PQAGA.<br />

Picture:<br />

Accessory:<br />

Air Guide........................................................................1EA<br />

Dimension<br />

Installation Procedure:<br />

587.6<br />

372.5<br />

1. Fix the air guide unit on the top <strong>of</strong> the outdoor unit as shown in the figure.<br />

600mm<br />

390<br />

Ap<strong>pl</strong>icable Models<br />

• Multi-V <strong>pl</strong>us chassis; UQ, UY, UW<br />

• Multi F DX chassis; UY, UW<br />

• Single A; UY, UW<br />

400 Mechanical accessories<br />

125<br />

2400mm<br />

723.5<br />

950mm Air guide<br />

950mm<br />

Functional Description:<br />

• It is an air guide that specially fits the Outdoor design.<br />

• Air discharge can be changed by a sim<strong>pl</strong>e installation.<br />

• With one outdoor unit top discharge and front discharge<br />

are available simultaneously.


5CSL0-06B<br />

2.4 Cassette cover<br />

Models : PTDCQ, PTDCM<br />

Picture:<br />

Functional Description:<br />

Maintains the ceiling elegance.<br />

• Covers the side area <strong>of</strong> cassette.<br />

• Gives elegant looks.<br />

• Light weight..<br />

• Suitable when false ceiling is unavailable.<br />

Ap<strong>pl</strong>icable Models:<br />

PTDCQ : UT09, UT12, UT18 TR/TQ CHASSIS<br />

PTDCM : UT24 ~ UT60 TP/TN/TM CHASSIS<br />

Cassette cover<br />

Mechanical accessories 401


Air Conditioner<br />

20 Yeouido-dong, Yeongdeungpo-gu,<br />

Yeouido P.O.Box 335 Seoul,<br />

150-721, Korea.<br />

http://www.lgeaircon.com<br />

All rights reserved<br />

Printed in Korea December/2010<br />

The specifications, designs, and<br />

information in this brochure are subject to<br />

change without notice.<br />

P/No.: 3828A20576H<br />

The air conditioners manufactured by LG have received ISO9001 certificate for<br />

quality assurance and ISO14001 certificate for environmental management system.