Pressure control and water make up system
Pressure control and water make up system
Pressure control and water make up system
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Pleno<br />
<strong>Pressure</strong> <strong>control</strong> <strong>and</strong> <strong>water</strong> <strong>make</strong> <strong>up</strong> <strong>system</strong><br />
Pressurisation & Water Quality Balancing & Control Thermostatic Control<br />
engineering ADVAnTAge<br />
<strong>Pressure</strong>-maintaining monitoring device in the sense of EN 12828-4.7.4. The Pleno ensures that<br />
the <strong>water</strong> reserve required for optimum functioning of the expansion vessels is given at all times.<br />
If the level drops below the minimum, <strong>water</strong> is automatically added to the <strong>system</strong>. The «fillsafe»<br />
electronically monitors <strong>and</strong> <strong>control</strong>s the <strong>water</strong> <strong>make</strong>-<strong>up</strong> <strong>and</strong> ensures maximum safety.
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
2
Pleno P<br />
Hydraulic unit | <strong>water</strong> <strong>make</strong>-<strong>up</strong> without pumps<br />
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />
• external <strong>control</strong> from pressure-maintaining or degassing stations, i.e. Compresso, Transfero or Vento<br />
• with contact <strong>water</strong> meter <strong>and</strong> back fl ow preventer type BA according to EN 1717, DVGW, SVGW, KIWA N.V., BELGAQUA,<br />
WRAS <strong>and</strong> ACS tested<br />
• with integrated wall mounting bracket<br />
• addition of antifreeze agent <strong>up</strong> to 50%<br />
Approx. throughput V | Pleno P<br />
Pleno P<br />
Pleno P<br />
TS: 65 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: G ½ SNS: G ½ IP: 65 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
B<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
PA<br />
kW<br />
KVS<br />
m 3 /h<br />
Article no.<br />
P 10 1700 200 125 3 0.02 0.5 813 1000<br />
The requirements for pNS must be taken into account for Statico <strong>and</strong> Compresso:<br />
• required fresh <strong>water</strong> pressure Compresso: pNS ≥ P0 (BrainCube) + 1,9 bar | pNS ≤ 10 bar<br />
• required fresh <strong>water</strong> pressure Statico: pNS ≥ P0 (BrainCube) + 1,7 bar | pNS ≤ 10 bar.<br />
pSNS pSA<br />
3
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
Pleno PI<br />
Control unit TecBox | <strong>water</strong> <strong>make</strong>-<strong>up</strong> without pumps<br />
• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />
• fi llsafe <strong>water</strong> <strong>make</strong>-<strong>up</strong> | pressure-dependent | for pressure expansion vessels with fi xed air cushion, i.e. Statico<br />
• with contact <strong>water</strong> meter <strong>and</strong> back fl ow preventer type BA according to EN 1717, DVGW, SVGW, KIWA N.V., BELGAQUA,<br />
WRAS <strong>and</strong> ACS tested<br />
• BrainCube <strong>control</strong> | self-optimising with memory function<br />
• with integrated wall mounting bracket<br />
• addition of antifreeze agent <strong>up</strong> to 50%<br />
• CE-tested according to the requirements of the European Directives 2004/108/EC, 2006/95/EC<br />
Approx. throughput V | Pleno PI<br />
4<br />
Pleno PI<br />
TS: 65 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: G ½ SNS: G ½ IP: 54 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
B<br />
mm<br />
Accessories for <strong>control</strong> modules • Communication module � page 6<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
PA<br />
kW<br />
KVS<br />
m 3 /h<br />
Pleno PI<br />
Article no.<br />
PI 10 1700 220 280 4 0.04 0.5 813 1010<br />
The requirements for pNS must be taken into account:<br />
• required fresh <strong>water</strong> pressure Statico: pNS ≥ P0 (BrainCube) + 1,7 bar | pNS ≤ 10 bar.<br />
pSNS pSA
Pleno PI<br />
Control unit TecBox | <strong>water</strong> <strong>make</strong>-<strong>up</strong> with pumps<br />
with fi lling function<br />
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
Pleno PI 9 Pleno PI 6<br />
• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />
• fi llsafe <strong>water</strong> <strong>make</strong>-<strong>up</strong> | pressure- or level-dependent | for pressure expansion vessels, i.e. Statico or pressure-maintaining<br />
stations, i.e. Compresso<br />
• with contact <strong>water</strong> meter <strong>and</strong> a break tank type AB according to EN 1717, SVGW-tested<br />
• BrainCube <strong>control</strong> | self-optimising with memory function<br />
• addition of antifreeze agent <strong>up</strong> to 50%<br />
• CE-tested according to the requirements of the European Directives PED/DEP 97/23/EC, 2004/108/EC, 2006/95/EC<br />
H<br />
H<br />
H<br />
SA<br />
SNS<br />
SA<br />
SNS<br />
B<br />
B<br />
B<br />
front<br />
back<br />
SA<br />
SNS<br />
front<br />
back<br />
front<br />
back<br />
Pleno PI 9.1<br />
• 1 pump<br />
• with integrated wall mounting bracket<br />
• high quality metal cover<br />
TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
Pleno PI 6.1<br />
• 1 pump<br />
• fl oor st<strong>and</strong>ing<br />
• high quality metal cover with h<strong>and</strong>les<br />
• inclusive of fl exible hose for inlet<br />
TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
B<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
PA<br />
kW<br />
SPL<br />
dB(A)<br />
DPp<br />
bar<br />
VNS<br />
l/h<br />
Article no.<br />
PI 6.1 8 390 1000 490 26 1.1 55 1-5.5 500 813 1020<br />
Pleno PI 6.2<br />
• 2 pumps | including a reserve pump<br />
• fl oor st<strong>and</strong>ing<br />
• high quality metal cover with h<strong>and</strong>les<br />
• inclusive of fl exible hose for inlet<br />
TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
B<br />
mm<br />
B<br />
mm<br />
H<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
G<br />
kg<br />
PA<br />
kW<br />
SPL<br />
dB(A)<br />
DPp<br />
bar<br />
VNS<br />
l/h<br />
Article no.<br />
PI 6.2 8 390 1000 490 37 1.1 55 1- 5.5 500 813 1030<br />
PA<br />
kW<br />
SPL<br />
dB(A)<br />
DPp<br />
bar<br />
VNS<br />
l/h<br />
Article no.<br />
PI 9.1 10 320 760 260 20 0.75 74 1-8 500 813 1040<br />
Accessories for <strong>control</strong> modules • Communication module � page 6<br />
5
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
6<br />
Accessories for <strong>control</strong> modules<br />
Communication module for BrainCube <strong>control</strong><br />
H<br />
H<br />
B<br />
B<br />
ComCube DCD<br />
• RS 485 interface for communicating with BrainCube, 6 digital inputs for the use of external volt free<br />
signals (NO), 9 volt free digital outputs, freely programmable; all outputs can be inversed<br />
• wall mounted, fi xing elements for cable management<br />
TU: 40 °C IP: 54 U: 230 V/50 Hz<br />
Type B<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
PA<br />
kW<br />
Article no.<br />
DCD 270 230 260 0.5 0.1 814 1000<br />
ComCube DCA<br />
• 2 separated analoge outputs 4-20 mA for connection to BMS, isolation voltage 2.5 kVAC<br />
• all cabeling inside the casing, wall mounted<br />
TU: 40 °C IP: 54 U: 230 V/50 Hz<br />
Type B<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
DCD DCA<br />
PA<br />
kW<br />
Article no.<br />
DCA 190 260 180 0.5 0.1 814 1010
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
7
Additional information<br />
System design: : Online calculation software SelectP!<br />
Short cuts | terms: : Datasheet Planning <strong>and</strong> calculation | Glossary<br />
The products, texts, photographs, graphics <strong>and</strong> diagrams in this brochure may be subject to alteration by TA Hydronics<br />
without prior notice or reasons being given. For the most <strong>up</strong> to date information about our products <strong>and</strong> specifications,<br />
please visit www.tahydronics.com.<br />
partner in your country : www.tahydronics.com<br />
RSPINEN011105