Pleno<br />

<strong>Pressure</strong> <strong>control</strong> <strong>and</strong> <strong>water</strong> <strong>make</strong> <strong>up</strong> <strong>system</strong><br />

Pressurisation & Water Quality Balancing & Control Thermostatic Control<br />

engineering ADVAnTAge<br />

<strong>Pressure</strong>-maintaining monitoring device in the sense of EN 12828-4.7.4. The Pleno ensures that<br />

the <strong>water</strong> reserve required for optimum functioning of the expansion vessels is given at all times.<br />

If the level drops below the minimum, <strong>water</strong> is automatically added to the <strong>system</strong>. The «fillsafe»<br />

electronically monitors <strong>and</strong> <strong>control</strong>s the <strong>water</strong> <strong>make</strong>-<strong>up</strong> <strong>and</strong> ensures maximum safety.


PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

2


Pleno P<br />

Hydraulic unit | <strong>water</strong> <strong>make</strong>-<strong>up</strong> without pumps<br />

PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />

• external <strong>control</strong> from pressure-maintaining or degassing stations, i.e. Compresso, Transfero or Vento<br />

• with contact <strong>water</strong> meter <strong>and</strong> back fl ow preventer type BA according to EN 1717, DVGW, SVGW, KIWA N.V., BELGAQUA,<br />

WRAS <strong>and</strong> ACS tested<br />

• with integrated wall mounting bracket<br />

• addition of antifreeze agent <strong>up</strong> to 50%<br />

Approx. throughput V | Pleno P<br />

Pleno P<br />

Pleno P<br />

TS: 65 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />

SA: G ½ SNS: G ½ IP: 65 U: 230 V/50 Hz<br />

Type PS<br />

bar<br />

B<br />

mm<br />

H<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

PA<br />

kW<br />

KVS<br />

m 3 /h<br />

Article no.<br />

P 10 1700 200 125 3 0.02 0.5 813 1000<br />

The requirements for pNS must be taken into account for Statico <strong>and</strong> Compresso:<br />

• required fresh <strong>water</strong> pressure Compresso: pNS ≥ P0 (BrainCube) + 1,9 bar | pNS ≤ 10 bar<br />

• required fresh <strong>water</strong> pressure Statico: pNS ≥ P0 (BrainCube) + 1,7 bar | pNS ≤ 10 bar.<br />

pSNS pSA<br />

3


PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

Pleno PI<br />

Control unit TecBox | <strong>water</strong> <strong>make</strong>-<strong>up</strong> without pumps<br />

• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />

• fi llsafe <strong>water</strong> <strong>make</strong>-<strong>up</strong> | pressure-dependent | for pressure expansion vessels with fi xed air cushion, i.e. Statico<br />

• with contact <strong>water</strong> meter <strong>and</strong> back fl ow preventer type BA according to EN 1717, DVGW, SVGW, KIWA N.V., BELGAQUA,<br />

WRAS <strong>and</strong> ACS tested<br />

• BrainCube <strong>control</strong> | self-optimising with memory function<br />

• with integrated wall mounting bracket<br />

• addition of antifreeze agent <strong>up</strong> to 50%<br />

• CE-tested according to the requirements of the European Directives 2004/108/EC, 2006/95/EC<br />

Approx. throughput V | Pleno PI<br />

4<br />

Pleno PI<br />

TS: 65 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />

SA: G ½ SNS: G ½ IP: 54 U: 230 V/50 Hz<br />

Type PS<br />

bar<br />

B<br />

mm<br />

Accessories for <strong>control</strong> modules • Communication module � page 6<br />

H<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

PA<br />

kW<br />

KVS<br />

m 3 /h<br />

Pleno PI<br />

Article no.<br />

PI 10 1700 220 280 4 0.04 0.5 813 1010<br />

The requirements for pNS must be taken into account:<br />

• required fresh <strong>water</strong> pressure Statico: pNS ≥ P0 (BrainCube) + 1,7 bar | pNS ≤ 10 bar.<br />

pSNS pSA


Pleno PI<br />

Control unit TecBox | <strong>water</strong> <strong>make</strong>-<strong>up</strong> with pumps<br />

with fi lling function<br />

PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

Pleno PI 9 Pleno PI 6<br />

• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />

• fi llsafe <strong>water</strong> <strong>make</strong>-<strong>up</strong> | pressure- or level-dependent | for pressure expansion vessels, i.e. Statico or pressure-maintaining<br />

stations, i.e. Compresso<br />

• with contact <strong>water</strong> meter <strong>and</strong> a break tank type AB according to EN 1717, SVGW-tested<br />

• BrainCube <strong>control</strong> | self-optimising with memory function<br />

• addition of antifreeze agent <strong>up</strong> to 50%<br />

• CE-tested according to the requirements of the European Directives PED/DEP 97/23/EC, 2004/108/EC, 2006/95/EC<br />

H<br />

H<br />

H<br />

SA<br />

SNS<br />

SA<br />

SNS<br />

B<br />

B<br />

B<br />

front<br />

back<br />

SA<br />

SNS<br />

front<br />

back<br />

front<br />

back<br />

Pleno PI 9.1<br />

• 1 pump<br />

• with integrated wall mounting bracket<br />

• high quality metal cover<br />

TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />

SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />

Type PS<br />

bar<br />

Pleno PI 6.1<br />

• 1 pump<br />

• fl oor st<strong>and</strong>ing<br />

• high quality metal cover with h<strong>and</strong>les<br />

• inclusive of fl exible hose for inlet<br />

TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />

SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />

Type PS<br />

bar<br />

B<br />

mm<br />

H<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

PA<br />

kW<br />

SPL<br />

dB(A)<br />

DPp<br />

bar<br />

VNS<br />

l/h<br />

Article no.<br />

PI 6.1 8 390 1000 490 26 1.1 55 1-5.5 500 813 1020<br />

Pleno PI 6.2<br />

• 2 pumps | including a reserve pump<br />

• fl oor st<strong>and</strong>ing<br />

• high quality metal cover with h<strong>and</strong>les<br />

• inclusive of fl exible hose for inlet<br />

TS: 30 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />

SA: Rp ¾ SNS: Rp ½ IP: 54 U: 230 V/50 Hz<br />

Type PS<br />

bar<br />

B<br />

mm<br />

B<br />

mm<br />

H<br />

mm<br />

H<br />

mm<br />

T<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

G<br />

kg<br />

PA<br />

kW<br />

SPL<br />

dB(A)<br />

DPp<br />

bar<br />

VNS<br />

l/h<br />

Article no.<br />

PI 6.2 8 390 1000 490 37 1.1 55 1- 5.5 500 813 1030<br />

PA<br />

kW<br />

SPL<br />

dB(A)<br />

DPp<br />

bar<br />

VNS<br />

l/h<br />

Article no.<br />

PI 9.1 10 320 760 260 20 0.75 74 1-8 500 813 1040<br />

Accessories for <strong>control</strong> modules • Communication module � page 6<br />

5


PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

6<br />

Accessories for <strong>control</strong> modules<br />

Communication module for BrainCube <strong>control</strong><br />

H<br />

H<br />

B<br />

B<br />

ComCube DCD<br />

• RS 485 interface for communicating with BrainCube, 6 digital inputs for the use of external volt free<br />

signals (NO), 9 volt free digital outputs, freely programmable; all outputs can be inversed<br />

• wall mounted, fi xing elements for cable management<br />

TU: 40 °C IP: 54 U: 230 V/50 Hz<br />

Type B<br />

mm<br />

H<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

PA<br />

kW<br />

Article no.<br />

DCD 270 230 260 0.5 0.1 814 1000<br />

ComCube DCA<br />

• 2 separated analoge outputs 4-20 mA for connection to BMS, isolation voltage 2.5 kVAC<br />

• all cabeling inside the casing, wall mounted<br />

TU: 40 °C IP: 54 U: 230 V/50 Hz<br />

Type B<br />

mm<br />

H<br />

mm<br />

T<br />

mm<br />

G<br />

kg<br />

DCD DCA<br />

PA<br />

kW<br />

Article no.<br />

DCA 190 260 180 0.5 0.1 814 1010


PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />

7


Additional information<br />

System design: : Online calculation software SelectP!<br />

Short cuts | terms: : Datasheet Planning <strong>and</strong> calculation | Glossary<br />

The products, texts, photographs, graphics <strong>and</strong> diagrams in this brochure may be subject to alteration by TA Hydronics<br />

without prior notice or reasons being given. For the most <strong>up</strong> to date information about our products <strong>and</strong> specifications,<br />

please visit www.tahydronics.com.<br />

partner in your country : www.tahydronics.com<br />

RSPINEN011105

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!