Pressure control and water make up system
Pressure control and water make up system
Pressure control and water make up system
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Pleno P<br />
Hydraulic unit | <strong>water</strong> <strong>make</strong>-<strong>up</strong> without pumps<br />
PNEUMATEX PRESSURE CONTROL AND WATER MAKE UP SYSTEM - PLENO<br />
• heating, solar <strong>and</strong> chilled <strong>water</strong> <strong>system</strong>s | for <strong>system</strong>s according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953<br />
• external <strong>control</strong> from pressure-maintaining or degassing stations, i.e. Compresso, Transfero or Vento<br />
• with contact <strong>water</strong> meter <strong>and</strong> back fl ow preventer type BA according to EN 1717, DVGW, SVGW, KIWA N.V., BELGAQUA,<br />
WRAS <strong>and</strong> ACS tested<br />
• with integrated wall mounting bracket<br />
• addition of antifreeze agent <strong>up</strong> to 50%<br />
Approx. throughput V | Pleno P<br />
Pleno P<br />
Pleno P<br />
TS: 65 °C TSmin: 0 °C TU: 40 °C PSmin: 0 bar<br />
SA: G ½ SNS: G ½ IP: 65 U: 230 V/50 Hz<br />
Type PS<br />
bar<br />
B<br />
mm<br />
H<br />
mm<br />
T<br />
mm<br />
G<br />
kg<br />
PA<br />
kW<br />
KVS<br />
m 3 /h<br />
Article no.<br />
P 10 1700 200 125 3 0.02 0.5 813 1000<br />
The requirements for pNS must be taken into account for Statico <strong>and</strong> Compresso:<br />
• required fresh <strong>water</strong> pressure Compresso: pNS ≥ P0 (BrainCube) + 1,9 bar | pNS ≤ 10 bar<br />
• required fresh <strong>water</strong> pressure Statico: pNS ≥ P0 (BrainCube) + 1,7 bar | pNS ≤ 10 bar.<br />
pSNS pSA<br />
3