Performance characteristics<br />
<strong>Electronic</strong> <strong>control</strong> <strong>gear</strong> <strong>units</strong><br />
for T5 fl uorescent lamps in Multi-Lamp technology<br />
• Universal ECG in Multi-Lamp technology offering automatic<br />
and exact lamp recognition and optimal drive for<br />
T5 fluorescent lamps<br />
• One luminaire be<strong>com</strong>es viable with different lamp<br />
packages (e.g. T5: 35 W, 49 W, 80 W)<br />
• Twingle- Technology: Operation with 1 or 2 lamps<br />
possible<br />
• High design flexibility thanks to reduced housing<br />
dimensions<br />
• Optimised warm start thanks to energy <strong>control</strong>led preheating<br />
for preserving the electrodes and for maximum<br />
lamp life independent of the switching frequency;<br />
starting time < 1 s<br />
• Cut-Off technology: no heating current through the electrodes<br />
during operation for optimised luminous efficacy<br />
and minimised power loss<br />
• Automatic safety switch-off in case of abnormal lamp<br />
operation, e.g. defective electrodes and end of lamp life;<br />
tested acc. to EN 61 347-2-3 + Test 2<br />
• Automatic restart after lamp replacement<br />
• For luminaires of protection class I and protection class II<br />
• Constant lamp output independent of mains voltage<br />
fluctuations<br />
• Reliable lamp recognition and ignition even at low temperatures<br />
of –20 °C<br />
• Suitable for direct current operation and application in<br />
emergency lighting installations : Conforms to requirements<br />
for emergency lighting acc. to EN 61 347-2-3/J<br />
• Energy efficiency index A2 BAT<br />
• Conformance with international regulations regarding<br />
safety and operation, electromagnetic <strong>com</strong>patibility and<br />
immunity to interference<br />
ECG model<br />
Markings<br />
7 4 110<br />
9<br />
ML-tec<br />
Version Order no. Lamp<br />
MLS80.1FR-11/220-240 10071608 1 x T5 28 W, 35 W<br />
1 x T5 49 W, 54 W, 80 W<br />
MLS80.1/54.2FR-11/220-240 10071609 1/2 x T5 28 W, 35 W, 49 W, 54 W<br />
1 x T5 80 W<br />
1/2 x TC-L 55W<br />
MLS39.1-2FR-11/220-240 10092026 1/2 x T5 14 W, 21 W, 24 W, 39 W<br />
1/2 x TC-L/F 18 W, 24 W, 36 W<br />
1/2 x TC-L 40 W<br />
Errors excepted. We reserve the right to make<br />
alternations in the interest of improving our products. 1/4<br />
www.<strong>BAGelectronics</strong>.<strong>com</strong>
Technical data<br />
<strong>Electronic</strong> <strong>control</strong> <strong>gear</strong> <strong>units</strong><br />
for T5 fl uorescent lamps in Multi-Lamp technology<br />
Mains voltage supply<br />
Rated voltage range 220 V – 240 V<br />
Max. admissible voltage range 198 V – 264 V<br />
(continuous)<br />
Frequency 0, 50 Hz ... 60 Hz<br />
Battery operation<br />
Voltage range for<br />
198 VDC – 278 VDC<br />
continuous operation<br />
Lowest limiting value for 176 VDC<br />
temporary operation<br />
1)<br />
Behaviour at mains overvoltage<br />
Switch-off of the lamp(s) at approx. 320 VAC 2)<br />
Overvoltage protection 350 VAC / 2 h<br />
Leakage current < 0.5 mA / EVG<br />
Ignition time of the lamp < 1.0 s<br />
Behaviour in case<br />
Switch-off of the lamp<br />
of defective lamp<br />
Automatic restart<br />
yes<br />
after lamp replacement<br />
Max. temperature<br />
+ 110 °C<br />
at housing surface<br />
(acc. EN 61 347-2-3/C)<br />
Nominal service life 50.000 h with failure rate<br />
≤ 10 % and operation at<br />
tc = tc, max<br />
100.000 h at tc = tc, max<br />
- 10 K<br />
Lamp and mains terminals for solid wire<br />
Type 90°-connector with<br />
push button<br />
Wire cross section 0.5 mm2 – 1.5 mm2 Wire stripping length 7.5 mm2 – 8.5 mm2 Lamp wire lengths see “wiring diagrams“<br />
1) Reliable lamp ignition only for ≥ 198 VDC<br />
2) Lamp restart after mains voltage interruption<br />
Admissible temperatures<br />
Version Ambient (ta) Case (tc)<br />
MLS 80.1FR - 25 °C ... + 55 °C 70 °C<br />
MLS39.1-2FR - 20 °C ... + 55 °C 75 °C<br />
MLS80.1/54.2FR - 20 °C ... + 55 °C 75 °C<br />
Inrush current/Circuit breaker<br />
Version typ. Ipeak /Δt No. of ECG at single-pole<br />
circuit breakers<br />
LS-Typ 10 A 16 A 20 A 25 A<br />
MLS 80.1FR 45 A / 120 μs B 13 21 26 32<br />
C 20 32 40 50<br />
MLS39.1-2FR 39 A / 135 μs B 13 25 32 40<br />
C 24 38 48 60<br />
MLS80.1/54.2FR 45 A / 120 μs B 11 18 23 29<br />
C 17 27 34 42<br />
All data for Usupply = 230 VAC, mains impedance = 1 Ω<br />
In case of multipolar CB the max. no. is reduced by 20 %<br />
The max. number may differ depending on CB manufacturer. Please consider the<br />
specifications of the manufacturer.<br />
Basically, CB with C-characteristics are re<strong>com</strong>mended to be used inlighting groups.<br />
I[A]<br />
I peak<br />
½ x I peak<br />
Errors excepted. We reserve the right to make<br />
www.<strong>BAGelectronics</strong>.<strong>com</strong> 2/4<br />
alternations in the interest of improving our products.<br />
∆t<br />
T
Operating data<br />
<strong>Electronic</strong> <strong>control</strong> <strong>gear</strong> <strong>units</strong><br />
for T5 fl uorescent lamps in Multi-Lamp technology<br />
Version Lamp System<br />
rating<br />
Input<br />
current*<br />
Operating<br />
frequency<br />
Power<br />
factor<br />
Lamp<br />
power<br />
Lamp<br />
socket<br />
a 6 b 4<br />
EEI Approvals<br />
W A kHz W<br />
MLS80.1FR-11/220-240 1 xT5 28 W 32 0.15 > 90 0.97 28 G5 A2 BAT a, b<br />
1 x T5 35 W 39 0.18 > 90 0.97 35 G5 A2 BAT a, b<br />
1 x T5 49 W 53.5 0.24 > 75 0.97 49 G5 A2 BAT a, b<br />
1 x T5 54 W 60 0.27 > 42 0.97 54 G5 A2 BAT a, b<br />
1 x T5 80 W 86 0.37 > 41 0.97 80 G5 A2 BAT a, b<br />
MLS80.1/54.2FR-11/220-240 1/2 x T5 28 W 32/64 0,15/0,28 67/63 0,93/0,98 28/57 G5 A2/A2 BAT a, b<br />
1/2 x T5 35 W 39/80 0,18/0,35 66/62 0,95/0,99 35/73 G5 A2/A2 BAT a, b<br />
1/2 x T5 49 W 55/104 0,24/0,45 57/59 0,97/0,99 51/98 G5 A2/A2 BAT a, b<br />
1/2 x T5 54 W 60/113 0,26/0,48 47 0,98/0,99 55/107 G5 A2/A2 BAT a, b<br />
1 x T5 80 W 86 0,36 46 0,99 79 G5 A2/A2 BAT a, b<br />
1/2 x TC-L 55 W 56/105 0,25/0,43 47 0,98/0,99 52/98 2G11 A2/A2 BAT a, b<br />
MLS39.1-2FR-11/220-240 1/2 x T5 14 W 17/33 0,08/0,15 98/86 0,9 14/28 G5 A2/ A2 BAT a, b<br />
1/2 x T5 21 W 24,5/48 0,11/0,20 92/82 0,9/0,97 21/42 G5 A2/ A2 BAT a, b<br />
1/2 x T5 24 W 28/54 0,12/0,23 67/66 0,92/0,97 24/48 G5 A2/ A2 BAT a, b<br />
1/2 x T5 39 W 42/82 0,17/0,35 67/66 0,96/0,98 39/78 G5 A2/ A2 BAT a, b<br />
1/2 x TC-L/F 18 W 19/35,5 0,09/0,15 66/67 0,9/0,94 16/32 2G10/ 2G11 A2/ A2 BAT a, b<br />
1/2 x TC-L/F 24 W 27/50 0,12/0,23 67 0,92/0,97 22/44 2G10/ 2G11 A2/ A2 BAT a, b<br />
1/2 x TC-L/F 36 W 34,5/69 0,14/0,29 67 0,94/0,98 32/64 2G10/ 2G11 A2/ A2 BAT a, b<br />
1/2 x TC-L 40 W 43,5/88 0,20/0,38 67 0,96/0,99 40/80 2G11 A2/ A2 BAT a, b<br />
* at UMains = 230 VAC<br />
Errors excepted. We reserve the right to make<br />
alternations in the interest of improving our products. 3/4<br />
www.<strong>BAGelectronics</strong>.<strong>com</strong>
Dimensions<br />
Wiring diagrams<br />
MLS80.1FR<br />
1<br />
2<br />
3<br />
4<br />
keep lamp wires as short as possible<br />
Wire lengths terminal 1, 2: max. 1.0 m<br />
Wire lengths terminal 3, 4; 5, 6: max. 2.0 m<br />
<strong>Electronic</strong> <strong>control</strong> <strong>gear</strong> <strong>units</strong><br />
for T5 fl uorescent lamps in Multi-Lamp technology<br />
X M<br />
MLS39.1-2FR / MLS80.1/54.2FR<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
X<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
ZM<br />
Y Z<br />
One-lamp operation<br />
1-lampiger Betrieb<br />
Version X XM Y Z ZM Weight<br />
mm mm mm mm mm kg<br />
MLS 80.1FR 280 265 30 21 8.5 0.23<br />
MLS39.1-2FR 280 265 30 21 8.5 0,22<br />
MLS80.1/54.2FR 280 265 30 21 8.5 0,24<br />
Conformance with regulations<br />
EN 61 347-1<br />
EN 61 347-2-3<br />
General and safety requirements<br />
1<br />
2<br />
EN 61 347-2-3/C<br />
3<br />
4Requirements<br />
for thermally protected ballasts<br />
EN 61 342-2-3/J<br />
5<br />
6Particular<br />
additional safety requirements<br />
for a.c./d.c. supplied electronic ballasts for<br />
emer gency lighting<br />
EN 60 929 Performance requirements<br />
EN 50 294 Measurement method of total input power<br />
of ballast-lamp circuits<br />
EN 61 000-3-2 Limits for harmonic current emissions<br />
EN 61 000-3-3 Limitation of voltage fluctuations and flicker<br />
General EMC immunity:<br />
EN 61 000-4-2 Electrostatic discharge<br />
EN 61 000-4-3 Radiated, radio-frequency, electromagnetic field<br />
EN 61 000-4-4 Electrical fast transient/burst<br />
EN 61 000-4-5 Surge<br />
EN 61 000-4-6 Conducted disturbances, induced by radiofrequency<br />
fields<br />
EN 61 000-4-8 Power frequency magnetic field<br />
EN 61 000-4-11 Voltage dips, short interruptions and voltage<br />
variations<br />
EN 61 547 EMC immunity: equipment for general lighting<br />
purposes<br />
EN 55 015 Radio disturbances, frequencies < 300MHz<br />
(CDN method)<br />
Environmental tests for mechanical capacity:<br />
IEC 60 068-2-6 Test Fc: vibrations (sinusoidal)<br />
IEC 60 068-2-27 Test Ea: shock and bump<br />
IEC 60 068-2-29 Test Eb: shock and bump<br />
Quality management certifi ed according to ISO 9001<br />
BAG electronics GmbH<br />
Kleinbahnstrasse 27 • 59759 Arnsberg/Germany · info@<strong>BAGelectronics</strong>.<strong>com</strong> • Phone +49 2932 9000-9800 • Fax +49 2932 9000-9796 MLS-MLtec-T5-evo2_EN(120223)<br />
Errors excepted. We reserve the right to make<br />
www.<strong>BAGelectronics</strong>.<strong>com</strong> 4/4<br />
alternations in the interest of improving our products.