7 Troubleshooting Z<br />

no<br />

Compressor<br />

noisy<br />

Compressor<br />

components<br />

deteriorated<br />

English<br />

yes<br />

Repair or<br />

replace<br />

compressor<br />

Z<br />

yes<br />

CP<br />

compressor<br />

thermal protection<br />

alarm<br />

Condenser<br />

dirty or<br />

obstructed<br />

no<br />

Compressor<br />

winding<br />

with partial<br />

loss of<br />

insulation<br />

no<br />

yes<br />

Clean<br />

condenser<br />

Lt Low evaporation temperature alarm<br />

Ld Low dew point alarm.<br />

Low<br />

cooling<br />

air<br />

temperature<br />

no<br />

Fan<br />

always<br />

working<br />

(PV pressure<br />

switch fault)<br />

no<br />

Hot gas<br />

valve<br />

not calibrated<br />

no<br />

FAULT CAUSE REMEDY<br />

yes<br />

yes<br />

yes<br />

yes<br />

Replace<br />

the coil<br />

Z<br />

Increase<br />

cooling air<br />

temperature<br />

Replace<br />

pressure switch<br />

Z<br />

Calibrate<br />

valve<br />

Z<br />

Liquid line<br />

solenoid valve<br />

closed<br />

no<br />

LP Low<br />

pressure<br />

alarm<br />

LP<br />

Low pressure<br />

switch fault<br />

no<br />

yes<br />

no<br />

Fan<br />

pressure switch<br />

(PV) not set<br />

no<br />

Low<br />

current<br />

absorption<br />

no<br />

High<br />

dew point<br />

warning<br />

Excessive thermal load<br />

(air flow, inlet temperature)<br />

yes<br />

yes<br />

Request external assistance<br />

Replace<br />

pressure<br />

switch<br />

Z<br />

Replace<br />

pressure switch<br />

Z<br />

No<br />

refrigerant.<br />

Recharge<br />

Z<br />

yes<br />

Ht<br />

High<br />

temperature<br />

alarm<br />

Cooling<br />

air<br />

high<br />

temperature<br />

no<br />

no<br />

Condenser<br />

dirty or<br />

obstructed<br />

no<br />

Low<br />

current<br />

absorption<br />

no<br />

yes<br />

yes<br />

yes<br />

Decrease<br />

cooling air<br />

temperature<br />

Decrease<br />

compressed<br />

air quantity<br />

temperature<br />

Clean<br />

condenser<br />

Replace<br />

pressure switch<br />

Z<br />

Replace fan<br />

Z<br />

yes<br />

yes<br />

yes<br />

yes<br />

yes<br />

HP<br />

high pressure<br />

alarm<br />

Cooling<br />

air<br />

high<br />

temperature<br />

no<br />

Excessive<br />

thermal load<br />

(inlet air flow,<br />

temperature)<br />

no<br />

Condenser<br />

dirty or<br />

obstructed<br />

Fan<br />

does not turn<br />

(PV pressure<br />

switch fault)<br />

Fan<br />

fault<br />

no<br />

no<br />

no<br />

PST120---350<br />

35