ENGLISH<br />

Symbol Description of possible operating status<br />

Pump operated in control mode ∆p-c by the serial data interface (see chap. 4.4). “On/off”<br />

function not activated at module. Only , , optimisation, “acknowledge error” can<br />

still be set at module. Exception, for pumps with P1 < 500 W (see rating plate) errors can<br />

only be acknowledged at the module. PLR mode can be interrupted via the IR monitor (for<br />

tests, for reading out data).<br />

Differential pressure set value set to H = 9.0 m.<br />

Pump set to a constant speed (1.800 RPM in this case) – regulator mode.<br />

Control system ∆p-c, regulated to constant differential pressure set value (Fig. 3).<br />

Control system ∆p-v, regulated to variable differential pressure set value (Fig. 4).<br />

The regulator mode control system deactivates the module regulations.<br />

The speed of the pump is kept at a constant value between 800 and 2800 RPM.<br />

The speed is set internally using the tuning button.<br />

Regulator mode activated, speed of pump set via the input 0…10 V (only applies to P1 10 V ≥ 500 W). The tuning button now has no set value input function.<br />

Control system ∆p-T, regulated to temperature dependent differential pressure set values<br />

(Fig. 5). The maximum set value HSmax. is displayed. This control system can only be<br />

activated via the IR monitor.<br />

on Pump switched on.<br />

off Pump switched off.<br />

Operating the tuning button: (Fig. 2, pos. 5) Starting<br />

with the basic setting, the setting menu (for the first<br />

menu: Press for longer than one second) the setting<br />

menus can be selected one after the other in a specific<br />

order. The relevant symbol blinks. By turning the<br />

button to the left or to the right the parameters on the<br />

display can be altered up or down. The symbol which<br />

has just been set blinks. The new setting is stored by<br />

pressing the button. Following this, the unit switches<br />

over to the next menu.<br />

The set value (differential pressure and speed) in the<br />

basic setting can be altered by turning the tuning<br />

button. The new value blinks. The new setting is<br />

stored by pressing the button.<br />

Should the new setting not be stored, the basic<br />

setting will appear after 30 seconds.<br />

The following menus appear one after the other when operating the displays of the single pump:<br />

Single pump mode: Setting when starting up for the first time/Menu order during standard use<br />

LC display Setting<br />

1<br />

After switching on the module, all symbols appear on the display for<br />

2 seconds. The current setting ➁ then appears.<br />

2<br />

Current (basic) setting (preset):<br />

auto ➝ Night-time mode possible<br />

Pump running in standard mode<br />

missing➝ Single pump<br />

e.g. H 5.0 m ➝ Nominal pump lift H S = 5.0 m and 1 /2 H max.<br />

(preset depends on pump)<br />