ENGLISH<br />
Symbol Description of possible operating status<br />
Pump operated in control mode ∆p-c by the serial data interface (see chap. 4.4). “On/off”<br />
function not activated at module. Only , , optimisation, “acknowledge error” can<br />
still be set at module. Exception, for pumps with P1 < 500 W (see rating plate) errors can<br />
only be acknowledged at the module. PLR mode can be interrupted via the IR monitor (for<br />
tests, for reading out data).<br />
Differential pressure set value set to H = 9.0 m.<br />
Pump set to a constant speed (1.800 RPM in this case) – regulator mode.<br />
Control system ∆p-c, regulated to constant differential pressure set value (Fig. 3).<br />
Control system ∆p-v, regulated to variable differential pressure set value (Fig. 4).<br />
The regulator mode control system deactivates the module regulations.<br />
The speed of the pump is kept at a constant value between 800 and 2800 RPM.<br />
The speed is set internally using the tuning button.<br />
Regulator mode activated, speed of pump set via the input 0…10 V (only applies to P1 10 V ≥ 500 W). The tuning button now has no set value input function.<br />
Control system ∆p-T, regulated to temperature dependent differential pressure set values<br />
(Fig. 5). The maximum set value HSmax. is displayed. This control system can only be<br />
activated via the IR monitor.<br />
on Pump switched on.<br />
off Pump switched off.<br />
Operating the tuning button: (Fig. 2, pos. 5) Starting<br />
with the basic setting, the setting menu (for the first<br />
menu: Press for longer than one second) the setting<br />
menus can be selected one after the other in a specific<br />
order. The relevant symbol blinks. By turning the<br />
button to the left or to the right the parameters on the<br />
display can be altered up or down. The symbol which<br />
has just been set blinks. The new setting is stored by<br />
pressing the button. Following this, the unit switches<br />
over to the next menu.<br />
The set value (differential pressure and speed) in the<br />
basic setting can be altered by turning the tuning<br />
button. The new value blinks. The new setting is<br />
stored by pressing the button.<br />
Should the new setting not be stored, the basic<br />
setting will appear after 30 seconds.<br />
The following menus appear one after the other when operating the displays of the single pump:<br />
Single pump mode: Setting when starting up for the first time/Menu order during standard use<br />
LC display Setting<br />
1<br />
After switching on the module, all symbols appear on the display for<br />
2 seconds. The current setting ➁ then appears.<br />
2<br />
Current (basic) setting (preset):<br />
auto ➝ Night-time mode possible<br />
Pump running in standard mode<br />
missing➝ Single pump<br />
e.g. H 5.0 m ➝ Nominal pump lift H S = 5.0 m and 1 /2 H max.<br />
(preset depends on pump)<br />
23