7<br />
Double pump mode: initial setting when starting up for the first time<br />
1<br />
1a<br />
ENGLISH<br />
LC display Setting<br />
OPt ➝ Optimisation, at zero amount and maximum speed the pump’s<br />
ability to log data is optimised. Occurs once on starting up. For this, the<br />
blocking device on the pressure side must be closed so that the flow<br />
Q = 0, off blinks,<br />
turn to on.<br />
This starts the optimisation process. When off blinks again the<br />
optimisation process has been completed. During optimisation,<br />
the unit cannot be operated.<br />
In single pump mode the display returns to basic setting ➁. In the event of a fault the error<br />
menu ⑩ appears before basic setting ➁. In double pump mode the display moves forward<br />
to menu ➇.<br />
After switching on the module, all symbols appear on the display for<br />
2 seconds. Then menu appears.<br />
The symbol MA (= master) blinks on the display of both pumps.<br />
Should the settings not be altered, both pumps will run at a constant<br />
speed (H S = 1 /2 H max. where Q = 0).<br />
By pressing the setting button on the left-hand pump the setting<br />
“mode” ➈ appears on the display. SL (= slave) automatically appears<br />
on the display of the right-hand pump.<br />
Consequently, the left-hand pump is the master and the right-hand<br />
pump the slave. The tuning button on the slave pump is no longer of<br />
importance. No more settings can be made here.<br />
Double pump mode: Menu order during normal use:<br />
After switching on the module, all symbols appear on the display for 2 seconds. The current setting ➁ then<br />
appears. By scrolling through the MA display, the menu order ➁…➆ is the same as for a single pump. Then<br />
the MA menu appears and remains on the screen permanently.<br />
8 By turning the MA, SL appears on this display. When the<br />
SL has been confirmed by pressing the button, the other (right-hand)<br />
pump becomes master. This is how a swop from master to slave is<br />
completed. Only the right-hand (MA-) pump can now be programmed.<br />
It is not possible to introduce settings on the SL.<br />
The swop from master to slave can only be made on the master.<br />