7<br />

Double pump mode: initial setting when starting up for the first time<br />

1<br />

1a<br />

ENGLISH<br />

LC display Setting<br />

OPt ➝ Optimisation, at zero amount and maximum speed the pump’s<br />

ability to log data is optimised. Occurs once on starting up. For this, the<br />

blocking device on the pressure side must be closed so that the flow<br />

Q = 0, off blinks,<br />

turn to on.<br />

This starts the optimisation process. When off blinks again the<br />

optimisation process has been completed. During optimisation,<br />

the unit cannot be operated.<br />

In single pump mode the display returns to basic setting ➁. In the event of a fault the error<br />

menu ⑩ appears before basic setting ➁. In double pump mode the display moves forward<br />

to menu ➇.<br />

After switching on the module, all symbols appear on the display for<br />

2 seconds. Then menu appears.<br />

The symbol MA (= master) blinks on the display of both pumps.<br />

Should the settings not be altered, both pumps will run at a constant<br />

speed (H S = 1 /2 H max. where Q = 0).<br />

By pressing the setting button on the left-hand pump the setting<br />

“mode” ➈ appears on the display. SL (= slave) automatically appears<br />

on the display of the right-hand pump.<br />

Consequently, the left-hand pump is the master and the right-hand<br />

pump the slave. The tuning button on the slave pump is no longer of<br />

importance. No more settings can be made here.<br />

Double pump mode: Menu order during normal use:<br />

After switching on the module, all symbols appear on the display for 2 seconds. The current setting ➁ then<br />

appears. By scrolling through the MA display, the menu order ➁…➆ is the same as for a single pump. Then<br />

the MA menu appears and remains on the screen permanently.<br />

8 By turning the MA, SL appears on this display. When the<br />

SL has been confirmed by pressing the button, the other (right-hand)<br />

pump becomes master. This is how a swop from master to slave is<br />

completed. Only the right-hand (MA-) pump can now be programmed.<br />

It is not possible to introduce settings on the SL.<br />

The swop from master to slave can only be made on the master.<br />

25