GIADA<br />
50 cm<br />
(1) In case of flues side by side, a chimney cap must be higher<br />
than the other one of at least 50 cm in order to avoid pressure<br />
transfers between the flues themselves.<br />
Picture 5<br />
2 m 10 m<br />
1<br />
m<br />
(1) The chimney cap must not show hindrances within 10 m from<br />
walls, pitches and trees. Otherwise raise it of at least 1 m over the<br />
hindrance.<br />
The chimney cap must exceed the ridge of the roof of at least 1 m.<br />
Picture 6<br />
> _ A<br />
>A<br />
0,5 m<br />
H min.<br />
(1)Ridge axis<br />
α<br />
(2)Roof<br />
Picture 7<br />
CHIMNEY CAPS - DISTANCES AND POSITIONING UNI 10683/98<br />
Inclination of the<br />
roof<br />
Distance between the roof<br />
ridge and the stack<br />
Minimum height of the stack<br />
(measured from the outlet)<br />
α A (m) H (m)<br />
15°<br />
30°<br />
45°<br />
60°<br />
< 1.85 m 0.50 m above the roof ridge<br />
> 1.85 m 1.00 m from the roof<br />
< 1.50 m 0.50 m above the roof ridge<br />
> 1.50 m 1.30 m from the roof<br />
< 1.30 m 0.50 m above the roof ridge<br />
> 1.30 m 2.00 m from the roof<br />
< 1.20 m 0.50 m above the roof ridge<br />
> 1.20 m 2.60 m from the roof<br />