RS-232 Communications Protocol & Command Set<br />
SET AVR MODE<br />
Sets AVR (Automatic Voltage Regulation) MODE.<br />
SET METER BRIGHTNESS<br />
Sets the LCD display and outlet bank indicator brightness.<br />
Command:<br />
!SET_AVR mode<br />
Send to UPS:<br />
!SET_BRIGHT xxx<br />
mode = {OFF, STANDARD, SENSITIVE}<br />
_________________________________________<br />
If specified mode is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid mode setting<br />
Response from UPS: $INVALID_PARAMETER<br />
$AVR = mode <br />
_________________________________________<br />
SET FEEDBACK MODE<br />
Sets the feedback mode to ON (unsolicited) or OFF (polled).<br />
When ON, a message will be sent to the controller every time the<br />
status of an input (i.e. button), output (i.e. outlet) or power state<br />
(i.e. overvoltage) changes.<br />
If feedback is OFF, the controller must request status with a query<br />
(see Queries section for more details).<br />
Send to UPS:<br />
!SET_FEEDBACK mode<br />
mode = {ON, OFF}<br />
_________________________________________<br />
If specified mode is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid mode setting<br />
Response from UPS: $INVALID_PARAMETER<br />
$FEEDBACK = mode<br />
_________________________________________<br />
SET LINEFEED MODE<br />
With LINEFEED MODE set, a linefeed character (, 10d, 0Ah)<br />
is appended to each response.<br />
Send to UPS:<br />
!SET_LINEFEED mode<br />
mode = {ON, OFF}<br />
_________________________________________<br />
If specified mode is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid mode setting<br />
xxx = {100, 075, 050, 025}<br />
_________________________________________<br />
If specified brightness setting is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid brightness setting<br />
Response from UPS: $INVALID_PARAMETER<br />
$BRIGHTNESS = xxx<br />
_________________________________________<br />
SET DISPLAY SCROLL MODE<br />
Sets the LCD display SCROLL mode<br />
Send to UPS:<br />
!SET_SCROLLMODE xxx<br />
xxx = {5SEC, 10SEC, OFF}<br />
_________________________________________<br />
If specified display scroll mode is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid mode setting<br />
Response from UPS: $INVALID_PARAMETER<br />
$SCROLL_MODE = xxx<br />
_________________________________________<br />
SET DISPLAY SLEEP MODE<br />
Sets the LCD display SLEEP mode<br />
Command:<br />
!SET_SLEEPMODE xxx<br />
xxx = {30SEC, 60SEC, OFF}<br />
If specified display sleep mode is invalid<br />
Action:<br />
No action will be taken, UPS will<br />
request a valid mode setting<br />
Response from UPS: $INVALID_PARAMETER<br />
$SLEEP_MODE = xxx<br />
_________________________________________<br />
Response from UPS: $INVALID_PARAMETER<br />
$LINEFEED = mode<br />
_________________________________________<br />