MDA,MDW,MDG/MUA,MUW,MUG/BDA,BDW,BDG - Engineering ...
MDA,MDW,MDG/MUA,MUW,MUG/BDA,BDW,BDG - Engineering ...
MDA,MDW,MDG/MUA,MUW,MUG/BDA,BDW,BDG - Engineering ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
I<br />
CONDENSAZIONE<br />
AD ARIA<br />
22 °C<br />
50%rH<br />
24 °C<br />
50%rH<br />
26 °C<br />
50%rH<br />
22 °C<br />
50%rH<br />
24 °C<br />
50%rH<br />
26 °C<br />
50%rH<br />
SCT = 48°C<br />
SCT = 55°C<br />
SCT = 48°C<br />
SCT = 55°C<br />
SCT = 48°C<br />
SCT = 55°C<br />
FA (1) - l/s<br />
- m 3 /h<br />
P VENT- kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
(1) : Ventilatori con trascinam. diretto<br />
SCT : Temp. satura di condensazione<br />
FA : Portata d'aria<br />
TOT : Potenza frigorifera totale<br />
SENS : Potenza frigorifera sensibile<br />
Pcomp : Pot. elettrica ass. dal compressore<br />
18<br />
R22<br />
CONDENSAZIONE<br />
AD ACQUA<br />
R22<br />
IWT = 20°C<br />
SCT = 40°C<br />
GLIC = 0%<br />
IWT = 40°C<br />
SCT = 55°C<br />
GLIC = 30%<br />
IWT = 20°C<br />
SCT = 40°C<br />
GLIC = 0%<br />
IWT = 40°C<br />
SCT = 55°C<br />
GLIC = 30%<br />
IWT = 20°C<br />
SCT = 40°C<br />
GLIC = 0%<br />
IWT = 40°C<br />
SCT = 55°C<br />
GLIC = 30%<br />
FA (1) - l/s<br />
- m 3 /h<br />
P VENT- kW<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
TOT - kW<br />
SENS - kW<br />
Pcomp - kW<br />
FW - l/h<br />
PD - kPa<br />
(1) : Ventilatori con trascinam. diretto<br />
IWT : Temperatura ingresso acqua<br />
SCT : Temp. satura di condensazione<br />
GLIC : Percentuale di glicole nell’acqua<br />
FA : Portata d'aria<br />
TOT : Potenza frigorifera totale<br />
SENS : Potenza frigorifera sensibile<br />
Pcomp : Pot. elettrica ass. dal compressore<br />
FW : Portata di acqua di condensazione<br />
PD : Perdita di carico del condensatore<br />
GB<br />
AIR-COOLED LUFTGEKÜHLTE<br />
GERÄTE<br />
D F E<br />
CONDENSATION<br />
PAR AIR<br />
CONDENSACION<br />
POR AIRE<br />
<strong>MDA</strong>0701 <strong>MDA</strong>0701 <strong>MDA</strong>1002 <strong>MDA</strong>1302 <strong>MDA</strong>1352 <strong>BDA</strong>2002 <strong>BDA</strong>2402 <strong>BDA</strong>3002<br />
2139 2139 2736 2736 4081 5694 6394 6794<br />
7700 7700 9850 9850 14690 20500 23020 24460<br />
1,0 1,0 2,2 2,2 3,3 4,4 6,0 7,2<br />
22,0 25,0 31,9 36,7 42,5 66,4 79,4 93,8<br />
22,0 24,4 30,1 32,1 42,5 63,4 72,6 84,5<br />
6,3 7,0 10,3 12,6 12,5 15,4 19,3 23,4<br />
20,5 23,2 29,6 34,3 39,7 62,7 75,3 89,0<br />
20,5 23,2 29,6 31,2 39,7 62,7 70,9 82,6<br />
7,0 7,7 11,2 13,9 13,8 18,1 22,6 27,1<br />
23,1 26,5 33,7 38,7 44,6 70,3 84,1 99,3<br />
23,1 25,0 30,8 32,9 44,6 65,0 74,3 86,6<br />
6,4 7,1 10,4 12,8 12,6 15,3 19,2 23,5<br />
21,6 24,4 31,4 36,2 41,7 66,6 79,8 94,3<br />
21,6 24,4 30,0 31,9 41,7 63,7 72,8 84,6<br />
7,1 7,8 11,5 14,1 14,0 18,0 22,5 27,1<br />
24,2 28,0 35,6 40,8 47,1 74,3 88,9 105,1<br />
24,2 25,7 31,5 33,5 45,7 66,6 76,0 88,5<br />
6,4 7,2 10,5 13,0 12,8 15,3 19,1 23,5<br />
22,7 26,0 33,2 38,2 43,8 70,4 84,4 99,8<br />
22,7 25,0 30,7 32,6 43,8 65,3 74,4 86,6<br />
7,2 21,3 11,6 14,4 14,2 18,0 22,4 27,1<br />
Direct driven fans<br />
Saturated Condensing Temperature<br />
Air volume<br />
Total cooling capacity<br />
Sensible cooling capacity<br />
Compressor electrical absorption<br />
Direkt Getrieben<br />
Temperatur bei vollständiger Kondensation<br />
Luftleistung<br />
Kälteleistung - gesamt<br />
Kälteleistung - sensibel<br />
Aufgenommene elektrische Leistung<br />
der Ventilatoren<br />
WATER-COOLED WASSERGEKÜHLTE<br />
GERÄTE<br />
Entraînement direct<br />
Température de condensation<br />
Débit d'air<br />
Puissance frigorifique - totale<br />
Puissance frigorifique - sensible<br />
Alimentation électrique des<br />
compresseurs<br />
CONDENSATION<br />
PAR EAU<br />
Acoplamiento directo<br />
Temperatura de condensación<br />
Caudal de aire<br />
Capacidad frigorífica - total<br />
Capacidad frigorífica - sensible<br />
Potencia eléctrica absorbida por el<br />
compresor<br />
CONDENSACION<br />
POR AGUA<br />
<strong>MDW</strong>0701 <strong>MDW</strong>0702 <strong>MDW</strong>1002 <strong>MDW</strong>1302 <strong>MDW</strong>1352 <strong>BDW</strong>2002 <strong>BDW</strong>2402 <strong>BDW</strong>3002<br />
2139 2139 2736 2736 4081 5694 6394 6794<br />
7700 7700 9850 9850 14690 20500 23020 24460<br />
1,0 1,0 2,2 2,2 3,3 4,4 6,0 7,2<br />
23,6 27,2 34,3 39,4 45,7 69,1 84,0 98,7<br />
23,6 25,3 31,0 33,3 44,8 64,6 74,4 86,5<br />
5,6 6,2 9,1 11,2 11,1 12,8 15,9 20,1<br />
1690 2020 2430 2720 3250 3705 4680 6398<br />
4,8 5,0 3,8 3,2 4,4 3,3 5,1 6,0<br />
20,5 23,2 29,6 34,3 39,7 61,9 75,3 89,0<br />
20,5 23,2 29,6 31,2 39,7 61,9 71,0 82,6<br />
7,0 7,7 11,2 13,9 13,8 18,1 22,6 27,1<br />
2900 3410 4030 4480 5470 5554 7270 11326<br />
14,1 14,4 10,5 8,8 12,7 7,6 12,3 18,7<br />
25,0 28,8 36,2 41,5 48,3 73,1 88,8 104,4<br />
24,0 25,9 31,8 34,0 46,0 66,2 76,1 88,5<br />
5,6 6,2 9,2 11,4 11,2 12,7 15,9 20,1<br />
1830 2200 2610 2910 3500 3906 4950 6898<br />
5,5 5,9 4,3 3,6 5,1 3,6 5,6 6,9<br />
21,6 24,4 31,4 36,2 41,7 65,6 79,7 94,3<br />
21,6 24,4 30,0 31,9 41,7 63,5 72,8 84,7<br />
7,1 7,8 11,5 14,1 14,0 18,0 22,5 27,1<br />
3170 3760 4450 4850 5960 5876 7740 12455<br />
16,6 17,1 12,6 10,2 14,9 8,4 13,8 22,2<br />
26,3 30,4 38,2 43,7 51,0 77,2 93,8 110,5<br />
24,6 26,5 32,4 34,6 47,1 67,7 77,7 90,4<br />
5,6 6,3 9,3 11,6 11,2 12,6 15,8 20,2<br />
1980 2400 2810 3120 3780 4120 5240 7462<br />
6,4 6,9 5,0 4,1 5,8 4,0 6,2 7,9<br />
22,7 26,0 33,2 38,2 43,8 69,4 84,4 99,8<br />
22,7 25,0 30,7 32,6 43,8 65,1 74,5 86,6<br />
7,2 7,9 11,6 14,4 14,2 18,0 22,4 27,1<br />
3470 4240 4890 5280 6510 6224 8260 13802<br />
19,7 21,3 15,0 11,9 17,5 9,3 15,6 26,7<br />
Direct driven fans<br />
Intake water temperature<br />
Saturated Condensing Temperature<br />
Glycol percentage<br />
Air volume<br />
Total cooling capacity<br />
Sensible cooling capacity<br />
Compressor electrical absorption<br />
Condenser water flow rate<br />
Condenser pressure drop<br />
Direkt Getrieben<br />
Wassereintrittstemperatur<br />
Temperatur bei vollständiger Kondensation<br />
Glykolanteil<br />
Luftleistung<br />
Kälteleistung - gesamt<br />
Kälteleistung - sensibel<br />
Aufgenommene elektrische Leistung der Verdichter<br />
Wassermenge durch den Verflüssigers<br />
Kondensatordruckverlust<br />
Entraînement direct<br />
Température entrée eau<br />
Température de condensation<br />
Pourcentage de glycole<br />
Débit d'air<br />
Puissance frigorifique - totale<br />
Puissance frigorifique - sensible<br />
Alimentation électrique des compresseurs<br />
Débit d’eau des condenseurs<br />
Perte de charge condenseur<br />
Acoplamiento directo<br />
Temperatura de entrada del agua<br />
Temperatura de condensación<br />
Porcentaje de glicol<br />
Caudal de aire<br />
Capacidad frigorífica - total<br />
Capacidad frigorífica - sensible<br />
Potencia eléctrica absorbida por el compresor<br />
Caudal de agua de condensación<br />
Pérdida de carga del condensador