Interruttori automatici 3VF - Siemens

Interruttori automatici 3VF - Siemens

Interruttori automatici 3VF - Siemens

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Apparecchi<br />

di Bassa Tensione<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>2 - 3 e 4 poli,<br />

da 16 A a 100 A 1/2<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>3-8 - 3 e 4 poli,<br />

da 16 a 2500 A 1/6<br />

Tabelle di scelta e di ordinazione 1/8<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> - Gruppi<br />

di commutazione 1/21<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> - Accessori 1/24<br />

<strong>Interruttori</strong> <strong>automatici</strong> 3ZF, UL489 - CSAC22.2 1/32<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> UL 508-CSA C22-2 1/35<br />

<strong>Interruttori</strong> <strong>automatici</strong> 3WN fino a 6300 A<br />

Programma 1/36<br />

Condensatori di potenza 4RB 1/37<br />

Gruppi <strong>automatici</strong> rifasamento 4RY 1/46<br />

1


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>2<br />

da 16 A a 100 A<br />

Descrizione<br />

Impiego ed esecuzioni<br />

L’interruttore automatico scatolato <strong>3VF</strong>2<br />

è progettato per soddisfare le esigenze di<br />

protezione di impianti con corrente nominale<br />

fino a 100 A.<br />

È previsto in esecuzione fissa 3 e 4 poli<br />

con potere di interruzione di 18 kA a<br />

415 V ac.<br />

L’interruttore è equipaggiato con sganciatori<br />

di sovracorrente di tipo magnetotermico<br />

per sovraccarichi termici e cortocircuiti.<br />

L’interruttore <strong>3VF</strong>2 è adatto per l’utilizzo<br />

sugli arrivi e sulle partenze in impianti<br />

di distribuzione. L’esecuzione quadripolare<br />

prevede la protezione di tutti e quattro<br />

i poli.<br />

Equipaggiamenti base:<br />

– La levetta indica in maniera inequivocabile<br />

lo stato dell’interrutore (apertoreset,<br />

chiuso, tripped).<br />

– Interruttore con sganciatore di sovracorrente<br />

non regolabile integrato.<br />

– Allacciamento conduttori principali tramite<br />

morsetti serracavo.<br />

Allacciamento<br />

Conduttori principali: nella esecuzione base<br />

i morsetti di allacciamento sono del tipo<br />

a serracavo per conduttori rigidi o tramite<br />

puntuale per conduttori flessibili. Sono<br />

fornibili (accessori) le sbarre di allacciamento<br />

posteriori.<br />

Conduttori ausiliari: gli accessori da montare<br />

sul lato dell’interruttore, prevedono<br />

l’allacciamento a morsetto.<br />

Condizioni di impiego<br />

Gli interruttori sono tropicalizzati di serie.<br />

Sono adatti per l’installazione in ambienti<br />

chiusi; polvere ed umidità oltre i limiti normali<br />

vanno inibiti con dispositivi di protezione<br />

adatti.<br />

Limiti di corrente<br />

Gli interruttori sono costruiti secondo il<br />

principio della limitazione di corrente. I<br />

contatti si aprono prima che venga raggiunto<br />

il valore di cresta presunto della<br />

corrente di corto circuito. Le parti interessate<br />

dell’impianto vengono in tal modo<br />

sollecitate solo parzialmente dagli effetti<br />

dinamici e termici creati dalle correnti di<br />

cortocircuito.<br />

Installazione<br />

L’interruttore è fornito in esecuzione fissa<br />

per montaggio su guide profilate DIN EN<br />

50022, 35 mm oppure mediante fissaggio<br />

tramite viti.<br />

Gli interruttori sono adatti anche per l’installazione<br />

in cassette e sistemi di distribuzione<br />

in quadro. È possibile il montaggio<br />

degli interruttori fianco a fianco; gli accessori,<br />

come per esempio la bobina a lancio<br />

di corrente o i contatti ausiliari, vanno<br />

montati lateralmente all’interruttore base<br />

mediante viti (montaggio sul lato sinistro),<br />

e pertanto è necessario tener conto dei<br />

necessari spazi di ingombro aggiuntivi.<br />

Accessori<br />

– Comando rotativo frontale<br />

– Contatti ausiliari di scattato relè<br />

– Contatti ausiliari<br />

– Bobina a lancio di corrente<br />

– Calotte coprimorsetti<br />

– Attacchi posteriori.<br />

Sganciatori di sovracorrente<br />

Gli sganciatori di sovraccarico e di cortocircuito<br />

sono di tipo magnetotermico non<br />

regolabile.<br />

Il 4° polo di neutro è protetto al 100%. La<br />

protezione di guasto verso terra si può<br />

realizzare esternamente all’interruttore<br />

tramite il relè differenziale 3UL2, composto<br />

dal trasformatore toroidale 3UL22 e<br />

dal relè di sgancio (istantaneo o ritardato)<br />

3UL21. In caso di guasto, i contatti ausiliari<br />

dello sganciatore fanno interrompere<br />

l’interruttore attraverso la bobina ausiliaria.<br />

Dopo l’intervento, l’interruttore e lo<br />

sganciatore devono essere ripristinati ponendo<br />

prima la leva di comando in posizione<br />

di interruttore aperto (“RESET”).<br />

Comando<br />

Il comando degli interruttori in esecuzione<br />

base è costituito da una levetta la quale<br />

indica in maniera inequivocabile lo stato<br />

dell’interruttore (aperto, chiuso, tripped).<br />

La levetta scatta nella posizione di<br />

sganciato (“Tripped”) se l’interruttore è<br />

intervenuto per qualche funzione di protezione<br />

(sovraccarico o cortocircuito) o<br />

per l’intervento dello sganciatore ausiliario.<br />

Dopo ogni intervento, per poter reinserire<br />

l’interruttore, è necessario spostare<br />

la leva di comando in posizione aperto<br />

(“RESET”); l’interruttore è così pronto<br />

per la chiusura.<br />

Attraverso un dispositivo di blocco (accessorio)<br />

la leva di comando può essere lucchettata.<br />

Comando frontale rotativo<br />

I comandi rotativi sono previsti per il montaggio<br />

diretto all’interruttore e trasformano<br />

il movimento verticale della leva di comando<br />

in un movimento rotatorio.<br />

Anche il comando rotativo può, tramite un<br />

accessorio, essere lucchettato.<br />

Sganciatori ausiliari<br />

Contatti ausiliari<br />

Sul lato sinistro dell’interruttore può essere<br />

montato un modulo corrispondente ai<br />

seguenti accessori: bobina a lancio di corrente,<br />

contatti ausiliari, contatti di allarme.<br />

Il collegamento dei conduttori ausiliari si<br />

effettua mediante morsetti a serracavo.<br />

Bobina a lancio di corrente<br />

(sganciatore “f”)<br />

La bobina a lancio di corrente è utilizzata<br />

per lo sgancio a distanza ed è dimensionata<br />

per essere alimentata solo per breve<br />

tempo.<br />

Non è possibile quindi mantenere un contatto<br />

permanente per impedire la chiusura<br />

dell’interruttore, cioè lo sganciatore non<br />

può essere utilizzato come dispositivo di<br />

blocco.<br />

Contatti ausiliari<br />

I contatti ausiliari sono utilizzati per la segnalazione<br />

e per il controllo. Sono disponibili<br />

in due esecuzioni:<br />

1L + 1R oppure 2L + 2R.<br />

Contatti di allarme<br />

Il contatto di allarme (1AS) commuta in<br />

caso di intervento per sovraccarico o cortocircuito<br />

o per effetto di uno sganciatore<br />

ausiliario.<br />

La funzione di segnalazione di sgancio<br />

viene ripristinata ponendo prima la leva di<br />

comando in posizione di interruttore aperto<br />

(“RESET”).<br />

Norme - Approvazioni<br />

Gli interruttori rispondono alle seguenti<br />

norme:<br />

IEC 947-2<br />

IEC 947-3 per idoneità al sezionamento.<br />

1/2<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>2 - 3 e 4 poli,<br />

da 16 A a 100 A<br />

Tabelle di scelta e di ordinazione - 3 poli<br />

Potere di interruzione standard Tipo da 16 A fino a 100 A<br />

Potere di interruzione nominale fino a 240 V kA 65<br />

estremo in corto circuito I CU<br />

fino a 415 V kA 18<br />

Potere di interruzione nominale fino a 240 V kA 33<br />

di servizio in corto circuito I CS<br />

fino a 415 V kA 9<br />

30<br />

Potere di chiusura nominale fino a 240 V kA 143<br />

in cortocircuito I CM<br />

fino a 415 V kA 36<br />

Corrente Corrente Corrente Potere di interruzione standard<br />

nominale d’intervento d’intervento<br />

I n<br />

sganciatori sganciatori<br />

contro i contro i Esecuzione fissa<br />

sovraccarichi cortocircuiti<br />

(sganciatore “a”) (sganciatore “n”)<br />

Nr. di ordinazione<br />

I r<br />

I i<br />

1<br />

A A A<br />

<strong>Interruttori</strong> <strong>automatici</strong> con sganciatori termici fissi<br />

16 16 350 <strong>3VF</strong>22 13–0FC41–0AA0<br />

20 20 450 <strong>3VF</strong>22 13–0FD41–0AA0<br />

25 25 500 <strong>3VF</strong>22 13–0FE41–0AA0<br />

32 32 600 <strong>3VF</strong>22 13–0FG41–0AA0<br />

40 40 750 <strong>3VF</strong>22 13–0FJ41–0AA0<br />

45 45 750 <strong>3VF</strong>22 13–0FK41–0AA0<br />

50 50 800 <strong>3VF</strong>22 13–0FL41–0AA0<br />

63 63 800 <strong>3VF</strong>22 13–0FN41–0AA0<br />

70 70 900 <strong>3VF</strong>22 13–0FP41–0AA0<br />

80 80 900 <strong>3VF</strong>22 13–0FQ41–0AA0<br />

90 90 1000 <strong>3VF</strong>22 13–0FR41–0AA0<br />

100 100 1000 <strong>3VF</strong>22 13–0FS41–0AA0<br />

Tabelle di scelta e di ordinazione - 4 poli<br />

Potere di interruzione standard Tipo da 16 A fino a 100 A<br />

Potere di interruzione nominale fino a 240 V kA 65<br />

estremo in corto circuito I CU<br />

fino a 415 V kA 18<br />

Potere di interruzione nominale fino a 240 V kA 33<br />

di servizio in corto circuito I CS<br />

fino a 415 V kA 9<br />

Potere di chiusura nominale fino a 240 V kA 143<br />

in cortocircuito I CM<br />

fino a 415 V kA 36<br />

Corrente Corrente Corrente Potere di interruzione standard<br />

nominale d’intervento d’intervento<br />

I n<br />

sganciatori sganciatori<br />

contro i contro i Esecuzione fissa<br />

sovraccarichi cortocircuiti<br />

(sganciatore “a”) (sganciatore “n”)<br />

Nr. di ordinazione<br />

I r<br />

A A A<br />

<strong>Interruttori</strong> <strong>automatici</strong> con sganciatori termici fissi, 4° polo protetto (N = 100%)<br />

I i<br />

16 16 350 <strong>3VF</strong>22 14–0JC41–0AA0<br />

20 20 450 <strong>3VF</strong>22 13–0JD41–0AA0<br />

25 25 500 <strong>3VF</strong>22 13–0JE41–0AA0<br />

32 32 600 <strong>3VF</strong>22 13–0JG41–0AA0<br />

40 40 750 <strong>3VF</strong>22 13–0JJ41–0AA0<br />

45 45 750 <strong>3VF</strong>22 13–0JK41–0AA0<br />

50 50 800 <strong>3VF</strong>22 13–0JL41–0AA0<br />

63 63 800 <strong>3VF</strong>22 13–0JN41–0AA0<br />

70 70 900 <strong>3VF</strong>22 13–0JP41–0AA0<br />

80 80 900 <strong>3VF</strong>22 13–0JQ41–0AA0<br />

90 90 1000 <strong>3VF</strong>22 13–0JR41–0AA0<br />

100 100 1000 <strong>3VF</strong>22 13–0JS41–0AA0<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/3


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>2 - 3 e 4 poli,<br />

da 16 A a 100 A<br />

Accessori - Tabelle di scelta<br />

Comandi<br />

Descrizione<br />

Nr. di ordinazione<br />

3 - 4 poli<br />

Comando frontale rotativo<br />

per il fissaggio diretto all’interruttore Nero <strong>3VF</strong>9 223–1AA00<br />

Grado di protezione IP 30<br />

lucchettabile con max 3 lucchetti Emergenza <strong>3VF</strong>9 223–1BA00<br />

Comando rinviato disinnestabile bloccoporta IP65<br />

Tipo B<br />

Comando frontale senza maniglia da completare con<br />

<strong>3VF</strong>9 223–1JA00<br />

Maniglia nera completa di mostrina e prolunga 300 mm oppure<br />

8UC6 112–1BD22<br />

Maniglia rossa completa di mostrina gialla e prolunga 300 mm<br />

8UC6 122–3BD22<br />

Allacciamenti Attacchi posteriori 1 set = 6 pezzi <strong>3VF</strong>9 224–1LD10<br />

completi di calotte coprimorsetti per interruttori<br />

da 45 A fino a 100 A 1 set = 8 pezzi <strong>3VF</strong>9 224–1LD20<br />

Calotte - Mostrine Calotte coprimorsetti 3 poli <strong>3VF</strong>9 224–1NB10<br />

IP30 per contatti principali<br />

1 set = 2 pezzi<br />

Calotte coprimorsetti 4 poli<br />

IP30 per contatti principali<br />

1 set = 2 pezzi<br />

Adattatore per mostrina 45 mm 1 set = 1 pezzo<br />

per interruttori 3 poli<br />

per interruttori 4 poli<br />

Mostrina copriforo 1 set = 1 pezzo<br />

per connessione con cavi<br />

<strong>3VF</strong>9 224–1NB20<br />

per connessione con cavi<br />

<strong>3VF</strong>9 220–1CA10<br />

<strong>3VF</strong>9 220–1CA20<br />

<strong>3VF</strong>9 220–1AA00<br />

Sganciatori ausiliari 1) Bobina a lancio di corrente Bobina senza contatti Bobina con contatti 2)<br />

AC 50/60 Hz<br />

DC<br />

– 12 V <strong>3VF</strong>9 221–1JC10 <strong>3VF</strong>9 221-1KC10<br />

– 24 V <strong>3VF</strong>9 221–1JD10 <strong>3VF</strong>9 221-1KD10<br />

– 48 V <strong>3VF</strong>9 221–1JH10 <strong>3VF</strong>9 221-1KH10<br />

– 110 - 125 V <strong>3VF</strong>9 221–1JL10 <strong>3VF</strong>9 221-1KL10<br />

110 - 127 V – <strong>3VF</strong>9 221–1JP10 <strong>3VF</strong>9 221-1KP10<br />

220 - 240 V – <strong>3VF</strong>9 221–1JM10 <strong>3VF</strong>9 221-1KM10<br />

380 - 415 V – <strong>3VF</strong>9 221–1JV10 <strong>3VF</strong>9 221-1KV10<br />

Contatti ausiliari 1) Contatti di allarme e sgancio 1 CO (1AS) <strong>3VF</strong>9 222–1AC10<br />

Contatti ausiliari 1 CO (1HS) <strong>3VF</strong>9 222–1BC10<br />

1 CO (1HS) + 1 CO (1AS) <strong>3VF</strong>9 222-1DC10<br />

2 CO (2HS) <strong>3VF</strong>9 222–1CC10<br />

1) È possibile il montaggio di uno solo di questi accessori con contatti in commutazione.<br />

2) Bobina a lancio di corrente con contatti ausiliari (1 in commutazione)<br />

<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>2 con accessori montati sul lato sinistro (possibilità di montaggio di un solo modulo)<br />

1/4<br />

<strong>Siemens</strong> - Distribuzione dell’energia


Dispositivo Differenziale <strong>3VF</strong>2 - 3 e 4 poli<br />

fino a 100 A<br />

Descrizione<br />

Il dispositivo di protezione differenziale è<br />

costituito da un modulo “Toroide” e da un<br />

modulo “Relè differenziale”.<br />

Il modulo differenziale si monta tramite<br />

due viti sul lato destro dell’interruttore.<br />

Le segnalazioni ed i comandi, sono riportati<br />

sul frontalino del differenziale.<br />

Dopo aver fissato il differenziale, si può<br />

montare il modulo del toroide.<br />

Questo viene montato nel lato inferiore<br />

dell’interruttore e si fissa al differenziale<br />

tramite due viti.<br />

Queste viti oltre al fissaggio meccanico,<br />

garantiscono anche la connessione elettrica<br />

Toroide - Differenziale.<br />

Il passaggio dei conduttori avviene attraverso<br />

dei fori previsti nel modulo toroide.<br />

Il dispositivo differenziale può essere<br />

montato indifferentemente sia su interruttori<br />

tripolari che tetrapolari.<br />

Caratteristiche<br />

Il dispositivo differenziale è regolabile in<br />

tempo e corrente mediante dip-switch.<br />

Sul frontalino oltre ai dip-switch, sono presenti<br />

il tasto di Reset, quello di Test, il led<br />

verde di ON (dispositivo alimentato), ed il<br />

led rosso di scattato.<br />

Il dispositivo contiene un circuito di vigilanza<br />

continua, che controlla la connessione<br />

elettrica tra toroide e differenziale e la<br />

continuità del toroide stesso. Ad un difetto<br />

di tali connessioni corrisponderebbe<br />

un’apertura dell’interruttore.<br />

Il differenziale deve essere alimentato dalle<br />

tre fasi e dal neutro ma può funzionare<br />

anche in mancanza di una o due fasi.<br />

Sul lato superiore del differenziale sono<br />

previsti due morsetti per il comando a distanza.<br />

La richiesta remota di manovra di<br />

apertura non permette la segnalazione di<br />

intervento mediante il led rosso di scattato.<br />

Il modulo differenziale presenta una finestratura<br />

di 45 mm.<br />

Il dispositivo permette il montaggio di un<br />

modulo con contatti ausiliari sul lato sinistro<br />

dell’interruttore.<br />

Il differenziale risponde alle norme vigenti<br />

ed in particolare alle IEC 947-2 Amendment<br />

1,<br />

Appendix B. Inoltre risponde alle prescrizioni<br />

per EMC (compatibilità elettromagnetica).<br />

Il dispositivo è di tipo A e AC, quindi adatto<br />

a correnti di guasto sinusoidali e in<br />

presenza di componenti pulsanti unidirezionali.<br />

Il dispositivo differenziale non interviene<br />

in presenza di transitori e/o avviamenti<br />

motori e soddisfa la prova con impulsi di<br />

corrente a 50Hz.<br />

I differenziali sono tutti marchiati CE.<br />

Dispositivo differenziale<br />

<strong>3VF</strong>9225-1AA10<br />

1<br />

Sigla d’ordinazione:<br />

<strong>3VF</strong>9225-1AA10<br />

Dati tecnici<br />

Corrente nominale In A 125<br />

Campo di regolazione I ∆n<br />

A 0,03-0,3-0,5-1-3<br />

Campo di regolazione t s 0,03(ist.)-0,15-0,3-1-3<br />

Tensione di alimentazione Vac 230<br />

Autoconsumo VA 2,5<br />

Protezione IP 30<br />

Temperatura di funzionamento °C -10 ¸ +50<br />

Temperatura di stoccaggio °C -15 ¸ +80<br />

Tensione d’isolamento (1 min.) V 1500<br />

Schema di inserzione<br />

Schema di principio<br />

<strong>3VF</strong>9221-1J..<br />

<strong>3VF</strong>9221-1K..<br />

2C1<br />

3C2 N L1 1 L2 3 L3 5<br />

<strong>3VF</strong>9225-1AA10<br />

DI<br />

<strong>3VF</strong>9222-1A.. <strong>3VF</strong>9222-1B..<br />

-1C..<br />

3 1 1 (4) 3 (6)<br />

I >> I >> I >> I >><br />

N<br />

T12T24T36<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/5


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Caratteristiche generali<br />

La serie di interruttori <strong>automatici</strong> scatolati<br />

<strong>3VF</strong> è indicata per la protezione di impianti<br />

elettrici di bassa tensione contro le sovracorrenti.<br />

Le grandezze costruttive sono<br />

sette e coprono un campo di correnti<br />

nominali da 10 A a 2500 A.<br />

Le caratteristiche di protezione sono inoltre<br />

differenziate in funzione del potere di<br />

interruzione nominale in tre esecuzioni:<br />

con potere nominale di interruzione normale,<br />

elevato ed elevatissimo che consentono<br />

a 380 V/415 V, 50/60 Hz di controllare<br />

correnti di cortocircuito presunte<br />

di valore fino a 100 kA, facendo corrispondere<br />

in maniera ottimale alle esigenze<br />

tecniche anche l’aspetto economico della<br />

scelta dei <strong>3VF</strong>.<br />

L’intercambiabilità degli sganciatori a partire<br />

dalla grandezza costruttiva 250 A consente<br />

una evidente facilitazione di sostituzione<br />

o di modifica delle caratteristiche richieste<br />

nell’ambito della stessa grandezza<br />

costruttiva.<br />

La limitazione di corrente diventa particolarmente<br />

efficace soprattutto con l’esecuzione<br />

che raggiunge 100 kA di potere di<br />

interruzione per effetto delle caratteristiche<br />

di repulsione dei contatti fissi e mobili<br />

che permettono quindi minori sollecitazioni<br />

elettrodinamiche e termiche per i<br />

componenti dell’impianto interessato al<br />

guasto.<br />

Gli interruttori <strong>automatici</strong> <strong>3VF</strong> rispondono<br />

alle norme IEC 947 e come loro i relativi<br />

accessori.<br />

Gli interruttori <strong>3VF</strong> possono essere classificati<br />

in funzione del tipo di utenze che devono<br />

proteggere poiché possono essere<br />

equipaggiati con sganciatori diversi per<br />

meglio adattarsi alle caratteristiche di funzionamento<br />

a cui sono preposti.<br />

In particolare possono essere equipaggiati<br />

di sganciatori elettromagnetici o elettronici<br />

di protezione contro i sovraccarichi<br />

fissi o regolabili e/o contro i cortocircuiti di<br />

tipo istantaneo e di tipo ritardato (solo<br />

elettronico).<br />

Pertanto gli interruttori <strong>automatici</strong> <strong>3VF</strong> sono<br />

adatti:<br />

• come interruttori di alimentazione e di<br />

potenza in un sistema di distribuzione,<br />

• come interruttori principali,<br />

• come interruttori di emergenza secondo<br />

DIN VDE 0113,<br />

• come interruttori di protezione di motori,<br />

trasformatori e condensatori.<br />

Esecuzioni<br />

Gli interruttori <strong>automatici</strong> <strong>3VF</strong> sono corredati<br />

di sganciatori di sovracorrente e possono<br />

essere equipaggiati internamente di<br />

sganciatori ausiliari di minima tensione o a<br />

lancio di corrente, contatti ausiliari e di allarme.<br />

I <strong>3VF</strong> riportano sulla calotta frontale una<br />

targhetta colorata che identifica il potere<br />

nominale di interruzione:<br />

• verde: potere nominale di interruzione<br />

25 kA<br />

• giallo: potere nominale di interruzione<br />

normale 40 kA<br />

(= I cu<br />

a 380 V/415 V c.a.)<br />

• blu: potere nominale di interruzione<br />

elevato 65 kA/70 kA<br />

(= I cu<br />

a 380 V/415 V c.a.)<br />

• rosso: potere nominale di interruzione<br />

elevatissimo 100 kA<br />

(= I cu<br />

a 380 V/415 V c.a.)<br />

Condizioni di impiego<br />

Gli interruttori <strong>3VF</strong> sono tropicalizzati di<br />

serie. Sono adatti per l’installazione in ambienti<br />

chiusi; polvere ed umidità, oltre i limiti<br />

normali, vanno inibite con dispositivi<br />

di protezione adatti (custodie, armadi<br />

ecc.).<br />

Installazione<br />

Possono essere montati e sistemati attaccati<br />

fra loro anche grazie alle guide di<br />

passaggio dei conduttori ausiliari che restano<br />

all’interno dell’ingombro dell’interruttore<br />

stesso ad eccezione di applicazioni<br />

particolari di morsettiera laterale, che<br />

invece richiedono degli spazi laterali (vedere<br />

dimensioni).<br />

Allacciamento<br />

Le grandezze costruttive <strong>3VF</strong>1, <strong>3VF</strong>3,<br />

<strong>3VF</strong>4 e <strong>3VF</strong>5 per correnti nominali 63/80<br />

A, 160 A, 250 A e 400 A sono forniti già<br />

con morsetti di allacciamento del tipo a<br />

serracavo che permettono il serraggio di<br />

conduttori multifilari flessibili con boccola.<br />

Per allacciare conduttori con capicorda<br />

o sbarre sono fornibili accessori di prolunga.<br />

I <strong>3VF</strong>6 (corrente nominale fino a 630 A)<br />

sono già predisposti per l’allacciamento<br />

delle sbarre e quindi di conduttori con capicorda.<br />

Gli interruttori <strong>automatici</strong> <strong>3VF</strong> possono<br />

essere alimentati dai morsetti superiori o<br />

inferiori indistintamente e senza per questo<br />

incorrere in declassamenti o limitazione<br />

alcuna (unica eccezione per l’esecuzione<br />

completa di dispositivo differenziale<br />

che può essere alimentata solo dall’alto).<br />

I conduttori o le sbarre allacciati ai morsetti<br />

superiori dell’interruttore devono essere<br />

isolati nell’ambito dello spazio riservato<br />

allo sfogo dei gas determinati dall’arco<br />

elettrico in caso di guasto.<br />

Gli accessori montati all’interno dell’interruttore<br />

possono essere forniti:<br />

• con morsettiera annessa,<br />

• con conduttori ausiliari.<br />

Approvazioni<br />

Gli interruttori <strong>automatici</strong> <strong>3VF</strong> rispondono<br />

alle seguenti norme:<br />

IEC 947-1<br />

DIN VDE 0660, parte 100<br />

IEC 947-2<br />

DIN VDE 0660, parte 101<br />

IEC 947-3 (per idoneità al sezionamento)<br />

IEC 947-4<br />

DIN VDE 0660, parte 104.<br />

Approvazioni navali: GL, LRS, DNV, ABS,<br />

RINA.<br />

1/6<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Accessori • Numero massimo di ausiliari interni<br />

La quantità massima di ausiliari interni coi<br />

quali possono essere equipaggiati gli interruttori<br />

<strong>3VF</strong> dipende dal tipo di grandezza<br />

costruttiva e dalla loro esecuzione.<br />

Dividendo la parte interna degli interruttori<br />

nelle aree relative ai poli di cui è costituita,<br />

si rileva che le parti disponibili per il<br />

montaggio degli accessori interni sono:<br />

Posizione di montaggio:<br />

<strong>3VF</strong>3 ÷ <strong>3VF</strong>7 3 Poli<br />

<strong>3VF</strong>5 4 Poli elettronico<br />

per distribuzione<br />

– per l’esecuzione 3 poli: il polo a sinistra<br />

e quello a destra<br />

– per l’esecuzione 4 poli: il polo a sinistra<br />

e i 2 poli a destra della levetta<br />

– per l’esecuzione 3 poli per protezione<br />

motori: il polo a sinistra della levetta<br />

– per l’esecuzione 4 poli differenziale: i 2<br />

poli a destra della levetta.<br />

<strong>3VF</strong>3 ÷ <strong>3VF</strong>5<br />

3 Poli<br />

esec. differenziale<br />

– per gli accessori con morsetti solo i poli<br />

esterni (non possibile sul polo a destra<br />

della levetta nell’esecuzione 4 poli).<br />

Per semplificare la scelta e la disponibilità<br />

degli accessori che possono essere montati<br />

e la loro posizione abbiamo riportato le<br />

configurazioni massime ammissibili nello<br />

schema seguente.<br />

<strong>3VF</strong>3, <strong>3VF</strong>5, <strong>3VF</strong>6<br />

3 Poli<br />

per protezione motori<br />

1<br />

Bobina r 1 HS Inutilizzabile 1 HS Bobina r<br />

opp. Bobina f opp. 2 HS opp. 2 HS opp. Bobina f 1 HS<br />

opp. 1 HS opp. 1 AS opp. 1 AS opp. 1 HS<br />

opp. 2 HS opp. 2 AS opp. 2 AS opp. 2 HS opp. 2 HS 6)<br />

opp. 1 AS opp. 1 HS + 1 AS opp. 1 HS + 1 AS opp 1 AS opp. 1 AS 6)<br />

opp. 2 AS opp. Bobina r opp. 2 AS opp. 2 AS 6)<br />

opp. 1 HS + 1 AS 3) opp. Bobina f opp. 1 HS + 1 AS 3) opp. 1 HS + 1 AS 6)<br />

<strong>3VF</strong>3÷<strong>3VF</strong>7 4 Poli <strong>3VF</strong>3÷<strong>3VF</strong>5 <strong>3VF</strong>8<br />

escluso <strong>3VF</strong>5 4 Poli elettronico 4 Poli 3/4 Poli<br />

per distribuzione<br />

esec. differenziale<br />

Lato superiore:<br />

4 HS<br />

(fino a 3 blocchetti)<br />

Inutilizzabile 4) Lato inferiore<br />

Bobina r 1 AS 1 HS Inutilizzabile 1 AS 1 HS Inutilizzabile 1 AS<br />

opp. Bobina f opp. Bobina f 2) opp. 2 HS 5) opp. Bobina r opp. 2 HS 5) opp. Bobina r<br />

opp. 1 HS opp. Bobina f opp. Bobina F opp. Bobina f<br />

opp. 1 AS<br />

opp. 2 AS<br />

opp. 1 HS + 1 AS 3)<br />

Accessori:<br />

Bobina r = Sganciatore di minima tensione<br />

Bobina f = Sganciatore a lancio di corrente<br />

1HS = 1 contatto ausiliario in commutazione<br />

1AS = 1 contatto ausiliario in allarme<br />

2) Previa modifica della bobina (vedi istruzioni di montaggio) per <strong>3VF</strong>3, a richiesta per <strong>3VF</strong>6, non possibile per <strong>3VF</strong>7.<br />

3) Disponibile solo per <strong>3VF</strong>3.<br />

4) Con la bobina “f” presente sul lato inferiore, è possibile montare o il contatto 2 AS o la bobina “r”.<br />

5) Quando si monta il 2 HS non è possibile montare nessun accessorio sulla fase “S” (solo <strong>3VF</strong>3).<br />

6) Solo <strong>3VF</strong>5 e <strong>3VF</strong>6.<br />

Esecuzioni<br />

Tra le varie esecuzioni disponibili, oltre all’esecuzione<br />

fissa attacchi anteriori/posteriori<br />

è fornibile:<br />

– l’esecuzione rimovibile attacchi ant./post.<br />

(per interruttori <strong>3VF</strong>3 ÷ <strong>3VF</strong>6 e <strong>3VF</strong>3 ÷<br />

<strong>3VF</strong>5 in esecuzione differenziale)<br />

– l’esecuzione estraibile attacchi ant./post.<br />

(per interruttori <strong>3VF</strong>3, <strong>3VF</strong>5, <strong>3VF</strong>6, <strong>3VF</strong>7)<br />

– la commutazione Rete-Emergenza; composta<br />

da due interruttori interbloccati<br />

meccanicamente in modo che possano<br />

stare ambedue in posizione OFF/<br />

TRIPPED ma alternativamente solo uno<br />

dei due in posizione ON<br />

– la commutazione Rete-Emergenza automatica;<br />

dove all’esecuzione sopra citata<br />

si aggiungono i comandi motore e<br />

l’apposita piastra con automatismo (fornita<br />

come accessorio).<br />

Esecuzione rimovibile<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/7


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>3<br />

fino a 225 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 25 kA 40 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione ordinazione<br />

(sganciatori a) (sganciatori n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>3 4)5)6)<br />

16 16 400 <strong>3VF</strong>31 13–0FC 41–0AA0 <strong>3VF</strong>31 13–1FC41–0AA0 <strong>3VF</strong>31 13–2FC41–0AA0 –<br />

20 20 400 <strong>3VF</strong>31 11–0FD 41–0AA0 <strong>3VF</strong>31 11–1FD41–0AA0 <strong>3VF</strong>31 11–2FD41–0AA0 –<br />

25 25 400 <strong>3VF</strong>31 11–0FE 41–0AA0 <strong>3VF</strong>31 11–1FE41–0AA0 <strong>3VF</strong>31 11–2FE41–0AA0 –<br />

32 32 400 <strong>3VF</strong>31 11–0FG 41–0AA0 <strong>3VF</strong>31 11–1FG41–0AA0 <strong>3VF</strong>31 11–2FG41–0AA0 <strong>3VF</strong>31 13–3FG 41–0AA0<br />

40 40 400 <strong>3VF</strong>31 11–0FJ 41–0AA0 <strong>3VF</strong>31 11–1FJ 41–0AA0 <strong>3VF</strong>31 11–2FJ 41–0AA0 <strong>3VF</strong>31 11–3FJ 41–0AA0<br />

50 50 400 <strong>3VF</strong>31 11–0FL41–0AA0 <strong>3VF</strong>31 11–1FL41–0AA0 <strong>3VF</strong>31 11–2FL41–0AA0 <strong>3VF</strong>31 11–3FL41–0AA0<br />

63 63 500 <strong>3VF</strong>31 11–0FN41–0AA0 <strong>3VF</strong>31 11–1FN41–0AA0 <strong>3VF</strong>31 11–2FN41–0AA0 <strong>3VF</strong>31 11–3FN41–0AA0<br />

80 80 630 <strong>3VF</strong>31 11–0FQ41–0AA0 <strong>3VF</strong>31 11–1FQ41–0AA0 <strong>3VF</strong>31 11–2FQ41–0AA0 <strong>3VF</strong>31 11–3FQ41–0AA0<br />

100 100 800 <strong>3VF</strong>31 11–0FS41–0AA0 <strong>3VF</strong>31 11–1FS41–0AA0 <strong>3VF</strong>31 11–2FS41–0AA0 <strong>3VF</strong>31 11–3FS41–0AA0<br />

125 125 1000 <strong>3VF</strong>32 11–0FU41–0AA0 <strong>3VF</strong>32 11–1FU41–0AA0 <strong>3VF</strong>32 11–2FU41–0AA0 <strong>3VF</strong>32 11–3FU41–0AA0<br />

160 160 1280 <strong>3VF</strong>31 11–0FW41–0AA0 <strong>3VF</strong>31 11–1FW41–0AA0 <strong>3VF</strong>31 11–2FW41–0AA0 <strong>3VF</strong>31 11–3FW41–0AA0<br />

200 200 2400 — <strong>3VF</strong>33 11–1FX41–0AA0 <strong>3VF</strong>33 11–2FX 41–0AA0 <strong>3VF</strong>33 11–3FX 41–0AA0<br />

225 225 2400 — <strong>3VF</strong>31 11–1FY41–0AA0 <strong>3VF</strong>31 11–2FY 41–0AA0 <strong>3VF</strong>31 11–3FY 41–0AA0<br />

50 40 ÷ 50 300 ÷ 500 — <strong>3VF</strong>31 11–1BL41–0AA0 <strong>3VF</strong>31 11–2BL 41–0AA0 <strong>3VF</strong>31 11–3BL 41–0AA0<br />

63 50 ÷ 63 315 ÷ 630 — <strong>3VF</strong>31 11–1BN41–0AA0 <strong>3VF</strong>31 11–2BN41–0AA0 <strong>3VF</strong>31 11–3BN41–0AA0<br />

80 63 ÷ 80 400 ÷ 800 — <strong>3VF</strong>31 11–1BQ41–0AA0 <strong>3VF</strong>31 11–2BQ41–0AA0 <strong>3VF</strong>31 11–3BQ41–0AA0<br />

100 80 ÷ 100 500 ÷ 1000 — <strong>3VF</strong>31 11–1BS41–0AA0 <strong>3VF</strong>31 11–2BS41–0AA0 <strong>3VF</strong>31 11–3BS41–0AA0<br />

125 100 ÷ 125 625 ÷ 1250 — <strong>3VF</strong>32 11–1BU41–0AA0 <strong>3VF</strong>32 11–2BU41–0AA0 <strong>3VF</strong>32 11–3BU41–0AA0<br />

160 125 ÷ 160 800 ÷ 1600 — <strong>3VF</strong>31 11–1BW41–0AA0 <strong>3VF</strong>31 11–2BW41–0AA0 <strong>3VF</strong>31 11–3BW41–0AA0<br />

200 160 ÷ 200 1000 ÷ 2000 — <strong>3VF</strong>33 11–1BX 41–0AA0 <strong>3VF</strong>33 11–2BX 41–0AA0 <strong>3VF</strong>33 11–3BX 41–0AA0<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>3 4)<br />

100 Senza 2400 — — <strong>3VF</strong>31 11–6BS31–0AA0 —<br />

160 sganciatori 2400 — — <strong>3VF</strong>32 11–6BW31–0AA0 —<br />

termici<br />

<strong>Interruttori</strong> per motori <strong>3VF</strong>3 1)4)<br />

(Potenza max. del motore da proteggere: 110 kW a 380 V, 50 Hz; 132 kW a 500 V, 50 Hz)<br />

80 40 ÷ 80 2) 15 × I r<br />

— <strong>3VF</strong>31 11–5EN71–0AA0 <strong>3VF</strong>31 11–6EN71–0AA0 —<br />

100 80 ÷ 100 2) 15 × I r<br />

— <strong>3VF</strong>31 11–5EQ71–0AA0 <strong>3VF</strong>32 11–6EQ71–0AA0 —<br />

160 100 ÷ 160 2) 15 × I r<br />

— <strong>3VF</strong>32 11–5ES71–0AA0 <strong>3VF</strong>32 11–6ES71–0AA0 —<br />

205 160 ÷ 205 3) 13 × I r<br />

— <strong>3VF</strong>33 11–5FU71–0AA0 <strong>3VF</strong>33 11–6FU71–0AA0 —<br />

Con<br />

protezione<br />

contro la<br />

mancanza<br />

di fase<br />

80 40 ÷ 80 15 × I r<br />

— <strong>3VF</strong>31 11–5DN71–0AA0 <strong>3VF</strong>31 11–6DN71–0AA0 —<br />

100 80 ÷ 100 15 × I r<br />

— <strong>3VF</strong>31 11–5DQ71–0AA0 <strong>3VF</strong>32 11–6DQ71–0AA0 —<br />

160 100 ÷ 160 15 × I r<br />

— <strong>3VF</strong>32 11–5DS71–0AA0 <strong>3VF</strong>32 11–6DS71–0AA0 —<br />

205 160 ÷ 205 3) 13 × I r<br />

— <strong>3VF</strong>33 11–5DU71–0AA0 <strong>3VF</strong>33 11–6DU71–0AA0 —<br />

Senza<br />

protezione<br />

contro la<br />

mancanza<br />

di fase<br />

<strong>Interruttori</strong> per avviatori <strong>3VF</strong>3 4)<br />

(Potenza max. del motore da proteggere: 110 kW a 380 V, 50 Hz; 132 kW a 500 V, 50 Hz)<br />

63 Senza 500 ÷ 1000 — — <strong>3VF</strong>31 11–6BS21–0AA0 —<br />

100 sganciatori 750 ÷ 1500 — — <strong>3VF</strong>32 11–6BU21–0AA0 —<br />

160 termici 1200 ÷ 2400 — — <strong>3VF</strong>32 11–6BW21–0AA0 —<br />

1) Sganciatori di sovracorrente elettronici.<br />

2) Grado di inerzia regolabile 5/10/15/20 s.<br />

3) Grado di inerzia fisso 10 s.<br />

4) Per modificare l’interruttore in esecuzione rimovibile o estraibile sostituire alla posizione 12 l’alfanumerico 1 con il 7.<br />

Es.: <strong>3VF</strong>31 11-1FS47-0AA0; parte fissa da ordinare sempre separatamente.<br />

5) U e<br />

max = 415 V per interruttori <strong>3VF</strong>3 con termico fisso fino alla corrente nominale I u<br />

= 40 A.<br />

6) Non è possibile il montaggio di nessun accessorio sull’interruttore da 25 kA.<br />

1/8<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>3<br />

fino a 225 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 25 kA 40 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione ordinazione<br />

(sganciatori a) (sganciatori n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>3 1)2)4)<br />

16 16 400 — <strong>3VF</strong>31 14–1RC 41–0AA0 — —<br />

20 20 400 — <strong>3VF</strong>31 11–1RD 41–0AA0 <strong>3VF</strong>31 14–2RD 41–0AA0 <strong>3VF</strong>31 14–3RD 41–0AA0<br />

25 25 400 — <strong>3VF</strong>31 11–1RE 41–0AA0 <strong>3VF</strong>31 11–2RE 41–0AA0 <strong>3VF</strong>31 11–3RE 41–0AA0<br />

32 32 400 — <strong>3VF</strong>31 11–1RG 41–0AA0 <strong>3VF</strong>31 11–2RG 41–0AA0 <strong>3VF</strong>31 11–3RG 41–0AA0<br />

40 40 400 — <strong>3VF</strong>31 11–1RJ 41–0AA0 <strong>3VF</strong>31 11–2RJ 41–0AA0 <strong>3VF</strong>31 11–3RJ 41–0AA0<br />

225 225 2400 — <strong>3VF</strong>33 12–1RY 41–0AA0 <strong>3VF</strong>33 12–2RY 41–0AA0 <strong>3VF</strong>33 12–3RY 41–0AA0<br />

50 40 ÷ 50 300 ÷ 500 — <strong>3VF</strong>31 12–1ML 41–0AA0 <strong>3VF</strong>31 12–2ML 41–0AA0 <strong>3VF</strong>31 12–3ML 41–0AA0<br />

63 50 ÷ 63 315 ÷ 630 — <strong>3VF</strong>31 11–1MN 41–0AA0 <strong>3VF</strong>31 11–2MN 41–0AA0 <strong>3VF</strong>31 11–3MN41–0AA0<br />

80 63 ÷ 80 400 ÷ 800 — <strong>3VF</strong>31 11–1MQ 41–0AA0 <strong>3VF</strong>31 11–2MQ 41–0AA0 <strong>3VF</strong>31 11–3MQ41–0AA0<br />

100 80 ÷ 100 500 ÷ 1000 — <strong>3VF</strong>31 11–1MS 41–0AA0 <strong>3VF</strong>31 11–2MS 41–0AA0 <strong>3VF</strong>31 11–3MS41–0AA0<br />

Neutro 125 100 ÷ 125 625 ÷ 1250 — <strong>3VF</strong>32 12–1MU41–0AA0 <strong>3VF</strong>32 12–2MU41–0AA0 <strong>3VF</strong>32 12–3MU41–0AA0<br />

non 160 125 ÷ 160 800 ÷ 1600 — <strong>3VF</strong>31 11–1MW41–0AA0 <strong>3VF</strong>31 11–2MW41–0AA0 <strong>3VF</strong>31 11–3MW41–0AA0<br />

protetto 200 160 ÷ 200 1000 ÷ 2000 — <strong>3VF</strong>33 12–1MX 41–0AA0 <strong>3VF</strong>33 12–2MX 41–0AA0 <strong>3VF</strong>33 12–3MX 41–0AA0<br />

16 16 400 (1) <strong>3VF</strong>31 14–0JC 41–0AA0 <strong>3VF</strong>31 14–1JC 41–0AA0<br />

20 20 400 (1) <strong>3VF</strong>31 11–0JD 41–0AA0 <strong>3VF</strong>31 11–1JD 41–0AA0 <strong>3VF</strong>31 14–2JD 41–0AA0 <strong>3VF</strong>31 14–3JD 41–0AA0<br />

25 25 400 (1) <strong>3VF</strong>31 11–0JE 41–0AA0 <strong>3VF</strong>31 11–1JE 41–0AA0 <strong>3VF</strong>31 11–2JE 41–0AA0 <strong>3VF</strong>31 11–3JE 41–0AA0<br />

32 32 400 (1) <strong>3VF</strong>31 11–0JG 41–0AA0 <strong>3VF</strong>31 11–1JG 41–0AA0 <strong>3VF</strong>31 11–2JG 41–0AA0 <strong>3VF</strong>31 11–3JG 41–0AA0<br />

40 40 400 (1) <strong>3VF</strong>31 11–0JJ 41–0AA0 <strong>3VF</strong>31 11–1JJ 41–0AA0 <strong>3VF</strong>31 11–2JJ 41–0AA0 <strong>3VF</strong>31 11–3JJ 41–0AA0<br />

50 50 400 (1) <strong>3VF</strong>31 12–0JL 41–0AA0 — — —<br />

63 63 500 (1) <strong>3VF</strong>31 11–0JN 41–0AA0 — — —<br />

80 80 630 (1) <strong>3VF</strong>31 11–0JQ 41–0AA0 — — —<br />

Neutro 100 100 800 (1) <strong>3VF</strong>31 11–0JS 41–0AA0 — — —<br />

protetto 125 125 1000 (2) <strong>3VF</strong>32 12–0JU 41–0AA0 — — —<br />

(1): N=100% 160 160 1280 (2) <strong>3VF</strong>31 11–0JW41–0AA0 — — —<br />

(2): N=60% 225 225 2400 (2) — <strong>3VF</strong>33 12–1JY 41–0AA0 <strong>3VF</strong>33 12–2JY 41–0AA0 <strong>3VF</strong>33 12–3JY 41–0AA0<br />

1<br />

50 40 ÷ 50 300 ÷ 500 (1) — <strong>3VF</strong>31 12–1HL 41–0AA0 <strong>3VF</strong>31 12–2HL 41–0AA0 <strong>3VF</strong>31 12–3HL41–0AA0<br />

63 50 ÷ 63 315 ÷ 630 (1) — <strong>3VF</strong>31 11–1HN 41–0AA0 <strong>3VF</strong>31 11–2HN 41–0AA0 <strong>3VF</strong>31 11–3HN 41–0AA0<br />

80 63 ÷ 80 400 ÷ 800 (1) — <strong>3VF</strong>32 12–1HQ 41–0AA0 <strong>3VF</strong>32 12–2HQ 41–0AA0 <strong>3VF</strong>32 12–3HQ 41–0AA0<br />

100 80 ÷ 100 500 ÷ 1000 (1) — <strong>3VF</strong>31 11–1HS 41–0AA0 <strong>3VF</strong>31 11–2HS 41–0AA0 <strong>3VF</strong>31 11–3HS 41–0AA0<br />

125 100 ÷ 125 625 ÷ 1250 (2) — <strong>3VF</strong>32 12–1HU 41–0AA0 <strong>3VF</strong>32 12–2HU 41–0AA0 <strong>3VF</strong>32 12–3HU 41–0AA0<br />

160 125 ÷ 160 800 ÷ 1600 (2) — <strong>3VF</strong>33 12–1HW 41–0AA0 <strong>3VF</strong>33 12–2HW41–0AA0 <strong>3VF</strong>33 12–3HW41–0AA0<br />

Neutro 200 160 ÷ 200 1000 ÷ 2000 (2) — <strong>3VF</strong>33 12–1HX 41–0AA0 <strong>3VF</strong>33 12–2HX 41–0AA0 <strong>3VF</strong>33 12–3HY 41–0AA0<br />

protetto<br />

(1): N=100%<br />

(2): N=60%<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>3 1)<br />

100 Senza 2400 — — <strong>3VF</strong>31 12–6DS31–0AA0 —<br />

160 sganciatori 2400 — — <strong>3VF</strong>32 12–6DW31–0AA0 —<br />

termici<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Bobina di minima tensione oppure bobina a lancio di corrente<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>3. ..–.....– ..<br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione ➀ ➁<br />

9 ÷ 12 V — 1 B 2 B<br />

24 V — 1 D 2 D<br />

48 ÷ 60 V — 1 F 2 F<br />

110 ÷ 127 V — 1 G 2 G<br />

208 ÷ 240 V — 1 H 2 H<br />

380 ÷ 480 V — 1 K 2 K<br />

480 ÷ 525 V — 1 L 2 L<br />

— 12 V 1 N 2 N<br />

— 24 V 1 P 2 P<br />

— 48 ÷ 60 V 1 Q 2 Q<br />

— 110 ÷ 125 V 1 R 2 R<br />

— 220 ÷ 250 V 1 S 2 S<br />

Con bobina a lancio di corrente<br />

12 ÷ 24 V 12 ÷ 24 V 7 C 8 C<br />

48 ÷ 127 V 48 ÷ 60 V 7 G 8 G<br />

110 ÷ 240 V 110 ÷ 125 V 7 K 8 K<br />

380 ÷ 600 V 220 ÷ 250 V 7 T 8 T<br />

➀ es. con conduttori di allacciamento<br />

➁ es. con morsetti di allacciamento<br />

Protezione differenziale (realizzabile con <strong>3VF</strong>3 fino a 160 A)<br />

2. Contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>3. ..–.....–.. <br />

<br />

Senza contatti ausiliari e<br />

senza contatti di segnalazione sgancio ➀ A0 ➁<br />

1 HS B 1 B 2<br />

2 HS C 1 C 2<br />

1 HS 3) F 1<br />

1 AS G 1 G 2<br />

1 HS + 1 AS N 1 N 2<br />

Se nessun sganciatore ausiliario viene incorporato sono anche possibili<br />

i seguenti equipaggiamenti<br />

<strong>3VF</strong>3. ..–.....–0A <br />

<br />

➀<br />

➁<br />

1 HS + 2 AS R 1 R 2<br />

2 HS + 1 AS P 1 P 2<br />

2 HS + 2 AS S 1 S 2<br />

1) Per modificare l’interruttore in esecuzione rimovibile o estraibile sostituire alla 3) 1 HS destro per <strong>3VF</strong>3 3 poli esecuzione<br />

posizione 12 l’alfanumerico 1 con il 7.<br />

per protezione motori. Fornibili dal 3/96.<br />

Es.: <strong>3VF</strong>31 11-1FS47-0AA0; parte fissa da ordinare sempre separatamente. 4) Non è possibile il montaggio di nessun<br />

2) U e<br />

max = 415 V per interruttori <strong>3VF</strong>3 con termico fisso fino alla corrente nominale accessorio sull’interruttore da 25 kA.<br />

I u<br />

= 40 A<br />

Per l’ordinazione degli interruttori <strong>3VF</strong>3 3 e 4 poli con protezione differenziale modificare la sigla d’ordinazione come segue:<br />

• 3 e 4 poli <strong>3VF</strong>3...-...41-0A..-ZA0101<br />

Per ulteriori informazioni si veda pag. 1/20.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/9


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>4<br />

fino a 250 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) (sganciatori n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>4 1)<br />

125 125 625 ÷ 1250 <strong>3VF</strong>42 11–1DF41–0AA0 <strong>3VF</strong>42 11–2DF41–0AA0 <strong>3VF</strong>42 11–3DF41–0AA0<br />

160 160 800 ÷ 1600 <strong>3VF</strong>31 11–1DH41–0AA0 <strong>3VF</strong>31 11–2DH41–0AA0 <strong>3VF</strong>31 11–3DH41–0AA0<br />

200 200 1000 ÷ 2000 <strong>3VF</strong>31 11–1DK41–0AA0 <strong>3VF</strong>31 11–2DK41–0AA0 <strong>3VF</strong>31 11–3DK41–0AA0<br />

250 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1DM41–0AA0 <strong>3VF</strong>31 11–2DM41–0AA0 <strong>3VF</strong>31 11–3DM41–0AA0<br />

125 100 ÷ 125 625 ÷ 1250 <strong>3VF</strong>42 11–1BF41–0AA0 <strong>3VF</strong>42 11–2BF41–0AA0 <strong>3VF</strong>42 11–3BF41–0AA0<br />

160 125 ÷ 160 800 ÷ 1600 <strong>3VF</strong>31 11–1BH41–0AA0 <strong>3VF</strong>31 11–2BH41–0AA0 <strong>3VF</strong>31 11–3BH41–0AA0<br />

200 160 ÷ 200 1000 ÷ 2000 <strong>3VF</strong>31 11–1BK41–0AA0 <strong>3VF</strong>31 11–2BK41–0AA0 <strong>3VF</strong>31 11–3BK41–0AA0<br />

250 200 ÷ 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1BM41–0AA0 <strong>3VF</strong>31 11–2BM41–0AA0 <strong>3VF</strong>31 11–3BM41–0AA0<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>4 1)<br />

250 Senza 3000 <strong>3VF</strong>42 11–5BM31–0AA0 <strong>3VF</strong>42 11–6BM31–0AA0 —<br />

sganciatori<br />

termici<br />

<strong>Interruttori</strong> per avviatori <strong>3VF</strong>4 1)<br />

(Potenza max. del motore da proteggere: 110 kW a 380 V, 50 Hz; 132 kW a 500 V, 50 Hz)<br />

125 Senza 1000 ÷ 2000 — <strong>3VF</strong>42 11–6BH21–0AA0 —<br />

160 sganciatori 1250 ÷ 2500 — <strong>3VF</strong>32 11–6BK21–0AA0 —<br />

200 (205) termici 1500 ÷ 3000 — <strong>3VF</strong>32 11–6BM21–0AA0 —<br />

1) Per modificare l’interruttore in esecuzione rimovibile sostituire alla posizione 12<br />

l’alfanumerico 1 con il 7. Es.: <strong>3VF</strong>4211-1BM47-0AA0.<br />

Parte fissa da ordinare sempre separatamente.<br />

1/10<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>4<br />

fino a 250 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) (sganciatori n)<br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>4 1)<br />

I >><br />

125 100 ÷ 125 625 ÷ 1250 <strong>3VF</strong>42 12–1MF41–0AA0 <strong>3VF</strong>42 12–2MF41–0AA0 <strong>3VF</strong>42 12–3MF41–0AA0<br />

160 125 ÷ 160 800 ÷ 1600 <strong>3VF</strong>31 11–1MH41–0AA0 <strong>3VF</strong>31 11–2MH41–0AA0 <strong>3VF</strong>31 11–3MH41–0AA0<br />

200 160 ÷ 200 1000 ÷ 2000 <strong>3VF</strong>31 11–1MK41–0AA0 <strong>3VF</strong>31 11–2MK41–0AA0 <strong>3VF</strong>31 11–3MK41–0AA0<br />

250 200 ÷ 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1MM41–0AA0 <strong>3VF</strong>31 11–2MM41–0AA0 <strong>3VF</strong>31 11–3MM41–0AA0<br />

1<br />

Neutro non protetto<br />

200 160 ÷ 200 1000 ÷ 2000 (N=60%) <strong>3VF</strong>42 12–1HK41–0AA0 <strong>3VF</strong>42 12–2HK41–0AA0 <strong>3VF</strong>42 12–3HK41–0AA0<br />

250 200 ÷ 250 1250 ÷ 2500 (N=60%) <strong>3VF</strong>31 11–1HM41–0AA0 <strong>3VF</strong>31 11–2HM41–0AA0 <strong>3VF</strong>31 11–3HM41–0AA0<br />

Neutro protetto<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>4 1)<br />

250 Senza 3000 <strong>3VF</strong>42 12–5DM31–0AA0 <strong>3VF</strong>42 12–6DM31–0AA0 —<br />

sganciatori<br />

termici<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Riferimento aggiuntivo<br />

bobina di minima tensione oppure bobina a lancio di corrente<br />

2. Riferimento aggiuntivo<br />

contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>4. ..–.....– ..<br />

<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>4. ..–.....–.. <br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione ➀ ➁<br />

12 V — 1 C 2 C<br />

24 V — 1 D 2 D<br />

48 ÷ 60 V — 1 F 2 F<br />

110 ÷ 127 V — 1 G 2 G<br />

208 ÷ 240 V — 1 H 2 H<br />

380 ÷ 500 V — 1 J 2 J<br />

— 12 V 1 N 2 N<br />

— 24 V 1 P 2 P<br />

— 48 ÷ 60 V 1 Q 2 Q<br />

— 110 ÷ 125 V 1 R 2 R<br />

— 220 ÷ 250 V 1 S 2 S<br />

Con bobina a lancio di corrente<br />

Senza contatti ausiliari e<br />

senza contatti di segnalazione sgancio<br />

➀<br />

➁<br />

1 HS B 1 B 2<br />

2 HS C 1 C 2<br />

1 AS G 1 G 2<br />

1 HS + 1 AS N 1 N 2<br />

A0<br />

Se nessun sganciatore ausiliario viene incorporato è possibile anche<br />

il seguente equipaggiamento<br />

<strong>3VF</strong>4. ..–.....–0A <br />

<br />

➀<br />

➁<br />

2 HS + 1 AS P 1 P 2<br />

12 ÷ 24 V 12 ÷ 24 V 7 C 8 C<br />

48 ÷ 60 V 48 ÷ 60 V 7 J 8 J<br />

110 ÷ 240 V 110 ÷ 125 V 7 K 8 K<br />

380 ÷ 440 V 220 ÷ 250 V 7 S 8 S<br />

480 ÷ 600 V — 7 V 8 V<br />

➀ es. con conduttori di allacciamento<br />

➁ es. con morsetti di allacciamento<br />

Protezione differenziale<br />

1) Per modificare l’interruttore in esecuzione rimovibile sostituire alla posizione 12<br />

l’alfanumerico 1 con il 7. Es.: <strong>3VF</strong>4211-1BM47-0AA0.<br />

Parte fissa da ordinare sempre separatamente.<br />

Per l’ordinazione degli interruttori <strong>3VF</strong>4 3 e 4 poli con protezione differenziale modificare la sigla d’ordinazione come segue:<br />

• 3 e 4 poli <strong>3VF</strong>4...-...41-0A..-ZA01<br />

Per ulteriori informazioni si veda pag. 1/20.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/11


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>5<br />

fino a 400 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40/45 kA 5) 65/70 kA 5) 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) ritardati (z) 6)<br />

e istantanei (n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>5 con sganciatore magnetotermico 3)<br />

200 200 1000 ÷ 2000 <strong>3VF</strong>52 11–1DF41–0AA0 <strong>3VF</strong>52 11–2DF41–0AA0 <strong>3VF</strong>52 11–3DF41–0AA0<br />

250 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1DH41–0AA0 <strong>3VF</strong>31 11–2DH41–0AA0 <strong>3VF</strong>31 11–3DH41–0AA0<br />

315 315 1575 ÷ 3150 <strong>3VF</strong>31 11–1DK41–0AA0 <strong>3VF</strong>31 11–2DK41–0AA0 <strong>3VF</strong>31 11–3DK41–0AA0<br />

400 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1DM41–0AA0 <strong>3VF</strong>31 11–2DM41–0AA0 <strong>3VF</strong>31 11–3DM41–0AA0<br />

200 160 ÷ 200 1000 ÷ 2000 <strong>3VF</strong>52 11–1BF41–0AA0 <strong>3VF</strong>52 11–2BF41–0AA0 <strong>3VF</strong>52 11–3BF41–0AA0<br />

250 200 ÷ 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1BH41–0AA0 <strong>3VF</strong>31 11–2BH41–0AA0 <strong>3VF</strong>31 11–3BH41–0AA0<br />

315 250 ÷ 315 1575 ÷ 3150 <strong>3VF</strong>31 11–1BK41–0AA0 <strong>3VF</strong>31 11–2BK41–0AA0 <strong>3VF</strong>31 11–3BK41–0AA0<br />

400 315 ÷ 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1BM41–0AA0 <strong>3VF</strong>31 11–2BM41–0AA0 <strong>3VF</strong>31 11–3BM41–0AA0<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>5 con sganciatore elettronico 4)<br />

a<br />

z<br />

n<br />

160 63 ÷ 160 2 ÷ 8 I r<br />

<strong>3VF</strong>52 11–1BD61–0AA0 <strong>3VF</strong>52 11–2BD61–0AA0 <strong>3VF</strong>52 11–3BD61–0AA0<br />

250 100 ÷ 250 (0 ÷ 300 ms) <strong>3VF</strong>52 11–1BH61–0AA0 <strong>3VF</strong>52 11–2BH61–0AA0 <strong>3VF</strong>52 11–3BH61–0AA0<br />

400 200 ÷ 400 + 4000 fissa <strong>3VF</strong>52 11–1BM61–0AA0 <strong>3VF</strong>52 11–2BM61–0AA0 <strong>3VF</strong>52 11–3BM61–0AA0<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>5 3)<br />

fino 400 Senza 4800 <strong>3VF</strong>52 11–5BM31–0AA0 <strong>3VF</strong>52 11–6BM31–0AA0 —<br />

sganciatori<br />

termici<br />

1) 3)<br />

<strong>Interruttori</strong> per motori <strong>3VF</strong>5<br />

(Potenza max. del motore da proteggere: 160 kW a 380 V, 50 Hz; 220 kW a 500 V, 50 Hz)<br />

315 2) 160 ÷ 315 15 × I r<br />

<strong>3VF</strong>51 11–5EL71–0AA0 <strong>3VF</strong>51 11–6EL71–0AA0 —<br />

Con protezione<br />

contro la mancanza<br />

di fase<br />

315 160 ÷ 315 15 × I r<br />

<strong>3VF</strong>51 11–5DL71–0AA0 <strong>3VF</strong>51 11–6DL71–0AA0 —<br />

Senza protezione<br />

contro la mancanza<br />

di fase<br />

<strong>Interruttori</strong> per avviatori <strong>3VF</strong>5 3)<br />

(Potenza max. del motore da proteggere: 160 kW a 380 V, 50 Hz; 220 kW a 500 V, 50 Hz)<br />

200 Senza 1500 ÷ 3000 — <strong>3VF</strong>51 11–6BH21–0AA0 —<br />

250 sganciatore 1800 ÷ 3800 — <strong>3VF</strong>51 11–6BK21–0AA0 —<br />

315 termico 2400 ÷ 4800 — <strong>3VF</strong>51 11–6BM21–0AA0 —<br />

1) Sganciatori di sovracorrente elettronici.<br />

2) Grado di inerzia regolabile 10, 15, 20, 30 s.<br />

3) Per modificare l’interruttore in esecuzione rimovibile o estraibile su carrello sostituire alla posizione 12 l’alfanumerico 1<br />

con il 7. Es.: <strong>3VF</strong>5 211-1BM47-0AA0. Parte fissa da ordinare sempre separatamente.<br />

4) Per esecuzione rimovibile o estraibile non utilizzare il kit, ma ordinare con il rif. 67.<br />

5) 45 kA e 70 kA solo per interruttori per distribuzione.<br />

6) Lo sganciatore z contro i cortocircuiti ritardati è presente solo negli interruttori per distribuzione con sganciatore<br />

elettronico.<br />

1/12<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>5<br />

fino a 400 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40/45 kA 2) 65/70 kA 2) 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) ritardati (z) 3)<br />

e istantanei (n)<br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>5 con sganciatore magnetotermico 1)<br />

I >><br />

200 160 ÷ 200 1000 ÷ 2000 <strong>3VF</strong>52 12–1MF41–0AA0 <strong>3VF</strong>52 12–2MF41–0AA0 <strong>3VF</strong>52 12–3MF41–0AA0<br />

250 200 ÷ 250 1250 ÷ 2500 <strong>3VF</strong>31 11–1MH41–0AA0 <strong>3VF</strong>31 11–2MH41–0AA0 <strong>3VF</strong>31 11–3MH41–0AA0<br />

315 250 ÷ 315 1575 ÷ 3150 <strong>3VF</strong>31 11–1MK41–0AA0 <strong>3VF</strong>31 11–2MK41–0AA0 <strong>3VF</strong>31 11–3MK41–0AA0<br />

400 315 ÷ 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1MM41–0AA0 <strong>3VF</strong>31 11–2MM41–0AA0 <strong>3VF</strong>31 11–3MM41–0AA0<br />

1<br />

Neutro non protetto<br />

315 250 ÷ 315 1575 ÷ 3150 <strong>3VF</strong>52 12–1HK41–0AA0 <strong>3VF</strong>52 12–2HK41–0AA0 <strong>3VF</strong>52 12–3HK41–0AA0<br />

(N=60%)<br />

400 315 ÷ 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1HM41–0AA0 <strong>3VF</strong>31 11–2HM41–0AA0 <strong>3VF</strong>31 11–3HM41–0AA0<br />

(N=60%)<br />

Neutro protetto<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>5 con sganciatore elettronico 4)<br />

a<br />

z<br />

n<br />

160 63 ÷ 160 2 ÷ 8 I r<br />

<strong>3VF</strong>52 12–1KD61–0AA0 <strong>3VF</strong>52 12–2KD61–0AA0 <strong>3VF</strong>52 12–3KD61–0AA0<br />

250 100 ÷ 250 (0 ÷ 300 ms) <strong>3VF</strong>52 12–1KH61–0AA0 <strong>3VF</strong>52 12–2KH61–0AA0 <strong>3VF</strong>52 12–3KH61–0AA0<br />

400 200 ÷ 400 + 4000 fissa <strong>3VF</strong>52 12–1KM61–0AA0 <strong>3VF</strong>52 12–2KM61–0AA0 <strong>3VF</strong>52 12–3KM61–0AA0<br />

Neutro non protetto<br />

a<br />

z<br />

n<br />

160 63 ÷ 160 2 ÷ 8 I r<br />

<strong>3VF</strong>52 12–1FD61–0AA0 <strong>3VF</strong>52 12–2FD61–0AA0 <strong>3VF</strong>52 12–3FD61–0AA0<br />

250 100 ÷ 250 (0 ÷ 300 ms) <strong>3VF</strong>52 12–1FH61–0AA0 <strong>3VF</strong>52 12–2FH61–0AA0 <strong>3VF</strong>52 12–3FH61–0AA0<br />

400 200 ÷ 400 + 4000 fissa <strong>3VF</strong>52 12–1FM61–0AA0 <strong>3VF</strong>52 12–2FM61–0AA0 <strong>3VF</strong>52 12–3FM61–0AA0<br />

(N=60%)<br />

Neutro protetto<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>5 1)<br />

fino 400 Senza 4800 (15 × I n<br />

) <strong>3VF</strong>52 12–5DM31–0AA0 <strong>3VF</strong>52 12–6DM31–0AA0 —<br />

sganciatore<br />

termico<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Bobina di minima tensione oppure bobina a lancio di corrente<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>5. ..–.....– ..<br />

<br />

2. Contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>5. ..–.....–.. <br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione ➀ ➁<br />

12 V — 1 C 2 C<br />

24 V — 1 D 2 D<br />

48 ÷ 60 V — 1 F 2 F<br />

110 ÷ 127 V — 1 G 2 G<br />

208 ÷ 240 V — 1 H 2 H<br />

380 ÷ 500 V — 1 J 2 J<br />

— 12 V 1 N 2 N<br />

— 24 V 1 P 2 P<br />

— 48 ÷ 60 V 1 Q 2 Q<br />

— 110 ÷ 125 V 1 R 2 R<br />

— 220 ÷ 250 V 1 S 2 S<br />

Con bobina a lancio di corrente<br />

12 ÷ 24 V 12 ÷ 24 V 7 C 8 C<br />

48 ÷ 60 V 48 ÷ 60 V 7 J 8 J<br />

110 ÷ 240 V 110 ÷ 125 V 7 K 8 K<br />

380 ÷ 440 V 220 ÷ 250 V 7 S 8 S<br />

480 ÷ 600 V — 7 V 8 V<br />

➀ es. con conduttori di allacciamento<br />

➁ es. con morsetti di allacciamento<br />

Senza contatti ausiliari e<br />

senza contatti di segnalazione sgancio<br />

➀<br />

➁<br />

1 HS B 1 B 2<br />

2 HS C 1 C 2<br />

1 AS G 1 G 2<br />

1 HS + 1 AS N 1 N 2<br />

Se nessun sganciatore ausiliario viene incorporato sono possibili anche<br />

i seguenti equipaggiamenti<br />

<strong>3VF</strong>5. ..–.....–0A <br />

<br />

➀<br />

➁<br />

1 HS + 2 AS R 1 R 2<br />

2 HS + 1 AS P 1 P 2<br />

2 HS + 2 AS S 1 S 2<br />

1) Per modificare l’interruttore in esecuzione rimovibile o estraibile su carrello sostituire alla posizione 12 l’alfanumerico 1 con<br />

il 7. Es.: <strong>3VF</strong>5 211-1BM47-0AA0. Parte fissa da ordinare sempre separatamente.<br />

2) 45 kA e 70 kA solo interruttori per distribuzione.<br />

3) Lo sganciatore z è presente solo negli interruttori per distribuzione con sganciatore elettronico.<br />

4) Per esecuzione rimovibile o estraibile non utilizzare il kit, ma ordinare con il rif. 67.<br />

Protezione differenziale (non fornibile in esecuzione con sganciatore elettronico)<br />

Per l’ordinazione degli interruttori <strong>3VF</strong>5 3 e 4 poli con protezione differenziale modificare la sigla d’ordinazione come segue:<br />

• 3 e 4 poli <strong>3VF</strong>5...-...41-0A..-ZA01<br />

Per ulteriori informazioni si veda pag. 1/20.<br />

A0<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/13


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>6<br />

fino a 800 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40/45 kA 5) 65/70 kA 5) 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) ritardati (z) 6)<br />

e istantanei (n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>6 con sganciatore magnetotermico 3)<br />

315 315 1600 ÷ 3200 <strong>3VF</strong>62 11–1DF44–0AA0 <strong>3VF</strong>62 11–2DF44–0AA0 <strong>3VF</strong>62 11–3DF44–0AA0<br />

400 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1DH44–0AA0 <strong>3VF</strong>31 11–2DH44–0AA0 <strong>3VF</strong>31 11–3DH44–0AA0<br />

500 500 2500 ÷ 5000 <strong>3VF</strong>31 11–1DK44–0AA0 <strong>3VF</strong>31 11–2DK44–0AA0 <strong>3VF</strong>31 11–3DK44–0AA0<br />

630 630 3150 ÷ 6300 <strong>3VF</strong>31 11–1DM44–0AA0 <strong>3VF</strong>31 11–2DM44–0AA0 <strong>3VF</strong>31 11–3DM44–0AA0<br />

300 800 3200 ÷ 6400 — <strong>3VF</strong>63 11–2DQ44–0AA0 4) —<br />

315 250 ÷ 315 1600 ÷ 3200 <strong>3VF</strong>62 11–1BF44–0AA0 <strong>3VF</strong>62 11–2BF44–0AA0 <strong>3VF</strong>62 11–3BF44–0AA0<br />

400 315 ÷ 400 2000 ÷ 4000 <strong>3VF</strong>31 11–1BH44–0AA0 <strong>3VF</strong>31 11–2BH44–0AA0 <strong>3VF</strong>31 11–3BH44–0AA0<br />

500 400 ÷ 500 2500 ÷ 5000 <strong>3VF</strong>31 11–1BK44–0AA0 <strong>3VF</strong>31 11–2BK44–0AA0 <strong>3VF</strong>31 11–3BK44–0AA0<br />

630 500 ÷ 630 3150 ÷ 6300 <strong>3VF</strong>31 11–1BM44–0AA0 <strong>3VF</strong>31 11–2BM44–0AA0 <strong>3VF</strong>31 11–3BM44–0AA0<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>6 con sganciatore elettronico 7)<br />

a<br />

z<br />

n<br />

630 315 ÷ 630 2 ÷ 8 I r<br />

<strong>3VF</strong>62 11–1BM64–0AA0 <strong>3VF</strong>62 11–2BM64–0AA0 <strong>3VF</strong>62 11–3BM64–0AA0<br />

(0 ÷ 300 ms)<br />

+ 5500 fissa<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>6 3)<br />

630 Senza 7500 <strong>3VF</strong>62 11–5BM34–0AA0 <strong>3VF</strong>61 11–6BK34–0AA0 —<br />

sganciatore (esecuz. 500 A)<br />

termico<br />

1) 3)<br />

<strong>Interruttori</strong> per motori <strong>3VF</strong>6<br />

(Potenza max. del motore da proteggere: 250 kW a 380 V, 50 Hz; 355 kW a 500 V, 50 Hz)<br />

500 2) 250 ÷ 500 15 × I r<br />

<strong>3VF</strong>61 11–5EL74–0AA0 <strong>3VF</strong>61 11–6EL74–0AA0 —<br />

Con protezione<br />

contro la mancanza<br />

di fase<br />

500 250 ÷ 500 15 × I r<br />

<strong>3VF</strong>61 11–5DL74–0AA0 <strong>3VF</strong>61 11–6DL74–0AA0 —<br />

Senza protezione<br />

contro la mancanza<br />

di fase<br />

<strong>Interruttori</strong> per avviatori <strong>3VF</strong>6 3)<br />

(Potenza max. del motore da proteggere: 250 kW a 380 V, 50 Hz; 355 kW a 500 V, 50 Hz)<br />

315 Senza 2400 ÷ 4800 — <strong>3VF</strong>61 11–6BH24–0AA0 —<br />

400 sganciatore 3000 ÷ 6000 — <strong>3VF</strong>51 11–6BK24–0AA0 —<br />

500 termico 3800 ÷ 7500 — <strong>3VF</strong>51 11–6BM24–0AA0 —<br />

1) Sganciatori di sovracorrente elettronici.<br />

2) Grado di inerzia regolabile 10, 15, 20, 30 s.<br />

3) Per modificare l’interruttore in esecuzione rimovibile o estraibile su carrello sostituire alla posizione 12 l’alfanumerico 4<br />

con il 7. Es.: <strong>3VF</strong> 6211-1BM47-0AA0. Parte fissa da ordinare sempre separatamente.<br />

4) 50 kA a 380/415V. <strong>3VF</strong>6 da 800A utilizzabile sono in esecuzione fissa.<br />

5) 45 kA e 70 kA solo per interruttori per distribuzione.<br />

6) Lo sganciatore z contro i cortocircuiti ritardati è presente solo negli interruttori per distribuzione con sganciatore<br />

elettronico.<br />

7) Per esecuzione rimovibile o estraibile non utilizzare il kit, ma ordinare con il rif. 67.<br />

1/14<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>6<br />

fino a 800 A<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 40/45 kA 2) 65/70 kA 2) 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i contro i Nr. di Nr. di Nr. di<br />

sovraccarichi cortocircuiti ordinazione ordinazione ordinazione<br />

(sganciatori a) ritardati (z) 3)<br />

e istantanei (n)<br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>6 con sganciatore magnetotermico 1)<br />

Neutro non protetto<br />

I >><br />

315 250 ÷ 315 1000 ÷ 2000 <strong>3VF</strong>62 12–1MF44–0AA0 <strong>3VF</strong>62 12–2MF44–0AA0 <strong>3VF</strong>62 12–3MF44–0AA0<br />

400 315 ÷ 400 1250 ÷ 2500 <strong>3VF</strong>31 11–1MH44–0AA0 <strong>3VF</strong>31 11–2MH44–0AA0 <strong>3VF</strong>31 11–3MH44–0AA0<br />

500 400 ÷ 500 2000 ÷ 4000 <strong>3VF</strong>31 11–1MK44–0AA0 <strong>3VF</strong>31 11–2MK44–0AA0 <strong>3VF</strong>31 11–3MK44–0AA0<br />

630 500 ÷ 630 3150 ÷ 6300 <strong>3VF</strong>31 11–1MM44–0AA0 <strong>3VF</strong>31 11–2MM44–0AA0 <strong>3VF</strong>31 11–3MM44–0AA0<br />

800 800 3200 ÷ 6400 — <strong>3VF</strong>63 12–2TQ 44–0AA0 4) —<br />

1<br />

500 400 ÷ 500 2500 ÷ 5000 (N=60%) <strong>3VF</strong>62 12–1HK44–0AA0 <strong>3VF</strong>62 12–2HK44–0AA0 <strong>3VF</strong>62 12–3HK44–0AA0<br />

630 500 ÷ 630 3150 ÷ 6300 (N=60%) <strong>3VF</strong>31 11–1HM44–0AA0 <strong>3VF</strong>31 11–2HM44–0AA0 <strong>3VF</strong>31 11–3HM44–0AA0<br />

800 800 3200 ÷ 6400 (N=60%) — <strong>3VF</strong>63 12–2LQ 44–0AA0 4) —<br />

Neutro protetto<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>6 con sganciatore elettronico 5)<br />

a<br />

z<br />

n<br />

630 315 ÷ 630 2 ÷ 8 I r<br />

<strong>3VF</strong>62 12–1KM64–0AA0 <strong>3VF</strong>62 12–2KM64–0AA0 <strong>3VF</strong>62 12–3KM64–0AA0<br />

(0 ÷ 300 ms)<br />

+ 5000 fissa<br />

Neutro non protetto<br />

a<br />

z<br />

n<br />

630 315 ÷ 630 2 ÷ 8 I r<br />

<strong>3VF</strong>62 12–1FM64–0AA0 <strong>3VF</strong>62 12–2FM64–0AA0 <strong>3VF</strong>62 12–3FM64–0AA0<br />

(0 ÷ 300 ms)<br />

+ 5500 fissa<br />

(N=60%)<br />

Neutro protetto<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>6 1)<br />

630 Senza 7500 <strong>3VF</strong>62 12–5DM34–0AA0 <strong>3VF</strong>61 12–6DK34–0AA0 —<br />

sganciatore (esecuzione 500 A)<br />

termico<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Bobina di minima tensione oppure bobina a lancio di corrente<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>6. ..–.....– ..<br />

<br />

2. Contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>6. ..–.....–.. <br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione ➀ ➁<br />

12 V — 1 C 2 C<br />

24 V — 1 D 2 D<br />

48 ÷ 60 V — 1 F 2 F<br />

110 ÷ 127 V — 1 G 2 G<br />

208 ÷ 240 V — 1 H 2 H<br />

380 ÷ 500 V — 1 J 2 J<br />

— 12 V 1 N 2 N<br />

— 24 V 1 P 2 P<br />

— 48 ÷ 60 V 1 Q 2 Q<br />

— 110 ÷ 125 V 1 R 2 R<br />

— 220 ÷ 250 V 1 S 2 S<br />

Con bobina a lancio di corrente<br />

12 ÷ 24 V 12 ÷ 24 V 7 C 8 C<br />

48 ÷ 60 V — 7 F 8 F<br />

— 48 ÷ 60 V 7 H 8 H<br />

— 110 ÷ 125 V 7 L 8 L<br />

110 ÷ 240 V — 7 M 8 M<br />

380 ÷ 440 V 220 ÷ 250 V 7 S 8 S<br />

480 ÷ 600 V — 7 V 8 V<br />

Senza contatti ausiliari e<br />

senza contatti di segnalazione sgancio<br />

➀<br />

➁<br />

1 HS B 1 B 2<br />

2 HS C 1 C 2<br />

1 AS G 1 G 2<br />

1 HS + 1 AS N 1 N 2<br />

Se nessun sganciatore ausiliario viene incorporato sono possibili anche<br />

i seguenti equipaggiamenti<br />

<strong>3VF</strong>6. ..–.....–0A <br />

<br />

➀<br />

➁<br />

1 HS + 2 AS R 1 R 2<br />

2 HS + 1 AS P 1 P 2<br />

2 HS + 2 AS S 1 S 2<br />

A0<br />

➀ es. con conduttori di allacciamento<br />

➁ es. con morsetti di allacciamento<br />

1) Per modificare l’interruttore in esecuzione rimovibile o estraibile su carrello sostituire alla posizione 12 l’alfanumerico 4 con<br />

il 7. Es.: <strong>3VF</strong> 6211-1BM47-0AA0. Parte fissa da ordinare sempre separatamente.<br />

2) 45 kA e 70 kA solo per interruttori per distribuzione.<br />

3) Lo sganciatore z è presente solo negli interruttori per distribuzione con sganciatore elettronico.<br />

4) 50 kA a 380/415 V. <strong>3VF</strong>6 da 800 A utilizzabile solo in esecuzione fissa.<br />

5) Per esecuzione rimovibile o estraibile non utilizzare il kit, ma ordinare con il rif. 67.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/15


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>7<br />

fino a 1250 A *<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 50 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori I = contro<br />

contro i i cortocircuiti Nr. di Nr. di Nr. di<br />

sovraccarichi ritardati (z) ordinazione ordinazione ordinazione<br />

(sganciatori a) e istantanei (n)<br />

I >><br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>7 1)<br />

a<br />

z<br />

n<br />

800 400 ÷ 800 2 ÷ 8 I r<br />

<strong>3VF</strong>71 11–1BK60–0AA0 <strong>3VF</strong>71 11–2BK60–0AA0 <strong>3VF</strong>71 11–3BK60–0AA0<br />

(0 ÷ 300 mS) <strong>3VF</strong>31 11<br />

+ 15000 fissa <strong>3VF</strong>31 11<br />

1250 630 ÷ 1250 2 ÷ 8 I r<br />

<strong>3VF</strong>72 11–1BM60–0AA0 <strong>3VF</strong>72 11–2BM60–0AA0 <strong>3VF</strong>72 11–3BM60–0AA0<br />

(0 ÷ 300 mS)<br />

+ 15000 fissa<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>7 1)<br />

800 Senza 15000 <strong>3VF</strong>71 11–1BK30–0AA0 <strong>3VF</strong>71 11–2BK30–0AA0 —<br />

sganciatore <strong>3VF</strong>31 11<br />

termico <strong>3VF</strong>31 11<br />

1250 15000 <strong>3VF</strong>72 11–1BM30–0AA0 <strong>3VF</strong>72 11–2BM30–0AA0 —<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Riferimento aggiuntivo<br />

bobina di minima tensione oppure bobina a lancio di corrente<br />

2. Riferimento aggiuntivo<br />

contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>7. ..–.....– ..<br />

<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>7. ..–.....–.. <br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione ➀ ➁<br />

12 V — 1 C 2 C<br />

24 V — 1 D 2 D<br />

48 ÷ 60 V — 1 F 2 F<br />

110 ÷ 127 V — 1 G 2 G<br />

208 ÷ 240 V — 1 H 2 H<br />

380 ÷ 500 V — 1 J 2 J<br />

— 12 V 1 N 2 N<br />

— 24 V 1 P 2 P<br />

— 48 ÷ 60 V 1 Q 2 Q<br />

— 110 ÷ 125 V 1 R 2 R<br />

— 220 ÷ 250 V 1 S 2 S<br />

Con bobina a lancio di corrente<br />

12 ÷ 24 V 12 ÷ 24 V 7 C 8 C<br />

48 ÷ 60 V — 7 F 8 F<br />

— 48 ÷ 60 V 7 H 8 H<br />

— 110 ÷ 125 V 7 L 8 L<br />

110 ÷ 240 V — 7 M 8 M<br />

380 ÷ 440 V 220 ÷ 250 V 7 S 8 S<br />

480 ÷ 600 V — 7 V 8 V<br />

Senza contatti ausiliari e<br />

senza contatti di segnalazione sgancio<br />

➀<br />

➁<br />

1 HS B 1 B 2<br />

2 HS C 1 C 2<br />

1 AS G 1 G 2<br />

1 HS + 1 AS N 1 N 2<br />

A0<br />

Se nessun sganciatore ausiliario viene incorporato sono possibili anche<br />

i seguenti equipaggiamenti<br />

<strong>3VF</strong>7. ..–.....–0A <br />

<br />

➀<br />

➁<br />

1 HS + 2 AS R 1 R 2<br />

2 HS + 1 AS P 1 P 2<br />

2 HS + 2 AS S 1 S 2<br />

* Sganciatori di sovracorrente elettronici.<br />

➀ es. con conduttori di allacciamento<br />

➁ es. con morsetti di allacciamento<br />

1) Per modificare l’interruttore in esecuzione estraibile su carrello sostituire alla<br />

posizione 12 l’alfanumerico 0 con il 7.<br />

Es.: <strong>3VF</strong>7111-1BK67-0AA0; parte fissa da ordinare sempre separatamente.<br />

1/16<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>7<br />

fino a 1250 A *<br />

Tabelle di scelta e di ordinazione<br />

a<br />

z<br />

n<br />

Corrente Corrente d’intervento opp. Esecuzione Esecuzione Esecuzione<br />

nominale campo di regolazione 50 kA 70 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori I = contro<br />

contro i i cortocircuiti Nr. di Nr. di Nr. di<br />

sovraccarichi ritardati (z) ordinazione ordinazione ordinazione<br />

(sganciatori a) e istantanei (n)<br />

A A A<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>7 1)<br />

I >><br />

800 400 ÷ 800 2 ÷ 8 I r<br />

<strong>3VF</strong>71 12–1KK60–0AA0 <strong>3VF</strong>71 12–2KK60–0AA0 <strong>3VF</strong>71 12–3KK60–0AA0<br />

(0 ÷ 300 ms) <strong>3VF</strong>31 11<br />

<strong>3VF</strong>31 11<br />

+15000 fissa<br />

1250 630 ÷ 1250 2 ÷ 8 I r<br />

<strong>3VF</strong>72 12–1KM60–0AA0 <strong>3VF</strong>72 12–2KM60–0AA0 <strong>3VF</strong>72 12–3KM60–0AA0<br />

(0 ÷ 300 ms)<br />

+15000 fissa<br />

1<br />

Neutro non protetto<br />

a<br />

z<br />

n<br />

800 400 ÷ 800 2 ÷ 8 I r<br />

<strong>3VF</strong>71 12–1FK60–0AA0 <strong>3VF</strong>71 12–2FK60–0AA0 <strong>3VF</strong>71 12–3FK60–0AA0<br />

(0 ÷ 300 ms) <strong>3VF</strong>31 11<br />

<strong>3VF</strong>31 11<br />

N = 60%,+15000 fissa<br />

1250 630 ÷ 1250 2 ÷ 8 I r<br />

<strong>3VF</strong>72 12–1FM60–0AA0 <strong>3VF</strong>72 12–2FM60–0AA0 <strong>3VF</strong>72 12–3FM60–0AA0<br />

(0 ÷ 300 ms)<br />

N = 60%,+15000 fissa<br />

Neutro protetto<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>7 1)<br />

800 Senza 15000 <strong>3VF</strong>71 12–1DK30–0AA0 <strong>3VF</strong>71 12–2DK30–0AA0 —<br />

sganciatore<br />

termico<br />

1250 15000 <strong>3VF</strong>72 12–1DM30–0AA0 <strong>3VF</strong>72 12–2DM30–0AA0 —<br />

* Sganciatori di sovracorrente elettronici. 1) Per modificare l’interruttore in esecuzione estraibile su carrello sostituire alla<br />

posizione 12 l’alfanumerico 0 con il 7.<br />

Es.: <strong>3VF</strong>7111-1BK67-0AA0; parte fissa da ordinare sempre separatamente.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/17


<strong>Interruttori</strong> <strong>automatici</strong> 3 poli <strong>3VF</strong>8<br />

fino a 2500 A *<br />

Tabelle di scelta e di ordinazione<br />

Corrente Corrente d’intervento oppure campo di regolazione Esecuzione Esecuzione<br />

nominale 70 kA 100 kA<br />

permanente<br />

I u<br />

Sganciatori Sganciatori contro i cortocircuiti<br />

contro i Sganciatori Tempo Sganciatori Nr. di Nr. di<br />

sovraccarichi ritardati di ritardo istantanei ordinazione ordinazione<br />

(sganciatori a) (sganciatori z) (sganciatori n)<br />

I >><br />

I >><br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>8<br />

A A A ms A<br />

a<br />

1600 800 ÷ 1600 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>82 11–2BM60–0AA0 <strong>3VF</strong>82 11–3BM60–0AA0<br />

2000 1000 ÷ 2000 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>83 11–2BM60–0AA0 <strong>3VF</strong>83 11–3BM60–0AA0<br />

z<br />

n<br />

2500 1600 ÷ 2500 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>84 11–2BM64–0AA0 1) <strong>3VF</strong>84 11–3BM64–0AA0 1)<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>8<br />

Corrente Corrente d’intervento opp. — Esecuzione Esecuzione<br />

nominale campo di regolazione 65 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i istantanei — Nr. di Nr. di<br />

sovraccarichi (sganciatori n) ordinazione ordinazione<br />

(sganciatori a)<br />

I >><br />

A A A<br />

1600 Senza 20000 — <strong>3VF</strong>82 11–2BM30–0AA0 —<br />

sganciatore <strong>3VF</strong>31 11<br />

termico <strong>3VF</strong>31 11<br />

2000 20000 — <strong>3VF</strong>83 11–2BM30–0AA0 —<br />

Accessori interni - Riferimenti aggiuntivi<br />

1. Riferimento aggiuntivo<br />

sganciatori ausiliari<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>8. ..–.....– ..<br />

<br />

1. Riferimento aggiuntivo<br />

sganciatori ausiliari<br />

Tensione<br />

Riferimento aggiuntivo<br />

50/60 Hz c.c. <strong>3VF</strong>8. ..–.....– ..<br />

<br />

Senza sganciatore ausiliario<br />

0 A<br />

Senza sganciatore ausiliario<br />

0 A<br />

Con bobina di minima tensione<br />

12 V — 1 C<br />

24 V — 1 D<br />

48 ÷ 60 V — 1 F<br />

110 ÷ 127 V — 1 G<br />

208 ÷ 240 V — 1 H<br />

380 ÷ 500 V — 1 J<br />

— 12 V 1 N<br />

— 24 V 1 P<br />

— 48 ÷ 60 V 1 Q<br />

— 110 ÷ 125 V 1 R<br />

— 220 ÷ 250 V 1 S<br />

Con bobina a lancio di corrente<br />

12 ÷ 24 V 12 ÷ 24 V 7 C<br />

48 ÷ 60 V — 7 F<br />

— 48 ÷ 60 V 7 H<br />

— 110 ÷ 125 V 7 L<br />

110 ÷ 240 V — 7 M<br />

380 ÷ 440 V 220 ÷ 250 V 7 S<br />

480 ÷ 600 V — 7 V<br />

2. Riferimento aggiuntivo<br />

contatti ausiliari e contatti di segnalazione sgancio in commutazione<br />

HS = 1 contatto ausiliario<br />

AS = 1 contatto di segnalazione sgancio<br />

Riferimento aggiuntivo<br />

<strong>3VF</strong>8. ..–.....–.. <br />

<br />

Senza contatti ausiliari<br />

A0<br />

* Sganciatori di sovracorrente elettronici.<br />

1) Già compreso di attacchi posteriori verticali.<br />

4 HS E1<br />

4 HS + 2 AS T1<br />

1/18<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> 4 poli <strong>3VF</strong>8<br />

fino a 2500 A *<br />

Tabelle di scelta e di ordinazione<br />

<strong>Interruttori</strong> per distribuzione <strong>3VF</strong>8<br />

Corrente Corrente d’intervento oppure campo di regolazione Esecuzione Esecuzione<br />

nominale 70 kA 100 kA<br />

permanente<br />

I u<br />

Sganciatori Sganciatori contro i cortocircuiti<br />

contro i Sganciatori Tempo Sganciatori Nr. di Nr. di<br />

sovraccarichi ritardati di ritardo istantanei ordinazione ordinazione<br />

(sganciatori a) (sganciatori z) (sganciatori n)<br />

I >><br />

A A A ms A<br />

I >><br />

1<br />

a<br />

1600 800 ÷ 1600 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>82 12–2KM60–0AA0 <strong>3VF</strong>82 12–3KM60–0AA0<br />

z<br />

n<br />

2000 1000 ÷ 2000 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>83 12–2KM60–0AA0 <strong>3VF</strong>83 12–3KM60–0AA0<br />

2500 1600 ÷ 2500 2 ÷ 8 I r<br />

0 ÷ 300 20000 <strong>3VF</strong>84 12–2KM64–0AA0 <strong>3VF</strong>84 12–3KM64–0AA0<br />

Neutro non protetto<br />

a<br />

1600 800 ÷ 1600 2 ÷ 8 × I r<br />

0 ÷ 300 20000 <strong>3VF</strong>82 12–2FM60–0AA0 <strong>3VF</strong>82 12–3FM60–0AA0<br />

(N=60%)<br />

z<br />

Neutro protetto<br />

n<br />

2000 1000 ÷ 2000 2 ÷ 8 × I r<br />

0 ÷ 300 20000 <strong>3VF</strong>83 12–2FM60–0AA0 <strong>3VF</strong>83 12–3FM60–0AA0<br />

(N=60%)<br />

2500 1600 ÷ 2500 2 ÷ 8 × I r<br />

0 ÷ 300 20000 <strong>3VF</strong>84 12–2FM64–0AA0 <strong>3VF</strong>84 12–3FM64–0AA0<br />

(N=60%)<br />

<strong>Interruttori</strong> principali <strong>3VF</strong>8<br />

Corrente Corrente d’intervento opp. — Esecuzione Esecuzione<br />

nominale campo di regolazione 65 kA 100 kA<br />

permanente<br />

I u<br />

sganciatori sganciatori<br />

contro i istantanei — Nr. di Nr. di<br />

sovraccarichi (sganciatori n) ordinazione ordinazione<br />

(sganciatori a)<br />

I >><br />

A A A<br />

1600 Senza 20000 — <strong>3VF</strong>82 12–2DM30–0AA0 —<br />

sganciatore <strong>3VF</strong>31 11<br />

termico <strong>3VF</strong>31 11<br />

2000 20000 — <strong>3VF</strong>83 12–2DM30–0AA0 —<br />

* Sganciatori di sovracorrente elettronici.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/19


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Tabelle di scelta e di ordinazione<br />

<strong>Interruttori</strong> <strong>3VF</strong> con protezione differenziale (Esecuzione U e<br />

= 415 V c.a.)<br />

<strong>Interruttori</strong> Corrente Regolazione Regolazione 3 poli e 4 poli Peso<br />

nominale corrente tempo di<br />

I n<br />

differenziale intervento t d<br />

3 poli 4 poli<br />

I∆ n<br />

t d<br />

Tipo A A 1) s kg kg<br />

<strong>3VF</strong>3 160 0,03 istantaneo <strong>3VF</strong>3 ...–...41–....–ZA01 2,8 ÷ 5,5 3,5<br />

0,1 0,06<br />

0,3 0,1<br />

0,5 0,25<br />

1,0 0,5<br />

3,0 1,0<br />

10<br />

30<br />

<strong>3VF</strong>4 250 <strong>3VF</strong>4 ...–...41–....–ZA01 5,2 6,7<br />

<strong>3VF</strong>5 400 <strong>3VF</strong>5 ...–...41–....–ZA01 6,7 ÷ 7,0 8,4<br />

Blocco di protezione differenziale (Alfanumerico solo per uso interno <strong>Siemens</strong>)<br />

Interruttore Tipo A U e<br />

= 415 V U e<br />

= 690 V<br />

3 p <strong>3VF</strong>93 25-1AA11 <strong>3VF</strong>93 25–1AB11<br />

<strong>3VF</strong>3 160<br />

4 p <strong>3VF</strong>93 25-1BA11 <strong>3VF</strong>93 25–1BB11<br />

3 p <strong>3VF</strong>94 25-1AA11 <strong>3VF</strong>94 25–1AB11<br />

<strong>3VF</strong>4 250<br />

4 p <strong>3VF</strong>94 25-1BA11 <strong>3VF</strong>94 25–1BB11<br />

3 p <strong>3VF</strong>95 25-1AA11 <strong>3VF</strong>95 25–1AB11<br />

<strong>3VF</strong>5 400<br />

4 p <strong>3VF</strong>95 25-1BA11 <strong>3VF</strong>95 25–1BB11<br />

Nota: il dispositivo differenziale deve essere sempre ordinato con l’interruttore. (Non è possibile il montaggio su interruttori da 25 kA).<br />

Nota: per l’ordinazione del blocco differenziale a 690 V specificare il rif. aggiuntivo ZA02<br />

1) La regolazione 30 mA può avere solamente un intervento istantaneo.<br />

1/20<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> - Gruppi di commutazione<br />

Introduzione<br />

Per assicurare l’affidabilità dell’impianto<br />

<strong>Siemens</strong> offre dei gruppi di commutazione<br />

già montati e cablati.<br />

Sono disponibili due principali tipi di comando:<br />

– Comando manuale<br />

– Comando motorizzato<br />

diverse esecuzioni:<br />

– fissa<br />

– rimovibile<br />

– sezionabile<br />

Gruppi di commutazione con comando manuale<br />

Il dispositivo è composto da un interblocco<br />

meccanico tra due interruttori della<br />

stessa grandezza costruttiva che permette<br />

la chiusura di uno solo degli interruttori<br />

e l’apertura di entrambi contemporaneamente.<br />

Il dispositivo di interblocco può essere fornito<br />

in esecuzione frontale o posteriore.<br />

Interblocco meccanico frontale:<br />

è realizzato tramite una barra metallica<br />

“snodata”; gli interruttori devono essere<br />

equipaggiati con un comando rinviato rotativo.<br />

Interblocco meccanico posteriore:<br />

è realizzato tramite una piastra di supporto<br />

munita di bilanciere ed è fornibile per i<br />

eseguenti interruttori:<br />

– <strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>3 fino a 225 A.<br />

– <strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>5 fino a 400 A.<br />

– <strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>6 fino a 630<br />

(800 A in esecuzione fissa).<br />

– <strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong>7 fino a 1250 A.<br />

Sono disponibili anche in esecuzione fissa,<br />

rimovibile e/o estraibile i tipi <strong>3VF</strong>3,<br />

<strong>3VF</strong>5 e <strong>3VF</strong>6, mentre in esecuzione fissa<br />

i <strong>3VF</strong>7.<br />

1<br />

Interblocco manuale frontale<br />

Tipo interruttore<br />

Interblocco<br />

Gruppi di commutazione con interblocco meccanico posteriore<br />

I gruppi di commutazione vengono forniti esclusivamente già<br />

montati presso la nostra fabbrica.<br />

<strong>3VF</strong>3 3VZ9 523 – 1VG20<br />

<strong>3VF</strong>4 3VZ9 523 – 1VG20<br />

<strong>3VF</strong>5 3VZ9 523 – 1VG20<br />

<strong>3VF</strong>6 3VZ9 723 – 1VG20<br />

<strong>3VF</strong>7 3VZ9 723 – 1VG20<br />

<strong>3VF</strong>8 3VZ9 823 – 1VG20<br />

Attenzione! Completare con comando rotativo<br />

disinnestabile bloccoporta.<br />

Esecuzione fissa 3 poli 4 poli<br />

<strong>3VF</strong>3 3VZ9 351 3VZ9 350<br />

<strong>3VF</strong>5 3VZ9 551 3VZ9 550<br />

<strong>3VF</strong>6 3VZ9 651 3VZ9 650<br />

<strong>3VF</strong>7 3VZ9 751 3VZ9 755<br />

Esecuzione rimovibile 3 poli 4 poli<br />

<strong>3VF</strong>3 allacciamento anteriore A richiesta A richiesta<br />

allacciamento posteriore A richiesta A richiesta<br />

<strong>3VF</strong>5 allacciamento anteriore A richiesta 3VZ9 550-1FA20<br />

allacciamento posteriore A richiesta 3VZ9 550-1FB20<br />

<strong>3VF</strong>6 allacciamento anteriore A richiesta 3VZ9 650-1FA20<br />

allacciamento posteriore A richiesta 3VZ9 650-1FB20<br />

Esecuzione estraibile 3 poli 4 poli<br />

<strong>3VF</strong>3 allacciamento anteriore A richiesta 3VZ9 350-1GA20<br />

allacciamento posteriore A richiesta 3VZ9 350-1GB20<br />

<strong>3VF</strong>5 allacciamento anteriore A richiesta A richiesta<br />

allacciamento posteriore A richiesta A richiesta<br />

<strong>3VF</strong>6 allacciamento anteriore A richiesta 3VZ9 650-1GA20<br />

allacciamento posteriore A richiesta 3VZ9 650-1GB20<br />

<strong>3VF</strong>7 allacciamento anteriore A richiesta 3VZ9 750-1GA20<br />

allacciamento posteriore A richiesta 3VZ9 750-1GB20<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/21


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> - Gruppi di commutazione<br />

Gruppi di commutazione motorizzati<br />

Il gruppo di commutazione con comando<br />

motorizzato è realizzabile soltanto utilizzando<br />

gli interruttori con interblocco meccanico<br />

posteriore per permettere il montaggio<br />

dei comandi a motore sul fronte<br />

degli interruttori; in ogni caso la manovra<br />

Comando a motore<br />

manuale è possibile agendo sulle manopole<br />

accessibili sul fronte dei comandi a<br />

motore.<br />

Per ricevere i gruppi di commutazione<br />

completi di comando a motore, è necessario<br />

aggiungere alla esecuzione non motorizzata,<br />

per ogni interruttore, almeno gli<br />

accessori riportati nella seguente tabella.<br />

Il gruppo di commutazione viene fornito<br />

già montato.<br />

<strong>3VF</strong>3<br />

<strong>3VF</strong>5<br />

<strong>3VF</strong>6<br />

<strong>3VF</strong>7<br />

<strong>3VF</strong>9 323-1N..0<br />

<strong>3VF</strong>9 523-1N..0<br />

<strong>3VF</strong>9 623-1N..0<br />

<strong>3VF</strong>9 723-1N..0<br />

Contatti ausiliari 1HS<br />

<strong>3VF</strong>3<br />

<strong>3VF</strong>5<br />

<strong>3VF</strong>6<br />

<strong>3VF</strong>7<br />

<strong>3VF</strong>9 322-1BB30<br />

<strong>3VF</strong>9 522-1BB30<br />

<strong>3VF</strong>9 622-1BB30<br />

<strong>3VF</strong>9 722-1BB30<br />

Contatti di allarme 1AS<br />

<strong>3VF</strong>3<br />

<strong>3VF</strong>5<br />

<strong>3VF</strong>6<br />

<strong>3VF</strong>7<br />

<strong>3VF</strong>9 322-1GB20<br />

<strong>3VF</strong>9 522-1GB20<br />

<strong>3VF</strong>9 622-1GB20<br />

<strong>3VF</strong>9 722-1GB20<br />

Dove richiesti: Blocco a chiave per comando<br />

a motore<br />

1/22<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong> - Commutazione automatica<br />

Dispositivo per la commutazione automatica<br />

<strong>Siemens</strong> offre un prodotto gestito da un PLC Simatic S7-200 che<br />

permette la commutazione automatica rete-emergenza.<br />

Non è necessaria una tensione di alimentazione ausiliaria, essendo<br />

il dispositivo connesso alla rete e/o al generatore.<br />

Sono riportate segnalazioni sullo stato degli interruttori e sullo<br />

stato di allarme.<br />

In caso di intervento degli interruttori, tramite il tasto di reset il<br />

gruppo può essere riportato alle condizioni iniziali.<br />

Questo interblocco è fornito già montato e testato e i circuiti ausiliari<br />

sono già cablati e numerati.<br />

Tramite un selettore è possibile impostare 4 modalità di funzionamento:<br />

– a commutazione automatica<br />

– con blocco della commutazione sull’alimentazione di rete primaria<br />

– con blocco della commutazione sull’alimentazione di emergenza<br />

– manuale con possibilità di comando manuale degli interruttori<br />

La commutazione automatica, dall’alimentazione normale di linea<br />

a quella di emergenza, avviene al mancare della tensione<br />

della rete primaria dopo il tempo “Ta=5s” preimpostato sull’automatismo.<br />

Prima del passaggio all’alimentazione di emergenza l’automatismo<br />

attende il segnale di conferma di avvenuto avviamento<br />

“gruppo” proveniente dalla sorgente. Specificare in fase di ordinazione<br />

il tipo di sorgente di alimentazione di emergenza.<br />

Al ritorno della tensione sull’alimentazione di rete primaria, dopo<br />

il tempo “Tb=1s” preimpostato, avviene il passaggio dall’alimentazione<br />

di emergenza a quella normale di linea.<br />

Agendo opportunamente sul software del PLC è possibile modificare<br />

i suddetti tempi variando i valori preimpostati nei temporizzatori<br />

“TON”:<br />

T38=Ta=5s (commutazione rete/emergenza)<br />

T40=Tb=1s (commutazione emergenza/rete)<br />

da 0,01s a 3200s.<br />

È possibile collegare all’automatismo un pannello operatore (ordinabile<br />

a richiesta) per l’impostazione e per la gestione a distanza<br />

dei segnali disponibili in uscita dallo stesso.<br />

Tensione nominale U n<br />

415 V c.a.<br />

Alimentazione ausiliaria dell’automatismo 24 V c.c.<br />

Tensione di alimentazione per comando dei motori 220 V c.a<br />

1<br />

Per la realizzazione del gruppo di commutazione rete-emergenza completo di dispositivo automatico sono necessari i seguenti componenti:<br />

1)Gruppo di commutazione motorizzato.<br />

2)Dispositivo per la commutazione automatica:<br />

– Per gruppi di commutazione realizzati con interruttori <strong>3VF</strong>3, <strong>3VF</strong>5, <strong>3VF</strong>6, dispositivo tipo 3VZ9 788–2A<br />

– Per gruppi di commutazione realizzati con interruttori <strong>3VF</strong>7, dispositivo tipo 3VZ9 788–1A.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/23


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Accessori<br />

Bobina di minima tensione<br />

Bobina a lancio di corrente<br />

Con Con Con Con<br />

cavi morsetti cavi morsetti<br />

<strong>3VF</strong>3 (160 - 225 A) 9 ÷ 12 V c.a. <strong>3VF</strong>9 321-1B B10 –1C B10 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 321-1H C10 –1J C10<br />

24 V c.a. <strong>3VF</strong>9 321-1B D10 –1C D10 48 ÷ 127 V c.a. 48 ÷ 60 V c.c. <strong>3VF</strong>9 321-1H G10 –1J G10<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 321-1B F10 –1C F10 110 ÷ 240 V c.a. 110 ÷ 125 V c.c. <strong>3VF</strong>9 321-1H K10 –1J K10<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 321-1B G10 –1C G10 380 ÷ 600 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 321-1H T10 –1J T10<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 321-1B H10 –1C H10<br />

380 ÷ 480 V c.a. <strong>3VF</strong>9 321-1B K10 –1C K10<br />

480 ÷ 525 V c.a. <strong>3VF</strong>9 321-1B L10 –1C L10<br />

12 V c.c. <strong>3VF</strong>9 321-1B N10 –1C N10<br />

24 V c.c. <strong>3VF</strong>9 321-1B P10 –1C P10<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 321-1B Q10 –1C Q10<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 321-1B R10 –1C R10<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 321-1B S10 –1C S10<br />

<strong>3VF</strong>4 (250 A)<br />

12 V c.a. <strong>3VF</strong>9 421-1B C10 –1C C10 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 421-1H C10 –1J C10<br />

24 V c.a. <strong>3VF</strong>9 421-1B D10 –1C D10 48 ÷ 60 V c.a. 48 ÷ 60 V c.c. <strong>3VF</strong>9 421-1H J10 –1J J10<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 421-1B F10 –1C F10 110 ÷ 240 V c.a. 110 ÷ 125 V c.c. <strong>3VF</strong>9 421-1H K10 –1J K10<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 421-1B G10 –1C G10 380 ÷ 440 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 421-1H S10 –1J S10<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 421-1B H10 –1C H10 480 ÷ 600 V c.a. — <strong>3VF</strong>9 421-1H V10 –1J V10<br />

380 ÷ 500 V c.a. <strong>3VF</strong>9 421-1B J10 –1C J10<br />

12 V c.c. <strong>3VF</strong>9 421-1B N10 –1C N10<br />

24 V c.c. <strong>3VF</strong>9 421-1B P10 –1C P10<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 421-1B Q10 –1C Q10<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 421-1B R10 –1C R10<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 421-1B S10 –1C S10<br />

<strong>3VF</strong>5 (400 A) 12 V c.a. <strong>3VF</strong>9 521-1B C10 –1C C10 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 521-1H C10 –1J C10<br />

24 V c.a. <strong>3VF</strong>9 521-1B D10 –1C D10 48 ÷ 60 V c.a. 48 ÷ 60 V c.c. <strong>3VF</strong>9 521-1H J10 –1J J10<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 521-1B F10 –1C F10 110 ÷ 240 V c.a. 110 ÷ 125 V c.c. <strong>3VF</strong>9 521-1H K10 –1J K10<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 521-1B G10 –1C G10 380 ÷ 600 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 521-1H S10 –1J S10<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 521-1B H10 –1C H10 480 ÷ 600 V c.a. <strong>3VF</strong>9 521-1H V10 –1J V10<br />

380 ÷ 500 V c.a. <strong>3VF</strong>9 521-1B J10 –1C J10<br />

12 V c.c. <strong>3VF</strong>9 521-1B N10 –1C N10<br />

24 V c.c. <strong>3VF</strong>9 521-1B P10 –1C P10<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 521-1B Q10 –1C Q10<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 521-1B R10 –1C R10<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 521-1B S10 –1C S10<br />

<strong>3VF</strong>6 (800 A) 12 V c.a. <strong>3VF</strong>9 621-1B C10 –1C C10 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 621-1H C10 –1J C10<br />

24 V c.a. <strong>3VF</strong>9 621-1B D10 –1C D10 48 ÷ 60 V c.a. — <strong>3VF</strong>9 621-1H F10 –1J F10<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 521-1B F10 –1C F10 — 48 ÷ 60 V c.c. <strong>3VF</strong>9 621-1H H10 –1J H10<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 621-1B G10 –1C G10 — 110 ÷ 125 V c.c. <strong>3VF</strong>9 621-1H L10 –1J L10<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 621-1B H10 –1C H10 110 ÷ 240 V c.a. — <strong>3VF</strong>9 621-1H M10 –1J M10<br />

380 ÷ 500 V c.a. <strong>3VF</strong>9 621-1B J10 –1C J10 380 ÷ 440 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 621-1H S10 –1J S10<br />

480 ÷ 600 V c.a. — <strong>3VF</strong>9 621-1H V10 –1J V10<br />

12 V c.c. <strong>3VF</strong>9 621-1B N10 –1C N10<br />

24 V c.c. <strong>3VF</strong>9 621-1B P10 –1C P10<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 621-1B Q10 –1C Q10<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 621-1B R10 –1C R10<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 621-1B S10 –1C S10<br />

<strong>3VF</strong>7 (1250 A) 12 V c.a. <strong>3VF</strong>9 721-1B C10 –1C C10 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 721-1H C10 –1J C10<br />

24 V c.a. <strong>3VF</strong>9 721-1B D10 –1C D10 48 ÷ 60 V c.a. — <strong>3VF</strong>9 721-1H F10 –1J F10<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 721-1B F10 –1C F10 — 48 ÷ 60 V c.c. <strong>3VF</strong>9 721-1H H10 –1J H10<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 721-1B G10 –1C G10 — 110 ÷ 125 V c.c. <strong>3VF</strong>9 721-1H L10 –1J L10<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 721-1B H10 –1C H10 110 ÷ 240 V c.a. — <strong>3VF</strong>9 721-1H M10 –1J M10<br />

380 ÷ 500 V c.a. <strong>3VF</strong>9 721-1B J10 –1C J10 380 ÷ 440 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 721-1H S10 –1J S10<br />

480 ÷ 600 V c.a. — <strong>3VF</strong>9 721-1H V10 –1J V10<br />

12 V c.c. <strong>3VF</strong>9 721-1B N10 –1C N10<br />

24 V c.c. <strong>3VF</strong>9 721-1B P10 –1C P10<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 721-1B Q10 –1C Q10<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 721-1B R10 –1C R10<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 721-1B S10 –1C S10<br />

<strong>3VF</strong>8 (2500 A) 12 V c.a. <strong>3VF</strong>9 821-1B C40 12 ÷ 24 V c.a. 12 ÷ 24 V c.c. <strong>3VF</strong>9 821-1H C40<br />

24 V c.a. <strong>3VF</strong>9 821-1B D40 48 ÷ 60 V c.a. — <strong>3VF</strong>9 821-1H F40<br />

48 ÷ 60 V c.a. <strong>3VF</strong>9 821-1B F40 — 48 ÷ 60 V c.c. <strong>3VF</strong>9 821-1H H40<br />

110 ÷ 127 V c.a. <strong>3VF</strong>9 821-1B G40 — 110 ÷ 125 V c.c. <strong>3VF</strong>9 821-1H L40<br />

208 ÷ 240 V c.a. <strong>3VF</strong>9 821-1B H40 110 ÷ 240 V c.a. — <strong>3VF</strong>9 821-1H M40<br />

380 ÷ 500 V c.a. <strong>3VF</strong>9 821-1B J40 380 ÷ 440 V c.a. 220 ÷ 250 V c.c. <strong>3VF</strong>9 821-1H S40<br />

480 ÷ 600 V c.a. — <strong>3VF</strong>9 821-1H V40<br />

12 V c.c. <strong>3VF</strong>9 821-1B N40<br />

24 V c.c. <strong>3VF</strong>9 821-1B P40<br />

48 ÷ 60 V c.c. <strong>3VF</strong>9 821-1B Q40<br />

110 ÷ 127 V c.c. <strong>3VF</strong>9 821-1B R40<br />

220 ÷ 250 V c.c. <strong>3VF</strong>9 821-1B S40<br />

1/24<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Contatti ausiliari Comando a motore lucchettabile 1)<br />

Con<br />

cavi<br />

Con<br />

morsetti<br />

1HS <strong>3VF</strong>9 322-1BB30 —<br />

<strong>3VF</strong>9 322<br />

montaggio a destra<br />

1HS 2) <strong>3VF</strong>9 322-1BB40 2) –<br />

1HS <strong>3VF</strong>9 322— -1BC20<br />

2HS <strong>3VF</strong>9 322-1CB20 -1CC20<br />

1AS<br />

<strong>3VF</strong>9 322-1GB20 -1GC20<br />

1AS <strong>3VF</strong>9 322-1GF20 4) —<br />

1HS+1AS 5) <strong>3VF</strong>9 322-1NB20 -1NC20<br />

montaggio a sinistra<br />

1HS <strong>3VF</strong>9 322— -1BC10<br />

2HS <strong>3VF</strong>9 322-1CB10 -1CC10<br />

1AS<br />

<strong>3VF</strong>9 322-1GB10 -1GC10<br />

2AS <strong>3VF</strong>9 422-1HB10 -1HC10<br />

1HS+1AS <strong>3VF</strong>9 322-1NB10 -1NC10<br />

1HS <strong>3VF</strong>9 422-1BB30 —<br />

2HS <strong>3VF</strong>9 422-1CB30 —<br />

montaggio a destra<br />

1HS <strong>3VF</strong>9 422— -1BC20<br />

2HS <strong>3VF</strong>9 422— -1CC20<br />

1AS<br />

<strong>3VF</strong>9 422-1GB20 -1GC20<br />

1HS+1AS 5) <strong>3VF</strong>9 422-1NB20 -1NC20<br />

montaggio a sinistra<br />

1AS<br />

<strong>3VF</strong>9 522-1GB10 -1GC10<br />

<strong>3VF</strong>9 522<br />

c.a. 3) c.c.<br />

— 24 V <strong>3VF</strong>9 323-1NA20<br />

42 V 48 V -1NB10<br />

— 60 V -1NC20<br />

110/127 V 110/127 V -1ND10<br />

220/240 V 220 V -1NE10<br />

Comando a solenoide<br />

c.a. 3) c.c.<br />

110/120 V — <strong>3VF</strong>9 323-1SD30<br />

220/240 V — -1SE30<br />

— 110/120 V -1SD20<br />

— 220/240 V -1SE20<br />

c.a. 3) c.c.<br />

— 24 V <strong>3VF</strong>9 423-1NA20<br />

42 V 48 V -1NB10<br />

— 60 V -1NC20<br />

110/127 V 110/127 V -1ND10<br />

220/240 V 220 V -1NE10<br />

1<br />

1HS <strong>3VF</strong>9 522-1BB30 —<br />

2HS <strong>3VF</strong>9 522-1CB30 —<br />

montaggio a destra<br />

1HS <strong>3VF</strong>9 522— -1BC20<br />

2HS 6) <strong>3VF</strong>9 522— -1CC20<br />

1AS<br />

<strong>3VF</strong>9 522-1GB20 -1GC20<br />

1HS+1AS 5) <strong>3VF</strong>9 522-1NB20 -1NC20<br />

montaggio a sinistra<br />

1AS<br />

<strong>3VF</strong>9 522-1GB10 -1GC10<br />

2AS <strong>3VF</strong>9 422-1HB10 -1HC10<br />

c.a. 3) c.c.<br />

— 24 V <strong>3VF</strong>9 523-1NA20<br />

42 V 48 V -1NB10<br />

— 60 V -1NC20<br />

110/127 V 110/127 V -1ND10<br />

220/240 V 220 V -1NE10<br />

1HS <strong>3VF</strong>9 622-1BB30 —<br />

2HS <strong>3VF</strong>9 622-1CB30 —<br />

montaggio a destra<br />

1HS <strong>3VF</strong>9 622— -1BC20<br />

2HS <strong>3VF</strong>9 622— -1CC20<br />

1AS<br />

<strong>3VF</strong>9 622-1GB20 -1GC20<br />

1HS+1AS 5) <strong>3VF</strong>9 622-1NB20 -1NC20<br />

montaggio a sinistra<br />

1AS<br />

<strong>3VF</strong>9 622-1GB10 -1GC10<br />

2AS <strong>3VF</strong>9 622-1HB10 -1HC10<br />

c.a. 3) c.c.<br />

— 24 V <strong>3VF</strong>9 623-1NA20<br />

42 V 48 V -1NB10<br />

— 60 V -1NC20<br />

110/127 V 110/127 V -1ND10<br />

220/240 V 220 V -1NE10<br />

montaggio a destra<br />

1HS <strong>3VF</strong>9 722-1BB30 -1BC20<br />

2HS <strong>3VF</strong>9 722-1CB30 -1CC20<br />

1AS<br />

<strong>3VF</strong>9 722-1GB20 -1GC20<br />

1HS+1AS 5) <strong>3VF</strong>9 722-1NB20 -1NC20<br />

montaggio a sinistra<br />

1AS<br />

<strong>3VF</strong>9 722-1GB10 -1GC10<br />

2AS <strong>3VF</strong>9 722-1HB10 -1HC10<br />

<strong>3VF</strong>9 722<br />

c.a. 3)<br />

c.c.<br />

— 48 V <strong>3VF</strong>9 723-1NB20<br />

110/125 V -1ND20<br />

110/127 V -1ND30<br />

220/240 V -1NE30<br />

montaggio a destra<br />

4HS <strong>3VF</strong>9 822-1EB40 —<br />

2AS <strong>3VF</strong>9 822-1HB40 —<br />

c.a. 3) c.c.<br />

— 48 V <strong>3VF</strong>9 833-1NB20<br />

110/127 V -1ND30<br />

220/240 V -1NE30<br />

HS = Contatto segnalazione dello stato dell’interruttore<br />

AS = Contatto segnalazione intervento dell’interruttore<br />

1) A richiesta sono fornibili per gli interruttori <strong>3VF</strong>4, 5,<br />

6 comandi a motore con tempi di manovra ridotti<br />

<strong>3VF</strong>9.23-1Q. Leva per comando locale a richiesta, tipo<br />

<strong>3VF</strong>96 23–1WB00.<br />

2) 1HS destro per <strong>3VF</strong>3 3 poli esecuzioni per protezione<br />

motori. Fornibili dal 3/96.<br />

3) Per Vc.a. 50/60 Hz.<br />

4) Solo per <strong>3VF</strong>3 4P montaggio Dx.<br />

5) Solo per esecuzione <strong>3VF</strong>. 3 Poli.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/25


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Accessori<br />

<strong>3VF</strong>3 (225 A)<br />

Attacchi posteriori Attacchi anteriori Calotte coprimorsetti IP3X Mostrina frontale<br />

a sbarra<br />

3 Poli (3 pezzi) 3 Poli (3 pezzi) 3 Poli (1 confezione = 1 coppia) Per interruttore standard<br />

<strong>3VF</strong>9324-1LD10 <strong>3VF</strong>9324-1JA10 <strong>3VF</strong>9324-1NB10 <strong>3VF</strong>9320-1AA00<br />

Per interruttore differenziale<br />

4 Poli (4 pezzi) 4 Poli (4 pezzi) 4 Poli (1 confezione = 1 coppia) <strong>3VF</strong>9320-1AB00<br />

<strong>3VF</strong>9324-1LD20 <strong>3VF</strong>9324-1JA20 <strong>3VF</strong>9324-1NB20 Mostrina cieca standard<br />

<strong>3VF</strong>9420-1AA10<br />

Piatta 3 Poli (1 conf. = 1 coppia) Mostrina cieca per differenziale<br />

3VZ9324-1LB10<br />

<strong>3VF</strong>9520-1AB10<br />

Piatta 4 Poli (1 conf. = 1 coppia) Mostrina per comando motore<br />

3VZ9324-1LB20<br />

3VZ9627-8NE00<br />

<strong>3VF</strong>4 (250 A) 3 Poli (3 pezzi) 3 Poli (3 pezzi) 3 Poli (1 confezione = 1 coppia) Per interruttore standard<br />

<strong>3VF</strong>9424-1LD10 <strong>3VF</strong>9424-1JA10 <strong>3VF</strong>9424-1NB10 <strong>3VF</strong>9420-1AA00<br />

4 Poli (4 pezzi) 4 Poli (4 pezzi) 4 Poli (1 confezione = 1 coppia) Per interruttore differenziale<br />

<strong>3VF</strong>9424-1LD20 <strong>3VF</strong>9424-1JA20 <strong>3VF</strong>9424-1NB20 <strong>3VF</strong>9420-1AB00<br />

Piatta 3 Poli (1 conf. = 1 coppia)<br />

3VZ9424-1LB10<br />

Piatta 4 Poli (1 conf. = 1 coppia)<br />

3VZ9424-1LB20<br />

Mostrina cieca standard<br />

<strong>3VF</strong>9420-1AA10<br />

Mostrina cieca per differenziale<br />

<strong>3VF</strong>9520-1AB10<br />

Mostrina per comando motore<br />

3VZ9627-8NE00<br />

<strong>3VF</strong>5 (400 A) 3 Poli (3 pezzi) 3 Poli (3 pezzi) 3 Poli (1 confezione = 1 coppia) Per interruttore standard<br />

<strong>3VF</strong>9524-1LD10 <strong>3VF</strong>9524-1JA10 <strong>3VF</strong>9524-1NB10 <strong>3VF</strong>9520-1AA00<br />

4 Poli (4 pezzi) 4 Poli (4 pezzi) 4 Poli (1 confezione = 1 coppia) Per interruttore differenziale<br />

<strong>3VF</strong>9524-1LD20 <strong>3VF</strong>9524-1JA20 <strong>3VF</strong>9524-1NB20 <strong>3VF</strong>9520-1AB00<br />

Mostrina cieca standard<br />

<strong>3VF</strong>9720-1AA10<br />

Mostrina cieca per differenziale<br />

<strong>3VF</strong>9520-1AB10<br />

Mostrina per comando motore<br />

3VZ9627-8NE00<br />

<strong>3VF</strong>6 (800 A) 3 Poli (3 pezzi) 3 Poli 3 Poli (1 confezione = 1 coppia) Per interruttore standard<br />

<strong>3VF</strong>9624-1LD10 di serie <strong>3VF</strong>9624-1NB10 <strong>3VF</strong>9620-1AA00<br />

4 Poli (4 pezzi) 4 Poli 4 Poli (1 confezione = 1 coppia) Per interruttore in esecuzione<br />

<strong>3VF</strong>9624-1LD20 di serie <strong>3VF</strong>9624-1NB20 estraibile<br />

<strong>3VF</strong>9720-1AC10<br />

Mostrina cieca standard<br />

<strong>3VF</strong>9720-1AA10<br />

Mostrina per comando motore<br />

3VZ9627-8NE00<br />

<strong>3VF</strong>7 (1250 A) 3 Poli (3 pezzi) 3 Poli (3 pezzi) Per interruttore standard<br />

<strong>3VF</strong>9724-1LD10 <strong>3VF</strong>9724-1JA10 — <strong>3VF</strong>9720-1AA00<br />

4 Poli (4 pezzi) 4 Poli (4 pezzi) Per interruttore in esecuzione<br />

<strong>3VF</strong>9724-1LD20 <strong>3VF</strong>9724-1JA20 estraibile<br />

<strong>3VF</strong>9720-1AC10<br />

Mostrina cieca standard<br />

<strong>3VF</strong>9720-1AA10<br />

<strong>3VF</strong>8 (2500 A) 3 Poli (3 pezzi) 3 Poli (3 pezzi) Per interruttore standard<br />

<strong>3VF</strong>9824-1LD10 <strong>3VF</strong>9824-1JA10 1) — <strong>3VF</strong>9820-1AA00<br />

4 Poli (4 pezzi) 4 Poli (4 pezzi)<br />

<strong>3VF</strong>9824-1LD20 <strong>3VF</strong>9824-1JA20 1)<br />

1) Per <strong>3VF</strong>8 3 e 4 poli fino a 2000 A<br />

1/26<br />

<strong>Siemens</strong> - Distribuzione dell’energia


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Per esecuzione rimovibile Per esecuzione estraibile Connettore<br />

per condutt. aux<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

att. ant. differenziale<br />

att. post. differenziale<br />

<strong>3VF</strong>9324-1FA10<br />

-1FB10<br />

<strong>3VF</strong>9324-1FE10<br />

-1FF10<br />

<strong>3VF</strong>9324-1FA20<br />

-1FB20<br />

<strong>3VF</strong>9324-1FE20<br />

-1FF20<br />

<strong>3VF</strong>9424-1FA10<br />

-1FB10<br />

<strong>3VF</strong>9424-1FE10<br />

-1FF10<br />

<strong>3VF</strong>9424-1FA20<br />

-1FB20<br />

<strong>3VF</strong>9424-1FE20<br />

-1FF20<br />

<strong>3VF</strong>9524-1FA10<br />

-1FB10<br />

<strong>3VF</strong>9524-1FE10<br />

-1FF10<br />

<strong>3VF</strong>9524-1FA20<br />

-1FB20<br />

<strong>3VF</strong>9524-1FE20<br />

-1FF20<br />

PARTE FISSA A 3 POLI 1)<br />

attacchi anteriori <strong>3VF</strong>9624-1FA10<br />

attacchi posteriori<br />

-1FB10<br />

PARTE FISSA A 4 POLI 1)<br />

attacchi anteriori <strong>3VF</strong>9624-1FA20<br />

attacchi posteriori<br />

-1FB20<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori 3VZ9324-1GA10<br />

attacchi posteriori<br />

-1GB10<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori 3VZ9324-1GA20<br />

attacchi posteriori<br />

-1GB20<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori 3VZ9524-1GA10<br />

attacchi posteriori<br />

-1GB10<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori 3VZ9524-1GA20<br />

attacchi posteriori<br />

-1GB20<br />

PARTE FISSA A 3 POLI 1)<br />

attacchi anteriori <strong>3VF</strong>9624-1GA10<br />

attacchi posteriori<br />

-1GB10<br />

PARTE FISSA A 4 POLI 1)<br />

attacchi anteriori <strong>3VF</strong>9624-1GA20<br />

attacchi posteriori<br />

-1GB20<br />

PARTE FISSA A 3 POLI<br />

attacchi anteriori <strong>3VF</strong>9724-1GA10<br />

attacchi posteriori<br />

-1GB10<br />

Montaggio laterale<br />

<strong>3VF</strong>9624-1VA40<br />

Connettori aggiun.<br />

per montaggio lat.<br />

<strong>3VF</strong>9624-1VJ40<br />

Montaggio centrale<br />

—<br />

Connettore<br />

separato 8 poli<br />

<strong>3VF</strong>9624-1VA30<br />

Montaggio laterale<br />

<strong>3VF</strong>9624-1VA40<br />

Connettori aggiun.<br />

per montaggio lat.<br />

<strong>3VF</strong>9624-1VJ40<br />

Montaggio centrale<br />

<strong>3VF</strong>9524-1VA50<br />

Connettori aggiun.<br />

per montaggio cen.<br />

<strong>3VF</strong>9624-1VJ50<br />

Connettore<br />

separato 8 poli<br />

<strong>3VF</strong>9624-1VA30<br />

Montaggio laterale<br />

<strong>3VF</strong>9624-1VA40<br />

Connettori aggiun.<br />

per montaggio lat.<br />

<strong>3VF</strong>9624-1VJ40<br />

Montaggio centrale<br />

<strong>3VF</strong>9524-1VA50<br />

Connettori aggiun.<br />

per montaggio cen.<br />

<strong>3VF</strong>9624-1VJ50<br />

Connettore<br />

separato 8 poli<br />

<strong>3VF</strong>9624-1VA30<br />

Montaggio laterale<br />

<strong>3VF</strong>9624-1VA40<br />

Connettori aggiun.<br />

per montaggio lat.<br />

<strong>3VF</strong>9624-1VJ40<br />

Montaggio centrale<br />

<strong>3VF</strong>9624-1VA50<br />

Connettori aggiun.<br />

per montaggio cen.<br />

<strong>3VF</strong>9624-1VJ50<br />

Connettore<br />

separato 8 poli<br />

<strong>3VF</strong>9624-1VA30<br />

1<br />

PARTE FISSA A 4 POLI<br />

attacchi anteriori<br />

attacchi posteriori<br />

<strong>3VF</strong>9724-1GA20<br />

-1GB20<br />

Montaggio centrale<br />

<strong>3VF</strong>9724-1VA50<br />

Montaggio laterale<br />

<strong>3VF</strong>9624-1VA40<br />

Connettore 24 poli<br />

per conduttori<br />

ausiliari<br />

<strong>3VF</strong>9824-1UA00<br />

1) Max 630 A.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/27


<strong>Interruttori</strong> <strong>automatici</strong> <strong>3VF</strong><br />

Accessori<br />

Altri accessori<br />

<strong>3VF</strong>3 (225 A) Prolunga della leva di comando —<br />

Dispositivo lucchettabile<br />

<strong>3VF</strong>9323-1VC00<br />

per la leva dell’interruttore<br />

Separatore di fasi<br />

<strong>3VF</strong>9324-1RA10<br />

(1 confezione = 1 coppia)<br />

<strong>3VF</strong>4 (250 A) Prolunga della leva di comando <strong>3VF</strong>9523-1VB00<br />

Dispositivo lucchettabile<br />

<strong>3VF</strong>9523-1VC00<br />

per la leva dell’interruttore<br />

Separatore di fasi<br />

<strong>3VF</strong>9524-1RA10<br />

(1 confezione = 1 coppia)<br />

<strong>3VF</strong>5 (400 A) Prolunga della leva di comando <strong>3VF</strong>9523-1VB00<br />

Dispositivo lucchettabile<br />

<strong>3VF</strong>9523-1VC00<br />

per la leva dell’interruttore<br />

Separatore di fasi<br />

<strong>3VF</strong>9524-1RA10<br />

(1 confezione = 1 coppia)<br />

<strong>3VF</strong>6 (800 A) Prolunga della leva di comando <strong>3VF</strong>9623-1VB00<br />

Dispositivo lucchettabile<br />

<strong>3VF</strong>9623-1VC00<br />

per la leva dell’interruttore<br />

Separatore di fasi<br />

<strong>3VF</strong>9624-1RA10<br />

(1 confezione = 1 coppia)<br />

Blocco a chiave per carrello<br />

3VZ9724-1VR00<br />

(esec. estraibile)<br />

Contatti di segnalazione per carrello<br />

<strong>3VF</strong>9624-1VL60<br />

inserito-estratto (esec. estraibile)<br />

<strong>3VF</strong>7 (1250 A) Prolunga della leva di comando Di serie<br />

Dispositivo lucchettabile<br />

<strong>3VF</strong>9723-1VC00<br />

per la leva dell’interruttore<br />

Separatore di fasi<br />

<strong>3VF</strong>9724-1RA10<br />

(1 confezione = 1 coppia)<br />

Blocco a chiave per carrello<br />

3VZ9724-1VR00<br />

(esec. estraibile)<br />

Contatti di segnalazione per carrello<br />

<strong>3VF</strong>9724-1VL60<br />

inserito-estratto (esec. estraibile)<br />

<strong>3VF</strong>8 (2500 A)<br />

Prolunga della leva di comando<br />

Di serie<br />

Dispositivo lucchettabile —<br />

per la leva dell’interruttore<br />

Separatore di fasi —<br />

1/28<br />

<strong>Siemens</strong> - Distribuzione dell’energia


Comandi frontali rotativi<br />

Descrizione<br />

Comandi frontali rotativi per manovre dirette<br />

sull’interruttore.<br />

Sono previste le esecuzioni normali e di<br />

emergenza, con o senza contatti anticipati<br />

all’apertura e alla chiusura lucchettabile<br />

max con 3 lucchetti.<br />

1<br />

Tabelle di scelta e di ordinazione<br />

Esecuzione Esecuzione Esecuzione normale Esecuzione Esecuzione Esecuzione<br />

normale IP 54 normale IP 54 IP 54 con contatti di emergenza IP 54 di emergenza IP 54 di emergenza<br />

Tipo In senza contatti con contatti ausiliari anticipati senza contatti con contatti IP 54 con contatti<br />

ausiliari ausiliari anticipati 3) all’apertura ausiliari ausiliari anticipati 3) anticipati<br />

A alla chiusura alla chiusura all’apertura<br />

Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione<br />

<strong>3VF</strong>3 160 <strong>3VF</strong>9 323–1AA00 <strong>3VF</strong>9 323–1AB00 <strong>3VF</strong>9 323–1AD00 <strong>3VF</strong>9 323–1BA00 <strong>3VF</strong>9 323–1BB00 <strong>3VF</strong>9 323–1BD00<br />

<strong>3VF</strong>4 250 <strong>3VF</strong>9 423–1AA00 <strong>3VF</strong>9 423–1AB00 <strong>3VF</strong>9 423–1AD00 <strong>3VF</strong>9 423–1BA00 <strong>3VF</strong>9 423–1BB00 <strong>3VF</strong>9 423–1BD00<br />

<strong>3VF</strong>5 400 <strong>3VF</strong>9 523–1AA00 <strong>3VF</strong>9 523–1AB00 <strong>3VF</strong>9 523–1AD00 <strong>3VF</strong>9 523–1BA00 <strong>3VF</strong>9 523–1BB00 <strong>3VF</strong>9 523–1BD00<br />

<strong>3VF</strong>6 800 <strong>3VF</strong>9 623–1AA00 <strong>3VF</strong>9 623–1AB00 <strong>3VF</strong>9 623–1AD00 <strong>3VF</strong>9 623–1BA00 <strong>3VF</strong>9 623–1BB00 <strong>3VF</strong>9 623–1BD00<br />

<strong>3VF</strong>7 1250 <strong>3VF</strong>9 723–1AA00 <strong>3VF</strong>9 723–1AB00 <strong>3VF</strong>9 723–1AD00 <strong>3VF</strong>9 723–1BA00 <strong>3VF</strong>9 723–1BB00 <strong>3VF</strong>9 723–1BD00<br />

<strong>3VF</strong>8 2500 <strong>3VF</strong>9 823–1AA01 <strong>3VF</strong>9 823–1AB01 <strong>3VF</strong>9 823–1AD01 <strong>3VF</strong>9 823–1BA01 <strong>3VF</strong>9 823–1BB01 <strong>3VF</strong>9 823–1BD01<br />

Comando frontale rotativo completo di dispositivo di blocco a chiave<br />

Nel comando rotativo tipo:<br />

3VZ9.23–1VA00<br />

il dispositivo di blocco a chiave è composto<br />

da una serratura tipo AREL 1) inserita<br />

nei comandi rotativi diretti. Il blocco viene<br />

effettuato in condizioni di interruttore<br />

aperto 2) .<br />

Tabelle di scelta e di ordinazione • Blocchi a chiave<br />

Per interruttore Comando frontale rotativo Dispositivo di blocco Dispositivo di blocco<br />

completo di dispositivo di blocco a chiave a chiave per comando rinviato a chiave per comando motore<br />

Tipo Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione<br />

<strong>3VF</strong>3 – – –<br />

<strong>3VF</strong>4 3VZ9 423–1VA00 – –<br />

<strong>3VF</strong>5 3VZ9 523–1VA00 – 3VZ0 960–1CH<br />

<strong>3VF</strong>6 3VZ9 623–1VA00 3VZ9 823–1BC00 3VZ0 960–1CH<br />

<strong>3VF</strong>7 3VZ9 723–1VA00 3VZ9 823–1BC00 3VZ0 970–1CH<br />

<strong>3VF</strong>8 3VZ9 823–1VA00 3VZ9 823–1BC00 –<br />

1) Per richiedere più dispositivi con serrature diverse<br />

segnalare in fase di ordinazione.<br />

2) In condizioni di chiuso è a richiesta. 3) A richiesta esecuzione con morsettiera.<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/29


Comandi rinviati rotativi disinnestabili bloccoporta per interruttori<br />

<strong>automatici</strong><br />

Comandi<br />

Norme-Prescrizioni<br />

I comandi sono conformi alle norme: VDE<br />

0113 (tipo B) - VDE 0660-500 - IEC 408 -<br />

IEC 204-1 (tipo B) - BS - NFC - SUVA<br />

Comando tipo B<br />

Tolleranza nel centraggio dell’elemento<br />

disinnestabile con la maniglia sulla porta.<br />

Leva di comando lucchettabile.<br />

Esecuzione con albero di prolunga I = 300 mm / 600 mm<br />

Comando in materiale isolante<br />

Protezione IP 65<br />

Esecuzioni: normale (maniglia nera con<br />

fondo argento)<br />

emergenza (maniglia rossa<br />

su fondo giallo)<br />

secondo IEC 204-1<br />

Esecuzione con contatti ausiliari anticipati<br />

per interruttori <strong>automatici</strong> con sganciatore<br />

di minima tensione per la rispondenza alle<br />

norme VDE 0113 degli equipaggiamenti<br />

elettrici delle macchine utensili.<br />

Tabelle di scelta e di ordinazione<br />

Esecuzione Esecuzione Esecuzione Esecuzione Esecuzione Esecuzione Albero<br />

normale normale normale di emergenza di emergenza di emergenza <br />

Tipo In senza contatti con contatti con contatti senza contatti con contatti con contatti<br />

ausiliari ausiliari anticipati ausiliari anticipati ausiliari ausiliari anticipati ausiliari anticipati<br />

A alla chiusura alla apertura alla chiusura alla apertura<br />

Tipo B IP65 Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione Nr. di ordinazione mm<br />

<strong>3VF</strong>3 160 <strong>3VF</strong>9 323–1EA00 <strong>3VF</strong>9 323–1EB00 <strong>3VF</strong>9 323–1ED00 <strong>3VF</strong>9 323–1FA00 <strong>3VF</strong>9 323–1FB00 <strong>3VF</strong>9 323–1FD00 8<br />

<strong>3VF</strong>4 250 <strong>3VF</strong>9 423–1EA00 <strong>3VF</strong>9 423–1EB00 <strong>3VF</strong>9 423–1ED00 <strong>3VF</strong>9 423–1FA00 <strong>3VF</strong>9 423–1FB00 <strong>3VF</strong>9 423–1FD00 8<br />

<strong>3VF</strong>5 400 <strong>3VF</strong>9 523–1EA00 <strong>3VF</strong>9 523–1EB00 <strong>3VF</strong>9 523–1ED00 <strong>3VF</strong>9 523–1FA00 <strong>3VF</strong>9 523–1FB00 <strong>3VF</strong>9 523–1FD00 8<br />

<strong>3VF</strong>6 630 <strong>3VF</strong>9 623–1EA00 <strong>3VF</strong>9 623–1EB00 <strong>3VF</strong>9 623–1ED00 <strong>3VF</strong>9 623–1FA00 <strong>3VF</strong>9 623–1FB00 <strong>3VF</strong>9 623–1FD00 12<br />

<strong>3VF</strong>7 1250 <strong>3VF</strong>9 723–1EA00 <strong>3VF</strong>9 723–1EB00 <strong>3VF</strong>9 723–1ED00 <strong>3VF</strong>9 723–1FA00 <strong>3VF</strong>9 723–1FB00 <strong>3VF</strong>9 723–1FD00 12<br />

<strong>3VF</strong>8 2500 <strong>3VF</strong>9 823–1EA01 <strong>3VF</strong>9 823–1EB01 <strong>3VF</strong>9 823–1ED01 <strong>3VF</strong>9 823–1FA01 <strong>3VF</strong>9 823–1FB01 <strong>3VF</strong>9 823–1FD01 12<br />

1/30<br />

<strong>Siemens</strong> - Distribuzione dell’energia


Parti di ricambio per comandi disinnestabili<br />

bloccoporta 8UC6<br />

Per interruttore Albero A: Nr. di ordinazione<br />

Maniglia Nera<br />

Maniglie complete di mostrina<br />

8UC61<br />

B:<br />

Tipo mm × mm Maniglia Rossa<br />

<strong>3VF</strong>1 6 × 6 A 8UC61 10–1BD<br />

B 8UC61 20–3BD<br />

1<br />

<strong>3VF</strong>3, 4,5 8 × 8 A 8UC62 10–1BD<br />

B 8UC62 20–3BD<br />

8UC62<br />

<strong>3VF</strong>6 12 × 12 A 8UC63 10–1BD<br />

B 8UC63 20–3BD<br />

8UC63<br />

<strong>3VF</strong>7 12 × 12 A 8UC64 10–1BB<br />

B 8UC64 20–3BB<br />

8UC64<br />

<strong>3VF</strong>8 12 × 12 A 8UC65 10–1BB<br />

B 8UC65 20–3BB<br />

8UC65<br />

Fungo autocentrante<br />

8UC61 (<strong>3VF</strong>1) 6 × 6 8UC60 11<br />

8UC62 (<strong>3VF</strong>3, 4, 5) 8 × 8 8UC60 12<br />

8UC63 10 × 10 8UC60 13<br />

8UC63 ÷ 8UC65 (<strong>3VF</strong>6, 7) 12 × 12 8UC60 14<br />

Albero di prolunga (lunghezza = 300 mm)<br />

8UC61 (<strong>3VF</strong>1) 6 × 6 8UC60 31<br />

8UC62 (<strong>3VF</strong>3, 4, 5) 8 × 8 8UC60 32<br />

8UC63 10 × 10 8UC60 33<br />

8UC63 ÷ 8UC65 (<strong>3VF</strong>6, 7) 12 × 12 8UC60 34<br />

8UC66 12 × 12 8UC60 35<br />

Albero di prolunga (lunghezza = 600 mm)<br />

8UC61 (<strong>3VF</strong>1) 6 × 6 8UC60 81<br />

8UC62 (<strong>3VF</strong>3, 4, 5) 8 × 8 8UC60 82<br />

8UC63 10 × 10 8UC60 83<br />

8UC63 ÷ 8UC65 (<strong>3VF</strong>6, 7) 12 × 12 8UC60 84<br />

Elemento di fissaggio albero<br />

8UC61 (<strong>3VF</strong>1) 6 × 6 8UC60 21<br />

8UC62 (<strong>3VF</strong>3, 4, 5) 8 × 8 8UC60 22<br />

8UC63 10 × 10 8UC60 23<br />

8UC63 ÷ 8UC65 (<strong>3VF</strong>6, 7, 8) 12 × 12 8UC60 24<br />

<strong>Siemens</strong> - Distribuzione dell’energia<br />

1/31