<strong>Tabellsamling</strong> Selektivitet med kaskadkoppling 380/415VSäkringsfri teknik 2010 Uppströms: NSX100-160 medMicrologic 2/5/6Nedströms: Multi 9UppströmsBrytförmåga (kA rms)NSX100B25 kANSX100F36 kANSX100N50 kANSX100H70 kANSX100S100 kANSX100L150 kAUtlösarblockMicrologic Micrologic Micrologic Micrologic Micrologic Micrologic2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0Nedströms märkström 40 100 40 100 40 100 40 100 40 100 40 100C60N 10 kA ≤16 20/20 20/20 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/3020 20/20 20/20 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/3025 20/20 20/20 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/3032 20/20 25/25 30/30 30/30 30/30 30/3040 20/20 25/25 30/30 30/30 30/30 30/305063C60H 15 kA ≤16 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4025 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4032 25/25 36/36 40/40 40/40 40/40 40/4040 20/20 36/36 40/40 40/40 40/40 40/405063C60L 25 kA ≤16 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4025 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 kA 32 25/25 36/36 40/40 40/40 40/40 40/4040 25/25 36/36 40/40 40/40 40/40 40/4015 kA 5063OBS: respektera de förhållanden mellan inställningarna som anges på sidan 35.UppströmsBrytförmåga (kA rms)NSX160B25 kANSX160F36 kANSX160N50 kANSX160H70 kANSX160S100 kANSX160L150 kAUtlösarblockMicrologic Micrologic Micrologic Micrologic Micrologic Micrologic2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0 2.0/5.0/6.0Nedströms märkström 80 160 80 160 80 160 80 160 80 160 80 160C60N 10 kA ≤16 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2520 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2525 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2532 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2540 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2550 20/20 20/20 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/2563 20/20 25/25 25/25 25/25 25/25 25/25C60H 15 kA ≤16 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4025 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4032 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4040 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4050 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/3063 25/25 30/30 30/30 30/30 30/30 30/30C60L 25 kA ≤16 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4025 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4020 kA 32 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4040 25/25 25/25 36/36 36/36 40/40 40/40 40/40 40/40 40/40 40/40 40/40 40/4015 kA 50 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/3063 25/25 30/30 30/30 30/30 30/30 30/30OBS: respektera de förhållanden mellan inställningarna som anges på sidan 35.149

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!