S2.3TRAJANJE BOOST OGREVANJA PRI PREHODUIZ NOČNE V DNEVNO TEMPERATUROZA MEŠALNI OGREVALNI KROG0 ÷ 200 m<strong>in</strong> 0S2.4POVEČANJE ŽELENE SOBNE TEMPERATUREPRI BOOST OGREVANJUZA MEŠALNI OGREVALNI KROG0 ÷ 8 K 4S2.5S2.6NAČIN DELOVANJA OBTOČNE ČRPALKE UWP (A.8) 0 ÷ 3 - 00 - obtočna črpalka mešalnega ogrevalnega kroga (standardno).1 - izklop črpalke UWP, ko je časovni program P1=OFF.2 - izklop črpalke UWP, ko je časovni program P2=OFF.3 - izklop črpalke UWP, ko je izbran časovni program na OFF.MINIMALNA TEMPERATURA DVIŽNEGA VODA MEŠAL-NEGA OGREVALNEGA KROGA10 ÷ 90 °C 20S2.7 MAKSIMALNA TEMPERATURA DVIŽNEGA VODAMEŠALNEGA OGREVALNEGA KROGA20 ÷ 150 °C 85/45S2.8MRTVA CONA REGULACIJE MEŠALNEGA VENTILA 1,0 ÷ 3,0 K 1S2.9 OJAČANJE 3-TOČKOVNE REGULACIJEMEŠALNEGA VENTILA0,5 ÷ 2,0 - 1S2.10 INTEGRACIJSKA KONSTANTA 3-TOČKOVNEREGULACIJE MEŠALNEGA VENTILA0,4 ÷ 2,5 - 1S2.11DIFERENCIALNA KONSTANTA 3-TOČKOVNEREGULACIJE MEŠALNEGA VENTILA0,4 ÷ 2,5 - 1S2.12 MAKSIMALNA TEMPERATURA ESTRIHA 10 ÷ 70 °C 25S2.13MNIMALNA TEMPERATURA DVIŽNEGA VODAZA HLAJENJE10 ÷ 20 °C 15S2.14 MEJNA SOBNA TEMPERATURA PRI DELOVANJUTOPLOTNE ČRP. Z OGREVANJEM SANITARNE VODE5 ÷ 30 °C 16S2.15 MAKSIMALNA DIFERENCA MED VF IN RLF 0 ÷ 30 K 00 - izklop diference1..30 - diferenca37 Servisna navodila za nastavitev