By og Byg Dokumentation 058<br />
<strong>Måling</strong> <strong>på</strong> <strong>alternative</strong><br />
<strong>isoleringsmaterialer</strong><br />
Borup Seniorby - et demonstrationsprojekt
<strong>Måling</strong>er <strong>på</strong> <strong>alternative</strong><br />
<strong>isoleringsmaterialer</strong><br />
Borup Seniorby - et demonstrationsprojekt<br />
Torben Valdbjørn Rasmussen<br />
Asta Nicolajsen<br />
By og Byg Dokumentation 058<br />
<strong>Statens</strong> Byggeforskningsinstitut 2004
Titel <strong>Måling</strong>er <strong>på</strong> <strong>alternative</strong> <strong>isoleringsmaterialer</strong><br />
Undertitel Borup Seniorby - et demonstrationsprojekt<br />
Serietitel By og Byg Dokumentation 058<br />
Udgave 1. udgave<br />
Udgivelsesår 2004<br />
Forfatter Torben Valdbjørn Rasmussen, Asta Nicolajsen<br />
Sprog Dansk<br />
Sidetal 91<br />
Litteraturhenvisninger<br />
Side 42<br />
English<br />
summary Side 43-44<br />
Emneord Alternative <strong>isoleringsmaterialer</strong>, fugt, termografering, løsfyldsisolering, byggeteknik,<br />
demonstrationsbyggeri, cellulose, glasuld, høruld, stenuld, træfiber, perlit<br />
ISBN 87-563-1204-0<br />
ISSN 1600-8022<br />
Pris Kr. 220,00 inkl.25 pct. moms<br />
Tekstbehandling Solveig Susanne Johansen<br />
Fotos Torben Valdbjørn Rasmussen, Peter Mossing, Jan Carl Westphall<br />
Udgiver By og Byg<br />
<strong>Statens</strong> Byggeforskningsinstitut,<br />
P.O. Box 119, DK-2970 Hørsholm<br />
E-post by-og-byg@by-og-byg.dk<br />
www.by-og-byg.dk<br />
Eftertryk i uddrag tilladt, men kun med kildeangivelsen: By og Byg Dokumentation 058: <strong>Måling</strong>er <strong>på</strong> <strong>alternative</strong><br />
<strong>isoleringsmaterialer</strong>. Borup Seniorby - et demonstrationsprojekt. (2004)
Indhold<br />
Forord ..............................................................................................................5<br />
Sammenfatning og konklusion ........................................................................6<br />
Konklusion ..................................................................................................6<br />
Fugtophobning .......................................................................................6<br />
Isoleringsarbejdets udførelse.................................................................6<br />
Velegnede <strong>isoleringsmaterialer</strong>..............................................................7<br />
Indledning........................................................................................................8<br />
Baggrund ....................................................................................................8<br />
Formål.........................................................................................................8<br />
Metode........................................................................................................8<br />
Teori............................................................................................................9<br />
Forsøg vedrørende fugtophobning................................................................10<br />
Isoleringsmateriale....................................................................................10<br />
Byggeriet Borup Seniorby.........................................................................10<br />
Konstruktionernes opbygning ...................................................................13<br />
Påvirkninger..............................................................................................15<br />
Registrerede <strong>på</strong>virkninger....................................................................15<br />
Undersøgelsesmetode .........................................................................17<br />
Fugtmåler .............................................................................................17<br />
Dataopsamling .....................................................................................17<br />
Forsøgsperiode ....................................................................................18<br />
Resultater vedrørende fugtophobning ......................................................18<br />
Diskussion.................................................................................................22<br />
Klima<strong>på</strong>virkning....................................................................................22<br />
Usikkerhed ...........................................................................................22<br />
Kriterier.................................................................................................22<br />
Fugtophobning i <strong>isoleringsmaterialer</strong> ...................................................22<br />
Er isoleringsarbejdet udført korrekt? .............................................................23<br />
Termografering .........................................................................................23<br />
<strong>Måling</strong>er................................................................................................23<br />
Resultat af termografering ........................................................................23<br />
Bemærkninger til termografering ..............................................................25<br />
Kategori A: Kolde overgange mellem lejlighedsskel og loft .................25<br />
Kategori B: Kolde hjørner mellem lejlighedsskel og facade.................26<br />
Kategori C: Kolde fodpaneler langs facade .........................................27<br />
Kategori D: Kolde områder ved spær, lagt an <strong>på</strong> bagvæg af<br />
letklinkerbeton ......................................................................................28<br />
Kategori E: Kolde områder i den isolerede facade ..............................29<br />
Kategori F: Kolde områder i den isolerede facade langs loftet............30<br />
Kategori G: Kolde hjørner ved lejlighedsskel/gavl, loft og facade........33<br />
Diskussion.................................................................................................34<br />
Årsag til lokalt forekommende temperaturforskelle..............................34<br />
Beregning af hulrum.............................................................................35<br />
Varmestrømsberegning........................................................................35<br />
Beregning af hulrum i facade isoleret med Ekofiber ............................37<br />
Temperatur ved overgangen mellem facade og loft.................................38<br />
Beregning af hulrum langs loft i facaden isoleret med Ekofiber ...............39<br />
Beregnede hulrum ....................................................................................40<br />
Manglende isolering .............................................................................41<br />
Litteratur ........................................................................................................42<br />
Summary .......................................................................................................43<br />
Bilag A Temperatur og fugt i facade- og loftkonstruktioner...........................45<br />
3
4<br />
Bilag B Temperatur og relativ luftfugtighed i lejligheder............................... 82<br />
Bilag C Temperatur og relativ luftfugtighed udendørs og i teknikrum .......... 91
Forord<br />
Borup Seniorby er udefra set en helt almindelig bebyggelse, men Borup Seniorby<br />
er også et demonstrationsbyggeri, der har til formål at demonstrere<br />
og dokumentere anvendelsen af en lang række traditionelle og <strong>alternative</strong><br />
<strong>isoleringsmaterialer</strong>.<br />
Bebyggelsen har givet en god mulighed for, i en række næsten ens boliger,<br />
at dokumentere de forskellige <strong>isoleringsmaterialer</strong>nes egenskaber vedrørende<br />
isoleringsevne, fugtophobning, arbejdsmiljø og isoleringsarbejdets<br />
udførelse. Denne dokumentation er nødvendig for at et bredt udsnit af projekterende<br />
og udførende rutinemæssigt kan anvende <strong>alternative</strong> <strong>isoleringsmaterialer</strong>.<br />
Forud for denne rapport har By og Byg udfærdiget en rapport med titlen<br />
"Praktiske erfaringer med <strong>alternative</strong> <strong>isoleringsmaterialer</strong>" (Valdbjørn Rasmussen<br />
& Feilberg Hansen, 2004). I rapporten er bebyggelsen præsenteret,<br />
og såvel <strong>isoleringsmaterialer</strong> som indbygningsprocesser er beskrevet, herunder<br />
indbygning af måleudstyr til måling af temperaturer og fugt.<br />
I tilknytning til projektet er der endvidere gennemført en undersøgelse af<br />
støvbelastningen knyttet til arbejdet med de valgte produkter og den valgte<br />
arbejdsproces. Resultaterne fra dette arbejde er rapporteret i (Breum,<br />
Schneider, Flyvholm, Jørgensen, Valdbjørn Rasmussen & Skibstrup Eriksen,<br />
2003).<br />
En særlig tak rettes til bygherren, Dansk SeniorByg A/S, der sammen<br />
med By og Byg realiserede muligheden for at gennemføre projektet. Søren<br />
Skibstrup Eriksen forestod ledelsen af By og Bygs andel frem til byggeriets<br />
afslutning i 2002.<br />
Demonstrationsprojektet og de tilknyttede undersøgelser er udført med<br />
økonomisk støtte fra Energistyrelsens udviklingsprogram Miljø- og arbejdsmiljøvenlig<br />
<strong>isoleringsmaterialer</strong>.<br />
By og Byg, <strong>Statens</strong> Byggeforskningsinstitut<br />
Afdelingen for Byggeteknik og Design<br />
Juni 2004<br />
Jørgen Munch-Andersen<br />
Konstitueret forskningschef<br />
5
6<br />
Sammenfatning og konklusion<br />
Interessen for at anvende <strong>alternative</strong> <strong>isoleringsmaterialer</strong>, fx papir, hør og<br />
ekspanderet perlit, har været stigende gennem de seneste år. Dette har<br />
medført et øget behov for at få kendskab til <strong>isoleringsmaterialer</strong>nes egenskaber,<br />
herunder hvordan de fungerer sammenlignet med de traditionelle<br />
<strong>isoleringsmaterialer</strong> af mineraluld.<br />
I denne rapport besvares følgende spørgsmål vedrørende <strong>isoleringsmaterialer</strong><br />
i konstruktionerne i Borup Seniorby:<br />
– vil der i løbet af en vinter, ske en skadelig fugtophobning i de konkrete<br />
konstruktioner med de valgte <strong>isoleringsmaterialer</strong>?<br />
– er isoleringsarbejdet udført korrekt, dvs. udfylder isoleringsmaterialet de<br />
hulrum, der skal isoleres?<br />
– er det enkelte isoleringsmateriale specielt velegnet til alle typer konstruktioner,<br />
eller bør der stilles specielle krav til konstruktionernes udformning?<br />
I Borup Seniorby er byggeriets boliger, to og to, isoleret med det samme<br />
isoleringsmateriale. Der blev isoleret med ni forskellige <strong>isoleringsmaterialer</strong>,<br />
fem løsfyldsprodukter, to typer hør og to typer mineraluld, se tabel 1. Konstruktionerne<br />
har været <strong>på</strong>virket af det aktuelle ude- og indeklima.<br />
Fugtindholdet i isoleringen i facadeelementer og i loftkonstruktioner blev<br />
registreret med fugtmåledyvler anbragt i konstruktionernes varme og kolde<br />
side. I isoleringen i facaden umiddelbart bag den tunge bagvæg af letklinkerbeton<br />
og i isoleringen umiddelbart bag vindspærren af vindgips. Alle resultater<br />
af fugtmålingerne er angivet i vægt pct. fugt i træ (træ-fugt), for at<br />
kunne sammenlignes med faregrænsen for svampeangreb <strong>på</strong> 20 % træ-fugt.<br />
For at undersøge om isoleringsarbejdet er udført korrekt, er der fortaget<br />
en termografisk registrering af de indvendige overflader. Termograferingen<br />
blev udført en vinterdag med svag til frisk vind og en udetemperatur <strong>på</strong> -1<br />
°C.<br />
Konklusion<br />
Fugtophobning<br />
Fugtmålinger i de enkelte <strong>isoleringsmaterialer</strong> viser, at der ikke sker en skadelig<br />
fugtophobning i isoleringen i de her anvendte konstruktioner, uanset<br />
om de er isoleret med <strong>alternative</strong> <strong>isoleringsmaterialer</strong> eller med mineraluld,<br />
idet de målte fugtindhold alle er under 20 % træ-fugt.<br />
Der er ikke signifikant forskel mellem middelværdien af fugtophobningen i<br />
de <strong>alternative</strong> <strong>isoleringsmaterialer</strong> og middelværdien af fugtophobningen i<br />
mineraluld.<br />
Der er lidt større fugtophobning den første vinter end den anden vinter.<br />
Dette indikerer, at der har været indbygget en vis mængde byggefugt.<br />
Isoleringsarbejdets udførelse<br />
Den termografiske gennemgang af de indvendige overflader viser, at uanset<br />
hvilket isoleringsmateriale der er anvendt, er der konstateret afgrænsede<br />
områder med lavere temperaturer end omgivelserne.<br />
Selv om der er afvigelser mellem de registrerede temperaturforskelle, kan<br />
der, ud fra de her refererede målinger, ikke konstateres signifikante afvigelser<br />
mellem temperaturforskelle <strong>på</strong> overflader af konstruktioner, der er isoleret<br />
med <strong>alternative</strong> <strong>isoleringsmaterialer</strong> og temperaturforskelle <strong>på</strong> overflader<br />
af konstruktioner, der er isoleret med mineraluld. Der er dog registreret lidt
højere temperaturforskelle <strong>på</strong> overflader af konstruktioner, der er isoleret<br />
med Perlite end <strong>på</strong> de øvrige overflader.<br />
Årsagen til lokalt forekommende temperaturforskelle kan ikke med sikkerhed<br />
angives, uden at der er foretaget en destruktiv undersøgelse af konstruktionen.<br />
Nogle af de lokalt forekommende temperaturforskelle indikerer<br />
at isoleringsarbejdet lokalt ikke er udført korrekt, eller at der er sket sætninger<br />
i isoleringen. Andre af de lokalt forekommende temperaturforskelle indikerer<br />
at der er væsentlige kuldebroer, dels ved fodpaneler langs facaden,<br />
hvilket må tilskrives en dårlig kuldebroafbrydelse mellem fundament og dæk,<br />
dels ved overgangen mellem lejlighedsskel og loft, idet lejlighedsskel er ført<br />
ubrudt op i loftrum som brandsektionering.<br />
Velegnede <strong>isoleringsmaterialer</strong><br />
Et materiales egnethed som isoleringsmateriale i en given konstruktion bedømmes<br />
<strong>på</strong> grundlag af materialets praktiske varmeledningsevne, den praktiske<br />
håndtering <strong>på</strong> en byggeplads og om materialet er i stand til at opretholde<br />
sin funktion i bygningens levetid.<br />
Tidligere observationer af indbygningen af de enkelte <strong>isoleringsmaterialer</strong><br />
har vist, at med en fornuftig udformning af konstruktionerne kan de anvendte<br />
<strong>isoleringsmaterialer</strong> håndteres <strong>på</strong> byggepladsen uden væsentlige problemer<br />
(Valdbjørn Rasmussen & Feilberg Hansen, 2004). Observationer foretaget i<br />
bebyggelsen under indbygningen af isoleringsmaterialet har dog vist, at det<br />
er nødvendigt at specificere krav til konstruktionernes tæthed, når der skal<br />
isoleres med løsfyldsprodukter. Kravet til konstruktionernes tæthed gælder<br />
alle typer samlinger og gennemføringer. Entreprenører og rådgivere bør være<br />
opmærksomme <strong>på</strong>, at kravet til konstruktionernes tæthed afhænger af<br />
løsfyldsisoleringens partikelstørrelse, idet en isolering med mange små partikler<br />
kræver en meget tæt konstruktion.<br />
Generelt skal konstruktionen i klimaskærmen være lufttæt, for at være<br />
velegnet til enhver form for isolering. Både for at forhindre fugtophobning i<br />
den isolerede del af klimaskærmen, men også for at forhindre luftgennemstrømning<br />
i den isolerede del af klimaskærmen, som vil reducere isoleringsevnen<br />
af isoleringsmaterialet.<br />
7
8<br />
Indledning<br />
Interessen for at anvende <strong>alternative</strong> <strong>isoleringsmaterialer</strong> fx papir, hør og<br />
ekspanderet perlit har været stigende gennem de seneste år. Dette har<br />
medført et øget behov for at få kendskab til <strong>isoleringsmaterialer</strong>nes egenskaber,<br />
herunder hvordan de fungerer sammenlignet med de traditionelle<br />
<strong>isoleringsmaterialer</strong> af mineraluld.<br />
Baggrund<br />
Denne rapport er en del af afrapporteringen af et demonstrationsprojekt. I<br />
projektet blev det undersøgt, hvordan det er at montere de enkelte <strong>isoleringsmaterialer</strong>,<br />
og det hertil knyttede arbejdsmiljø blev målt. Desuden blev<br />
det undersøgt, hvordan de enkelte <strong>isoleringsmaterialer</strong> fungerer herunder<br />
om der sker en skadelig opfugtning i løbet af vinteren.<br />
De praktiske erfaringer der er høstet, ved at følge isoleringsarbejdet under<br />
opførelsen af demonstrationsbyggeriet Borup Seniorby, er rapporteret i<br />
By og Byg publikationen "Praktiske erfaringer med alternativ isolering"<br />
(Valdbjørn Rasmussen & Feilberg Hansen, 2004).<br />
De arbejdsmiljømæssige gener, som er knyttet til anvendelsen af <strong>isoleringsmaterialer</strong>,<br />
er primært hud- og luftvejsgener for isoleringsarbejderne,<br />
knyttet til forekomster af støv. <strong>Måling</strong>erne af støvforekomster samt en vurdering<br />
af behovet for beskyttelsesdragter og åndedrætsværn blev ikke foretaget<br />
<strong>på</strong> byggepladsen, men foretaget ved isolering af en sektion af byggeriet<br />
opført som en fuldskalamodel i en forsøgshal hos By og Byg. <strong>Måling</strong>erne er<br />
rapporteret af Arbejdsmiljøinstituttet i (Breum et al., 2002).<br />
Formål<br />
Formålet for den del af projektet der er afrapporteret her, er at belyse følgende<br />
spørgsmål:<br />
– vil der i løbet af en vinter, ske en skadelig fugtophobning i de her valgte<br />
konstruktioner med de valgte <strong>isoleringsmaterialer</strong>?<br />
– er isoleringsarbejdet udført korrekt, dvs. udfylder isoleringsmaterialet de<br />
hulrum, der skal isoleres?<br />
– er det enkelte isoleringsmateriale velegnet til alle typer konstruktioner, eller<br />
bør der stilles specielle krav til konstruktionernes udformning?<br />
Metode<br />
<strong>Måling</strong> af den fugtophobning, der i løbet af en vinter sker i konstruktioner<br />
isoleret med <strong>alternative</strong> <strong>isoleringsmaterialer</strong>, kan bedst ske ved at udsætte<br />
konstruktionerne for en fugtbelastning svarende til belastningen i almindelige<br />
boliger. Det blev derfor valgt at instrumentere facader og loftkonstruktioner i<br />
en række ens boliger, isoleret med forskellige <strong>alternative</strong> <strong>isoleringsmaterialer</strong>,<br />
og som reference måle i tilsvarende boliger isoleret med traditionelle og<br />
velkendte isoleringsprodukter af mineraluld.<br />
For at undersøge om isoleringsarbejdet er udført korrekt, dvs. om isoleringsmaterialet<br />
udfylder det hulrum, der skal isoleres, foretages termovision
af de indvendige overflader under vinterforhold. Ved termovision registreres<br />
de indvendige overfladers temperatur ved en fotografisk lignende proces.<br />
Teori<br />
I rapporten (Stang, 2002) er der en kort beskrivelse af den teoretiske baggrund<br />
for kondensdannelse i facadekonstruktioner. En mere grundlæggende<br />
gennemgang af emnet kan findes i SBI-anvisning 178 (Andersen, Christensen<br />
& Nielsen, 1993) eller i (Nevander og Elmarsson, 1994). Den teoretiske<br />
baggrund for den her rapporterede undersøgelse kan kort resumeres som<br />
følger:<br />
Den relative luftfugtighed bestemmes af luftens fugtindhold i forhold til<br />
den maksimale mængde fugt der kan indeholdes ved den givne temperatur.<br />
Ved afkøling af varm fugtig luft vil den relative luftfugtighed<br />
stige indtil en relativ luftfugtighed <strong>på</strong> 100 % (mætningsdamptrykket)<br />
nås. Hvis luften afkøles yderligere, vil der dannes kondens, som typisk<br />
vil sætte sig <strong>på</strong> kolde overflader. Luftens fugtindhold som funktion af<br />
temperaturen kan optegnes som et vanddampdiagram. Af et vanddampdiagram<br />
kan bl.a. aflæses, at luft ved en typisk indendørs<br />
temperatur <strong>på</strong> 22 °C kan indeholde omkring 4 gange mere vand i g/m 3<br />
end luft ved 0 °C.<br />
Fugtindholdet indendørs regnet i g/m 3 følger generelt fugtindholdet<br />
i udeluften. Der er dog et væsentligt bidrag fra husets beboere, madlavning,<br />
badning og tøjtørring mm. Begrænset udluftning vil derfor bevirke,<br />
at fugtindholdet indendørs er højere end fugtindholdet udendørs.<br />
Dette gælder selv om forskellen i temperatur ude og inde bevirker,<br />
at den relative luftfugtighed er væsentlig lavere indendørs. Fugttransporten<br />
gennem materialer styres af forskellen i partialdamptryk<br />
(Lund-Hansen, 1967). Partialdamptrykket er en funktion af vanddamp<br />
koncentrationen og temperaturen. På en typisk vinterdag med en<br />
temperatur <strong>på</strong> 0 °C og en relativ luftfugtighed <strong>på</strong> 90 % RF er partialdamptrykket<br />
udendørs 550 Pa, mens det tilsvarende typiske indendørs<br />
partialdamptryk ved en temperatur <strong>på</strong> 20 °C og en relativ luftfugtighed<br />
<strong>på</strong> 40 % RF er 930 Pa. Da partialdamptrykket er højere inde<br />
end ude, vil der være en transport af fugt indefra og ud.<br />
På grund af denne fugttransport gennem ydervægskonstruktioner<br />
er det vigtigt at opbygge vægge <strong>på</strong> en måde, så fugttransporten ikke<br />
standses inde i væggen. Dette sikres ved at have en høj dampdiffu<br />
sionsmodstand <strong>på</strong> den varme side af konstruktionen og omvendt have<br />
en lav dampdiffusionsmodstand længere ude i konstruktionen. En<br />
tommelfingerregel siger, at damdiffusionsmodstanden <strong>på</strong> den varme<br />
side af isoleringen skal være 10 gange større end dampdiffusionsmodstanden<br />
<strong>på</strong> den kolde side af isoleringen. På denne måde sikres<br />
at der ikke ophobes fugt i konstruktionen.<br />
Skadelig fugtophobning i konstruktioner kan skyldes indtrængning af vand fx<br />
gennem mangelfulde inddækninger eller kondens i konstruktionen. De fleste<br />
konstruktioner udføres med en dampspærre for at undgå kondens, men facadekonstruktioner,<br />
som de her undersøgte med en bagvæg af letklinkerbeton,<br />
udføres normalt uden dampspærre.<br />
By og Byg har i en undersøgelse (Stang, 2002) vist, at facadekonstruktioner<br />
med bagvæg af letklinkerbeton er yderst følsomme over for fugt.<br />
De tidligere undersøgte facadekonstruktioner har alle været udført med<br />
mineraluld. Det er derfor vigtig, at undersøge om anvendelse af andre <strong>isoleringsmaterialer</strong><br />
har indflydelse <strong>på</strong> den fugtophobning, der sker i facadekonstruktionen.<br />
9
10<br />
Forsøg vedrørende fugtophobning<br />
Isoleringsmateriale<br />
Til isolering af byggeriet blev der valgt ni forskellige isoleringsprodukter, som<br />
alle var tilgængelige <strong>på</strong> det danske marked ved byggeriets start. De enkelte<br />
produkter er enten anvendt som løsfyld eller som formstykker. Tabel 1 indeholder<br />
en oversigt over de anvendte produkter opdelt efter materiale og producenter,<br />
og om de er anvendt som løsfyld eller som formstykker.<br />
Tabel 1. Isoleringsprodukter anvendt som varmeisoleringsmateriale i Borup Seniorby.<br />
Materiale Produktnavn Producent Type<br />
Cellulose (genbrugspapir) Ekofiber, vind Ekofiber AB Løsfyld<br />
Cellulose (genbrugspapir) Isodan Isodan Løsfyld<br />
Cellulose (genbrugspapir) Papiruld Miljøisolering ApS Løsfyld<br />
Træfiber Thermocell Thermocell Danmark A/S Løsfyld<br />
Høruld Høruld i formstykker Dansk Naturisolering A/S Formstykker<br />
Høruld Heraflax Heraklith Formstykker<br />
Perlit Perlit, 0515SC Nordisk Perlite ApS Løsfyld<br />
Stenuld Rockwool, A-batts Rockwool A/S Formstykker<br />
Glasuld Isover Saint Gobain Isover A/S Formstykker<br />
Byggeriet Borup Seniorby<br />
Byggeriet består af 24 selvstændige boliger fordelt <strong>på</strong> tre selvstændige længehuse<br />
(blokke) i 1-2 etager med hver otte lejligheder. Figur 1 og figur 2 viser<br />
udsnit af bebyggelsen. Bebyggelsen er nærmere beskrevet i (Valdbjørn<br />
Rasmussen & Feilberg Hansen, 2004), her er byggeriets parter ligeledes<br />
nævnt. Byggeriets boliger er to og to isoleret med samme isoleringsmateriale.<br />
Figur 3 viser hvor i byggeriet de ni <strong>isoleringsmaterialer</strong> er placeret.
Figur 1. Et af de tre længehuse i 1-2 etager som udgør bebyggelsen Borup Seniorby. Facaden vender<br />
mod vest og gavlen mod syd.<br />
Figur 2. Et af de tre længehuse i 1-2 etager som udgør bebyggelsen Borup Seniorby. Facaden vender<br />
mod vest. Bygningen er set fra nord.<br />
11
12<br />
N<br />
Blok A<br />
Blok B<br />
Blok C<br />
Thermocell<br />
Isodan<br />
Ekofiber<br />
Heraflex Rockwool<br />
Underetage<br />
Hør i formstykker Isover<br />
Underetage<br />
Papiruld Perlite<br />
Underetage<br />
Figur 3. Placeringen af de ni isoleringsprodukter i byggeriets tre blokke. Byggeriets underetager og<br />
gavle er isoleret med Isover.
Konstruktionernes opbygning<br />
Figur 4 viser et tværsnit i 2 etager. Opbygningen af de konstruktioner der er<br />
væsentlige for forståelse af resultaterne, er angivet nedenfor. Opbygningen<br />
af de øvrige konstruktioner er angivet i (Valdbjørn Rasmussen & Feilberg<br />
Hansen, 2004).<br />
Figur 4. Tværsnit i 2 etagers længehus.<br />
13
14<br />
Facaderne er opbygget af:<br />
– 100 mm bærende bagvæg i helvægselementer af letklinkerbeton<br />
– træstolper per 600 mm med 200 mm isolering<br />
– 9 mm udvendig vindgips<br />
– ventileret luftspalte<br />
– udvendig beklædning af træ <strong>på</strong> klink eller fibercementplader.<br />
Nogle af facaderne er udført med toprem andre uden toprem, så der er forbindelse<br />
imellem loftisoleringen og facadeisoleringen.<br />
Lejlighedsskellene er opbygget af:<br />
– 150 mm letklinkerbetonelementer.<br />
Letklinkerbetonelementerne er ført ubrudt op igennem tagrummet til undersiden<br />
af tagbeklædningen.<br />
Loftkonstruktionen er opbygget af:<br />
– 2 lag 13 mm gipsplade,<br />
– dampspærre,<br />
– forskalling,<br />
– gitterspær per 900 mm med isolering.<br />
Tykkelsen af loftisoleringen er beregnet af den rådgivende ingeniør ud fra<br />
varmetabsberegninger. Isoleringstykkelsen er, sammen med den til beregningen<br />
anvendte varmeledningsevne (lambda), angivet i tabel 2.<br />
Beregningerne af varmetabet er udført efter DS 418 (Dansk Ingeniørforening,<br />
1986 og Dansk Standard, 2000). Beregningerne af varmetabet skal<br />
blandt andet sikre, at varmetabet for den enkelte bolig ligger inden for varmetabsrammen,<br />
angivet i BR 95 (Boligministeriet, 1995). Alle gavle (undtagen<br />
i bolig med termocell) og facader i underste etage i de to-etagers boliger<br />
er isoleret med Isover.<br />
Kravet om max. U-værdi for tagkonstruktioner <strong>på</strong> 0,25 W/m 2 K medfører<br />
minimum 150 mm mineraluld i tagkonstruktioner.<br />
De udvendige overflader for de enkelte boliger har forskellige arealer, og<br />
de anvendte <strong>isoleringsmaterialer</strong> har forskellige lambda. Det er derfor nødvendigt,<br />
<strong>på</strong> lofterne at anvende isolering af forskellig tykkelse for at alle boliger<br />
kan få det samme samlede varmetab. Tykkelserne af loftisolering er beregnet<br />
ved, at der for hver isoleringstype er beregnet et samlet varmetab for<br />
boligerne isoleret med den aktuelle isoleringstype og med Isover. Derefter er<br />
der beregnet hvor meget mere af den aktuelle isolering, der skal lægges <strong>på</strong><br />
loftet for at få det samme varmetab som med Isover.<br />
For løsuldsprodukter er der tillagt den i DS 418 krævede overtykkelse (til<br />
sætning) <strong>på</strong> henholdsvis 25 % for cellulosefibre og 1 % for ekspanderet perlit.
Tabel 2. Varmeledningsevne for væg- og loftisolering samt tykkelse af loftisolering.<br />
Lambda, væg<br />
W/mK<br />
Lambda, loft<br />
W/mK<br />
Ekofiber 0,050 0,055 415<br />
Isodan 0,050 0,055 375<br />
Papiruld 0,050 0,055 375<br />
Thermocell 0,055 0,055 280<br />
Høruld i formstykker 0,055 0,055 200<br />
Heraflax 0,042 0,042 200<br />
Perlite 0,045 0,045 200<br />
Rockwool 0,039 0,039 150<br />
Isover 0,039 0,039 150<br />
Påvirkninger<br />
Isoleringstykkelse <strong>på</strong> loft<br />
mm<br />
Den fugt<strong>på</strong>virkning facade- og loftkonstruktioner med de valgte <strong>isoleringsmaterialer</strong><br />
bliver udsat for, afhænger af forskellen i damptryk <strong>på</strong> de to sider<br />
af konstruktionerne, dvs. indendørs og udendørs. Damptrykket er en funktion<br />
af temperatur og relativ luftfugtighed. Det er specielt vigtigt at måle temperatur<br />
og relativ luftfugtighed indendørs, fordi temperatur og relativ luftfugtighed<br />
højere end ”normalt”, kan bevirke høj fugtophobning i isoleringen,<br />
hvilket kan tolkes som et problem for organiske <strong>isoleringsmaterialer</strong>.<br />
Temperatur og relativ luftfugtighed blev målt ved hjælp af TinyTags af typen<br />
TGU-1500. TGU-1500, som er en datalogger med dimensionerne 72 x<br />
60 x 33 mm 3 med en vægt <strong>på</strong> 50 g. Den kan måle både temperatur og relativ<br />
luftfugtighed. Temperaturer mellem 0 og 50 °C kan måles med en nøjagtighed<br />
<strong>på</strong> ± 0,2 °C. Den relative luftfugtighed mellem 0 og 95 % kan måles med<br />
en nøjagtighed <strong>på</strong> ± 3 % ved 23 °C. Hver enkelt TinyTags blev efter måleperiodens<br />
ophør kontrolleret ved 23 °C og henholdsvis 50, 65 og 80 % RF, for<br />
om nødvendigt at kunne korrigere målingerne opsamlet i bebyggelsen. I<br />
hver lejlighed blev temperatur og relativ luftfugtighed målt i stuen, i badeværelse<br />
og i et vestvendt værelse, der blev anvendt som kontor eller soveværelse.<br />
Temperatur og relativ luftfugtighed blev også målt seks skyggefulde<br />
steder udendørs i de seks lejligheder beliggende i underetagen og i de tre<br />
uopvarmede teknikrum.<br />
Registrerede <strong>på</strong>virkninger<br />
Temperatur og relativ luftfugtighed blev målt hver anden time i perioden juni<br />
2002 til maj 2003.<br />
Temperatur og relativ luftfugtighed i de enkelte boliger, herunder også i<br />
boliger beliggende i underetagen i den del af byggeriet der er i to etager, er<br />
vist i bilag B, figur 151 til figur 174. Temperatur og relativ luftfugtighed udendørs<br />
og i de tre uopvarmede teknikrum er vist i bilag C, figur 175 og figur<br />
176.<br />
Et eksempel <strong>på</strong> opsamlede data, temperatur og relativ luftfugtighed i en<br />
lejlighed isoleret med Isover er vist i figur 5. Her er vist middelværdier målt<br />
over fem døgn (60 målinger) for at udjævne døgnvariationen ved brug af boligens<br />
funktioner. I bilag B, figur 166 er alle måleværdier for lejligheden vist.<br />
Temperatur og relativ luftfugtighed målt i samtlige lejligheder er vist i bilag B,<br />
figur 151 til figur 174.<br />
15
16<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
-10<br />
Lejlighed B 1.6, Isover<br />
september 01 januar 02 juni 02 oktober 02<br />
Tid [måned:år]<br />
marts 03<br />
Stue, RF<br />
Stue, T<br />
Kontor, RF<br />
Kontor, T<br />
Bad, RF<br />
Bad, T<br />
Figur 5. Middelværdier af temperatur og relativ luftfugtighed målt over 5 døgn i en bolig isoleret med<br />
formstykker af mineraluld i form af glasuld fra Isover. <strong>Måling</strong>erne er foretaget i stuen, i kontoret og i<br />
badeværelset.<br />
<strong>Måling</strong> af temperatur og relativ luftfugtighed i den enkelte bolig havde til formål,<br />
at dokumentere det indeklima konstruktionerne blev <strong>på</strong>virket af. Resultaterne<br />
peger <strong>på</strong> en brug af de enkelte boliger, som er i overensstemmelse<br />
med almindelig brug, idet de observerede temperaturer og relative luftfugtigheder<br />
er inden for det, der i Bygningers fugtisolering (Andersen, Christensen<br />
& Nielsen, 1999) angives som svarende til en almindelig brug af boligen.<br />
Eksempler <strong>på</strong> temperaturer og relative luftfugtigheder målt udendørs er<br />
vist i figur 6. Her er vist middelværdier målt over fem døgn (60 målinger) for<br />
at udjævne døgnvariationen. I bilag C, figur 175 er angivet temperaturer målt<br />
uden for blokkenes teknikrum og i figur 176 temperatur og relativ luftfugtighed<br />
i teknikrummene.<br />
De TinyTags der målte temperaturer udendørs skulle også måle den relative<br />
luftfugtighed udendørs, men bortset fra de to viste måleserier, var måleværdierne<br />
ikke <strong>på</strong>lidelige. En nærmere undersøgelse viser, at TinyTags anvendelsesinterval<br />
op til 95 % relativ luftfugtighed øjensynlig skal tages meget<br />
bogstaveligt, da målinger tæt <strong>på</strong> grænseværdien ofte resulterer i et 100 %<br />
udslag. Den efterfølgende kalibrering ved 80 % relativ luftfugtighed og ca. 23<br />
°C af de TinyTags der var anvendt udendørs, viste en fejl <strong>på</strong> målingerne, så<br />
måleværdierne blev ca. 5% for høje.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Udendørs ved udhus<br />
-10<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Tid [måned:år]<br />
Ved blok A, RF Ved blok C, RF Ved blok A, T Ved blok C, T<br />
Figur 6. Middelværdier af temperatur og relativ luftfugtighed målt over fem døgn udendørs ved et udhus<br />
i blok A og blok C.<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
RF [%]<br />
RF [%]
Undersøgelsesmetode<br />
For at undersøge om der sker en skadelig fugtophobning i konstruktionerne,<br />
måles over to vintre fugtindholdet i isoleringen, dels for at sikre at en evt. høj<br />
fugtophobning den første vinter ikke skyldes byggefugt, og dels for at få målt<br />
om der sker en tilstrækkelig udtørring i løbet af forår og sommer.<br />
Fugtindholdet måles i facade og loftisoleringen i følgende punkter:<br />
– I facader mod vest måles der for hver type isoleringsmateriale i facader<br />
ud for stue og værelse.<br />
– I facader mod øst måles der for hver type isoleringsmateriale i facader ud<br />
for bad og ud for værelse eller køkken, således at der for hvert isoleringsmateriale<br />
bliver målt i en facade ud for et værelse og køkken.<br />
– I loftkonstruktionen måles der for hver type isoleringsmateriale over bad<br />
og køkken.<br />
I hvert punkt bliver fugtindholdet målt i den varme og i den kolde side af isoleringen.<br />
I facaderne måles der ca. 400 mm over bundremmen, se figur 4 og<br />
ca. 40 mm under facadeisoleringens øverste kant, begge steder midt mellem<br />
to træstolper. For loftisoleringen af løsuld er målerne, til måling i den kolde<br />
side af isoleringen, anbragt i en højde, der er ca. 40 mm lavere end den beregnede<br />
isoleringstykkelse (tabel 2). Dette betyder, at der for løsuldsprodukter<br />
kan være op til 80 mm isolering over målepunktet <strong>på</strong> grund af den i<br />
DS 418 krævede overtykkelse til sætning.<br />
Fugtmåler<br />
Fugtmålerne består af en fugtmåledyvel af bøgetræ og en termistor til måling<br />
af temperaturen (til korrektion). Fugten bestemmes ved måling af modstanden<br />
mellem to elektroder, der er presset ned i trædyvelen. Modstanden omregnes<br />
til fugtindhold ved hjælp af kalibreringskurver (Brandt, Hjorslev Hansen,<br />
Hommel Hansen & Mossing, 1998). Fugtindholdet angives, selv om det<br />
er målt i et isoleringsmateriale, som vægtpct. fugt i træ (træ-fugt), dvs. svarende<br />
til fugtindholdet i trædyvelen.<br />
Kalibrering af fugtmåledyvlerne er tidskrævende og dermed forbundet<br />
med store omkostninger. Derfor kalibreres de enkelte fugtdyvler ikke, men<br />
inden forsøgene kontrolleres fugtdyvlerne samlet ved 80 % relativ luftfugtighed<br />
og 23 ° C. Kravet for godkendelse af den enkelte fugtdyvel er, at målingen<br />
ikke afviger mere end 5 % fra middelværdien af alle målingerne.<br />
Fugtmåledyvler og termistorer er parvist monteret <strong>på</strong> pvc-vinkler, der er<br />
skruet fast i henholdsvis bagvæggen eller forskallingen i loftkonstruktionen.<br />
På pvc-vinklerne er der monteret en såkaldt ”node” (engelsk: knudepunkt),<br />
hvortil fugtmåledyvler og termistorer er forbundet. I hver blok er alle ”nodes”<br />
serieforbundet til en PC, som bruges til at opsamle data.<br />
Dataopsamling<br />
Dataopsamlingen foregår ved hjælp af et PC styret program med automatisk<br />
gem af data og automatisk genopstart ved strømafbrydelse. I forsøgsperioden<br />
blev modstanden i dyvler og temperaturer målt og registreret 2 gange<br />
dagligt (kl. 12 og kl. 00). I måleperioden er der enkelte udfald af data, fordi<br />
dataloggeren til måleudstyret brød sammen. Nogle af dataene for den ene<br />
lejlighed isoleret med Perlite mangler, fordi ledningen til de serieforbundne<br />
målepunkter er afbrudt. Bruddet <strong>på</strong> ledningen kunne ikke lokaliseres, hvorfor<br />
forbindelsen ikke umiddelbart kunne genoprettes og dataene anses derfor<br />
for at være tabt.<br />
Enkelte termistorer til måling af temperaturen i et målepunkt er i forsøgsperioden<br />
holdt op med at fungere. Temperaturmålinger fra tilsvarende målepunkter<br />
i samme isoleringsmateriale er derfor benyttet ved beregningen af<br />
fugtindholdet.<br />
17
18<br />
Forsøgsperiode<br />
Byggeriet, instrumentering og indbygning af forsøgsudstyr blev udført i perioden<br />
fra december 2000 til september/oktober 2001.<br />
Forsøgene blev gennemført i perioden september (blok B og C)/oktober<br />
(blok A) 2001 til april 2003.<br />
Resultater vedrørende fugtophobning<br />
Temperaturforløb og fugtindhold i samtlige målepunkter i isoleringsmaterialet<br />
i hver enkelt bolig er optegnet i de grafer, der er vedlagt som figur 45 til figur<br />
150 i bilag A. For den enkelte bolig omfattet af undersøgelsen er temperaturer<br />
i loftisoleringen og i facaderne henholdsvis mod vest og øst, og fugtindhold<br />
i loftisoleringen og i facaderne henholdsvis mod vest og øst vist. Målepunkternes<br />
placering er beskrevet i afsnittet "Undersøgelsesmetode".<br />
Eksempler <strong>på</strong> målte temperaturer fra en lejligheden isoleret med formstykker<br />
af mineraluld i form af glasuld fra Isover er vist i figur 7 til figur 9. De<br />
målte temperaturer er vist som middelværdier af temperaturer målt over en<br />
periode <strong>på</strong> fem døgn (10 målinger). Temperaturen er målt i isoleringen <strong>på</strong><br />
henholdsvis den side som vender mod boligen (den varme side) og den side<br />
der vender mod det fri (den kolde side). Figur 7 viser temperaturer målt i<br />
loftisoleringen. Figur 8 viser temperaturer målt i vestvendt væg og figur 9 viser<br />
temperaturer målt i facadeisoleringen i en østvendt væg.<br />
Temperatur [ o C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.6, Isover, Loft<br />
-10<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Tid [måned:år]<br />
Loft ov er bad mod det fri Loft ov er bad mod boligen<br />
Loft ov er køkken mod det fri Loft ov er køkken mod boligen<br />
Figur 7. Temperaturer i loftisoleringen over en bolig, der er isoleret med formstykker af mineraluld i form<br />
af glasuld fra Isover. Temperaturerne er målt i isoleringen i henholdsvis den side, som vender mod boligen<br />
og i den kolde side, der vender mod loftrummet, og er angivet som middelværdi over fem døgn.
Temperatur [ o C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.6, Isover, Facade mod V<br />
-10<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Værelse, nedre mod det fri<br />
Tid [måned:år]<br />
Værelse, nedre mod boligen Værelse, øv re mod det fri<br />
Værelse, øv re mod boligen Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øv re mod det fri Stue, øv re mod boligen<br />
Figur 8. Temperaturer i isoleringen i facaden mod vest i en bolig, der er isoleret med formstykker af mineraluld<br />
i form af glasuld fra Isover. Temperaturerne er målt i isoleringen i henholdsvis den side, som<br />
vender mod boligen og i den kolde side og er angivet som middelværdi over fem døgn.<br />
Temperatur [ o C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.6, Isover, Facade mod Ø<br />
-10<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Bad, nedre mod det fri<br />
Tid [måned:år]<br />
Bad, nedre mod boligen Bad, øv re mod det fri<br />
Bad, øv re mod boligen Køkken, nedre mod det fri Køkken, nedre mod boligen<br />
Køkken, øv re mod det fri Køkken, øv re mod boligen<br />
Figur 9. Temperaturer i isoleringen i facaden mod øst i en bolig, der er isoleret med formstykker af mineraluld<br />
i form af glasuld fra Isover. Temperaturerne er målt i isoleringen i henholdsvis den side, som vender<br />
mod boligen og i den kolde side og er angivet som middelværdi over fem døgn.<br />
Eksempeler <strong>på</strong> fugtmålinger er vist i figur 10 til figur 12 for lejligheder isoleret<br />
med formstykker af mineraluld i form af glasuld fra Isover. Fugtindholdet er<br />
vist som middelværdi af træ-fugt målt over en periode <strong>på</strong> fem døgn (10 målinger).<br />
Fugtindholdet er målt i isoleringen <strong>på</strong> henholdsvis den side som vender<br />
mod boligen (den varme side) og den side der vender mod det fri (den<br />
kolde side). Fugtindholdet i isoleringsmaterialet er målt med trædyvel. Dyvelernes<br />
fugtindhold er i ligevægt med, og derfor et udtryk for, den relative<br />
luftfugtighed, som der er i isoleringen rundt om måledyvlen. Figur 10 viser<br />
fugtindhold i loftisoleringen. Figur 11 viser fugtindhold i isolering i facaden,<br />
som vender mod vest, og figur 12 viser fugtindhold i isolering i facaden, som<br />
vender mod øst.<br />
19
20<br />
Fugtindhold [vægt-%]<br />
20,0<br />
19,0<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.6, Isover, Loft<br />
10,0<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Tid [måned:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 10. Fugtindhold i loftisoleringen over en bolig, der er isoleret med formstykker af mineraluld i form<br />
af glasuld fra Isover. Fugtindholdet er målt i isoleringen i henholdsvis den side, som vender mod boligen<br />
og i den kolde side, der vender mod loftrummet. Fugtindholdet er angivet som vægtpct. i træ og som<br />
middelværdi over fem døgn.<br />
Fugtindhold [vægt-%]<br />
20,0<br />
19,0<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.6, Isover, Facade mod V<br />
10,0<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Tid [måned:år]<br />
Værelse, nedre mod det fri Værelse, nedre mod boligen Værelse, øvre mod det fri<br />
Værelse, øvre mod boligen St ue, nedre mod det f ri Stue, nedre mod boligen<br />
St ue, øvre mod det fri St ue, øvre mod boligen<br />
Figur 11. Fugtindhold i isoleringen i facade mod vest i en bolig, der er isoleret med formstykker af mineraluld<br />
i form af glasuld fra Isover. Fugtindholdet er målt i isoleringen i henholdsvis den side, som vender<br />
mod boligen og i den kolde side. Fugtindholdet er angivet som vægtpct. i træ og som middelværdi over<br />
fem døgn.<br />
Fugtindhold [vægt-%]<br />
20,0<br />
19,0<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.6, Isover, Facade mod Ø<br />
10,0<br />
september 01 januar 02 juni 02 oktober 02 marts 03<br />
Tid [måned:år]<br />
Bad, nedre mod det fri Bad, nedre mod boligen Bad, øvre mod det fri<br />
Bad, øvre mod boligen Køkken, nedre mod det fri Køkken, nedre mod boligen<br />
Køkken, øvre mod det fri Køkken, øvre mod boligen<br />
Figur 12. Fugtindhold i isoleringen i facade mod øst i en bolig, der er isoleret med formstykker af mineraluld<br />
i form af glasuld fra Isover. Fugtindholdet er målt i isoleringen i henholdsvis den side, som vender<br />
mod boligen og i den kolde side. Fugtindholdet er angivet som vægtpct. i træ og som middelværdi over<br />
fem døgn.
I tabel 3 til 5 er angivet det højeste fugtindhold om vinteren målt i den kolde<br />
side i henholdsvis loft- og facadeisoleringen. Værdierne er aflæst af graferne<br />
i bilag A, som den højeste værdi for hver af de to vintre, der er dog set bort<br />
fra deciderede spidsværdier der kan være fejlbehæftet og som under alle<br />
omstændigheder er så kortvarige at de er uden praktisk betydning.<br />
Middelværdien af de aflæste fugtindhold i <strong>alternative</strong> <strong>isoleringsmaterialer</strong> i<br />
facader er 13,3 træ-fugt og i mineraluld 13,6 træ-fugt.<br />
Tabel 3. Højeste fugtindhold i vægtpct. træ-fugt om vinteren i loftisoleringen i den kolde side, målt over<br />
bad og køkken.<br />
Lejlighed 1 Lejlighed 2<br />
1. Vinter 2. Vinter 1. Vinter 2. Vinter<br />
Bad Køkken Bad Køkken Bad Køkken Bad Køkken Middelværdi<br />
Ekofiber 12,5 12,5 12,5 12,5 12 12,5 12 12,5 12,4<br />
Isodan 13 14,5 12 13,5 13,5 12,5 12,5 12,5 13<br />
Papiruld 15 13 15 13 12,5 12,5 12,5 12,5 13,3<br />
Thermocell 14,5 14 12 12 14,5 14,5 12 12 13,2<br />
Høruld i f. st. 12,5 12,5 12,5 12,5 12 12 12 12 12,3<br />
Heraflex 13,5 12 12,5 12,5 14 12,5 12,5 12,5 12,8<br />
Perlite 12,5 12,5 12,5 12,5 13,5 12,5 12,7<br />
Rockwool 14,5 13 12,5 12 14 15 12 12,5 13,2<br />
Isover 14 12 12,5 12 12,5 12 12,5 12 12,4<br />
Tabel 4. Højeste fugtindhold i vægtpct. træ-fugt om vinteren i isoleringen ved fodremmen i facaden mod<br />
vest i den kolde side, målt ud for stue og værelse.<br />
Lejlighed 1 Lejlighed 2<br />
1. Vinter 2. Vinter 1. Vinter 2. Vinter<br />
Stue Værelse Stue Værelse Stue Værelse Stue Værelse Middelværdi<br />
Ekofiber 13 13 12 12 13,5 13,5 12 12 12,6<br />
Isodan 12,5 12,5 12 12 12,5 12,5 12 12 12,3<br />
Papiruld 12,5 12,5 12,5 12,5 13 13 12,5 12,5 12,6<br />
Thermocell 14,5 14,5 12,5 12,5 14,5 14,5 12 13 13,5<br />
Høruld i f. st. 15,5 15,5 14 14 13 15 12,5 15 14,3<br />
Heraflex 13 13 12,5 12,5 12 12 12 12 12,4<br />
Perlite 13,5 13,5 12,5 12,5 13<br />
Rockwool 16 13 13 12 14,5 14,5 13 13,5 13,7<br />
Isover 13,5 13,5 12,5 12,5 15 18 13,5 16 14,3<br />
Tabel 5. Højeste fugtindhold vægtpct. træ-fugt om vinteren i isoleringen ved fodremmen i facaden mod<br />
øst i den kolde side, målt ud for bad og værelse eller køkken.<br />
Lejlighed 1 Lejlighed 2<br />
1. Vinter 2. Vinter 1. Vinter 2. Vinter<br />
Bad Værelse Bad Værelse Bad Køkken Bad Køkken Middelværdi<br />
Ekofiber 13,5 14,5 12,5 12,5 13,5 14 12,5 12,5 13,2<br />
Isodan 15 15 12,5 12,5 15 15 12,5 12,5 13,8<br />
Papiruld 15 14,5 12,5 12,5 14,5 15 12,5 12,5 13,5<br />
Thermocell 16,5 16,5 15,5 15,5 16 15 15 14 15,5<br />
Høruld i f. st. 14,5 13 14 13 14 14 13 13 13,6<br />
Heraflex 12,5 12,5 12,5 12,5 13,5 12 12 12 12,4<br />
Perlite 15 17 12,5 13,5 16 12 14,3<br />
Rockwool 15 15,5 12 14 15,5 15 12,5 13 14,1<br />
Isover 12 14 12 12 13 13 12 12 12,5<br />
21
22<br />
Diskussion<br />
I diskussionen af forsøgsresultaterne indgår en vurdering af forsøgs<strong>på</strong>virkninger,<br />
usikkerhed <strong>på</strong> målingerne, og kriterier for acceptabelt fugtindhold.<br />
Klima<strong>på</strong>virkning<br />
Klima<strong>på</strong>virkningerne <strong>på</strong> konstruktionerne er temperatur og relativ luftfugtighed<br />
i den enkelte bolig og udendørs. <strong>Måling</strong>erne peger <strong>på</strong> en brug af boligerne,<br />
som er i overensstemmelse med almindelig brug. Ved vurdering af<br />
resultaterne skal der derfor tages højde for, at andre boliger kan have en<br />
højere fugt<strong>på</strong>virkning indefra, og at dette kan medføre en højere fugtophobning<br />
i konstruktionerne.<br />
Usikkerhed<br />
Års målinger af fugtindhold i konstruktioner, målt med fugtmåledyvler, hos<br />
By og Byg, har vist, at målingerne har en måleusikkerhed <strong>på</strong> 1-2 % træ-fugt.<br />
Kriterier<br />
Kriteriet for vurdering af, om der i konstruktionerne forekommer et uacceptabelt<br />
højt fugtindhold, er 20 % træ-fugt ved en temperatur <strong>på</strong> 5 °C. Dette er<br />
det normalt anvendte kriterium for vurdering af risiko for vækst af råd og<br />
trænedbrydende svampe. Det har dog været diskuteret, om kriterierne skulle<br />
ændres til et fugtindhold <strong>på</strong> 15 % træ-fugt <strong>på</strong> grund af risikoen for skimmelvækst,<br />
(Nevander og Elmarsson, 1994).<br />
Nyere forskning peger <strong>på</strong>, at der for træbaserede produkter ikke er risiko<br />
for skimmelvækst ved 20 °C når fugtniveau er under 16 % træ-fugt; at der er<br />
en svag risiko ved 16-18 % træ-fugt; middel risiko ved 18-20 % træ-fugt og<br />
stor risiko når fugtniveauet er over 20 % træ-fugt hvis opfugtningen er langvarig<br />
(By og Byg anvisning 204). I dette arbejde er det valg at fastholde<br />
grænsen for det maksimale fugtindhold <strong>på</strong> 20 % træ-fugt ved 5 °C.<br />
Fugtophobning i <strong>isoleringsmaterialer</strong><br />
Af figurerne i bilag A og tabel 3 til tabel 5 fremgår, at det maksimale fugtindhold<br />
i <strong>isoleringsmaterialer</strong>ne er 16,5 % træfugt. Disse værdier er målt i ydersiden<br />
af isoleringen om vinteren, hvor temperaturen har været lav (mellem 5<br />
og 10 °C).<br />
Selv om der er usikkerhed <strong>på</strong> målingerne og fugtindholdet kan blive højere,<br />
hvis den relativ luftfugtighed i boligerne er højere, har alle konstruktioner,<br />
uanset anvendt isoleringsmateriale, et fugtindhold der ligger under kriteriet<br />
<strong>på</strong> 20 % træ-fugt.<br />
Selv om der er forskel <strong>på</strong> de målte fugtophobninger i de forskellige <strong>isoleringsmaterialer</strong>,<br />
er forskellene ikke signifikante. Middelværdien af fugtindholdet<br />
målt i alle de <strong>alternative</strong> <strong>isoleringsmaterialer</strong> i facaderne er 13,3 % træfugt<br />
og i mineraluld er middelværdien 13,6 % træ-fugt. Der er altså ikke signifikant<br />
forskel mellem middelværdien for fugtophobningen i <strong>alternative</strong> <strong>isoleringsmaterialer</strong><br />
og middelværdien for fugtophobningen i mineralulds baserede<br />
<strong>isoleringsmaterialer</strong>.<br />
Af figurerne i bilag A og tabel 3 til tabel 5 fremgår, at fugtindholdet i facaden,<br />
målt i ydersiden af isoleringen, er lidt højere den første vinter end den<br />
anden vinter. Dette indikerer, at der har været indbygget en vis mængde<br />
byggefugt.
Er isoleringsarbejdet udført korrekt?<br />
For at undersøge om isoleringsarbejdet er udført korrekt, dvs. om isoleringsmaterialet<br />
udfylder det hulrum, der skal isoleres, foretages en termografering<br />
af de indvendige overflader under vinterforhold. Ved termograferingen registreres<br />
de indvendige overfladers temperatur. Lokalt forekommende temperaturforskelle<br />
kan indikere, at isoleringsarbejdet ikke er udført korrekt. Lokalt<br />
forekommende temperaturforskelle kan også skylles kuldebroer som ikke<br />
kan relateres til de isolerede konstruktioner.<br />
Termografering<br />
Overflader med en temperatur over det absolutte nulpunkt (-273 °C) udstråler<br />
varme. Jo varmere overfladen er, desto mere intens er udstrålingen.<br />
Mennesket kan kun se varmen fra overflader med en temperatur <strong>på</strong> mindst<br />
500 °C. Ved bestemmelse af temperaturen <strong>på</strong> overflader, hvor temperaturen<br />
er under 500 °C, kan termografering anvendes, idet udstyret, der anvendes<br />
til termografering, kan "se" varmestråling fra en overflade med meget lavere<br />
temperaturer end det menneskelige øje kan se. Ved termograferingen omsættes<br />
intensiteten af strålingen fra en overflade til en temperatur. Til denne<br />
beregning benyttes en omregningsformel og kendskabet til overfladens<br />
egenskaber for udstråling, også kaldet emissiviteten.<br />
<strong>Måling</strong>er<br />
Termografering kan foretages indefra eller udefra. Selv om bagvægge af letklinkerbeton<br />
til en vis grad vil udjævne lokalt forekommende temperaturforskelle,<br />
er termograferingen i dette projekt foretaget indefra, idet der ikke kan<br />
termograferes udefra, når facaden er udført med en ventileret luftspalte.<br />
Der blev foretaget termografering af alle lejligheder, med undtagelse af de<br />
seks lejligheder i underetagen.<br />
Termografien blev foretaget den 12. og 13. februar 2003, ved ca. -1 °C.<br />
Vejret var stabilt, med nogen sol i løbet af dagen og svag til let vind mest fra<br />
sydøst.<br />
Termograferingen blev foretaget med et AGEMA 570 kamera, der var kalibreret<br />
forud for målingerne. Ved måling med kameraet kræves kendskab til<br />
overfladernes emissivitet samt omgivelsernes temperatur og relative luftfugtighed.<br />
Emissiviteten er valgt til 0,68, som er emissiviteten for hvidt papir,<br />
idet overfladerne i de enkelte lejligheder er hvidmalet tapet. Mørke overflader,<br />
fx mørkt træ og læder, har en anden emissivitet end de hvide vægge.<br />
Dette medfører, at mørke overflader <strong>på</strong> de termografiske billeder vil fremstå,<br />
som om de har en højere temperatur end de hvide overflader. Referanceværdier<br />
for temperatur og relativ luftfugtighed blev indtastet i termograferingsudstyret<br />
ud fra målinger taget <strong>på</strong> stedet.<br />
Resultat af termografering<br />
Ved termograferingen blev der registreret lokalt forekommende temperaturforskelle<br />
mellem lokalt afgrænsede områder og et vægpartis generelle temperatur.<br />
De registrerede lokale temperaturforskelle blev efterfølgende opdelt<br />
i syv kategorier, der er anført i tabel 6.<br />
23
24<br />
Tabel 6. Registrerede lokalt forekommende områder med temperaturforskelle opdelt i syv kategorier.<br />
Kategori<br />
A Kolde overgange mellem lejlighedsskel og loft<br />
B Koldt hjørner mellem lejlighedsskel og facade<br />
C Kolde fodpaneler langs facade<br />
D Kolde områder ved spær, lagt an <strong>på</strong> bagvæg af letklinkerbeton<br />
E Kolde områder i den isolerede facade<br />
F Kolde områder i den isolerede facade langs loftet<br />
G Kolde hjørner mellem lejlighedsskel/gavl, loft og facader<br />
Registreringen af overfladetemperaturer ved termografering sker i form af<br />
termografiske farvebilleder. Billederne er digitale og temperaturen i billedets<br />
enkelte punkter aflæses ved hjælp af et PC baseret program.<br />
I Figur 14 til figur 38 er vist en række eksempler <strong>på</strong> områder, hvor der er<br />
registret lokale temperaturforskelle. Temperaturforskellene forekommer i de<br />
digitale billeder som lokalt afgrænsede områder og dets temperatur sættes i<br />
forhold til den <strong>på</strong>gældende vægs generelle temperatur. Figurerne er grupperet<br />
efter kategori jvf. tabel 6, og for hver kategori er årsagen til temperaturforskellen<br />
søgt belyst, idet nogle temperaturforskelle sandsynligvis skylles<br />
kuldebroer i den valgte konstruktion og andre isoleringsfejl.<br />
I tabel 7 er, for de enkelte <strong>isoleringsmaterialer</strong>, angivet de temperaturforskelle,<br />
der er registret inden for hver kategori. Der er ikke angivet, hvor<br />
mange områder eller hvor store arealer der med den angivede temperaturforskel,<br />
er registreret inden for hver isoleringsmateriale/kategori, fordi der<br />
kan være flere områder med temperaturforskelle end de i tabel 7 opførte,<br />
idet termograferingen ikke var total, da der fx ikke blev flyttet møbler før termograferingen.<br />
Middelværdien af de registrerede temperaturforskelle, inden for hver isoleringsmateriale,<br />
er vist i figur 13. Middelværdien af de registrerede temperaturforskelle<br />
<strong>på</strong> overflader, hvor konstruktionen er isoleret med <strong>alternative</strong><br />
isoleringsmateriale, er 3,4 °C og 3,1 °C når konstruktionen er isoleret med<br />
mineraluld.<br />
Tabel 7. Temperaturforskelle registret ved termografering opdelt efter isoleringsmateriale og kategori jvf.<br />
tabel 6. Temperaturforskelle er differencen mellem den <strong>på</strong>gældende vægs generelle temperatur og den<br />
laveste temperatur i et <strong>på</strong> væggen lokalt afgrænset område. For nogle <strong>isoleringsmaterialer</strong> og/eller kategorier<br />
blev der registreret flere lokalt afgrænsede områder med temperaturer forskellige fra den <strong>på</strong><br />
den øvrige væg. Der er da angivet den laveste og den højeste temperaturforskel. ”-” angiver at der ikke<br />
blev fundet områder med lokalt forekommende temperaturforskelle i den <strong>på</strong>gældende kategori.<br />
Kategori A<br />
°C<br />
B<br />
°C<br />
C<br />
°C<br />
D<br />
°C<br />
E<br />
°C<br />
F<br />
°C<br />
G<br />
°C<br />
Middel<br />
°C<br />
Ekofiber 2,5 2,0 4,3-8,3 0,9-1,5 2,4 3,1-5,4 4,2-5,8 3,4<br />
Isodan 4,9-5,1 1,0 4,7-8,3 1,4-1,5 - 1,6-3,8 2,6-4,9 2,9<br />
Papiruld 5,1 - 2,0-9,0 - - 3,4 5,7 2,8<br />
Thermocell 3,5-4,2 1,3-2,0 4,0-10,6 1,3-1,8 4,2 - 1,8-2,6 3,0<br />
Høruld i formstykker 3,1-5,2 - 5,8-8,8 1,5-3,8 - 2,6 5,3 2,7<br />
Heraflax 4-6,3 - 6,5-12,3 2,3 - 2,5 7,2 3,8<br />
Perlite 5,6 1,7 2,3-6,6 1,0-3,1 - 4,9-8,2 13,6 5,3<br />
Rockwool 4,4-6,5 1,2 0,5-9,3 1,3 - 2,0 3 2,8<br />
Isover 4,4-6,4 1,0-1,3 3,2-6,8 0,8-1,5 4,2 5,3 1,8 3,4
Temperatur [° C]<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
Ekofiber<br />
Isodan<br />
Papiruld<br />
Thermocell<br />
Høruld i f.st.<br />
Heraflex<br />
Perlite<br />
Isover<br />
Rockwool<br />
Figur 13. Middelværdien af de registrerede temperaturforskelle mellem temperaturen i lokalt afgrænsede<br />
områder og temperaturen <strong>på</strong> den øvrige væg <strong>på</strong> indvendige overflader, som funktion af hvilket isoleringsmateriale<br />
konstruktionen er isoleret med.<br />
Bemærkninger til termografering<br />
Kategori A: Kolde overgange mellem lejlighedsskel og loft<br />
Lejlighedsskel dækker dels over de traditionelle lejlighedsskel mellem to ved<br />
siden af hinanden i samme vandrette plan beliggende lejligheder, dels over<br />
længehusenes afsluttende afgrænsning vinkelret <strong>på</strong> facaden, herunder udadgående<br />
hjørner ved husets gavl og indhakket ved længehusenes indgangspartier.<br />
Lejlighedsskellet er opført af 100 mm letklinkerbetonelementer<br />
ført op gennem loftrummet til lige under tagkonstruktionen. Tagrummet er<br />
ventileret og alle de termograferede lejligheder viste sig at have en kold<br />
overgang mellem loftet og lejlighedsskellet eller gavlen i lejlighedens fulde<br />
dybde, se figur 14 og figur 15.<br />
<strong>Måling</strong>erne viser, at denne løsning til brandsektionering af loftrummet<br />
mellem lejlighederne medfører kuldebroer.<br />
Figur 14. Overgang mellem lejlighedsskellene og loft i stue. Lejlighedens loft er isoleret med cellulose i<br />
form af genbrugspapir fra Miljøisolering. På det termografiske billede til venstre repræsenterer farven<br />
rød 23 °C og farven mørkeblå 18 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
25
26<br />
Figur 15. Overgang mellem lejlighedsskel (til venstre) og loft i soveværelse. Lejlighedens loft er isoleret<br />
med mineraluld i form af stenuld fra Rockwool. På det termografiske billede til venstre repræsenterer<br />
farven rød 19 °C og farven mørkeblå 13 °C. Til højre er vist et sædvanligt fotografi taget fra samme<br />
sted.<br />
Kategori B: Kolde hjørner mellem lejlighedsskel og facade<br />
Lejlighedsskel dækker dels over det traditionelle lodrette lejlighedsskel mellem<br />
to ved siden af hinanden i samme vandrette plan beliggende lejligheder<br />
dels over udadgående hjørne ved husets gavl.<br />
Hjørnesamlingen mellem gavl og facade giver traditionelt risiko for små<br />
svært tilgængelige hulrum. Gøres der isoleringsmæssigt ikke noget ekstraordinært<br />
for at isolere i hjørnet mellem facade og gavl vil hjørnet være lidt<br />
koldere end de tilstødende vægflader da netop hjørnet er <strong>på</strong>virket af kulden<br />
fra to sider, se figur 16 og figur 17.<br />
<strong>Måling</strong>erne viser, at hvis der i et byggeri ikke gøres noget ekstraordinært<br />
for varmeteknisk at sikre et velisoleret gavlhjørne, kan det medføre kuldebroer.<br />
Figur 16. Hjørne mellem lejlighedsskel (til venstre) og facade i værelse. Lejlighedens facade er isoleret<br />
med cellulose i form af træfiber fra Thermocell. På det termografiske billede til venstre repræsenterer<br />
farven blå 19 °C og farven rødgul 21 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 17. Hjørne mellem gavl, til højre og facade i soveværelse. Lejlighedens gavl og facade er isoleret<br />
med mineraluld i form af glasuld fra Isover. På det termografiske billede til venstre repræsenterer farven<br />
grøn 17 °C og farven rød 18 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.
Kategori C: Kolde fodpaneler langs facade<br />
Kolde fodpaneler langs facaden blev observeret i alle de termografisk registrerede<br />
lejligheder, hvor den indvendige letklinkerbetonvæg stod <strong>på</strong> fundamentet.<br />
Kolde fodpaneler blev ikke observeret <strong>på</strong> steder med en isoleret facade<br />
nedenunder. Fundamentet består af 300 mm <strong>på</strong> stedet støbt beton, der<br />
er afsluttet med lecablokke. På lecablokkene er bagvæggen af 100 mm letklinkerbetonelementer<br />
opsat. Soklen er pudset udvendigt.<br />
Denne opbygning af fundamentet og samling med bagvæggen har vist<br />
sig at give en væsentlig kuldebro ved fodpanelet inde i lejlighederne, se figur<br />
18 og figur 19. Til sammenligning viser figur 20 et fodpanel langs facaden i<br />
en stue, hvor ydervægsisoleringen er ført forbi etageadskillelsen, kun brudt<br />
af væggens bundrem, idet lejligheden ligger ovenover en tilsvarende lejlighed.<br />
Imellem underetagen og teknikrum er der i hver blok en passage/port, se<br />
figur 3. I lejligheder, der er beliggende over porten, er der observeret kolde<br />
fodpaneler, se figur 21 og figur 22.<br />
<strong>Måling</strong>erne viser en fundamentsløsning samt en løsning over en passage/port,<br />
der varmeteknisk ikke er særlig hensigtsmæssig.<br />
Figur 18. Fodpanel i soveværelse langs facade. På væggen langs facaden er der opsat et varmeapparat.<br />
Lejlighedens facade er isoleret med cellulose i form af genbrugspapir fra Isodan. På det termografiske<br />
billede til venstre repræsenterer farven mørkeblå 12 °C og farven gul 20 °C. Til højre er vist et<br />
sædvanligt fotografi taget fra samme sted.<br />
Figur 19. Fodpanel i stuen langs facade. Op til panelet mod facaden er der lagt et tæppe. Lejlighedens<br />
facade er isoleret med cellulose i form af genbrugspapir fra Isodan. På det termografiske billede til venstre<br />
repræsenterer farven mørkeblå 17 °C og farven rød 24 °C. Til højre er vist et sædvanligt fotografi<br />
taget fra samme sted.<br />
27
28<br />
Figur 20. Fodpanel i stuen langs facade. Lejligheden ligger ovenover en tilsvarende lejlighed og dens<br />
facade er isoleret med mineraluld i form af stenuld fra Rockwool. På det termografiske billede til venstre<br />
repræsenterer farven gul 22 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted. De røde<br />
farver, <strong>på</strong> det termografiske billede, vil normalt repræsentere overflader med en temperatur, der er højere<br />
end de 22 °C, der er målt <strong>på</strong> væggen. Den tilsyneladende højere temperatur skylles, at de mørke<br />
overflader har en anden emissivitet end den, væggen har og som kameraet er indstillet til.<br />
Figur 21. Fodpanel i stue langs facade. Lejlighedens facade er isoleret med plantefibre i form af høruld<br />
fra Heraklith. På det termografiske billede til venstre repræsenterer farven sortblå 10 °C og farven gul<br />
21 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted. Temperaturen <strong>på</strong> væggen over radiatoren<br />
er også 21 °C.<br />
Figur 22. Fodpanel i stue langs facade. Lejlighedens facade er isoleret med mineraluld i form af stenuld<br />
fra Rockwool. På det termografiske billede til venstre repræsenterer farven sortblå 13 °C og farven gul<br />
18 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted. Temperaturen <strong>på</strong> væggen over radiatoren<br />
er også 18 °C.<br />
Kategori D: Kolde områder ved spær, lagt an <strong>på</strong> bagvæg af<br />
letklinkerbeton<br />
Termografiske observationer af overgangen mellem facade og loft viser<br />
spærfodens kontaktpunkt med bagvæggen af letklinkerbeton som regelmæssige<br />
punktformede vel afgrænsede områder med temperaturforskelle<br />
<strong>på</strong> loft og væg. Afhængigt af hvor omhyggelig isoleringsarbejdet er udført<br />
omkring spærfoden vil de regelmæssige punktformede områder med temperaturforskelle<br />
i en omegn <strong>på</strong> loft og væg mod facaden være mere eller mindre<br />
vel afgrænsede, se figur 23 og figur 24.
<strong>Måling</strong>erne viser den varmetekniske konsekvens af at lægge spærfoden<br />
an mod bagvæggen af letklinkerbeton.<br />
Figur 23. Overgang mellem loft og facade i soveværelse. Lejlighedens loft og facade er isoleret med et<br />
mineralsk granulat i form af perlit fra Nordisk Perlite. På det termografiske billede til venstre repræsenterer<br />
farven gul 17 °C og farven mørkeblå 14 °C. Til højre er vist et sædvanligt fotografi taget fra samme<br />
sted.<br />
Figur 24. Overgang mellem loft og facade i stue. Lejlighedens loft og facade er isoleret med mineraluld i<br />
form af stenuld fra Rockwool. På det termografiske billede til venstre repræsenterer farven gul 23 °C og<br />
farven blå 21 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Kategori E: Kolde områder i den isolerede facade<br />
Kolde områder i den isolerede facade blev observeret i alle lejligheder under<br />
termograferingen. Under databehandlingen af de termograferede lejligheder<br />
blev der skelnet mellem lokalt afgrænsede kolde områder og kolde områder<br />
ved loft. Lokalt afgrænsede kolde områder i den isolerede facade blev observeret<br />
i nogle lejligheder under termograferingen. Områderne repræsenterer<br />
kuldebroer i facaden og viser sig <strong>på</strong> den indvendige side af det 100 mm<br />
tykke letklinkerbetonelement som afgrænsede kolde områder, se figur 25 til<br />
figur 27.<br />
<strong>Måling</strong>erne viser den varmeteknisk konsekvens af inhomogen varmeisolering<br />
af facaden. I afsnittet Beregning af hulrum er der, ved hjælp af et PCprogram<br />
til beregning af varmestrøm, beregnet, hvor stor inhomogenitet, der<br />
skal være i isoleringen for at give de målte temperaturforskelle.<br />
29
30<br />
Figur 25. Facade mellem vindue og øvre køkkenskabe i køkken. Lejlighedens facade er isoleret med<br />
cellulose i form af genbrugspapir fra Ekofiber. På det termografiske billede til venstre repræsenterer farven<br />
rød 20 °C, gul 19,6 °C og farven mørkeblå 17 °C. Til højre er vist et sædvanligt fotografi taget fra<br />
samme sted. Køkkenskabet ses i højre side af billedet.<br />
Figur 26. Facade under øvre køkkenskabe i køkken. Lejlighedens facade er isoleret med mineraluld i<br />
form af glasuld fra Isover. På det termografiske billede til venstre repræsenterer farven gul 19 °C og farven<br />
mørkeblå 14 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 27. Facade mellem to vinduer i stuen. Lejlighedens facade er isoleret med Cellulose i form af træfiber<br />
fra Thermocell. På det termografiske billede til venstre repræsenterer farven gul 21 °C og farven<br />
mørkeblå 16 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Kategori F: Kolde områder i den isolerede facade langs loftet<br />
Kolde områder i den isolerede facade langs overgangen mellem facaden og<br />
loftet blev observeret i de fleste lejligheder under termograferingen. Områderne<br />
repræsenterer kuldebroer i konstruktionen og viser sig <strong>på</strong> den indvendige<br />
side af det 100 mm tykke letklinkerbetonelement som et afgrænset<br />
koldt område, se figur 28 til figur 36. Samlingen mellem loft og facade giver<br />
risiko for små svært tilgængelige hulrum som kan give anledning til en kuldebro.<br />
Ved isolering af overgangen mellem facaden og loftet er det nødvendigt<br />
at sikre sig, at isoleringen ikke glider fra hinanden, samt at isoleringen<br />
samles så tæt, at kold luft ikke kan passere ind <strong>på</strong> den varme side af isoleringen.<br />
<strong>Måling</strong>erne viser den varmetekniske konsekvens af at isoleringen i facaden<br />
langs loftet er varmeledningsmæssig inhomogen. I afsnittet Beregning<br />
af hulrum er der, ved hjælp af et PC-program til beregning af varmestrøm,
eregnet, hvor store inhomogenitet der skal være i isoleringen, for at give de<br />
målte temperaturforskelle.<br />
Figur 28. Overgang mellem loft og facade i stue. Lejlighedens loft og facade er isoleret med cellulose i<br />
form af genbrugspapir fra Ekofiber. På det termografiske billede til venstre repræsenterer farven rød 20<br />
°C, gul 19 °C og mørkeblå 16 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 29. Overgang mellem loft og facade i stue. Lejlighedens loft og facade er isoleret med cellulose i<br />
form af genbrugspapir fra Ekofiber. På det termografiske billede til venstre repræsenterer farven rød 20<br />
°C, gul 19 °C og mørkeblå 14 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 30. Overgang mellem loft og facade i stue. I denne lejlighed er facaden vinklet. Lejlighedens loft<br />
og facade er isoleret med cellulose i form af genbrugspapir fra Isodan. På det termografiske billede til<br />
venstre repræsenterer farven gul 22 °C, grøn 20 °C og mørkeblå 17 °C. Til højre er vist et sædvanligt<br />
fotografi taget fra samme sted.<br />
31
32<br />
Figur 31. Overgang mellem loft og facade i soveværelse. Lejlighedens loft og facade er isoleret med<br />
cellulose i form af genbrugspapir fra Miljøisolering. På det termografiske billede til venstre repræsenterer<br />
farven gul 14 °C og mørkeblå 10 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 32. Overgang mellem loft og facade i soveværelse. Lejligheden er isoleret med mineraluld i form<br />
af glasuld fra Isover. På det termografiske billede til venstre repræsenterer farven gul 20 °C og blå 14<br />
°C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 33. Overgang mellem loft og facade i stue. Lejlighedens loft og facade er isoleret med plantefibre i<br />
form af høruld fra Dansk Naturisolering. På det termografiske billede til venstre repræsenterer farven<br />
grøn 20 °C og mørkeblå 17 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 34. Overgang mellem loft og facade i soveværelse. Lejlighedens loft og facade er isoleret med<br />
plantefibre i form af høruld fra Heraklith. På det termografiske billede til venstre repræsenterer farven<br />
gul 19 °C og mørkeblå 16 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.
Figur 35. Overgang mellem loft og facade i kontor. Lejlighedens loft og facade er isoleret med et mineralsk<br />
granulat i form af perlit fra Nordisk Perlite. På det termografiske billede til venstre repræsenterer<br />
farven gul 22 °C og mørkeblå 17 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Figur 36. Overgang mellem loft og facade i stue. Lejlighedens loft og facade er isoleret med mineraluld i<br />
form af stenuld fra Rockwool. På det termografiske billede til venstre repræsenterer farven gul 22 °C og<br />
blå 20 °C. Til højre er vist et sædvanligt fotografi taget fra samme sted.<br />
Kategori G: Kolde hjørner ved lejlighedsskel/gavl, loft og facade<br />
Kolde områder i hjørnet ved lejlighedsskel/gavl, loft og facade blev observeret<br />
i alle lejlighederne under termograferingen. Områderne repræsenterer<br />
kuldebroer i konstruktionen og viser sig <strong>på</strong> den indvendige side af det 100<br />
mm tykke letklinkerbetonelement som et afgrænset koldt område, se figur 37<br />
og figur 38. Samlingen ved lejlighedsskel/gavl, loft og facade giver risiko for<br />
små svært tilgængelige hulrum som derved kan give anledning til en introduceret<br />
kuldebro.<br />
<strong>Måling</strong>erne viser den varmetekniske konsekvens af varmeledningsmæssig<br />
inhomogenitet i isoleringen i hjørnet ved lejlighedsskel/gavl, loft og facade.<br />
Figur 37. Hjørne i køkken med lejlighedsskel til højre og facade til venstre. Lejlighedens loft og facade er<br />
isoleret med plantefibre i form af høruld fra Heraklith. På det termografiske billede til venstre repræsenterer<br />
farven rød 22 °C og farven mørkeblå 14 °C. Til højre er vist et sædvanligt fotografi taget fra samme<br />
sted.<br />
33
34<br />
Figur 38. Hjørne i kontor med facade til venstre og gavl til højre. Lejlighedens loft og facade er isoleret<br />
med et mineralsk granulat i form af perlit fra Nordisk Perlite. På det termografiske billede til venstre repræsenterer<br />
farven gul 21 °C og mørkeblå 8 °C. Til højre er vist et sædvanligt fotografi taget fra samme<br />
sted.<br />
Diskussion<br />
For at undersøge om isoleringsarbejdet er udført korrekt, dvs. om isoleringsmaterialet<br />
udfylder det hulrum, der skal isoleres, er der foretaget en termografering<br />
af de indvendige overflader under vinterforhold. Ved termograferingen<br />
registreres de indvendige overfladers temperatur og dermed lokalt<br />
forekommende afgrænsede områder med en temperatur forskellig fra temperaturen<br />
<strong>på</strong> den øvrige væg.<br />
Af tabel 7 fremgår at de registrerede temperaturforskelle varierer efter<br />
isoleringsmateriale og efter kategori. For at kunne foretage en sammenligning<br />
af <strong>isoleringsmaterialer</strong>ne, er middelværdien af lokalt forekommende<br />
temperaturforskelle beregnet for de enkelte <strong>isoleringsmaterialer</strong> og vist i<br />
figur 13.<br />
På overflader af konstruktioner, der er isoleret med <strong>alternative</strong> <strong>isoleringsmaterialer</strong>,<br />
er middelværdien af de registrerede temperaturforskelle 3,4 °C<br />
mod 3,1 °C <strong>på</strong> overflader af konstruktioner, der er isoleret med mineraluld.<br />
Middelværdien af de registrerede lokalt forekommende temperaturforskelle<br />
<strong>på</strong> overflader af konstruktioner, der er isoleret med det mineralske granulat,<br />
Perlite fra Nordisk Perlite lidt højere end middelværdierne for de øvrige <strong>isoleringsmaterialer</strong>.<br />
Middelværdien af de registrerede temperaturforskelle <strong>på</strong><br />
overflader af konstruktioner, der er isoleret med andre <strong>alternative</strong> <strong>isoleringsmaterialer</strong><br />
end Perlite er 3,1 °C.<br />
Selv om der er forskelle <strong>på</strong> de registrerede lokalt forekommende temperaturforskelle<br />
kan der ud fra de her refererede målinger ikke konstateres signifikante<br />
forskelle mellem temperaturforskelle <strong>på</strong> overflader af konstruktioner,<br />
der er isoleret med <strong>alternative</strong> <strong>isoleringsmaterialer</strong> og temperaturforskelle<br />
<strong>på</strong> overflader af konstruktioner, der er isoleret med mineraluld.<br />
Årsag til lokalt forekommende temperaturforskelle<br />
Årsagen til lokalt forekommende temperaturforskelle kan ikke med sikkerhed<br />
angives, uden at der foretages en destruktiv undersøgelse af konstruktionerne.<br />
Oprindeligt var det hensigten, at der skulle foretages termografiske<br />
observationer af de isolerede bygningsdele, umiddelbart efter at bygningsdelene<br />
var blevet isoleret. Hensigten med disse observationer var, sammenholdt<br />
med de senere termografiske observationer, at kunne skelne mellem<br />
hulrum opstået over tid og hulrum introduceret under isoleringsarbejdet. De<br />
termografiske observationer kræver temperaturfald over isoleringen, som<br />
opnås i vinterhalvåret. Da bebyggelsens isoleringsarbejde strakte sig over<br />
en periode ud over vinterhalvåret, ville nogle bygningsdele først kunne termograferes<br />
den efterfølgende vinter. På det tidspunkt ville hensigten med de<br />
første termografiske observationer ikke længere være til stede, da konstruktionerne<br />
dermed ikke var isoleret for nyligt. De termografiske observationer<br />
blev derfor ikke foretaget af de isolerede bygningsdele umiddelbart efter, at
ygningsdelene var blevet isoleret. Lokalt forekommende temperaturforskelle<br />
kan indikere følgende:<br />
– der er kuldebroer (som ikke er relaterede til de isolerede konstruktioner)<br />
– isoleringsarbejdet er ikke udført korrekt<br />
– der er efterfølgende sket sætninger i isoleringen.<br />
Der er øjensynligt væsentlige kuldebroer ved:<br />
– Fodpaneler langs facaden.<br />
– Overgangen mellem lejlighedsskel og loft.<br />
Der er øjensynligt mindre kuldebroer ved:<br />
– Spær lagt an <strong>på</strong> bagvæg.<br />
– Hjørner mellem lejlighedsskel/gavl og facade.<br />
Isoleringsarbejdet er øjensynligt ikke udført korrekt eller der er sket sætninger<br />
af isoleringen:<br />
– I lokale område i facaden.<br />
– I facaden langs loftet.<br />
Beregning af hulrum<br />
For at få et indtryk af isoleringsfejlene og/eller sætningerne, er der foretaget<br />
beregning af, hvor store hulrum der skal være i isoleringen, for at give de registrerede<br />
lokale temperaturforskelle.<br />
Beregningerne er gennemført med et kommercielt program HEAT 2, version<br />
5.0 (Lunds Universitet, 2002) til beregning af todimensionale varmestrømme<br />
svarende til at geometrien er fuldt bestemt ved det valgte tværsnit.<br />
HEAT 2 er et PC-baseret program til beregning af todimensional varierende<br />
eller stabile varmestrømme. PC programmets beregninger gennemføres i<br />
overensstemmelse med standarden ISO 10211-1 (International Organization<br />
for Standardization, 1995).<br />
Varmestrømsberegning<br />
Beregningerne er gennemført ved at opbygge en model af den anvendte<br />
konstruktion med de rette dimensioner og materialer. Varmeledningsevnen<br />
er for <strong>isoleringsmaterialer</strong> sat til 0,039 W/mK, idet dette skønnes at give en<br />
bedre overensstemmelse med de termografiske registreringer end de i tabel<br />
2 angivne værdier, der er med diverse tillæg. Da programmet kun kan beregne<br />
todimensionale varmestrømme er træstolperne i facaden og spærene<br />
i tagkonstruktionen ikke medtaget i modellen. De i modellen anvendte materialer,<br />
dimensioner og varmeledningsevner er vist i tabel 8. Modellen er opbygget<br />
med en indvendig væghøjde <strong>på</strong> 2,4 m og med en indvendig loftlængde<br />
<strong>på</strong> 1,5 m.<br />
35
36<br />
Tabel 8. Varmeledningsevne og tykkelse for de enkelte materialer anvendt i model til todimensionale<br />
beregninger af varmestrøm gennem facade og loft isoleret med Ekofiber. Varmeledningsevnen er for<br />
(alle) <strong>isoleringsmaterialer</strong> valgt til 0,039 W/mK, idet det skønnes at give en bedre overensstemmelse<br />
med de termografiske registreringer end de i tabel 2 angivne værdier, der er med diverse tillæg.<br />
Materialer Varmeledningsevne<br />
W/mK<br />
Tykkelse<br />
mm<br />
Træbeklædning 0,16 24<br />
Ventileret hulrum 0,24 22<br />
Vindgips 0,17 9<br />
Isolering i facade 0,039 200<br />
Letklinkerbetonelement 0,9 100<br />
Gips 0,17 26<br />
loftisolering 0,039 415<br />
Figur 39 viser grafisk den opbyggede model af facaden og samlingen mellem<br />
facaden og loftkonstruktionen. Modellen er vist med korrekt placeret facade-<br />
og loftisolering og med en ubrudt samling af facade- og loftisolering. I<br />
byggeriet er der anvendt facadekonstruktioner med toprem, men i de undersøgte<br />
konstruktioner er topremmen åbnet ved gennemsavning eller helt fjernet.<br />
I figur 40 er vist den tilsvarende grafiske model af facaden og samlingen<br />
mellem facaden og loftkonstruktionen, men med en toprem i facaden.<br />
Figur 39. Model til beregning af varmestrøm gennem facade og samlingen mellem facade og loftkonstruktion<br />
med korrekt placeret isolering. Modellens dimensioner er angivet i tabel 8.
Figur 40. Detalje af model til beregning af varmestrøm gennem samlingen mellem facade og loftkonstruktion<br />
med korrekt placeret isolering og med en toprem, se i øvrigt figur 39.<br />
Beregning af hulrum i facade isoleret med Ekofiber<br />
Med udgangspunkt i Kategori E: Kolde områder i den isolerede facade beregnes<br />
det ækvivalente hulrum som resulterer i de ved termografien registrerede<br />
lokalt forekommende temperaturforskelle. Hulrummet i isoleringen antages<br />
at være et luftfyldt rektangulært hulrum. Tabel 9 viser anvendte værdier<br />
til beregning af hulrummet. Ved beregningen er det forudsat, at der ikke er<br />
nogen varmestrøm gennem de afgrænsede snit vinkelret <strong>på</strong> facadens plan.<br />
Tabel 9. Parametre og anvendte værdier til beregning af et ækvivalent hulrum i isoleringen i en facade.<br />
Parameter Værdi med enhed<br />
Temperaturen ude -1 ° C<br />
Overgangsisolans ude 0,04 m2K/W Luftens varmekapacitet 1,239 kJ/(m3K) Luftskiftet 0 gange i timen<br />
Emissivitet til hulrummets 4 sider 0,9<br />
Konvektionskoefficienten 3 W/(m2K) Referencetemperaturen 10 °C<br />
Overgangsisolans inde (facade) 0,13 m2K/W Overgangsisolans inde (loft) 0,10 m2K/W Temperaturen inde 20 °C<br />
Figur 41 viser resultaterne af en varmestrømsberegning i en facade med et<br />
idealiseret hulrum i isoleringen. Hulrummet er <strong>på</strong> figur 41 angivet med symbolet<br />
1:1, og har en højde <strong>på</strong> 300 mm i hele isoleringens tykkelse. Hulrummet<br />
er beregnet ud fra det kriterium, at temperaturen <strong>på</strong> den indvendige<br />
vægoverflade i et lokalt afgrænset område skal være 2,4 °C lavere end temperaturen<br />
<strong>på</strong> den øvrige facadeindervæg, når der er isoleret med Ekofiber,<br />
jf. tabel 7. Hulrummets højde er fundet ved at foretage en varmestrømsbe-<br />
37
38<br />
regning med en gættet højde og derefter gentage beregningen med nye<br />
højder indtil den ønskede temperaturforskel er opnået.<br />
Figur 41. Temperaturforløb i facade med et idealiseret hulrum i isoleringen. Hulrummet, som er idealiseret<br />
ved at være rektangulært, er angivet med symbolet 1:1 og har en beregnet højde <strong>på</strong> 300 mm i hele<br />
isoleringens tykkelse. Hulrummets højde er beregnet ud fra det kriterium, at temperaturen <strong>på</strong> den indvendige<br />
vægoverflade, i et lokalt afgrænset område, skal være 2,4 °C lavere end temperaturen <strong>på</strong> den<br />
øvrige facadeindervæg, når der er isoleret med Ekofiber, jf. tabel 7. På figuren er temperaturfeltet omkring<br />
isotermen som repræsenterer 17 °C fremhævet med farven hvid (temperaturen <strong>på</strong> den indvendige<br />
vægoverflader <strong>på</strong> 19,4 °C minus temperatusænkningen <strong>på</strong> 2,4 °C).<br />
Temperatur ved overgangen mellem facade og loft<br />
Da overgangen mellem facade og loft er <strong>på</strong>virket af kulde fra to sider er det<br />
velkendt, at overgangen kan have en temperatur, der er lavere end temperaturen<br />
<strong>på</strong> tilstødende vægge og lofter. Den forventede lokale temperaturforskel<br />
i overgangen mellem facade og loft er beregnet med og uden toprem<br />
placeret langs letbetonelementets øvre kant for at vurdere topremmens indflydelse<br />
<strong>på</strong> den lokale temperaturforskel.<br />
Figur 42 og figur 43 viser resultaterne af en varmestrømsberegning af<br />
overgangen mellem facade og loft, henholdsvis med og uden en toprem<br />
øverst i facadeelementet. De til beregningen anvendte værdier er vist i tabel<br />
9. Ved beregningen er det forudsat at der ikke er nogen varmestrøm gennem<br />
de afgrænsende snit vinkelret <strong>på</strong> facadens plan.
Figur 42. Temperaturforløb i facade, loft og overgangen mellem facade og loft i en konstruktion med<br />
toprem. Topremmen har en højde <strong>på</strong> 45 mm. Temperaturen <strong>på</strong> midten af den indvendige vægoverflade<br />
er 19,5 °C. Temperaturen <strong>på</strong> den indvendige vægoverflade i overgangen mellem facadeelementet og<br />
loftet er 18,7 °C.<br />
Figur 43. Temperaturforløb i facade, loft og overgangen mellem facade og loft i en konstruktion uden<br />
toprem. Temperaturen <strong>på</strong> midten af den indvendige vægoverflader er 19,5 °C. Temperaturen <strong>på</strong> den<br />
indvendige vægoverflade i overgangen mellem facadeelementet og loftet er 19 °C.<br />
Beregning af hulrum langs loft i facaden isoleret med Ekofiber<br />
Med udgangspunkt i Kategori F: Kolde områder i den isolerede facade langs<br />
loftet beregnes det ækvivalente hulrum, i den isolerede del af facadekonstruktionen,<br />
som resulterer i de ved termografien registrerede lokale temperaturforskelle.<br />
Da forskellen <strong>på</strong> temperaturen <strong>på</strong> overgangen mellem facade<br />
og loft i konstruktion med og uden toprem kun er 0,3 °C, er der kun foretaget<br />
beregninger <strong>på</strong> konstruktioner uden toprem. Hulrummet i isoleringen anta-<br />
39
40<br />
ges at være et luftfyldt firkantet hulrum. Tabel 9 viser anvendte værdier til<br />
beregning af hulrummet. Ved beregningen er det forudsat at der ikke er nogen<br />
varmestrøm gennem de afgrænsende snit vinkelret <strong>på</strong> facadens plan.<br />
Figur 44 viser resultaterne af en varmestrømsberegningen omkring overgangen<br />
mellem facade og loft i en konstruktion uden toprem med et idealiseret<br />
hulrum i isoleringen. Hulrummet er <strong>på</strong> figur 44 angivet med symbolet 1:1<br />
og har en højde <strong>på</strong> 200 mm i hele isoleringens tykkelse. Hulrummet er beregnet<br />
ud fra det kriterium, at temperaturen i overgangen mellem facade og<br />
loft skal være 3,4 °C lavere end temperaturen <strong>på</strong> facadeindervæggen. Hulrummets<br />
højde er fundet ved at foretage en varmestrømsberegning med en<br />
gættet højde og derefter gentage beregningen med nye højder indtil den ønskede<br />
temperaturforskel er opnået.<br />
Figur 44. Temperaturforløb i facade, loft og overgangen mellem facade og loft i en konstruktion uden<br />
toprem med et idealiseret hulrum i isoleringen. Hulrummet, som er idealiseret ved at være rektangulært,<br />
er angivet med symbolet 1:1 og har en beregnet højde <strong>på</strong> 200 mm i hele isoleringens tykkelse. Hulrummets<br />
højde er beregnet ud fra det kriterium, at temperaturen <strong>på</strong> overgangen mellem facade og loft<br />
skal være 3,4 °C lavere end temperaturen <strong>på</strong> facadeindervægen. På figuren er temperaturfeltet omkring<br />
isotermen som repræsenterer 16 °C fremhævet med farven hvid (temperaturen <strong>på</strong> den indvendige<br />
vægoverflader <strong>på</strong> 19,4 °C minus temperaturforskellen <strong>på</strong> 3,4 °C).<br />
Beregnede hulrum<br />
Analog til beregningerne af de ækvivalente hulrum i konstruktioner isoleret<br />
med Ekofiber, er hulrum i konstruktioner isoleret med de øvrige <strong>isoleringsmaterialer</strong><br />
beregnet. Resultaterne er angivet i tabel 10. Der er beregnet hulrum<br />
for to kategorier: Kolde områder i den isolerede facade (Kategori E) og<br />
Kolde områder i den isolerede facade langs loftet (Kategori F).<br />
Da programmet, der er anvendt til beregningerne bygger <strong>på</strong> todimensionale<br />
varmestrømme, og varmestrømmene er mere eller mindre tredimensionale,<br />
vil programmet ikke altid give realistiske størrelse <strong>på</strong> de ækvivalente<br />
hulrum.
Tabel 10. Højden <strong>på</strong> idealiserede hulrum i isoleringen. Hulrummenes højde er beregnet ud fra det kriterium,<br />
at hulrummet skal resultere i en temperaturforskel <strong>på</strong> den indvendige vægoverflade, der svarer til<br />
de ved termografering registrerede temperaturforskelle, se tabel 7.<br />
Højde af ækvivalent hulrum<br />
kategori E<br />
mm<br />
Højde af ækvivalente hulrum<br />
kategori F<br />
mm<br />
Ekofiber 120 150-500<br />
Isodan - 36-450<br />
Papiruld - 225<br />
Thermocell 1000 -<br />
Høruld i formstykker - 65<br />
Heraflax - 55<br />
Perlite - 800<br />
Rockwool - 35<br />
Isover 1000 800<br />
Manglende isolering<br />
De beregnede ækvivalente hulrum er beregnet ud fra et modelleret tværsnit i<br />
facade og loft konstruktionen. I beregningerne indgår tal for varmeledningsevne<br />
for de anvendte materialer som konstruktionen er opbygget af. De anvendte<br />
tal for varmeledningsevne er ikke målte værdier. Beregningerne er<br />
derfor vejledende og kan kun bruges som en indikation af hvor stort et hulrum,<br />
der må kunne forventes i den isolerede del af konstruktionen.<br />
Hulrum kan opstå i den isolerede del af konstruktionen enten ved at isoleringsmaterialet<br />
er blevet inhomogent fordelt i forbindelse med udførelsen af<br />
arbejdet eller såfremt isoleringsmaterialet med tiden sætter sig eller kryber.<br />
41
42<br />
Litteratur<br />
Andersen T., Fynholm P., Hjorslev Hansen M., Nicolajsen A. (2002). Fugtsikre<br />
træfacader. Fugtindhold i højisolerede træfacader. (By og Byg Dokumentation<br />
025). Hørsholm: <strong>Statens</strong> Byggeforskningsinstitut.<br />
Andersen, N. E., Christensen, G. og Nielsen, F. (1993). Bygningers fugtisolering<br />
(SBI-anvisning 178). Hørsholm: <strong>Statens</strong> Byggeforskningsinstitut.<br />
Boligministeriet (1995). Bygningsreglement 1995. København.<br />
Brandt, E., Hjorslev Hansen, M., Hommel Hansen, O., & Mossing, P. (1998).<br />
<strong>Måling</strong> af træfugt ved modstandsmåling. Byggeindustrien, 49(5), 26-30.<br />
Breum, N. O., Schneider, T., Flyvholm, M,. Jørgensen, O,. Valdbjørn Rasmussen,<br />
T,. & Skibstrup Eriksen, S. (2002) Luftforureninger ved anvendelse<br />
af <strong>alternative</strong> <strong>isoleringsmaterialer</strong>. (Ami Rapport 57) København: Arbejdsmiljø<br />
Instituttet, & <strong>Statens</strong> Byggeforskningsinstitut.<br />
Dansk Ingeniørforening. (1986). Dansk Ingeniørforenings regler for beregning<br />
af bygningers varmetab (5. udg.) (Dansk Standard – DS 418 = Normstyrelsens<br />
publikationer NP-186-S). København: Teknisk Forlag.<br />
Dansk Standard. (2000). Tillæg 2 til DS 418, beregning af bygningers varmetab:<br />
Tillæg omhandlende løsfyldsprodukter (DS 418/Til.2). København.<br />
International Organization for Standardization (1995). 10211-1:1995 Thermal<br />
bridges in building construction – Heat flows and surface temperatures –<br />
Part 1: General calculation methods.<br />
Lund-Hansen, P. (1967). Fugttransport i byggematerialer (Meddelelse nr.<br />
15). Danmarks Tekniske Højskole, Laboratoriet for Varmeisolering. Lyngby:<br />
Polyteknisk Forlag.<br />
Lunds Universitet, Dept. Of Building Physics, Lund Group for Computational<br />
Building Physics. (2002). HEAT2 (version 5.0). Lund. [PC-program].<br />
Nevander, L. E. og Elmersson, B. (1994). Fukthandbok: Praktik och teori.<br />
Stockholm: Svensk Byggtjänst.<br />
Rasmussen, T. V. og Feilberg Hansen K. (2004). Praktiske erfaringer med<br />
<strong>alternative</strong> <strong>isoleringsmaterialer</strong> (By og Byg Resultater 036). Hørsholm: <strong>Statens</strong><br />
Byggeforskningsinstitut.<br />
Stang, B. D. (2002). Fugtforhold i træfacader med letbeton bagvægge. (By<br />
og Byg Dokumentation 033). Hørsholm: <strong>Statens</strong> Byggeforskningsinstitut.<br />
Valbjørn, O. (2003). Undersøgelse og vurdering af fugt og skimmelsvampe i<br />
bygninger. By og Byg anvisning 204. Hørsholm: <strong>Statens</strong> Byggeforskningsinstitut.
Summary<br />
By og Byg Documentation 058: Measurements of <strong>alternative</strong> insulating<br />
materials<br />
Onsite observations of moisture and temperature distribution in 9 different<br />
insulation materials<br />
Tests were made of the performance of 9 different materials used for thermal<br />
insulation in walls and attics on site. The materials included both loosefill<br />
materials and materials of a fixed shape, see Table 1. The assessment of<br />
the performance was based on thermographic observations and measurements<br />
of temperature and moisture conditions within the different materials<br />
used.<br />
The investigation covered two, in principle, identical observations of each<br />
material used for thermal insulation in two apartments. Measuring points<br />
were placed at identical locations in walls and attics in all apartments included<br />
in the investigation. The investigation covered a real-life situation<br />
where the inhabitants and normal weather conditions influenced the thermal<br />
insulation.<br />
Moisture conditions at the warm side and cold side of the materials, used<br />
for thermal insulation, were observed in the insulation material in the wall<br />
cavity and attics. Moisture measuring dowels of wood were used for these<br />
observations. For exterior walls the warm side faced the lightweight concrete<br />
wall that served as the load bearing constructional inner wall. The cold side<br />
of the exterior walls faced the wind barrier made of gypsum.<br />
All the moisture measurement results are expressed as wood moisture<br />
content (weight-%), so that the results can be compared with the danger<br />
zone of 20 % for dry-rot attack in timber. The moisture content within the<br />
material used for thermal insulation was recorded twice a day, at noon and<br />
at midnight. The external and the internal temperature, together with the external<br />
and internal relative humidity, were recorded once every 2 hours.<br />
Moisture accumulation for materials used for thermal insulation<br />
Observations of the moisture conditions within the materials used for thermal<br />
insulation showed no sign of moisture problems for the materials and construction<br />
used. The observed moisture content for the individual materials<br />
was below 20 % (wood moisture). However, the observed moisture content<br />
showed the presence of moisture related to the construction period.<br />
The individual materials, in exterior walls and attics, were influenced by<br />
environmental conditions, described by temperature and relative humidity<br />
related to a normal use of the apartments.<br />
Thermographic observations<br />
Thermographic observations of the insulated exterior walls and building<br />
parts showed a number of thermal bridges. The most important thermal<br />
bridges were related to the architectural design of the building. The two most<br />
important thermal bridges were observed at 1) the joint between foundation,<br />
the slab on the ground and the lightweight concrete wall serving as the load<br />
bearing inner wall, 2) the fire separation of the attic room between apartments<br />
and the apartment boundary. Observations also revealed, that for<br />
some of the insulated walls local areas were discovered with a lower temperature<br />
than seen for the overall wall, those indicating local pockets within<br />
43
44<br />
the insulated areas. Furthermore, it is shown that for some of the insulated<br />
walls, local areas towards the ceiling were discovered to have a lower temperature<br />
than the overall wall, indicating that settling or cold air was able to<br />
reach the inner wall. However, a minor temperature decrease was expected<br />
as the location had low temperature action from two sides, from the attic and<br />
the facade, respectively. One product could not be kept within the wall cavity,<br />
and larger areas were found to have a lower temperature than the overall<br />
wall.<br />
Suitable thermal insulation materials and specific design requirements<br />
Materials used for thermal insulation in walls and attics should meet the following<br />
performance requirements (i) acceptable thermal characteristics, (ii)<br />
ability to be handled on site, and (iii) performance staying the same during<br />
the acknowledged time compared with the lifetime of the construction. For<br />
the material to be able to maintain its performance, it has to keep its thermal<br />
characteristics and fill out the volume as intended. Former observations<br />
have shown that the described materials can be used on site. However,<br />
specifications to describe the tightness of the cavity intended to hold the<br />
materials were found to be needed together with quality assurance. Specifications<br />
to describe the tightness of the individual wall cavity has to be described<br />
on the basis of the characteristics of the material that the cavity is<br />
intended to hold.
Bilag A Temperatur og fugt i facade- og<br />
loftkonstruktioner<br />
Fugtindholdet er angivet som massepct. = vægtpct. fugt i træ, dels fordi<br />
fugtindholdet er målt med trædyvler, dels for umiddelbart at kunne sammenligne<br />
med faregrænsen for vækst af råd og trænedbrydende svampe <strong>på</strong> træ.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
Lejlighed A 1.1, Thermocell, Loft<br />
0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 45. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af træfiber. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.1, Thermocell, Facade mod V<br />
-5<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod det fri Værelse, V, øvre mod boligen<br />
Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øvre mod det fri Stue, øvre mod boligen<br />
Figur 46. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af træfiber.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
45
46<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.1, Thermocell, Facade mod Ø<br />
-5<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 47. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af træfiber.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Fugtindhold [masse-%]<br />
Lejlighed A 1.1, Thermocell, Loft<br />
15,00<br />
14,50<br />
14,00<br />
13,50<br />
13,00<br />
12,50<br />
12,00<br />
11,50<br />
11,00<br />
10,50<br />
10,00<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 48. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af træfiber. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.1, Thermocell, Facade mod V<br />
10,0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod det fri Værelse, V, øvre mod boligen<br />
Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øvre mod det fri Stue, øvre mod boligen<br />
Figur 49. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af træfiber.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.
Fugtindhold [masse-%]<br />
18,00<br />
17,00<br />
16,00<br />
15,00<br />
14,00<br />
13,00<br />
12,00<br />
11,00<br />
Lejlighed A 1.1, Thermocell, Facade mod Ø<br />
10,00<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 50. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af træfiber.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
Lejlighed A 1.2, Thermocell, Loft<br />
0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 51. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af træfiber. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.2, Thermocell, Facade mod V<br />
-5<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod det fri Værelse, V, øvre mod boligen<br />
Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øvre mod det fri Stue, øvre mod boligen<br />
Figur 52. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af træfiber.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
47
48<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.2, Thermocell, Facade mod Ø<br />
-5<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri Bad, nedre mod boligen<br />
Bad, øvre mod det fri Bad, øvre mod boligen<br />
Køkken, nedre mod det fri Køkken, nedre mod boligen<br />
Køkken, øvre mod det fri Køkken, øvre mod boligen<br />
Figur 53. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af træfiber.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed A 1.2, Thermocell, Loft<br />
10,0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 54. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af træfiber. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.2, Thermocell, Facade mod V<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod det fri Værelse, V, øvre mod boligen<br />
Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øvre mod det fri Stue, øvre mod boligen<br />
Figur 55. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af træfiber.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.2, Thermocell, Facade mod Ø<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri Bad, nedre mod boligen<br />
Bad, øvre mod det fri Bad, øvre mod boligen<br />
Køkken, nedre mod det fri Køkken, nedre mod boligen<br />
Køkken, øvre mod det fri Køkken, øvre mod boligen<br />
Figur 56. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af træfiber.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.3, HBC-Hør, Loft<br />
-5<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 57. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og i<br />
den side der vender mod den kolde side (loftrummet). Produktnavn: Heraflax.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
-10<br />
Lejlighed A 1.3, HBC-Hør, Facade mod V<br />
-15<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod det fri Værelse, V, øvre mod boligen<br />
Stue, nedre mod det fri Stue, nedre mod boligen<br />
Stue, øvre mod det fri Stue, øvre mod boligen<br />
Figur 58. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
høruld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side. Produktnavn: Heraflax.<br />
49
50<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.3, HBC-Hør, Facade mod Ø<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 59. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Produktnavn: Heraflax.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed A 1.3, HBC-Hør, Loft<br />
10,0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 60. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn:<br />
Heraflax.<br />
Fugtindhold [masse-%]<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed A 1.3, HBC-Hør, Facade mod V<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 61. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn: Heraflax.
Fugtindhold [masse-%]<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
10,0<br />
Lejlighed A 1.3, HBC-Hør, Facade mod Ø<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 62. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn: Heraflax.<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.4, HBC-Hør, Loft<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 63. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Produktnavn: Heraflax.<br />
51
52<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.4, HBC-Hør, Facade mod V<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 64. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
høruld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side. Produktnavn: Heraflax.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.4, HBC-Hør, Facade mod Ø<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 65. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Produktnavn: Heraflax.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed A 1.4, HBC-Hør, Loft<br />
10,0<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 66. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn:<br />
Heraflax.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed A 1.4, HBC-Hør, Facade mod V<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 67. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn: Heraflax.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.4, HBC-Hør, Facade mod Ø<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 68. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ. Produktnavn: Heraflax.<br />
53
54<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed A 1.5, Rockw ool, Loft<br />
-5<br />
16.10.01 04.01.02 25.03.02 13.06.02 01.09.02 20.11.02 08.02.03 29.04.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 69. Temperaturer i loftisoleringen over en bolig der er isoleret med batts af stenuld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.5, Rockw ool, Facade mod V<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 70. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med batts af stenuld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.5, Rockw ool, Facade mod Ø<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 71. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med batts af stenuld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed A 1.5, Rockw ool, Loft<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 72. Fugtindhold i loftisoleringen over en bolig der er isoleret med batts af stenuld. Fugtindholdet er<br />
målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
20,0<br />
19,0<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
Lejlighed A 1.5, Rockw ool, Facade mod V<br />
12,0<br />
11,0<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 73. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med batts af stenuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.5, Rockw ool, Facade mod Ø<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 74. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med batts af stenuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
55
56<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.6, Rockw ool, Loft<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 75. Temperaturer i loftisoleringen over en bolig der er isoleret med batts af stenuld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
-10<br />
Lejlighed A 1.6, Rockw ool, Facade mod V<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 76. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med batts af stenuld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed A 1.6, Rockw ool, Facade mod Ø<br />
-10<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 77. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med batts af stenuld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed A 1.6, Rockw ool, Loft<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 78. Fugtindhold i loftisoleringen over en bolig der er isoleret med batts af stenuld. Fugtindholdet er<br />
målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
20,0<br />
19,0<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
Lejlighed A 1.6, Rockw ool, Facade mod V<br />
12,0<br />
11,0<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 79. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med batts af stenuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed A 1.6, Rockw ool, Facade mod Ø<br />
10,0<br />
16.10.01 4.1.02 25.3.02 13.6.02 1.9.02 20.11.02 8.2.03 29.4.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 80. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med batts af stenuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
57
58<br />
Temperatur [oC]<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.1, Isodan, Loft<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 81. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.1, Isodan, Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 82. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.1, Isodan, Facade mod Ø<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 83. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
16,00<br />
15,00<br />
14,00<br />
13,00<br />
12,00<br />
11,00<br />
Lejlighed B 1.1, Isodan, Loft<br />
10,00<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Loft over bad mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 84. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.1, Isodan, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 85. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,00<br />
15,00<br />
14,00<br />
13,00<br />
12,00<br />
11,00<br />
Lejlighed B 1.1, Isodan, Facade mod Ø<br />
10,00<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 86. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
59
60<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.2, Isodan, Loft<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 87. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.2, Isodan, Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 88. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.2, Isodan, Facade mod Ø<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 89. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed B 1.2, Isodan, Loft<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 90. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.2, Isodan, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 91. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.2, Isodan, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 92. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
61
62<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.3, LRC-Hør, Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 93. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.3, LRC-Hør, Facade mod V<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Loft over køkken mod boligen<br />
Figur 94. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
høruld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.3, LRC-Hør, Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 95. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed B 1.3, LRC-Hør, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 96. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
18,0<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.3, LRC-Hør, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 97. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.3, LRC-Hør, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 98. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
63
64<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.4, LRC-Hør, Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 99. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.4, LRC-Hør, Facade mod V<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 100. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
høruld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.4, LRC-Hør, Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 101. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af<br />
høruld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.
Fugtindhold [masse-%]<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed B 1.4, LRC-Hør, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 102. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af høruld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.4, LRC-Hør, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 103. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.4, LRC-Hør, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 104. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af høruld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
65
66<br />
Temperatur [oC]<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed B 1.5, Isover, Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 105. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af glasuld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
den side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.5, Isover, Facade mod V<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 106. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
glasuld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed B 1.5, Isover, Facade mod Ø<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 107. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af<br />
glasuld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
Lejlighed B 1.5, Isover, Loft<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02<br />
Tid [dd:mm:år]<br />
9.1.03 30.3.03<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 108. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af glasuld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
19,0<br />
18,0<br />
17,0<br />
Lejlighed B 1.5, Isover, Facade mod V<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 109. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af<br />
glasuld. Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.5, Isover, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 110. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af glasuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
67
68<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
Lejlighed B 1.6, Isover, Loft<br />
0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 111. Temperaturer i loftisoleringen over en bolig der er isoleret med formstykker af glasuld. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
den side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
-10<br />
Lejlighed B 1.6, Isover, Facade mod V<br />
-15<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 112. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med formstykker af<br />
glasuld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
Lejlighed B 1.6, Isover, Facade mod Ø<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 113. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med formstykker af<br />
glasuld. Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.
Fugtindhold [masse-%]<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed B 1.6, Isover, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 114. Fugtindhold i loftisoleringen over en bolig der er isoleret med formstykker af glasuld. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
20,0<br />
18,0<br />
16,0<br />
14,0<br />
12,0<br />
Lejlighed B 1.6, Isover, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 115. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med formstykker af<br />
glasuld. Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed B 1.6, Isover, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 116. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med formstykker af glasuld.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
69
70<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.1, Ekofiber (Vind), Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 117. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.1, Ekofiber (Vind), Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 118. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed C 1.1, Ekofiber (Vind), Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 119. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
13,50<br />
13,00<br />
12,50<br />
12,00<br />
11,50<br />
11,00<br />
10,50<br />
Lejlighed C 1.1, Ekofiber (Vind), Loft<br />
10,00<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Loft over bad mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 120. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.1, Ekofiber (Vind), Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 121. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
15,00<br />
14,50<br />
14,00<br />
13,50<br />
13,00<br />
12,50<br />
12,00<br />
Lejlighed C 1.1, Ekofiber (Vind), Facade mod Ø<br />
11,50<br />
11,00<br />
10,50<br />
10,00<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 122. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
71
72<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.2, Ekofiber (Vind), Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 123. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.2, Ekofiber (Vind), Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 124. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.2, Ekofiber (Vind), Facade mod Ø<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 125. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed C 1.2, Ekofiber (Vind), Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 126. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
10,0<br />
Lejlighed C 1.2, Ekofiber (Vind), Facade mod V<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 127. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
10,0<br />
Lejlighed C 1.2, Ekofiber (Vind), Facade mod Ø<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 128. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
73
74<br />
Temperatur [oC]<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
-10<br />
Lejlighed C 1.3, Papiruld, Loft<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 129. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.3, Papiruld, Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 130. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed C 1.3, Papiruld, Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 131. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.3, Papiruld, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 132. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.3, Papiruld, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 133. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
17,0<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.3, Papiruld, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 134. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
75
76<br />
Temperatur [oC]<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.4, Papiruld, Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 135. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den<br />
side der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.4, Papiruld, Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 136. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod<br />
boligen, og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed C 1.4, Papiruld, Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 137. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed C 1.4, Papiruld, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Loft over bad mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod det fri Loft over køkken mod boligen<br />
Figur 138. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af cellulose. Fugtindholdet<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
15,0<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
10,0<br />
Lejlighed C 1.4, Papiruld, Facade mod V<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 139. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.4, Papiruld, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Køkken, nedre mod det fri<br />
Køkken, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Køkken, nedre mod boligen<br />
Køkken, øvre mod boligen<br />
Figur 140. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af cellulose.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
77
78<br />
Temperatur [oC]<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.5, Perlite, Loft<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 141. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af perlit. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.5, Perlite, Facade mod V<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 142. Temperaturer i isoleringen, i facaden mod vest, i en bolig der er isoleret med løsfyld af perlit.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
-5<br />
Lejlighed C 1.5, Perlite, Facade mod Ø<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 143. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af perlit.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.
Fugtindhold [masse-%]<br />
15,00<br />
14,50<br />
14,00<br />
13,50<br />
13,00<br />
12,50<br />
12,00<br />
11,50<br />
11,00<br />
10,50<br />
Lejlighed C 1.5, Perlite, Loft<br />
10,00<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Loft over bad mod det fri<br />
Loft over køkken mod det fri<br />
Tid [dd:mm:år]<br />
Loft over bad mod boligen<br />
Loft over køkken mod boligen<br />
Figur 144. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af perlit. Fugtindholdet er<br />
målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
14,5<br />
14,0<br />
13,5<br />
13,0<br />
12,5<br />
12,0<br />
11,5<br />
11,0<br />
10,5<br />
Lejlighed C 1.5, Perlite, Facade mod V<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Værelse, V, nedre mod det fri<br />
Værelse, V, øvre mod det fri<br />
Stue, nedre mod det fri<br />
Stue, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Værelse, V, nedre mod boligen<br />
Værelse, V, øvre mod boligen<br />
Stue, nedre mod boligen<br />
Stue, øvre mod boligen<br />
Figur 145. Fugtindhold i isoleringen, i facade mod vest, i en bolig der er isoleret med løsfyld af perlit.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og<br />
i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
Fugtindhold [masse-%]<br />
19,00<br />
18,00<br />
17,00<br />
16,00<br />
15,00<br />
14,00<br />
13,00<br />
12,00<br />
11,00<br />
10,00<br />
Lejlighed C 1.5, Perlite, Facade mod Ø<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Værelse, Ø, nedre mod det fri<br />
Værelse, Ø, øvre mod det fri<br />
Tid [dd:mm:år]<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Værelse, Ø, nedre mod boligen<br />
Værelse, Ø, øvre mod boligen<br />
Figur 146. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af perlit.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
79
80<br />
Temperatur [oC]<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.6, Perlite, Loft<br />
-5<br />
-10<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Figur 147. Temperaturer i loftisoleringen over en bolig der er isoleret med løsfyld af perlit. Temperaturerne<br />
er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen, og den side<br />
der vender mod den kolde side (loftrummet).<br />
Temperatur [oC]<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
Lejlighed C 1.6, Perlite, Facade mod Ø<br />
-5<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri Bad, nedre mod boligen<br />
Bad, øvre mod det fri Bad, øvre mod boligen<br />
Figur 148. Temperaturer i isoleringen, i facaden mod øst, i en bolig der er isoleret med løsfyld af perlit.<br />
Temperaturerne er målt to gange i døgnet i isoleringen i henholdsvis den side som vender mod boligen,<br />
og i den kolde side.<br />
Fugtindhold [masse-%]<br />
16,0<br />
15,0<br />
14,0<br />
13,0<br />
12,0<br />
11,0<br />
Lejlighed C 1.6, Perlite, Loft<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Loft over bad mod det fri Loft over bad mod boligen<br />
Figur 149. Fugtindhold i loftisoleringen over en bolig der er isoleret med løsfyld af perlit. Fugtindholdet er<br />
målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen, og den side der<br />
vender mod den kolde side (loftrummet). Fugtindholdet er angivet som vægtpct. fugt i træ.
Fugtindhold [masse-%]<br />
22,0<br />
20,0<br />
18,0<br />
16,0<br />
14,0<br />
12,0<br />
Lejlighed C 1.6, Perlite, Facade mod Ø<br />
10,0<br />
16.9.01 5.12.01 23.2.02 14.5.02 2.8.02 21.10.02 9.1.03 30.3.03<br />
Tid [dd:mm:år]<br />
Bad, nedre mod det fri<br />
Bad, øvre mod det fri<br />
Bad, nedre mod boligen<br />
Bad, øvre mod boligen<br />
Figur 150. Fugtindhold i isoleringen, i facade mod øst, i en bolig der er isoleret med løsfyld af perlit.<br />
Fugtindholdet er målt to gange i døgnet i isoleringen i henholdsvis den side, som vender mod boligen,<br />
og i den kolde side. Fugtindholdet er angivet som vægtpct. fugt i træ.<br />
81
82<br />
Bilag B Temperatur og relativ luftfugtighed i<br />
lejligheder<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 0.1, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02 08-02-03 09-04-03<br />
Stue, T Bad, TDato Stue, RF Bad, RF<br />
Figur 151. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen og <strong>på</strong> badeværelset. Lejligheden er beliggende i<br />
underetagen, i den del af byggeriet som er i to etager.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 0.2, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Sovevær., T Bad, T<br />
Stue, RF Sovevær., RF Bad, RF<br />
Figur 152. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset. Lejligheden<br />
er beliggende i underetagen, i den del af byggeriet som er i to etager.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.1, Thermocell<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Kontor, T<br />
Kontor, RF<br />
Bad, T<br />
Bad, RF<br />
Figur 153. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af træfiber. <strong>Måling</strong>erne er foretaget i stuen, i rummet anvendt til kontor og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.2, Thermocell<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 154. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af træfiber. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.3, HBC-hør<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Sovevær., T Bad, T<br />
Stue, RF Sovevær., RF Bad, RF<br />
Figur 155. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af høruld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]<br />
83
84<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.4, HBC-hør<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 156. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af høruld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.5, Rockw ool<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 157. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
batts af stenuld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed A 1.6, Rockw ool<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Kontor, T Bad, T<br />
Stue, RF Kontor, RF Bad, RF<br />
Figur 158. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
batts af stenuld. <strong>Måling</strong>erne er foretaget i stuen, i rummet anvendt til kontor og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 0.1, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Bad, T Stue, RF Bad, RF<br />
Figur 159. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen og <strong>på</strong> badeværelset. Lejligheden er beliggende i<br />
underetagen i den del af byggeriet som er i to etager.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 0.2, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Bad, T Stue, RF Bad, RF<br />
Figur 160. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen og <strong>på</strong> badeværelset. Lejligheden er beliggende i<br />
underetagen i den del af byggeriet som er i to etager.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.1, Isodan<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 161. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]<br />
85
86<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.2, Isodan<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 162. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.3, LRC-hør<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 163. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af høruld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.4, LRC-hør<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 164. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af høruld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.5, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Sovevær., T Bad, T<br />
Stue, RF Sovevær., RF Bad, RF<br />
Figur 165. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed B 1.6, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Kontor, T Bad, T<br />
Stue, RF Kontor, RF Bad, RF<br />
Figur 166. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen, i rummet anvendt til kontor og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 0.1, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Bad, T Stue, RF Bad, RF<br />
Figur 167. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen og i soveværelset. Lejligheden er beliggende i<br />
underetagen i den del af byggeriet som er i to etager.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]<br />
87
88<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 0.2, Isover<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Bad, T Stue, RF Bad, RF<br />
Figur 168. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
formstykker af glasuld. <strong>Måling</strong>erne er foretaget i stuen og <strong>på</strong> badeværelset. Lejligheden er beliggende i<br />
underetagen i den del af byggeriet som er i to etager.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.1, Ekofiber<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Kontor, T<br />
Kontor, RF<br />
Bad, T<br />
Bad, RF<br />
Figur 169. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i rummet anvendt til kontor og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.2, Ekofiber<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 170. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.3, Papiruld<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 171. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.4, Papiruld<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 172. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af cellulose. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.5, Perlite<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T Kontor, T Bad, T<br />
Stue, RF Kontor, RF Bad, RF<br />
Figur 173. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af perlit. <strong>Måling</strong>erne er foretaget i stuen, i rummet anvendt til kontor og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
RF [%]<br />
RF [%]<br />
89
90<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Lejlighed C 1.6, Perlite<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Stue, T<br />
Stue, RF<br />
Sovevær., T<br />
Sovevær., RF<br />
Bad, T<br />
Bad, RF<br />
Figur 174. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for en bolig isoleret med<br />
løsfyld af perlit. <strong>Måling</strong>erne er foretaget i stuen, i soveværelset og <strong>på</strong> badeværelset.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]
Bilag C Temperatur og relativ luftfugtighed<br />
udendørs og i teknikrum<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Ude foran Teknikrum<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
v.TekA, T v.TekB, T v.TekC T<br />
Figur 175. Temperatur i °C angivet hver anden time udenfor de uisolerede teknikrum i henholdsvis blok<br />
A, B og C.<br />
T [°C]<br />
40<br />
30<br />
20<br />
10<br />
0<br />
Teknikrum<br />
-10<br />
13-06-02 12-08-02 11-10-02 10-12-02<br />
Dato<br />
08-02-03 09-04-03<br />
Teknik A, T Teknik B, T Teknik C, T<br />
Teknik A, RF Teknik B, RF Teknik C, RF<br />
Figur 176. Temperatur i °C og relativ luftfugtighed i % angivet hver anden time for de uisolerede teknikrum<br />
i henholdsvis blok A, B og C. I vinterperioden er den relative luftfugtighed i teknikrummet i blok A<br />
højere end i teknikrummene i blok B og C, årsagen til dette var oversvømmelse i teknikrummet i blok A.<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
RF [%]<br />
91
Borup Seniorby er et demonstrationsbyggeri hvori der<br />
både er anvendt <strong>alternative</strong> <strong>isoleringsmaterialer</strong> og mineraluld.<br />
Denne rapport viser fugtophobningen i de valgte<br />
isoleringsprodukter, og redegør for hvorvidt isoleringsarbejder<br />
er udført korrekt. Ni forskellige produkter enten i<br />
form af løsfyld eller formstykker indgår i undersøgelsen.<br />
Der redegøres for fugtophobningen i løbet af to vintre, om<br />
isoleringsmaterialet udfylder de hulrum, der var tiltænkt<br />
isoleret, og om de enkelte <strong>isoleringsmaterialer</strong> egner sig<br />
bedre til nogle typer opgaver end andre.<br />