3000628-2006-04-26.fm Technical specifications<br />

4.1 Connection to external clock<br />

Testing<br />

the fan<br />

To select the second speed, close the connection between clips 124 and 125 with a<br />

potential-free contact.<br />

If a<br />

situation arises... … in which operation may be dangerous Switch off the automatic<br />

components and make sure that they cannot be restarted acci<strong>de</strong>ntally.<br />

Risk-free operation is not possible when the automatic components:<br />

• are visibly damaged,<br />

• have been stored for an exten<strong>de</strong>d period in unfavourable conditions,<br />

• have been subjected to serious stresses during transport.<br />

5. Technical specifications<br />

Power supply: 3 x 400V +5%/–10%<br />

Motor load (AC3): 7,0A<br />

Fuses: max. 10A<br />

Protection class<br />

(IEC 529)<br />

Step Action Check that …<br />

1 Disconnect the cable in clip 73 ... the fan turns slowly.<br />

2 Reattach the cable. -<br />

3 Disconnect the cable in clip 40 • the motor stops<br />

(OHM).<br />

• the warning lamps OHM (4) in the<br />

automatic system box and OHM<br />

(4) on the control panel light up.<br />

4 Reattach the cable. -<br />

5 Switch off the function circuit breaker (in<br />

the automatic system box) for 5 seconds<br />

and then switch it on again (reset).<br />

… the fan motor runs normally.<br />

6 When the dial (2) is in position 1, the<br />

potentiometer (5) can be used to<br />

adjust the minimum speed of<br />

revolution of the fan motor.<br />

7 If an external clock or a similar <strong>de</strong>vice<br />

has been connected for 2-speed<br />

operation, use the potentiometer (6)<br />

on the automatic system panel to set<br />

the ventilation volume with the contact<br />

set over clips 124 and 125 closed.<br />

8 Set the dial (2) to position 10. … the full load current of the motor<br />

corresponds to its stamp data.<br />

Ambient temperature: (operation): –20°C to 40°C<br />

Automatic system box: IP54<br />

Control panel: IP20<br />

4/16