3000628-2006-04-26.fm Technical specifications<br />
4.1 Connection to external clock<br />
Testing<br />
the fan<br />
To select the second speed, close the connection between clips 124 and 125 with a<br />
potential-free contact.<br />
If a<br />
situation arises... … in which operation may be dangerous Switch off the automatic<br />
components and make sure that they cannot be restarted acci<strong>de</strong>ntally.<br />
Risk-free operation is not possible when the automatic components:<br />
• are visibly damaged,<br />
• have been stored for an exten<strong>de</strong>d period in unfavourable conditions,<br />
• have been subjected to serious stresses during transport.<br />
5. Technical specifications<br />
Power supply: 3 x 400V +5%/–10%<br />
Motor load (AC3): 7,0A<br />
Fuses: max. 10A<br />
Protection class<br />
(IEC 529)<br />
Step Action Check that …<br />
1 Disconnect the cable in clip 73 ... the fan turns slowly.<br />
2 Reattach the cable. -<br />
3 Disconnect the cable in clip 40 • the motor stops<br />
(OHM).<br />
• the warning lamps OHM (4) in the<br />
automatic system box and OHM<br />
(4) on the control panel light up.<br />
4 Reattach the cable. -<br />
5 Switch off the function circuit breaker (in<br />
the automatic system box) for 5 seconds<br />
and then switch it on again (reset).<br />
… the fan motor runs normally.<br />
6 When the dial (2) is in position 1, the<br />
potentiometer (5) can be used to<br />
adjust the minimum speed of<br />
revolution of the fan motor.<br />
7 If an external clock or a similar <strong>de</strong>vice<br />
has been connected for 2-speed<br />
operation, use the potentiometer (6)<br />
on the automatic system panel to set<br />
the ventilation volume with the contact<br />
set over clips 124 and 125 closed.<br />
8 Set the dial (2) to position 10. … the full load current of the motor<br />
corresponds to its stamp data.<br />
Ambient temperature: (operation): –20°C to 40°C<br />
Automatic system box: IP54<br />
Control panel: IP20<br />
4/16