Ergänzende technische<br />
Informationen<br />
Selektivität<br />
Einspeisung: NSX 0 bis 0<br />
Abgangsseitig: C1 0N/H, NG1<br />
Kennlinien B, C, D<br />
Einspeisung NSX250B/F/N/H/S/L NSX400F/N/H/S/L NSX630F/N/H/S/L<br />
Auslöser Micrologic 2.0, 5.0, 6.0<br />
Isd: 10 Ir<br />
Micrologic 2.0, 5.0, 6.0<br />
Isd: 10 Ir<br />
558F4310_Ver2.0-DE.indd Version: .0<br />
Micrologic 2.0, 5.0, 6.0<br />
Isd: 10 Ir<br />
Abgangsseitig Typ (A) 250 400 630<br />
Ir 100 125 160 200 250 160 200 250 320 400 250 320 400 500 630<br />
Selektivitätsgrenze (kA)<br />
C120N/H 16 T T T T T T T T T T T T T T T<br />
Kennlinien B, C 20 T T T T T T T T T T T T T T T<br />
25 T T T T T T T T T T T T T T T<br />
32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
100 T T T T T T T T T<br />
125 T T T T T T<br />
C120N/H 16 T T T T T T T T T T T T T T T<br />
Kennlinie D 20 T T T T T T T T T T T T T T T<br />
25 T T T T T T T T T T T T T T T<br />
32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
100 T T T T T T T T T<br />
125 T T T T T T<br />
NG125N/S/H y 20 T T T T T T T T T T T T T T T<br />
Kennlinien B, C 25, 32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
100 T T T T T T T T T<br />
125 T T T T T T<br />
NG125N/S/H y 20 T T T T T T T T T T T T T T T<br />
Kennlinie D 25, 32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
100 T T T T T T T T T<br />
125 T T T T T T<br />
NG125L y 16 T T T T T T T T T T T T T T T<br />
Kennlinien B, C 20 T T T T T T T T T T T T T T T<br />
25, 32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
NG125L y 16 T T T T T T T T T T T T T T T<br />
Kennlinie D 20 T T T T T T T T T T T T T T T<br />
25, 32 T T T T T T T T T T T T T T T<br />
40 T T T T T T T T T T T T T T T<br />
50 T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T<br />
T Totale Selektivität bis zum Schaltvermögen des nachgeschalteten Sicherungsautomaten.<br />
Selektivitätsgrenze = 4 kA.<br />
Keine Selektivität.