<strong>Expo</strong>-<strong>Telektron</strong> <strong>Mini<strong>Purge</strong></strong> Z purge Handbook ML 307 Issue A<br />
Relief Valve opens continuously or<br />
intermittently<br />
Is the PE<br />
pressure too high?<br />
NO<br />
Is there<br />
Debris on the RLV<br />
disk allowing air to<br />
leak from<br />
the valve?<br />
NO<br />
Call<br />
<strong>Expo</strong>-<strong>Telektron</strong><br />
YES<br />
YES<br />
8.2.1 Pressure sensor calibration<br />
C:\Main System Files\Marketing\Memo\ML307 ISSUE A.doc<br />
Page 8-4<br />
If it is decided that the minimum pressure /purge flow sensor needs recalibrating it must be<br />
returned to <strong>Expo</strong> <strong>Telektron</strong> for this service<br />
The Leakage Compensation Valve (LCV) is too far<br />
open. Adjust the LCV as described in Section<br />
6.9.2 above.<br />
Remove the RLV cover and clean the valve disk.<br />
If it is necessary to remove the disk and sping<br />
from the RLV draw a line around it with a pencil to<br />
allow accurate replacement before removal,<br />
otherwise the opening pressure may be affected.<br />
Page 8-4