RZ eta-engl Kopie - HOWATHERM
RZ eta-engl Kopie - HOWATHERM
RZ eta-engl Kopie - HOWATHERM
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
10<br />
Benefits of “smart”<br />
frequency<br />
converters<br />
Volume flow measu-<br />
ring technology<br />
ETA SYSTEM designs are generously sized,<br />
with flow velocities of around 2 m/s.<br />
This means that the droplet eleminator on<br />
the cooler can be void, resulting in a further<br />
decrease in internal pressure losses. In<br />
fact, the lower velocity reduces both the<br />
pressure loss (by a square correlation) and<br />
the electrical power consumption (by a<br />
third correlation). Moreover, the power<br />
consumption of the new drive concept is<br />
lower in relative terms at reduced pressures<br />
(approx. 15% savings at 1000 Pa, about<br />
40% at 400 Pa), implying still higher relative<br />
electrical power savings - with the result<br />
of further economic benefits.<br />
The power consumption of these units was<br />
measured on <strong>HOWATHERM</strong> test rigs and in<br />
RWTÜV trials and is EUROVENT-certified.<br />
An additional improvement feature is the<br />
execution of the fan casing in the thermally<br />
insulated ETA 40 T sectional structure.<br />
This design minimizes thermal bridges, and<br />
the casing is air-tight to DIN EN 1886 tightness<br />
class B.