Chapter 2: Monitoring relays - Hiquel
Chapter 2: Monitoring relays - Hiquel
Chapter 2: Monitoring relays - Hiquel
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
TCC-H<br />
overview<br />
AC or DC over or under current monitor<br />
DPCO output max. 6A<br />
3 measuring ranges 5mA - 10A RMS<br />
level and hysteresis adjustments<br />
programmable latch/no latch alarm<br />
LED indicators for power supply,<br />
contact and reaction timer<br />
45mm DIN rail mount housing<br />
operating conditions<br />
specification<br />
supply voltage variation nominal voltage +10% / -15%<br />
frequency range<br />
48-63Hz<br />
duty cycle<br />
100%<br />
start surge delay<br />
0 - 10s<br />
reaction time<br />
0-5s<br />
reset time<br />
< 100ms<br />
output relay specification max. 6A 230V~<br />
Ue/Ie AC-15<br />
120V/4A 240V/3A<br />
Ue/Ie DC-13<br />
24V/2A<br />
expected life time<br />
DPCO SPCO<br />
mechanical<br />
2x10<br />
electrical<br />
6<br />
resp. 1 x 10 7 operations<br />
1x10 5<br />
resp. 1 x 10 5<br />
operations<br />
screws<br />
pozidrive 1<br />
screw tightening torque 0,6..0,8Nm<br />
-20 to +60 °C non condensing<br />
* EN 60947-5-1 VDE 0435<br />
ordering information<br />
part no supply output<br />
TCC-H 230Vac 230V~ 2,5VA<br />
DPCO<br />
TCC-H 115Vac 115V~ 2,5VA<br />
DPCO<br />
TCC-H 24Vac<br />
24V~ 2,5VA<br />
DPCO<br />
TCC-H 24Vdc<br />
24V= 2W<br />
DPCO<br />
* The measurement input is galvanically isolated from the power supply<br />
Function<br />
Control relay active<br />
Control relay passive<br />
Contact closed<br />
Contact open<br />
under current<br />
over current<br />
HIQUEL 2009<br />
X01.00<br />
U<br />
In%<br />
no<br />
Latch<br />
R<br />
Latch<br />
R<br />
U<br />
In%<br />
no<br />
Latch<br />
R<br />
Latch<br />
R<br />
E1<br />
input<br />
E1-M<br />
E2-M<br />
E3-M<br />
4 S1<br />
HIGH QUALITY ELECTRONICS<br />
t s<br />
t s<br />
+24V=<br />
0V<br />
3<br />
TCC-H<br />
U<br />
I n %<br />
2<br />
Hyst.<br />
1<br />
E2<br />
E3<br />
A2 - M<br />
same<br />
potential<br />
t r<br />
t r<br />
5<br />
M<br />
3<br />
M<br />
4<br />
230VAC<br />
50<br />
1<br />
S1<br />
100%<br />
R 0 50% 0 5 T<br />
A1<br />
A2<br />
1<br />
t r<br />
t r<br />
2<br />
Over/Under Current Control<br />
0<br />
2<br />
AC DC<br />
Over Under<br />
No Latch Latch<br />
25<br />
2,5<br />
sup. galv. Gehäusetypen<br />
iso*<br />
yes<br />
yes<br />
yes<br />
yes<br />
yes<br />
yes<br />
no<br />
yes<br />
5<br />
10<br />
ts<br />
tr<br />
E1<br />
t s<br />
t s<br />
E2<br />
E3<br />
1 Threshold “In”<br />
2 Hysteresis<br />
3 Monitored current<br />
4 Latch<br />
ts... Start surge delay<br />
tr... Reaction timer<br />
T... LED indication reaction timer<br />
Over/under current control<br />
relay<br />
On application of the supply<br />
voltage the output relay pulls in<br />
and the timing period ts starts.<br />
Current control with no latch<br />
(auto reset) function<br />
At the end of ts,<br />
when the<br />
measured current exceeds the<br />
set threshold, timing period tr<br />
starts. At the end of tr the output<br />
relay changes over if the current<br />
measurement still exceeds the<br />
threshold.<br />
The output relay resets immediately<br />
when the monitored<br />
current reaches the hysteresis<br />
set value.<br />
.<br />
Current control with latch<br />
(manual reset) function.<br />
At the end of ts,<br />
if the measured<br />
current exceeds the set threshold,<br />
timing period tr starts. At the end<br />
of tr the output relay changes over<br />
and remains in this condition, even<br />
if the monitored current reaches<br />
the hysteresis set value.<br />
An external reset (S1) must be<br />
operated to reset the relay.<br />
Supply = U = A1-A2<br />
M<br />
><br />
><br />
+~ S1<br />
A1<br />
A2<br />
- ~<br />
range resistance I (20°C)<br />
EMAX<br />
11<br />
12<br />
14<br />
21<br />
5mA - 100mA 1,0 Ohm 1,5 A<br />
50mA - 1A 0,1 Ohm 3,5 A<br />
0,5A - 10A 0,01 Ohm 14 A<br />
R R<br />
22<br />
housing types<br />
C<br />
C<br />
C<br />
C<br />
24<br />
<<br />
<<br />
2<br />
I<br />
5mA-10A<br />
DIN<br />
C US<br />
2:03<br />
over/under current control