CURRENT RATINGS AND VOLTAGE DROP TABLE<br />

(Unarmoured Cable)<br />

<strong>Cables</strong> installed in free air<br />

Plain annealed stranded <strong>co</strong>nductor, mica tape lapping, XLPE insulated, LSF cables, 600/1000V<br />

Conditions of installation:<br />

Ambient temperature : 30 o C<br />

Maximum Conductor temperature : 90 o C<br />

26<br />

Nominal<br />

area of<br />

<strong>co</strong>nductor<br />

mm 2<br />

2-Single Cores<br />

Touching<br />

2-Single Cores<br />

Touching<br />

26<br />

Table 1<br />

INSTALLATION METHODS<br />

Single Core Cable Multi<strong>co</strong>re Cable<br />

3-Single Cores<br />

Trefoil<br />

3-Single Cores<br />

Spaced Horizontal<br />

3-Single Cores<br />

Spaced Vertical<br />

2 Loaded<br />

Conductor<br />

1.5 27 23 22 27 23 26 23<br />

2.5 35 31 30 37 31 36 32<br />

3 Loaded<br />

Conductor<br />

A B C D E F G<br />

d1<br />

d1 d1 d1<br />

d1<br />

d1 d1<br />

d1<br />

4 49 42 40 52 44 49 42<br />

6 63 54 52 67 55 63 54<br />

10 88 76 73 95 76 86 75<br />

16 137 100 96 150 112 115 100<br />

25 161 141 135 182 161 149 127<br />

35 200 176 169 226 201 185 157<br />

50 242 215 207 275 246 225 192<br />

70 310 279 268 353 318 289 246<br />

95 377 341 328 430 389 352 298<br />

120 437 399 382 500 454 410 346<br />

150 504 462 443 577 527 473 399<br />

185 575 531 509 661 605 542 456<br />

240 679 631 604 781 719 641 538<br />

300 783 731 699 902 833 741 620<br />

400 940 880 839 1085 1008 - -<br />

500 1083 1006 958 1253 1169 - -<br />

630 1254 1117 1077 1454 1362 - -<br />

800 1460 1262 1152 1696 1595 - -<br />

1000 1683 1432 1240 1958 1847 - -<br />

Group installation <strong>co</strong>rrection factor for methods A to E, please refer to Table 2<br />

Group installation <strong>co</strong>rrection factor for methods F to G, please refer to Table 3<br />

Correction factors for ambient air temperature other than 30 o C, please refer to Table 6<br />

d1: Clearance to wall not less than one cable diameter<br />

d2: Minimum 0.3 times the diameter of cable<br />

d2<br />

d2