Card Description P<strong>DP</strong>-TP Communication<br />

Preparation of the <strong>Profibus</strong> cable (bus cable)<br />

4 PREPARATION OF THE PROFIBUS CABLE (BUS CABLE)<br />

The preparation of the bus cabling on the <strong>Profibus</strong> network is an essential factor in ensuring reliable<br />

operation and electromagnetic compatibility (EMC) on both the <strong>Profibus</strong> card and the target hardware.<br />

The EMC values (immunity and emission) specified in the technical data of the target hardware<br />

can only be guaranteed if the following cable preparation is completed.<br />

The <strong>Profibus</strong> cable (topology, cable, connectors, termination) must be prepared in compliance with the<br />

<strong>Profibus</strong> standard (EN50170).<br />

4.1 PROFIBUS TOPOLOGY<br />

A <strong>Profibus</strong> network must be configured as a linear topology through all bus stations, and must be<br />

terminated at both ends. Branches and spur lines are not permitted. A bus segment can connect up to<br />

32 bus stations with each other. Several bus segments can be linked by means of repeaters<br />

(bidirectional amplifiers).<br />

4.2 BUS CABLE<br />

Data is transferred in the <strong>Profibus</strong> network via shielded twisted pair cables. Only use type A cables as<br />

specified in the <strong>Profibus</strong> standard (EN50170).<br />

Rated ripple resistance : 150 Ohm (135...165 Ohm)<br />

Capacitance per unit length : < 30 pF/m<br />

Loop resistance : > 110 Ohm/km<br />

Core cross section : ≥ 0.34 mm 2 (22 AWG)<br />

4.3 CABLE LENGTHS<br />

The physical interface of the <strong>Profibus</strong> is based on the EIA RS 485 standard (differential voltage<br />

transmission). The corresponding cable length limits and wiring recommendations apply.<br />

The following lengths for a bus segment apply to cables in compliance with the <strong>Profibus</strong> standard<br />

(EN50170) for cable type A.<br />

Baud rate in<br />

Kbit/s<br />

9.6 1200<br />

19.2 1200<br />

93.75 1200<br />

187.5 1000<br />

500 400<br />

1500 200<br />

12000 100<br />

Length in m<br />

Non-observation of these limits may cause transmission errors.<br />

8<br />

Subject to technical modifications<br />

M000872-01.DOC<br />