11.2 INPUTS TO MOTOR CONTROL AND MONITORING:<br />

11.21 INPUTS FROM THE OWN HYDRAULIC UNIT:<br />

Seite 5 von 12 C:\Eigene<br />

Dateien\Texte\Manuals\HYmanu\VBHengl1105.doc<br />

eMail<br />

info@mva-messvt.de<br />

interNet<br />

www.mva-messvt.de<br />

PAL Pressure to low – Alarm WARNING<br />

If another HY-units not o.k. then ALARM, locking<br />

actuators<br />

PLL Pressure to low motor ON, WARNING<br />

If another HY-units not o.k. then ALARM, locking<br />

actuators<br />

PL Pressure low motor ON<br />

PH Pressure high motor OFF<br />

PHH Pressure to high motor OFF, WARNING<br />

OPTIONS: NLL LEVEL OIL to low motor OFF, WARNING<br />

If another HY-units not o. k. then ALARM, locking<br />

actuators<br />

THH Temperature to high motor OFF, WARNING<br />

If another HY-units not o. k. then ALARM, locking<br />

actuators<br />

11.22 MANUAL INPUTS:<br />

ON not locking motor ON, pressure limits are not in<br />

order<br />

AUTO locking logic and control systems are running<br />

11.23 INTERNAL DECISION:<br />

MOTOR RUNS AGAIN AND AGAIN time more than 10 to 20 minutes<br />

WARNING<br />

11.24 OUTPUTS:<br />

M1, M2 motor ON/OFF pump motors on and off with rellay<br />

WA WARNING fault – control systens are running<br />

AL ALARM manual and automatic systems<br />

default, only safety direction are possible<br />

OPTION: M.A.D. all actuator systems are locked<br />

12. CONNECTING HYDRAULIC- AND PUMP-UNITS: If there is more than one pump unit installed for<br />

redundant reasons, so there are two units connected with one common tank. For service with two pumps<br />

are systems with one or two separated tanks suited, the difference is the internal circuit system.<br />

DATA SHEET FOR HYDRAULIC UNIT<br />

1 Project: Proj. ABB Meliti Achlada HDU - <strong>MVA</strong> No. 0805.99 and NDU for example<br />

2 Item no.: I II III<br />

3 kks code: MAN10 LCE10 LBH20<br />

4 HYDRAULIC ACTUATOR: AH200/80-80FO AH100/50-45 AH100/50-35